Air cooling evaporators for cold rooms, blast freezers, air-conditioning, etc., will have
finned pipe coils in all but very small coolers, there will be fans to blow the air over the
coil. Construction materials will be the same as for air-cooled condensers. Aluminum
fins on copper tube are the most common for the halocarbons, with stainless steel or
aluminum tube for ammonia. Frost or condensed water will form on the fin surface and
must be drained away. To permit this, fins will be vertical and the air flow horizontal,
with a drain tray provided under. The size of the tube will be such that the velocity of
the boiling fluid within it will cause turbulence to promote heat transfer. Tube
diameters will vary from 9 mm to 32 mm, according to the size of coil. Fin spacing
will be a compromise between compactness (and cost) and the tendency for the spaces
to block with condensed moisture or frost. Spacings will vary from 2 mm on a compact
air-conditioner to 12 mm on a low-temperature cold-room coil.
We will design manually and by Techinsolve software
Evaporator Design:
Cooling load:
Qc = ̇ a ha in ha out)
123 = ̇ a (114.15 90) ̇ a=5.02kg/sec.
Coil design:
For Tube side (ref.):
( )
( )
[ ( ) ]
* +
[ ( ) ]
[ ]
( )
R=0.75 kj/kg.k
√
Ts1
Ts1 =30.56 0c
√
Ts2
Ts2 =25.45 0c
∆Trm=
= = 20.9 0c
Ai=
= = 3 m2
Ao=Ai*(18.5)= m2
Nr=6
̇ ref = ( )
0.898= ( )
Nc 26
NC=
H =26*0.0254 = 0.66 m
Aface=
=1.731 m2
Aface=H*LL = 2.62 m
Tube length:
L= Nt = 24 tubes
Fin calculations
Assume
( )
( )
From chart
Assume w=15cm
) 𝐴𝑜 𝑚
( )
Technisolve Software for Evaporator coil design
1st Step:
2nd Step:
3rd Step (Run Calculation from F9 button or button):
Coil Manufacturing Report
Recoil (5/8 inch - 38.1x50.8)
1016 x 1264 4r 6f 40c
DX 15938 / 20 / 04 / 6.00 / 1264 Cu/GI (40)
Pipe Connections
Size = 67 mm
Heat Transfer
ho = 44.102 W/m²°C
Ui = 3.780 kW/m²°C
Uo = 36.800 W/m²°C
Ntu = 0.434
Cr = 0.000
Qt = e x Qmax
= 0.352 x 350.216 = 123.242 kW
Psychrometrics
Bypass factor = 0.358
Apparatus Dew Point = 22.8 °C
Refrigerant (R134a) Duty
Superheat = 7.5 °C
Mass flow = 0.790 kg/s (approx)
Mass flux = 101.7 kg/sqm.s (approx)
Velocity = 0.080 m/s
Qt = mr x dh
= 0.790 x 156 = 123.26 kW
Dimensions
Height 1016.0 mm
Length 1264.0 mm
Depth 152.4 mm
Rows 4
Fins 6.00 fpi
Weight 135.4 kg
Circuiting
Tubes High 20
Tube Count 80
Circuits 40
Circuit Basis Tubes high
Tubes/Circuits 2
Unlinked tubes 0
Serpentine 2
Eq Length 3.8 m
Connections Same end
Fin
Thickness 0.200 mm
Area factor 1.000 mm
Material
Fin Cu
Tube Cu
Casing GI
Psychrometric Chart :
Condenser
The circulation of air over the condenser surface is maintained by using a fan or a
blower. These condensers normally use fins on air-side for good heat transfer. The fins
can be either plate type or annular type. This type of condensers is commonly used in
window air conditioners, water coolers and packaged air conditioning plants. The face
velocity is usually around 2m/s to 3.5 m/s to limit the pressure drop due to frictional
resistance. The coils of the tube in the flow direction are called rows. A condenser may
have two to eight rows of the tubes carrying the refrigerant. The moist air flows over
the fins while the refrigerant flows inside the tubes. The fins are usually of aluminum
and tubes are made of copper.
Holes of diameter slightly less than the tube diameter are punched in the plates and
plates are slid over the tube bank. Then the copper tubes are pressurized which expands
the tubes and makes a good thermal contact between the tube and fins.
Air Cooled Condenser design :
We will design the Air cooled condenser by Software and manually
To design the Air cooled condenser by Software, we will use ( Technisolve air cooled
condenser software)
Input values to Technisolve air cooled condenser software:
1st Step:
2nd Step:
3rd Step (Run Calculation from F9 button or button):
Model
Recoil (5/8 inch - 38.1x50.8)
1118 x 2858 6r 12f 11c
CD 15938 / 22 / 06 / 12.00 / 2858 Cu/GI (11)
Pipe Connections
Size = 35 mm
Heat Transfer
ho = 71.064 W/m²°C
Ui = 1.616 kW/m²°C
Uo = 29.092 W/m²°C
Ntu = 1.607
Cr = 0.000
Qt = e x Qmax
= 0.799 x 187.671 = 150.029 kW
Psychrometrics
Bypass factor = 0.020
Apparatus Dew Point = 33.1 °C
Fin
Thickness 0.200 mm
Area factor 1.000 mm
Material
Fin Cu
Tube Cu
Casing GI
Psychrometric Chart:
14.1. Design of Air cooled condenser manually:
̇ Given Data
̇ (1)
(2)
̇ (3) ⁄
(4)
*
(5)
(6)
Where { ⁄ }
̇ ⁄
⁄ *
Assume
ε=
Afrontal = L × H = 3 ×1 = 3
Assume 2.54
Check on
( )
( )
[ ( ) ]
[ ]
Fin calculations
Assume
( )
( )
From chart
Assume w=15cm
( )