Home > Actual values > Metering > Transformer

Transformer
6.4.2.1 Differential and restraint currents
ACTUAL VALUES ðò METERING ð TRANSFORMER ð DIFFERENTIAL AND RESTRAINT
n DIFFERENTIAL AND ó REFERENCE WINDING:
n RESTRAINT Winding 1

ô DIFF PHASOR Iad:


0.000 pu 0.0°

ô REST PHASOR Iar:


0.000 pu 0.0°

ô DIFF 2ND HARM Iad:


0.0% fo 0.0°

ô DIFF 5TH HARM Iad:


0.0% fo 0.0°

ô DIFF PHASOR Ibd:


0.000 pu 0.0°

ô REST PHASOR Ibr:


0.000 pu 0.0°

ô DIFF 2ND HARM Ibd:


0.0% fo 0.0°

ô DIFF 5TH HARM Ibd:


0.0% fo 0.0°

ô DIFF PHASOR Icd:


0.000 pu 0.0°

ô REST PHASOR Icr:


0.000 pu 0.0°

ô DIFF 2ND HARM Icd:


0.0% fo 0.0°

ñ DIFF 5TH HARM Icd:


0.0% fo 0.0°

The metered differential current, restraint current, second harmonic current, and fifth harmonic current are displayed for
each phase. See the Percent Differential section in chapter 5 for details on how these values are calculated.
If differential current in any phase is below the hard-coded cutoff of 0.04 pu, then the differential, 2nd harmonic, and
5th harmonic currents are forced to zero.

6.4.2.2 Thermal elements

mk:@MSITStore:C:\Program%20Files%20(x86)\GE%20Power%20Management\URPC\... 11-12-2019
Transformer Page 2 of 2

ACTUAL VALUES ðò METERING ð TRANSFORMER ð THERMAL ELEMENTS


n THERMAL ó TOP OIL °C:
n ELEMENTS 70°C

ô HOTTEST-SPOT °C:
130°

ô AGING FACTOR:
1.2

ô DAILY RATE LOL:


15 hrs

ñ XFMR LIFE LOST:


100000 hrs

The daily rate loss of life is summarized at 00:00 h, and displayed for the next 24 hour period. The transformer
accumulated loss of life in hours is also available. It can be reset by either changing the XFMR INITIAL LOSS OF
LIFE setting or through the COMMANDS ðò CLEAR RECORDS ðò CLEAR LOSS OF LIFE RECORDS command.