PANDUAN SETTING KONFIGURASI TP48200A

1. Koneksikan laptop ke SMU

2. Setting IP laptop ke 192.168.0.9 subnet mask 255.255.255.0


3. Dari CMD, coba ping test ke 192.168.0.10.Kalau Reply artinya Laptop sudah terhubung ke TP48200A,
kalau belum periksa kembali koneksi LAN cable, setting proxy di internet explorer, dll
4. Buka browser, masukkan IP 192.168.0.10. Jika tidak bisa masuk pakai https://192.168.0.10/relogin.asp

5. Masukkan user dan passwordnya


User : admin
Password : 000001 ; Kalau tidak masuk pakai “Changeme”  C nya capslock
Tampilannya seperti ini, di OK kan saja
6. Tampilan Menu di Power system

7. Setting 6 external alarm, di LMT sudah harus muncul semua


TP48200A port UIM
External Alarm Name Alarm Type Remark Severity EMUB port
module
AC L1 Failured Power support Critical ALM1 S1
AC L2 Failured Power support Critical ALM2 S2
AC L3 Failured Power support Critical ALM3 S3
Rectifier Failured Environment support Major ALM4 S4
Rectifier High Voltage Failured Environment support Major
ALM5 S5
Rectifier Low Voltage Failured Environment support Major
Door NodeB Open Environment support Major use default use default
Shelter Door Open Environment support Major use default use default

Door Open = Burglar alarm & tidak perlu disetting. sudah automatic
8. Koneksikan kabel dari UIM02C ke EMUB (per port 2 kabel)

TP48200A port UIM


External Alarm Name EMUB port
module
AC L1 Failured ALM1 S1
AC L2 Failured ALM2 S2
AC L3 Failured ALM3 S3
Rectifier Failured ALM4 S4
Rectifier High Voltage Failured
ALM5 S5
Rectifier Low Voltage Failured
Batt low voltage ALM6 S6

9. Setting ALM port di power system web


AC L1,L2, L3 Failed
System setting Alarm parameters Power system (confirm)
Checklist AC Phase L1 failure, L2 failure, L3 failure
Select output relay, ALM 1untuk L1, ALM2 untuk L2, ALM3 untuk L3

Jangan lupa klik submit

Recti High & Recti Low  ALM 5


System setting Alarm parameter  Rectifier Group

Recti failure  ALM 4


System setting Alarm parameter  Rectifier
Battery Low voltage  ALM6
System setting Alarm parameter  Battery Group

10. Pastikan di LMT juga sudah disetting oleh integrator


11. Setting Battery sesuai dengan capacity per bank
Monitoring Battery group  Running parameter
12. Simulasikan 6 Alarm external tersebut dengan integrator