Input Current for 60 KVA Module: 102A ( Ref: attached UPS datasheet Page No :17),
Considering additional 10% of rated current input due to voltage fluctuation, i.e 102+10%= 112A,
Therefore suitable cable size of 60KVA UPS is 50Sq mm 4C CU cable (considering 30% derating factor,
Rated value of cable current capacity is coming: 162*.7= 113A) ,( Ref: attached Cable datasheet Page No :17),
Input Current for 150 KVA Module: 255A ( Ref: attached UPS datasheet Page No :17),
Considering additional 10% of rated current input due to voltage fluctuation, i.e 255+10%= 280A,
Therefore suitable cable size of 60KVA UPS is 240Sq mm 4C CU cable (considering 30% derating factor,
Rated value of cable current capacity is coming: 426*.7= 298A) ,( Ref: attached Cable datasheet Page No :17),