The Flamgard and TXgard Plus range of detectors offer reliable detection of flammable, toxic or oxygen gases with a local display and
optional relays.
Flamgard Plus:
Flamgard Plus is a Flameproof (Ex d), ATEX and UL certified flammable gas detector, which uses poison-resistant pellistors to detect
explosive levels of hydrocarbons, hydrogen and other flammable gases and vapours, including aviation fuel and leaded petrol vapours.
TXgard Plus:
TXgard Plus is a Flameproof (Ex d), ATEX and UL certified toxic or oxygen gas detector with local LCD display. A choice of sensors
are available enabling use in a wide range of applications, including water treatment, oil and gas exploration, chemical plants and steel
production.
TXgard-IS+:
TXgard-IS+ is a Intrinsically Safe (I.S.) toxic and oxygen gas detector with local LCD display. A wide choice of sensors is available for use
in a variety of applications. TXgard-IS+ is ATEX certified for use in Zone 0,1 or 2 hazardous areas, and also UL and cUL certified for use
in Division 1 or 2 hazardous areas.
Flexible output options
Optional relays for alarm and fault Can be used for switching local alarms
Non-intrusive calibration
Calibration can be performed locally without the need for hot work permits
Minimises operational down-time
Local display and buttons enable calibration without opening the junction box
Choice of catalytic beads for a wide selection of flammable gases and vapours
Gas detector tailored to your requirements
Extensive range of electrochemical sensors for toxic gases and oxygen
TXgard Plus and Flamgard Plus are constructed using marine grade aluminium
with a stainless steel sensor housing
Proven track record for operation in the harshest environments
TXgard-IS+ is made from tough carbon loaded nylon
Junction box: Marine grade alloy Junction box: Carbon loaded nylon
Enclosure material Sensor housing: 316 stainless steel Sensor housing: ABD Plastic
Ingress Protection IP65
Cable entries 2 x M20 or 1/2” NPT 1 x M20 or 1/2” NPT with adaptor
Operating temperatures -10oC to +55oC (14oF to 131oF) -10oC to +55oC (14oF to 131oF) * -20oC to +55oC (-4oF to 131oF) *
Display 3-digit LCD back-lit display, LED status indicator 2-Line, 16 character LCD
Response time T90 <15 seconds typically Contact Crowcon for a full list of sensor response times
Zone 0, 1 or 2
Hazardous area zones Division 1 or 2
Zone 1 or 2
(when connected via an isolation
device)
Ex II 2 G Ex II 1 G
Approvals Exd IIC T6 Gb Exia IIC T4 Ga
UL Class I Zone 1 UL Class I, groups A, B, C and D
* Figures shown exclude the sensors - Please contact Crowcon for a full list of sensor operating temperatures
Ammonia (NH3) 25 35 50, 100, 1000ppm - Acetylene (C2H2)* 2.3 0-100% LEL
Carbon monoxide (CO) 30 200 250, 500ppm 100, 250, 500, 1000ppm Ammonia (NH3) 15 0-100% LEL
Chlorine (CL2) - 0.5 5, 10, 20ppm - Butane (C4H10) 1.4 0-100% LEL
Chlorine dioxide CLO2) 0.1 0.3 1 ppm - Ethanol (C2H5OH) 3.1 0-100% LEL
Hydrogen (H2) - - 2000ppm, 50% LEL, 100% LEL - Ethane (C2H6) 2.4 0-100% LEL
Hydrogen cyanide (HCN) - 10 (MEL) 25ppm - Ethylene (C2H4) 2.3 0-100% LEL
Hydrogen fluoride (HF) 1.8 3 10ppm - Hexane (C6H14) 1.0 0-100% LEL
Hydrogen sulphide (H2S) 5 10 25, 50, 100, 200ppm 15, 20, 25, 50, 100, 200ppm Hydrogen (H2) 4 0-100% LEL
Phosgene (COCl2) 0.02 0.06 1ppm - Pentane (C5H12) 1.1 0-100% LEL
Phosphine (PH3) 0.1 0.2 2ppm - Petrol vapor 1.3 0-100% LEL
Sulphur Dioxide (SO2) 1 1 10, 20, 30ppm - Propane (C3H8) 1.7 0-100% LEL
STEL & LTEL figures are derived from the UK HSE document: EH40. Other thresholds may apply in countries outside the UK. Propanol (C3H8O) 2.1 0-100% LEL