Communications
LonWorks Networks
A LonWorks communications network uses a
TP/FT-10 Free Topology configuration. Controllers
on a LonWorks network can communicate with each
other in a peer-to-peer fashion. A LonWorks network
has a communications speed of 78 kbps, using
unshielded, twisted-pair cabling, with connections
that are not polarity sensitive.
S-Link
The Sensor Link (S-Link) communications wiring
provides power and a communication interface for an
MN-Sx MicroNet sensor. The various MN-Sx sensors
can provide room temperature, room humidity,
© 2009 Schneider Electric. All rights reserved.
Schneider Electric 1354 Clifford Avenue, P.O. Box 2940, Loves Park, IL 61132-2940, USA 1-888-444-1311 www.schneider-electric.com/buildings
MODELS
Part Number Description Inputs/Outputs Profiles
MNL-10Rxx a
TAC I/A Series MicroNet 100 1 Digital Input (DI)
series controller
2 Universal Inputs (UI)
4 Digital Outputs (DO)
MNL-15Rxxa TAC I/A Series MicroNet 150 3 Universal Inputs (UI)
series controller Heat Pump
2 Digital Outputs (DO) Fan Coil
2 Analog Outputs (AO) Packaged Rooftop
Satellite
MNL-20Rxx a
TAC I/A Series MicroNet 200 2 Digital Inputs (DI)
series controller
3 Universal Inputs (UI)
6 Digital Outputs (DO)
2 Analog Outputs (AO)
a
“xx” denotes LonMark profile and profile version (F=Fan Coil, H=Heat Pump, R=Rooftop, S=Satellite). Satellite profile is based on Rooftop profile.
Schneider Electric 1354 Clifford Avenue, P.O. Box 2940, Loves Park, IL 61132-2940, USA 1-888-444-1311 www.schneider-electric.com/buildings
Architecture
PDA
MicroNet Sensor Universal
Desktop PC or (MN-S5 Shown) 5
Notebook PC with Network
WorkPlace Tech Controller
4 MNL-V3RVx
Tool Software 1 MN 100, MN 150, or
2 or MN 50
MN 200 Controller
Controller
SW
24H
SW 3
MNL-CIM
24H
SW 2
24H
24H 1
24G
GN AO
D
UI
S-L
K/C DI
MicroNet Controller
OM
S-L
K
LO
N
LO
N
Interface Module
LONWORKS Router 6
Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le material brouilleur du Canada
This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
interference that may cause undesired operation.
device may not cause harmful interference, and (2) This device must accept any interference received, including
This device conforms with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This
D E C O N N E C T E R AVA N T E N T R E T E N .
D I S C O N N E C T P O W E R B E F O R E S E RV I C I N G .
I N T E R C O N N E C T S E PA R AT E C L A S S 2 C I R C U I T S .
R I S K O F E L E C T R I C A L S H O C K O R F I R E . D O N OT
C5
DO5
Network
DO5: 250VAC, 3A Max, COS f = 0.4.
(if required)
DO1-DO4: 24VAC, 0.4A Max Total Load.
S-LK: 16VDC Max, Class 2.
CAUTION
DO4
8.5VA + DO1-DO4 loads.
24VAC
DO3
I/A
DO2
24VAC
DO1
Se
E9429
934G
MN rie
80 s®
T
I
M
X
0
V
C
E
R
C
V
SRVC
R
S
LON
J1
LON
S-LK
S-LK
COM 0V
COM 0V
UI1
MNL-11RF2
I/A Series
UI2
24VAC
UI3
GND
0V
3 MNL-V1RVx or 4
MN 110 or MN 130 MNL-V2RVx MN 800 MicroNet Sensor
Controller Controller Controller (MN-S3 Shown)
1 A PC can be connected to the LONWORKS TP/FT-10 Network, either directly or through the LONWORKS network jack of a
LONWORKS controller or MN-Sxxx Wall Sensor. The PC must have an Echelon™ LONTALK™ adapter card.
2 Programming any of the TAC I/A Series controllers, or the TAC I/A Series MN 800 controller, requires WorkPlace Tech Tool.
3 This controller is not suitable for exposed mounting on a wall or panel, or in any other easily accessible place due to the
possibility of personal contact with the high-voltage terminals. It must be mounted inside a suitable grounded metal enclosure.
4 MicroNet Sensors can be connected to any MN controller.
5 A PDA running the Pocket I/A interface software may be used to communicate with TAC I/A Series MicroNet controllers.
6 When routers are used, WP Tech is able to communicate through them to any of the TAC I/A Series devices on the network.
D E C O N N E C T E R AVA N T E N T R E T E N .
D I S C O N N E C T P OW E R B E F O R E S E RV I C I N G .
I N T E R C O N N E C T S E PA R ATE C L A S S 2 C I R C U I T S .
R I S K O F E L E C T R I C A L S H O C K O R F I R E . D O N OT
C5
DO5
DO4
8.5VA + DO1-DO4 loads.
24VAC
DO3
DO2
24VAC
DO1
E9429
934G
T
I
M
Enterprise Server
X
V
C
E
R
C
V
SRVC
R
S
LON
J1
LON
S-LK
S-LK
COM 0V
COM 0V
UI1
MNL-11RF2
I/A Series
UI2
LONWORKS
24VAC
UI3
GND
0V
Network
6 Router
Ethernet (if required)
CLO
SE
OP 24G
EN
SW 24G
24H
SW 3
24H
SW 2
24H
24H 1
24G
GN AO
D CO
M
UI
S-L
K/C DI
OM
S-L
K
LO
N
LO
N
Universal 4
Network MNL-V1RVx or MNL-V3RVx MicroNet Sensor
© 2009 Schneider Electric. All rights reserved.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there
remain references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Schneider Electric 1354 Clifford Avenue, P.O. Box 2940, Loves Park, IL 61132-2940, USA 1-888-444-1311 www.schneider-electric.com/buildings