Project: DTSM Rating Program: XEngine 1.0.

7229
Unit Tag: CH-01 Software Version: YW 19.05
Engineer: Date: 11/06/2019 10:16:24
Customer: BT CONSULTORES
SALES REPORT

Unit Specifications
Model YMC2-S1231ABS Refrigerant R-134a
Specified Net Capacity (Tons) 350.0 Refrigerant Charge (lb) 666
Rated Net Capacity (Tons) 350.0 Variable Orifice V2
Heat Rejection Capacity (MBtu/h) 5.100
Full Load (kW/Ton.R) 0.7227 Isolation Valve Y
NPLV.IP (kW/Ton.R) 0.4418 OptiSound Control Y
Input Power (kW) 252.9 Voltage / Hz 460 / 60.0
Starter Type HYP0490XHC***-46A FLA (Amps) 336
Compressor M2C-218FAC A-Weighted SPL (dBA) 81
Evaporator EB2910-481-BS*-1*** Min Circuit Ampacity 421
Condenser CB2510-471-CS*-1*** Max Circuit Breaker Amps 700

Evaporator Condenser
Fluid Water* Water*
Tube MTI No. 481 471 / 471
Passes 1* 1*
Fouling Factor (hr-ft²-°F/Btu) 0.000100* 0.000250*
Entering Fluid Temp (°F) 42.00* 88.00*
Leaving Fluid Temp (°F) 38.02 97.76
Fluid Flow (gpm) 2100* 1050*
Fluid Pressure Drop (ft H2O) 12.1 3.01
(*) Designates User Specified Input

Outside the scope of AHRI Water-Cooled Water Chilling and Heat Pump Water-Heating Packages Using Vapor Compressor Cycle
Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).
Compliant with ASHRAE 90.1-2004.
Compliant with ASHRAE 90.1-2007.
Compliant with ASHRAE 90.1-2010.
Compliant with ASHRAE 90.1-2013.
Compliant with ASHRAE 90.1-2016.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit (EAc4).
Materials and construction per mechanical specifications - Form 160.84-EG1.
Auxiliary components included in total kW - Chiller controls.

Page 2 of 4
Project: DTSM Rating Program: XEngine 1.0.7229
Unit Tag: CH-01 Software Version: YW 19.05
Engineer: Date: 11/06/2019 10:16:24
Customer: BT CONSULTORES

Partload Data (User Defined - Specific Point)


Net Capacity Input Power EEFT ELFT CEFT CLFT
% Load % Power kW/Ton.R
(Tons) (kW) (°F) (°F) (°F) (°F)
100 350.0 100 252.9 42.00 38.02 88.00 97.76 0.7227
75 262.5 69 174.2 41.01 38.02 86.00 93.24 0.6635
50 175.0 45 114.3 40.01 38.02 84.00 88.84 0.6534
25 87.50 29 72.54 39.02 38.02 82.00 84.57 0.8291

Outside the scope of AHRI Water-Cooled Water Chilling and Heat Pump Water-Heating Packages Using Vapor Compressor Cycle
Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).
Compliant with ASHRAE 90.1-2004.
Compliant with ASHRAE 90.1-2007.
Compliant with ASHRAE 90.1-2010.
Compliant with ASHRAE 90.1-2013.
Compliant with ASHRAE 90.1-2016.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit (EAc4).
Materials and construction per mechanical specifications - Form 160.84-EG1.
Auxiliary components included in total kW - Chiller controls.

Page 3 of 4
Project: DTSM Rating Program: XEngine 1.0.7229
Unit Tag: CH-01 Software Version: YW 19.05
Engineer: Date: 11/06/2019 10:16:24
Customer: BT CONSULTORES

Outside the scope of AHRI Water-Cooled Water Chilling and Heat Pump Water-Heating Packages Using Vapor Compressor Cycle
Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).
Compliant with ASHRAE 90.1-2004.
Compliant with ASHRAE 90.1-2007.
Compliant with ASHRAE 90.1-2010.
Compliant with ASHRAE 90.1-2013.
Compliant with ASHRAE 90.1-2016.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit (EAc4).
Materials and construction per mechanical specifications - Form 160.84-EG1.
Auxiliary components included in total kW - Chiller controls.