1. Connect the laptop to the SMU and configure the laptop IP to 192.168.0.9. Ping 192.168.0.10 to confirm the connection.
2. Access the TP48200A web interface at 192.168.0.10 and log in with the default username "admin" and password "000001" or "Changeme".
3. Configure 6 external alarms for AC failure, rectifier failure, battery low voltage through the power system web interface and connect the alarm ports to the EMUB monitoring system.
1. Connect the laptop to the SMU and configure the laptop IP to 192.168.0.9. Ping 192.168.0.10 to confirm the connection.
2. Access the TP48200A web interface at 192.168.0.10 and log in with the default username "admin" and password "000001" or "Changeme".
3. Configure 6 external alarms for AC failure, rectifier failure, battery low voltage through the power system web interface and connect the alarm ports to the EMUB monitoring system.
1. Connect the laptop to the SMU and configure the laptop IP to 192.168.0.9. Ping 192.168.0.10 to confirm the connection.
2. Access the TP48200A web interface at 192.168.0.10 and log in with the default username "admin" and password "000001" or "Changeme".
3. Configure 6 external alarms for AC failure, rectifier failure, battery low voltage through the power system web interface and connect the alarm ports to the EMUB monitoring system.
1. Connect the laptop to the SMU and configure the laptop IP to 192.168.0.9. Ping 192.168.0.10 to confirm the connection.
2. Access the TP48200A web interface at 192.168.0.10 and log in with the default username "admin" and password "000001" or "Changeme".
3. Configure 6 external alarms for AC failure, rectifier failure, battery low voltage through the power system web interface and connect the alarm ports to the EMUB monitoring system.
2. Setting IP laptop ke 192.168.0.9 subnet mask 255.255.255.0
3. Dari CMD, coba ping test ke 192.168.0.10.Kalau Reply artinya Laptop sudah terhubung ke TP48200A, kalau belum periksa kembali koneksi LAN cable, setting proxy di internet explorer, dll 4. Buka browser, masukkan IP 192.168.0.10. Jika tidak bisa masuk pakai https://192.168.0.10/relogin.asp
5. Masukkan user dan passwordnya
User : admin Password : 000001 ; Kalau tidak masuk pakai “Changeme” C nya capslock Tampilannya seperti ini, di OK kan saja 6. Tampilan Menu di Power system
7. Setting 6 external alarm, di LMT sudah harus muncul semua
TP48200A port UIM External Alarm Name Alarm Type Remark Severity EMUB port module AC L1 Failured Power support Critical ALM1 S1 AC L2 Failured Power support Critical ALM2 S2 AC L3 Failured Power support Critical ALM3 S3 Rectifier Failured Environment support Major ALM4 S4 Rectifier High Voltage Failured Environment support Major ALM5 S5 Rectifier Low Voltage Failured Environment support Major Door NodeB Open Environment support Major use default use default Shelter Door Open Environment support Major use default use default
Door Open = Burglar alarm & tidak perlu disetting. sudah automatic 8. Koneksikan kabel dari UIM02C ke EMUB (per port 2 kabel)
TP48200A port UIM
External Alarm Name EMUB port module AC L1 Failured ALM1 S1 AC L2 Failured ALM2 S2 AC L3 Failured ALM3 S3 Rectifier Failured ALM4 S4 Rectifier High Voltage Failured ALM5 S5 Rectifier Low Voltage Failured Batt low voltage ALM6 S6
9. Setting ALM port di power system web
AC L1,L2, L3 Failed System setting Alarm parameters Power system (confirm) Checklist AC Phase L1 failure, L2 failure, L3 failure Select output relay, ALM 1untuk L1, ALM2 untuk L2, ALM3 untuk L3
Jangan lupa klik submit
Recti High & Recti Low ALM 5
System setting Alarm parameter Rectifier Group
Recti failure ALM 4
System setting Alarm parameter Rectifier Battery Low voltage ALM6 System setting Alarm parameter Battery Group
10. Pastikan di LMT juga sudah disetting oleh integrator
11. Setting Battery sesuai dengan capacity per bank Monitoring Battery group Running parameter 12. Simulasikan 6 Alarm external tersebut dengan integrator