6.4.2.1 Differential and restraint currents
ACTUAL VALUES ðò METERING ð TRANSFORMER ð DIFFERENTIAL AND RESTRAINT
n DIFFERENTIAL AND ó REFERENCE WINDING:
n RESTRAINT Winding 1
The metered differential current, restraint current, second harmonic current, and fifth harmonic current are displayed for
each phase. See the Percent Differential section in chapter 5 for details on how these values are calculated.
If differential current in any phase is below the hard-coded cutoff of 0.04 pu, then the differential, 2nd harmonic, and
5th harmonic currents are forced to zero.
mk:@MSITStore:C:\Program%20Files%20(x86)\GE%20Power%20Management\URPC\... 11-12-2019
Transformer Page 2 of 2
ô HOTTEST-SPOT °C:
130°
ô AGING FACTOR:
1.2
The daily rate loss of life is summarized at 00:00 h, and displayed for the next 24 hour period. The transformer
accumulated loss of life in hours is also available. It can be reset by either changing the XFMR INITIAL LOSS OF
LIFE setting or through the COMMANDS ðò CLEAR RECORDS ðò CLEAR LOSS OF LIFE RECORDS command.