Professional Documents
Culture Documents
04 Water Soure Heat Pumps
04 Water Soure Heat Pumps
04 Water Soure Heat Pumps
SYSTEMS
Water Source
Heat Pump
Systems
This TDP module will provide an understanding of the components in water source heat
pump systems, configuration options, system benefits, and many applications associated with the
overall system. WSHP systems have become a very popular choice for use in commercial
buildings where individual zones of control are required to maintain comfort conditions. Building
types that exhibit a simultaneous cooling and heating load are ideal candidates. WSHP systems
have other desirable characteristics like zoning capability, ease of design, and reliability so that
buildings where little or no reclaim will take place are often still considered for using a WSHP
system.
Printed in Syracuse, NY
CARRIER CORPORATION
Carrier Parkway
Syracuse, NY 13221, U.S.A.
Table of Contents
Introduction...................................................................................................................................... 1
Water Source Heat Pump Unit Operation........................................................................................ 2
Cooling Mode .............................................................................................................................. 3
Heating Mode .............................................................................................................................. 3
Mode Changeover........................................................................................................................ 4
WSHP System Operation................................................................................................................. 4
Cooling Mode (Summer Operation) ............................................................................................ 5
Heating Mode (Winter Operation)............................................................................................... 6
Intermediate Season (Spring and Fall Operation)........................................................................ 7
System Advantages and Disadvantages........................................................................................... 7
System Advantages...................................................................................................................... 8
System Disadvantages ............................................................................................................... 12
Product Overview .......................................................................................................................... 14
WSHP Components ................................................................................................................... 14
Compressor ............................................................................................................................ 14
Reversing Valve..................................................................................................................... 15
Refrigerant-to-Water Heat Exchanger ................................................................................... 15
Expansion Metering Device................................................................................................... 16
Refrigerant-to-Air Heat Exchanger........................................................................................ 17
Fan Assembly ........................................................................................................................ 17
Condensate Drain................................................................................................................... 18
Filters ..................................................................................................................................... 18
Unit Controls.......................................................................................................................... 18
Hydronic Accessories ............................................................................................................ 20
WSHP Unit Types ..................................................................................................................... 22
Horizontal Units..................................................................................................................... 23
Vertical Units......................................................................................................................... 24
Console Units......................................................................................................................... 24
Stack Units............................................................................................................................. 25
Rooftop Units......................................................................................................................... 26
Water-to-Water Heat Pump Units.......................................................................................... 27
System Overview........................................................................................................................... 28
Components ............................................................................................................................... 28
Cooling Tower ....................................................................................................................... 28
Boiler (Heat Adder) ............................................................................................................... 30
Air Distribution System ......................................................................................................... 32
Ventilation Air Distribution Units ......................................................................................... 32
Water Pumps.......................................................................................................................... 33
Air Separator and Expansion Tank ........................................................................................ 33
Controls.................................................................................................................................. 34
Example System Configurations................................................................................................ 34
Single-Story Buildings........................................................................................................... 35
Two to Four-Story Buildings ................................................................................................. 35
High-Rise Buildings .............................................................................................................. 36
System Variations ......................................................................................................................36
Variable Volume and Temperature (VVT®) System .............................................................36
VAV in the Interior Zone.......................................................................................................37
Variable Flow Systems .......................................................................................................... 37
Hot Water Pre-Heating...........................................................................................................38
Sprinkler Piping Integrated with the WSHP Loop.................................................................38
System Without a Boiler ........................................................................................................39
System With a Storage Tank..................................................................................................39
System Application Topics ............................................................................................................41
WSHP Units With Reheat.......................................................................................................... 41
Freeze Protection ....................................................................................................................... 41
Antifreeze Solutions...................................................................................................................43
Water Conditioning.................................................................................................................... 44
Ventilation System Energy Recovery ........................................................................................45
System IAQ Topics....................................................................................................................48
Acoustics Considerations...........................................................................................................52
Refrigerants................................................................................................................................53
Airside Economizer.................................................................................................................... 53
Water-Regulating Valves...........................................................................................................54
Maintenance ...............................................................................................................................54
Geothermal Systems ...................................................................................................................... 55
Closed-Loop Systems ................................................................................................................56
Open-Loop Ground Water Systems ...........................................................................................59
Geothermal System Advantages ................................................................................................60
Codes and Standards ......................................................................................................................61
Performance Related Codes and Standards................................................................................61
Safety Related Codes and Standards..........................................................................................64
UL/CSA and ETL .................................................................................................................. 64
System Sizing and Layout Tips .....................................................................................................64
WSHP Units............................................................................................................................... 65
Cooling Tower Selection ........................................................................................................... 66
Boiler (Heat Adder) ................................................................................................................... 67
Ventilation System.....................................................................................................................68
Piping Systems...........................................................................................................................71
Pumps.........................................................................................................................................73
Air Separator and Expansion Tank ............................................................................................74
Controls..........................................................................................................................................74
WSHP Thermostats and Controllers ..........................................................................................75
Water Sensors and Switches ......................................................................................................77
Pump Control .............................................................................................................................77
Cooling Tower and Boiler.......................................................................................................... 77
Ventilation System.....................................................................................................................78
System Safety and Alarms .........................................................................................................78
Reducing Operating Cost ........................................................................................................... 79
Overall System Control..............................................................................................................79
Summary ........................................................................................................................................ 81
Work Session .................................................................................................................................82
Work Session Answers .................................................................................................................. 86
References......................................................................................................................................89
Appendix A –
Water Quality ..........................................................................................................................90
WATER SOURCE HEAT PUMP SYSTEMS
Introduction
Water source heat pump (WSHP) systems have become a popular choice for commercial
buildings where multiple zones of control are desired. They can also be applied successfully in
smaller installations like residences. This TDP module will discuss both applications, but will
concentrate on the commercial applications. The usage of WSHP systems breaks down to roughly
60 percent new construction and
40 percent retrofit and replacement.
In this TDP module, we will learn
about the various types of water
source heat pump units that can be
used to comprise a HVAC system.
The internal components in a typical
WSHP unit and the function of each
will be explained. This will allow the
reader to understand how the WSHP
units operate when connected to a
system water loop. System
components will be then discussed.
Figure 1
These include boilers, towers, pumps,
piping, and controls. See Figure 1. Typical WSHP System
There are many overall variations for WSHP systems. They may be categorized into two
main groups. The first system type is a standard closed-loop system where the loop piping runs
inside the building. This system typically includes a boiler (also called a heat adder), a cooling
tower (also called a heat rejecter), pumps, and controls as shown in Figure 1.
The second type of WSHP system uses the Earth’s resources as a heat sink. These systems
are called geothermal systems. A lake, river, well, or the ground itself is used to add or remove
heat to maintain an operable water temperature. Some of these systems are closed-loop and some
are open loop. Open-loop means the water is used in a once-thru configuration. A separate section
on geothermal systems is included in this TDP.
Commercial WSHP systems are popular because they can supply simultaneous heating and
cooling. This leads to comfortable conditions in zones that have different requirements. A WSHP
system typically requires a dedicated outdoor air unit to maintain required ventilation levels as
specified by ASHRAE (American Society of Heating, Refrigerating, and Air Conditioning
Engineers) Standard 62.1. This TDP module will examine the various ways to deliver ventilation
air.
Control of the individual units, the water loop temperature, and other components in the
system are also covered in this TDP. Recommendations on proper application of units to
minimize radiated sound along with the required maintenance considerations are included.
This TDP module is meant to complement the Carrier System Design Guide on Water Source
Heat Pumps. In this TDP we will reference the Design Guide in several areas, the most notable
being the design process and layout of an example building. The Design Guide can be used for a
step-by-step approach to selecting and designing an entire WSHP system including an operating
cost analysis comparison to other systems.
After reading this TDP, the reader will understand how WSHP units and systems work, and
why they are a popular, reliable, and versatile alternative to other air-conditioning systems.
Cooling Mode
In the cooling mode, the WSHP unit’s refrigerant-to-water heat exchanger acts as a condenser
and its refrigerant-to-air heat exchanger acts as an evaporator. The reversing valve is energized
for cooling.
During the cooling mode, heat is extracted from the air by evaporating the refrigerant in the
refrigerant-to-air heat exchanger. This extracted heat plus the compressor heat is rejected into the
water loop. This is called the heat of rejection. Hot gas from the compressor discharge is directed
by the reversing valve to the refrigerant-to-water heat exchanger. Here the hot gas is condensed
into liquid as the gas gives up heat to
the colder water passed through the
exchanger. Liquid refrigerant then
passes through a metering device
that causes a drop in its pressure and
temperature. The cold liquid-vapor
mixture then enters the refrigerant-
to-air heat exchanger where it
evaporates. The indoor air is cooled
to condition the space. Cool
refrigerant vapor then is drawn into
the compressor where its
temperature and pressure are
increased so the cycle can be Figure 2
repeated. See Figure 2. Cooling Mode
Heating Mode
In the heating mode, the WSHP unit’s refrigerant-to-water heat exchanger acts as an
evaporator and its refrigerant-to-air coil acts as a condenser. The reversing valve is deenergized
for heating.
The hot compressor discharge gas is directed by the reversing valve to the refrigerant-to-air
heat exchanger, which will act as a condenser. Air is then heated as it passes over the refrigerant-
to-air heat exchanger as it condenses
the refrigerant and heats the space.
Liquid refrigerant flows through the
metering device to the refrigerant-to-
water heat exchanger that acts as the
evaporator. Heat is extracted from the
water loop as it passes through the
refrigerant-to-water heat exchanger
and the cold liquid refrigerant
evaporates. The cold vapor then is
drawn into the compressor and the
cycle repeats. See Figure 3. The heat
that is extracted is known as the heat
of absorption. Figure 3
Heating Mode
Mode Changeover
The reversing valve in the unit’s refrigeration circuit is located on the compressor discharge.
The reversing valve causes the changeover from cooling to heating mode and from heating to
cooling mode. In a reversible system, some of the traditional components must have special
features to allow for reverse flow. For example, the metering device must be capable of metering
flow in both directions. This type of metering device is usually called bi-directional.
In addition to the reversing valve and metering device, there are other design considerations
that make the heat pump different from the conventional air-conditioning unit. The compressor is
specially designed to operate over the wide range of compression ratios encountered in the
heating mode. Both the air and water heat exchangers are specially designed for WSHP use
because they must both evaporate and condense refrigerant. For example, the refrigerant-to-air
heat exchanger, when acting as a condenser in the heating cycle, must have adequate surface area
to keep the condensing temperature and pressure at reasonable levels.
When more zones need cooling than heating, the loop temperature rises (approaching 90° F), and
the cooling tower is activated to reject unneeded heat. A separate ventilation system provides
outdoor air to the zones. The ventilation system provides fresh air either directly to each WSHP
unit or by ducting the fresh air to within a few feet or less of each unit if a ceiling plenum return
air system is used. Additional discussion of the ventilation system can be found later in this
manual.
The loop flow is often variable. A VFD (variable Loop Flow
frequency drive) controlled loop pump varies the total loop
flow based on supplying water only to those WSHP units A VFD-controlled loop pump
whose compressors are running. In this way, pump energy is varies the total loop flow by
saved. See the Variable Speed Pumping section of this TDP. supplying water only to
those WSHP units whose
Let’s take a look at the system operating modes for compressors are running.
various times of the year to learn the heat recovery
capability of a WSHP system.
Because zones on different sides of a building will have their peak load occur at different
times, the total installed capacity of the WSHP units will usually be greater than the block load of
the building. The block load is the single largest combination of actual zone loads at a particular
time. The block-cooling load is seldom the sum of the zone peak loads and it is normally smaller
than the sum of these peak loads. In northern latitudes the block load occurs typically in late
afternoon in July or August.
Diversity can be found by dividing the block load by the sum of the peak loads for all zones.
Most large commercial buildings will exhibit some diversity ranging from 80 to 85 percent.
Unlike WSHP systems, central chilled-water systems can usually take advantage of diversity
in the sizing of the chiller. The chiller total installed tons need be only the size of the block load.
The installed WSHP unit’s capacity, however, will have a sum greater than the block load.
System Advantages
Low Installed Costs
Operating costs of WSHP systems compare favorably and often are lower than packaged,
unitary, and air-cooled central systems. Units serving individual zones can operate close to full-
load efficiency while the rest of the units in the system remain off. For example, a central system
that utilizes an air-cooled water chiller under the same building loads could be operating at a less
efficient part-load condition. Many WSHP systems offer the maximum diversity possible with
only those units operating that are required based on individual space control.
Standard WSHP units applied in closed-loop applications using a boiler and a cooling tower
provide competitive full load efficiencies with cooling EERs (energy efficiency ratio) of about
11.0 and heating COPs (coefficient of performance) around 3.7. High-efficiency models are also
available with cooling EERs above 15.5 and COPs of 4.5. At the higher efficiency levels the
WSHP system can compare favorably to central water-cooled chiller plant systems that use
centrifugal or screw chillers.
The value for EER is found by dividing the net unit cooling capacity (in Btuh) by the total
unit input Watts. The value for COP is found by dividing the total heat of output (in Watts) by the
total input Watts.
Operating Flexibility
Reliability
Since the early 1960s, WSHP systems have been in operation in the United States. According
to the Electric Power Research Institute (EPRI), WSHP systems have an average reliability of
98.5 percent – at least as well, if not
better, than all similarly priced
systems. According to EPRI studies,
the compressors used in WSHP units
have a long service life and very low
replacement rates.
Also, part of the reliability
advantage of a WSHP system is the
redundancy. If one heat pump unit
fails, the rest of the system stays
operational. See Figure 10.
Figure 10
Redundancy Advantage
Design Flexibility
Easy to Design
Figure 12
System Design Guide
System Disadvantages
As with any system, there are
some potential disadvantages with
WSHP systems as shown in Figure
15. Here is a brief discussion of them.
Acoustics
For installation, WSHP units are
located close to or in the conditioned
space. Each heat pump contains a
compressor and a fan that can
generate radiated sound. However,
there are various installation practices
based on the unit type that, when
followed, result in an acceptable Figure 15
WSHP operating sound level. Disadvantages of a WSHP
Condensate Piping
Each WSHP unit requires an individual condensate
piping line to be run from the unit. The drain pan under the Secondary Drain Pan
refrigerant-to-air heat exchanger may require chemical A secondary drain pan is used
cleaning to keep it free of algae that may clog the as a precaution on many
condensate drains. projects. This is subject to local
requirements.
A condensate pump may also be required on some
WSHP units in order to remove condensate that cannot drain by gravity. Also, there is potential
leakage of condensate from WSHP units into the finished ceiling if the drain pan were to
overflow.
Separate Ventilation System
Many central system and rooftop packaged designs incorporate the introduction of outdoor
air into the unit. All WSHP systems require a dedicated outdoor air unit. The exception may be
console type WSHP units where the wall box accessory can be used to introduce outdoor air.
However, this requires a wall penetration at each unit and is not popular with many architects.
Also, ASHRAE 62.1 requirements for ventilation air may be difficult to achieve without a
separate ventilation system.
Multiple Electrical Power and Control Wiring Connection Points
Each heat pump unit requires a power supply and disconnect. Control wiring also is required
between each space thermostat and the WSHP unit.
Product Overview
This chapter describes the components that comprise a WSHP unit along with various
equipment types and accessories that are available for use in WSHP systems. Its contents are
intended to be an aid in the early stages of system design when it is necessary to decide which
units are likely to be the best choice for a particular WSHP project.
WSHP Components
A WSHP unit is composed of the following internal components. The exact configuration
may vary slightly from manufacturer to manufacturer.
Compressor
Reversing Valve
Figure 17
Reversing Valve
Brazed-plate heat exchangers are also used on WSHP units (depending on the manufacturer
and unit size). They consist of a series of stainless steel plates brazed together with every second
plate turned 180 degrees as shown in
Figure 19. This design creates two
highly turbulent fluid channels that
flow in opposite directions over a
surface area with a high heat transfer
coefficient and good performance
characteristics. Counterflow of the
water and refrigerant maximizes heat
transfer. Each layer or circuit is linked
to an inlet and outlet via a manifold at
either end.
Closed Circuit
On tube-in-tube and brazed- Figure 19
plate heat exchangers, the Brazed-Plate Heat Exchanger
better choice is to use a closed
circuit for the loop water. On tube-in-tube and brazed-plate heat exchangers, the
better choice is to use a closed circuit for the loop water.
That is because the internal water passages on these types of condensers are not mechanically
cleanable. A closed-circuit cooling tower (or open tower with an intermediate heat exchanger) is
used with WSHP systems using these heat exchangers.
In the cooling mode, the refrigerant hot gas is condensed to a liquid in the refrigerant-to-
water heat exchanger and then metered, by the TXV, to the refrigerant-to-air heat exchanger.
The second type of expansion device, the capillary tube, is the simplest of all the expansion
device designs. It is a small diameter tube selected to produce the desired pressure drop that
allows for expansion of the refrigerant into a gas. This is accomplished by selecting the tube with
the correct diameter and length to produce a certain flow at a given pressure. On a capillary tube
there are no moving parts.
Standard efficiency WSHP units often use capillary tubes as their expansion device. Premium
efficiency models and larger units are equipped with TXVs.
Figure 21
Refrigerant-to-Air Heat Exchanger
Fan Assembly
Figure 22
Fan Assembly
Condensate Drain
Filters
Figure 24
Typical Filters
Unit Controls
Figure 25
Unit Control Board
Freeze Protection
Most WSHP units have an air heat exchanger and water heat exchanger freeze protection
device built in. For the water heat exchanger, a sensor is set at 30° F for standard closed loop
applications, or approximately 10° F for colder ground loop applications. The sensor is used to
shut off the compressor if water temperatures fall below this set point. For the refrigerant-to-air
heat exchanger, a sensor set at 30° F is typically used.
Condensate Overflow
This sensor is located in the condensate pan and will shut down the compressor if condensate
builds up in the drain pan indicating a potential overflow situation. This function is typically
automatic reset.
Unit-Mounted Controllers
Two basic unit-mounted WSHP controllers are typically available: a non-communicating
type (which means the controller is not capable of being connected to a building-wide network
communications bus) or a communicating type for use on a building wide network.
Hydronic Accessories
The following are several important accessories that are used with most WSHP installations.
Automatic balancing valves in piping packages are growing in popularity as they are a major
cost reduction method and offer constant flow control over a wide range of operating pressures
and flow rates. See Figure 28. The major advantage is the constant adjustment to operating
conditions. Automatic balancing
valves maintain proper system flow
control without periodic manip-
ulation of the flow control devices
to accomplish a balance in the
system. That means there is a
significant reduction in cost to
setup and maintain the system.
Figure 28
Manual and Automatic Valves
(Photo courtesy of Hays Fluid Controls)
Condensate Hoses
A condensate hose is often a clear, vinyl hose accessory. The hose comes with a pre-formed
trap. They are usually 46 inches in length and can be field cut to a desired length. Hoses are UL
94 rated and treated with anti-
fungicidal elements to allow for
long life with undisturbed flow.
Condensate hoses are available in
kit form, with end fittings, blow-
down fitting tee and clamps. See
Figure 29.
Ball Valves
Ball valves are used for full
open/closed service with limited
capability for control. Their
advantage is low cost, high
capacity, low leakage, and tight
sealing properties. Other valve Figure 29
types are best for balancing. Condensate Hose with Pre-Formed Trap
(Photo courtesy of Hays Fluid Controls)
Gate Valves
A gate valve can be used to isolate the WSHP system from the main supply and return.
Gate valves are sometimes preferred on larger heat pump applications. Gate valves, also known
as “stop valves,” are designed for shutoff duty. When the valve is in the wide-open position, the
gate is completely out of the fluid stream, thus providing straight through flow and a very low
pressure drop.
Strainers
A strainer can be used on the supply line to the heat pump to
Strainer
keep the refrigerant-to-water heat exchanger free of debris. Use
of strainers on individual WSHP units in closed loop A 16 to 20 mesh rating
applications is not always done, but a 16 to 20 rated mesh for the strainer is fine
strainer is recommended for any open system like a well or pond enough to strain out
application. On closed-loop systems, a central strainer is particles found in typical
recommended at the circulating pump. open-loop water
systems.
Automatic Shutoff Valve
Some WSHP systems utilize variable water flow in order to save pumping energy. When a
unit cycles off on a constant flow system, water continues to circulate through the refrigerant-to-
water heat exchanger. An automatic shutoff valve will stop the flow of water to the exchanger
when the compressor is deenergized, allowing the pump to save energy by only pumping water
through active units. A bypass line is typically installed in the piping system to allow minimum
pump flow.
Horizontal Units
Figure 30
Horizontal Unit
Units are hung from the ceiling with isolation hangers to minimize vibration and the
transmission of noise to the occupied spaces as shown in Figure 31. Typically, horizontal WSHP
units are suspended by their lifting bracket using threaded connector rods and a rubber grommet
isolator. On installations
where mostly larger units are
used (over 3 tons) and
vibration is a concern, the
units may be installed with
springs. Large capacity units
(3 tons or more) are typically
located over corridors, over
public spaces, or in utility
closets. These locations
isolate the units acoustically
from the conditioned space
and make them accessible for
service.
Figure 31
Typical Horizontal Unit Installation
Office Buildings
Horizontal units are the most commonly used WSHPs for
Horizontal units are the large office buildings. They occupy no floor space and are
most commonly used positioned above standard T-bar ceilings, which allow access for
WSHPs for large office
maintenance.
buildings. They occupy
no floor space and are Horizontal units are utilized for both interior and perimeter
positioned above zones, and are easily integrated with a separate ventilation
standard T-bar ceilings, system to provide fresh air to the zone. Air from the conditioned
which allow access for zone is returned to the horizontal unit through either a ceiling
maintenance.
plenum return or direct-ducted return system.
Vertical Units
Console Units
Figure 33
Console units are typically Typical Vertical Unit Installation in Utility Closet
available in capacities from 1/2 to 2
tons. See Figure 34. Console units
require minimal use of the
conditioned floor space. Units
typically come with a removable front
service panel, providing service
access to all major components.
Console units are suited for
installations beneath windows in
perimeter zones or in entryways.
Units are commonly used in perimeter
offices, hotel rooms, hospital rooms,
apartments, dormitories, and
condominiums. Figure 34
Console Unit
Stack Units
Figure 35
Stack units are typically available Typical Console Unit Installation
in capacities from 1/2 to 3 tons, and
are usually built into the wall with
only the face panel exposed to the
conditioned space. See Figure 36.
Exposed cabinet models are also
available. Units may also be located
in the conditioned space with the pipe
risers located in the wall. Stack units
are commonly used in high-rise
hotels, condominiums, and apartments
where floor space is limited and the
“vertical-stacking” feature of the
product can simplify piping
installation. Supply, return, and
condensate pipe risers are built into
the rear of the unit at the factory, Figure 36
thereby minimizing field installation Stack Unit
labor.
Supply air can be ducted from the top of the unit or supplied from a grille built into
the cabinet. Air is typically returned from the zone to the unit through a grille in the front of
the cabinet. Units typically
come with a removable
service panel to provide
service access to all major
components.
Ventilation with stack
units is typically provided by
a separate ventilation system.
Shown in Figure 37 is an
example of stack units
installed in a multi-floor
building. Direct return piping
is shown, but reverse return
piping is also utilized.
Figure 37
Typical Stack Unit Installation
Rooftop Units
Rooftop water source heat pump units are available in capacities from approximately 3 to
20 tons, and are ideal for applications where it is not desirable to install equipment in a ceiling,
utility closet, or small equipment
room. See Figure 38. Units are
commonly used in low-rise office
buildings, schools, hotels, motels,
nursing homes, and hospitals. Since
the units are located on the roof, no
floor space is required, and outside
walls need not be penetrated. Units
are typically located on the roof over
less acoustically critical areas like
storage rooms or rest rooms. Units
typically come with removable
service panels, providing service
access to all major components.
Figure 38
Rooftop WSHP Unit
A rooftop WSHP is used for applications where a larger tonnage unit is necessary and no
ceiling or floor space is available for other WSHP unit configurations. Unlike a conventional air-
cooled rooftop, a water source rooftop
can be connected to the building water
loop. See Figure 39.
No Available Space
A rooftop WSHP is used for
applications where a larger
tonnage unit is necessary and
no ceiling or floor space is
available.
These units can be piped in multiples in a parallel or series configuration. These arrangements
are meant to provide additional capacity beyond what a single unit can offer. If large capacity is
required, units may be piped in
parallel as shown in Figure 41. Total
pressure drop is the same as a single
unit.
In a series arrangement, lower
leaving water temperatures are
available than could be accomplished
by a parallel or single unit. The
leaving load water temperature of the
first unit becomes the load entering
water temperature of the second unit.
This arrangement provides an
additional decrease in water
temperature beyond the capability of a
single unit. Capacity control is Figure 41
accomplished by cycling the units on Series and Parallel Piping
or off.
For piping diagrams showing integration of water-
Preconditioning Ventilation Air
to-water heat pumps in a WSHP system, see the System
Water-to-water WSHP units are Variations section of this TDP.
used in several applications. One
is to precondition the ventilation
air in the dedicated outdoor air
unit by extracting heat or cool
energy from the common loop.
System Overview
Components
In this section, we will discuss the components of a closed-loop, commercial water source
heat pump system.
Cooling Tower
The purpose of the cooling tower is to reject excess heat from the common WSHP water
loop. The cooling tower is staged to be on full capacity when the loop starts to approach its upper
value of 90° F.
There are two types of cooling tower designs that are used for a closed-loop WSHP system:
• Closed-circuit cooling tower
• Open cooling tower with a heat exchanger
Both options ensure that the loop water never comes in contact with the atmosphere. This is
accomplished with the open tower by using a plate and frame heat exchanger. The WSHP loop
passes through one circuit and the tower loop through the other. Because loop water does not
come in contact with the atmosphere, both corrosion and scaling in the WSHP refrigerant-to-
water heat exchangers are eliminated. Scaling degrades WSHP unit performance and reduces
equipment life.
Both options make use of the evaporative cooling effect, which takes advantage of both
sensible and latent heat exchange. The cooling capability of a tower is dependent on entering wet
bulb temperature of the outdoor air, not the entering dry bulb temperature as with a dry cooler.
Since wet bulb temperatures are always less than the associated dry bulb temperature, the
potential for a greater cooling effect is realized.
If the rejected heat available from the WSHP units operating in the cooling mode is not
sufficient to meet the needs of zones requiring heating, a boiler (also known as a heat adder) is
required to maintain the loop temperature. The boiler may run on fossil fuel (oil or gas), or
electricity depending on the availability, convenience, and relative cost of the various forms of
energy.
Figure 45
Electric Boiler Piping
Water source heat pump units (other than console and water-to-water type) deliver a constant
volume of air through a low-pressure duct system to the conditioned space. This duct system
typically terminates at one or more diffusers located in the ceiling of the conditioned space. In
order to provide proper room air
distribution during both cooling and
heating modes of operation, care must
be given to the sizing of the ductwork
and the selection and location of the
diffusers.
Water source heat pump systems
benefit from using simple
symmetrical duct layouts as shown in
Figure 46. One of the benefits of
WSHP systems is that the ductwork is
a simple low velocity, low pressure
design. The design is simplified Figure 46
further if a return duct system is not Symmetrical Duct Layouts
used.
The basic WSHP air distribution design should accomplish the following objectives:
• Produce a low pressure drop within the confines of the space available for the ductwork
• Minimize sound levels by reducing airflow velocities
• Maintain low cost by using simple layouts and direct duct runs
can only accomplish approximately 20° F rise in the air. An energy wheel may be used with the
rooftop unit to precondition the outdoor air.
Water Pumps
Air separators are used in addition to an expansion tank in a closed system. Air separators
eliminate entrained air from the system. Circulation of the water through an air separator can
remove a large percentage of this air. This will improve the overall heat transfer efficiency of the
system (air is an insulator) and also reduce corrosion caused by dissolved oxygen.
An expansion tank should be
sized to handle the excess volume of
water that is a result of temperature
change. A water expansion tank
should be part of every closed-loop
system. See Figure 49. The change in
volume for a WSHP system is
approximately 2 percent for the range
of temperatures of a typical closed-
loop system. The change in water
system volume is usually about 1
percent for chilled-water systems and
about 3 to 4 percent for normal hot Figure 49
water systems in the 180 to 200° F Air Separator and Expansion Tank
range.
Controls
The system control requirements for WSHP are in addition to the unit-mounted controls
discussed earlier. The system level controls should have the ability to control the following:
• Loop water temperature by sequencing the heat adder and heat rejecter
• Occupied and unoccupied time scheduling
• Pumps and their sequencing
• Ventilation air supply
• Alarm, emergency shutdown, maintenance
• Warm up or cool down cycle
• Communications to other building systems like lights and fire safety (optional)
• Integration to outside building automation controls (optional)
For a discussion of the WSHP controls, refer to the Controls section of this TDP.
Single-Story Buildings
Single-story buildings are usually good candidates for WSHP systems. They may contain
areas of different sizes and usage patterns requiring different air conditioning needs. Larger areas
may require their own independently metered HVAC systems.
A single-zone cooling/heating
unit installed on the roof supplies
ventilation air. The arrangement in
Figure 50 shows how the major
components of a WSHP system can
be configured on ground level to serve
a one story building. Air is distributed
by ductwork in the ceiling plenum
space. Horizontal heat pump units can
be suspended above the ceiling to
leave more available floor space for
rental.
Figure 50
Single-Story WSHP Layout
Here in Figure 51 is a modern looking high-rent, medium size building that can be handled
economically by a WSHP System. On this building the WSHP system incorporates a central
station air-handling unit with energy
recovery located in a rooftop
penthouse. The boiler, tower, and
pumps have also been located in the
rooftop penthouse. Horizontal WSHP
units provide heating and cooling
throughout the rest of the building.
Figure 51
Two to Four-Story WSHP Layout
High-Rise Buildings
A VVT system can provide a small, separate zoning system for individual WSHP units. The
VVT concept would utilize a standard WSHP unit coupled to a variable volume and temperature
computerized control system. The
system includes zone dampers
controlled by special zone controllers
and zone sensors. All controllers
communicate to their respective zone
damper and then to the WSHP unit
through an air source unit controller.
A complete VVT system will have
numerous zone controllers arranged in
a linkage coordinator/zone controller
relationship. A VVT system uses a
system pilot user interface to provide
access and to program the VVT
system as well as any other device Figure 53
residing on the communication bus. VVT System with WSHP
See Figure 53.
The WSHP unit with VVT delivers a variable volume of
VVT Systems
either cold or hot supply air to each zone as load dictates.
For a complete discussion Constant airflow, however, is maintained through the WSHP
on VVT systems, refer to unit by use of a bypass damper and controller. For a complete
TDP-704, Variable Volume discussion on VVT systems, refer to TDP-704, Variable
and Temperature Systems. Volume and Temperature Systems.
The use of variable flow in the WSHP loop is widespread and can provide pump energy
savings for many buildings that have temporary occupancy areas like hotels, motels, or multiple-
tenant offices. Because the occupancy varies significantly during the occupied period, many of
the WSHP units may be in the off mode for significant periods of time. When individual WSHP
compressors are off, water flow to the unit’s refrigerant-to-water heat exchanger is controlled by
an automatic isolation valve. The result is a reduction in overall system flow and a savings in
pump energy.
The main loop pump must be
provided with a VFD (variable
frequency drive), controlled by a
differential pressure sensor located in
the piping. See Figure 55. The two-way
automatic isolation valves must be
provided on the return lines for each
WSHP unit. The valves should be slow
response type to prevent water pressure
damage. The WSHP manufacturer can
normally supply these valves as an
accessory. At the end of the water loop,
some automatic three-way valves (or a
single-bypass water line) should be used Figure 55
to provide a minimum flow as required Variable Flow WSHP System
by the boiler.
If PVC pipe is used for the loop piping in conjunction with a variable flow system, it is
important to avoid high loop water temperature. Piping could sag at high temperatures and low
flow. Again, a bypass line for minimum constant loop flow should be considered.
The purpose of using a few automatic three-way isolation valves is to bypass the WSHP unit
when the compressor is off and still maintain some water flow in the system. In this way, a
minimum circuit flow is ensured to protect the pump and/or boiler.
Buildings in warm climates typically have year-round cooling loads and are a good supply for
low-grade heat. Rather than reject this heat through the cooling tower, the rejected heat may be
used as pre-heat for the building’s domestic hot water needs in applications like hotels, hospitals,
and schools. A separate water-to-water heat exchanger is required to pre-heat the domestic water
with loop water.
When allowed by local building and fire codes, combining the building fire-sprinkler with the
WSHP water loop can lower installed cost. The design can be used with either single or double
riser systems. The piping to the WSHP is tapped into the sprinkler grid. The supply line to each
unit must include a shut-off valve and an automatic balancing valve. See Figure 56. The return
line requires a check valve and a
shut-off valve. In addition, the
piping layout for the two-riser
system includes a bypass with check
valve (around the cooling tower,
boiler, and pump) to provide a direct
path for the sprinkler water coming
in from the city in case of fire
emergency.
During fire emergency, when
sprinklers are activated, the pump of
the hydronic circuit is shut off. Each
sprinkler head is then supplied
directly with the necessary amount
of water under pressure from the city Figure 56
main or from a fire pump. During Sprinkler System Integrated with the WSHP Loop
normal operation, the loop water is
circulated.
The system has various other requirements related to codes governing the fire sprinklers and
may need a considerable amount of engineering work, as well as close coordination between the
HVAC, control, and sprinkler specialists during design, installation, and start-up. Applications are
subject to proper qualification by a consulting engineer and the applicable codes.
During the winter or intermediate seasons, some WSHP systems with substantial interior
cooling loads may generate more rejected heat to the loop than can be absorbed by perimeter
heating units. If that is the case,
excess heat can be stored in a tank
instead of rejected to the atmosphere
through the tower. In the heating
season, this excess heat can be used to
minimize the use of the boiler. See
Figure 58.
A storage tank increases the fluid
volume in the WSHP system. The
storage tank acts as a heat sink whose
heated or cooled water can be released
whenever it is needed. Depending on
the load profile of the building and the
local utility’s demand structure, a
storage tank can help minimize the Figure 58
electrical demand charges caused by System with Storage Tank
an electric boiler.
Storage tanks are sometimes used to maintain loop temperature during the morning warm-up
or cool-down period. During the morning warm-up period, all the WSHP units simultaneously
require their THA (total heat of absorption) from the water loop. The unit THA is shown in
WSHP printed literature or can be generated by their selection software. During this period, the
storage tank can help maintain the loop temperature from falling too low by adding heat to the
loop.
If the beginning of the occupied cycle requires a cool-down mode instead a warm-up mode,
all the heat pumps will start in the cooling mode. The rejected heat for each unit will enter the
water loop simultaneously. This value (in Btuh) is available from the manufacturer for each heat
pump. During this period, the storage tank can help maintain the loop temperature from rising too
high by adding cooled water to the loop.
Water-to-water heat pump units can use heating or cooling from the common water loop for
various applications like pre-conditioning the ventilation air or for reheating supply air. A typical
application during the cooling season is for the heat pump to pre-cool and dehumidify building’s
central ventilation air. On the load side of the water-to-water heat pump, chilled water is
circulated to the air-handling unit
where it cools and dehumidifies
ventilation air. The water absorbs heat
from the ventilation air and returns
back to the water-to-water heat pump
where the heat is removed via the
refrigeration circuit and then trans-
ferred to the source heat exchanger.
Heated water from the source heat
exchanger is used to reheat air in the
ventilation unit. The heat is then
absorbed from the water by the air in
the reheat coil and, if necessary,
returned to the cooling tower, boiler, Figure 59
or ground loop for further heat
Water-to-Water Heat Pump in Cooling Season Applications
rejection. See Figure 59.
During the heating season, the
water-to-water unit can extract heat
from the building’s exhaust system by
use of a coil in the exhaust air. The
unit uses the heat to provide hot water
to the ventilation unit’s heating coil to
temper the air entering the building.
On the load side of the heat
exchanger, hot water is circulated to
the air-handling unit for heating
ventilation air. As the heat from the
water is released to the air, the water
is circulated back to the unit. On the
source side of the unit, water is Figure 60
circulated through the heat recovery Water-to-Water Heat Pump in Heating Season Applications
coil, is heated by the exhaust airstream, and then is circulated to the water-to-water unit. Control
valves, as shown in Figure 60, maximize the process of extracting heat from the exhaust. Control
valves on the source heat exchanger supply and return water work to minimize or eliminate the
need for additional heat from boilers.
Freeze Protection
Water source heat pump systems that have piping exposed to loop temperatures below 32° F
should be protected from potential freeze-up.
The major component of a conventional WSHP system that may be susceptible to freezing is
the water coil inside the closed circuit cooling tower. If an open tower with heat exchanger is
used, the critical part of the system for freeze protection is the heat exchanger. To ensure proper
freeze protection, locate the heat exchanger indoors. Closed circuit towers are normally
winterized (protected from freezing) by one or more of the following methods:
Maintaining full tower coil flow year round is the easiest and most typical way of preventing
freeze-ups. Moving water should not freeze.
Locating the closed-circuit tower indoors reduces heat loss of the system loop and minimizes
the potential for freeze-up.
Sump Heater
especially when the concentration of the anti-freeze exceeds 10 to 15 percent. Use of anti-freeze
solution also results in a reduction of in WSHP capacity.
As the degree of concentration rises, the protection in the fluid increases from burst level
protection (where slush is going to form), to freeze protection (where no crystals at all are going
to form). A decision must be reached as to the level of protection desired. This can vary with the
type of system under consideration. Refer to TDP-622, Air-Cooled Chillers for a detailed
discussion of freeze versus burst protection.
Antifreeze Solutions
Antifreeze solutions are used more frequently in closed-
loop, geothermal systems where the piping is buried Fresh Water
underground than in conventional loop piping systems inside Water may contain chemical
the building. Their use can result in an increased pressure additives for corrosion,
drop through the refrigerant-to-water heat exchanger and a scale, and bacteria and still
decrease in capacity over fresh water. The term “fresh water” be considered fresh water.
applies to water that contains no antifreeze.
Glycols
The ability of glycols to lower the freezing point of water is the main reason that glycol based
heat transfer fluids are popular. Ethylene glycol based fluids are widely used and consist of
ethylene glycol (EG), water, and corrosion inhibitors. The term “inhibited” means that additives
have added to prevent (inhibit) the effects of corrosion. Ethylene glycol’s disadvantage is that it is
toxic if ingested and cannot be used where contact with food or potable water may occur.
Propylene glycol consists of a mixture of
Ethylene Glycol propylene glycol (PG), water, and corrosion
inhibitors. Propylene glycol fluids are
The disadvantage of ethylene glycol is
recommended for use where incidental contact
that it is toxic if ingested and cannot
be used where contact with food or with potable water is possible, or where use of a
potable water may occur. propylene glycol-based fluid is required by state or
local regulations.
Brines
Brine solutions are corrosive and leakage can cause damage to surrounding materials. It is not
recommended for use with WSHP systems.
While salt solutions provide satisfactory Brine
performance especially in low temperature applications
like ice rinks, they should be avoided in WSHP Salt solutions should be avoided
applications because of their potential for corrosion. in WSHP applications because of
The use of salt solutions will void some manufacturer’s their potential for corrosion.
warranties.
Methanol
This freeze protection fluid consists of a mixture of methanol and corrosion inhibitors and it
is sometimes used in closed-loop ground source heat pump applications. Methanol is also used
with industrial refrigeration. It has a low viscosity at the lower temperatures, which makes it
attractive from a pumping and heat transfer standpoint.
If antifreeze is used, methanol or propylene glycol solutions are the chosen fluids. Freeze
protection should be maintained to 15° F below the lowest expected entering loop temperature. For
example, if on a geothermal application the
Table 1
lowest expected entering loop temperature is Antifreeze Percentage by Volume
30° F, the freeze protection solution should Minimum Temperature for
offer protection down to 30° F - 15° F = Antifreeze Freeze Protection (°F)
15° F. So either 21 percent methanol or 10 15 20 25
30 percent propylene glycol is required. See
Methanol (%) 25 21 16 10
Table 1.
100% USP Food Grade
38 30 22 15
Propylene Glycol (%)
Water Conditioning
As we have seen, WSHP systems typically utilize small coaxial refrigerant-to-water heat
exchangers that must be kept clean to maintain proper heat transfer and system efficiency. The
entire loop should be cleaned and flushed before initial start-up. The refrigerant-to-water heat
exchangers are bypassed with hoses during this process.
Water quality varies from location to location and is unique for each project. Water
characteristics such as pH value, alkalinity, hardness, and specific conductance are important in
WSHP systems. See Appendix A.
A low pH and a high alkalinity can cause system problems. The term pH refers to the acidity,
basicity, or neutrality of the water supply. A pH below 7.0 means the water is acidic. A pH above
7.0 means the water is basic. Neutral water has a pH of 7.0. Water typically includes impurities
and hardness that must be removed. The required treatment will depend on the water quality and
the system type.
The three main problems that can
result from poor quality water are:
• Scale formation caused by hard
water reduces the heat transfer rate
and increases the water pressure
drop through the heat exchanger.
As water is heated, minerals and
salts are precipitated from a
solution and are deposited on the
inside surface of the pipe or tube.
See Figure 64.
• Corrosion is caused by absorption Figure 64
of gases from the air coupled with
Scale
water on exposed metal.
• Organic growths such as algae can reduce the heat transfer rate by forming an insulating coating
on the inside tube surface. Algae can also promote corrosion by pitting.
Figure 66
Side-by-Side Recovery
ASHRAE Standard 90.1 requires that individual fan systems that have both a design supply
air volume of 5,000 cfm or greater, and bring in at least 70 percent of the supply air from the
outside be equipped with energy recovery. Dedicated outdoor air units on WSHP systems are a
prime candidate for energy recovery. In this section we will describe several energy recovery
options that may be incorporated into the ventilation air unit for a WSHP system.
For more detailed information, see TDP-910, Energy Recovery.
Energy Wheel
An energy wheel is a revolving exchanger filled with an air-permeable medium. This medium
has a large internal surface area. The exchanger is designed to be installed between two adjacent
ducts with opposing flow directions. This establishes a counterflow heat exchange pattern similar
to that illustrated in Figure 67. The
wheel rotates between 10 and 60
revolutions per minute depending on
the application. When the wheel
passes through the higher-temperature
airstream, the media temperature
increases as heat is transferred and
stored in the media material. When
the media wheel rotates into low-
temperature airstream, the media are
cooled and release heat.
The wheel can be coated with a
desiccant, which allows for total
recovery. Total recovery means the
transference of both latent and Figure 67
sensible heat between the ventilation Energy Wheel with Rooftop WSHP
and exhaust airstreams. In this type
application, the building ventilation and exhaust systems are routed into single ducts and brought
in close proximity to one another. The wheel then rotates between the two airstreams.
Effectiveness is a term used to describe the ability of the energy recovery device to change
the condition of supply air from outdoor air to indoor air. The higher the effectiveness, the greater
heat or energy transfer occurs. Effectiveness for a rotary wheel is typically in the 60 to 80 percent
range. This is high relative to other forms of air-to-air recovery.
Wheels are often mounted inside the cabinet of the ventilation system air handler or rooftop
packaged unit. They are also available mounted in a separate cabinet with a supply and an
exhaust fan for use next to or remote from the ventilation unit. When packaged this way the unit
is called an ERV, or energy recovery ventilator as shown in Figure 67.
Heat Pipes
Heat pipe exchangers have the appearance of ordinary finned coils, but each successive tube
is independent and not connected to other tubes. Each tube is built with an internal capillary
“wick” material. The tube is
evacuated, filled with a fluid (like
refrigerant or water) and individually
sealed. See Figure 68.
With the tubes installed
horizontally, one-half of the heat
exchanger will act like an evaporator
and the other half acts as a condenser.
There is a partition between the halves
of the heat exchanger. In summer, the
high-temperature outside airstream
passes over half of the tubes. As the
internal refrigerant is warmed and
vaporized in the evaporator half, the Figure 68
incoming outdoor air is cooled. The Heat Pipes
internal vapor pressure drives the gas (Photo courtesy of Heat Pipe Technologies)
to the condenser end of the tube. In
the condenser end, the fluid releases the latent energy of vaporization as it condenses, thereby
transferring the heat from the incoming outdoor air to the cooler building exhaust air.
Heat pipes are useful for sensible heat transfer only. However, some small amount of latent
effect is achieved if the hot, humid outdoor airstream is cooled sufficiently to condense moisture
on the evaporator end of the unit.
A heat pipe’s typical effectiveness is approximately 40 to 50 percent. Heat pipes, like all
recovery devices, are most effective when the airflows are balanced. Heat pipes can also be
mounted in rooftop units and air handlers to precondition the ventilation air.
Fixed-plate heat exchangers are manufactured so there is little or no leakage between the
airstreams. Air leakage, however, may occur outside of the fixed-plate exchanger, such as within
the air-handling unit casing.
Effectiveness of heat transfer is about 60 to 75 percent. Airside pressure drops range from
approximately 0.35 in. wg to over 1.5 in. wg of pressure drop in each airstream.
Fixed-plate exchangers can be factory-mounted in air handlers or used in ventilation air
distribution units. However, wheels are used more often than fixed-plate heat exchangers because
they transfer sensible and latent heat.
Runaround Loops
A coil energy recovery runaround loop is a heat recovery system and distinct from the
individual pieces of equipment like energy wheels or heat pipes. Runaround systems circulate a
fluid (usually a glycol mixture) between two airstreams to transfer heat using standard finned tube
coils. See Figure 70. In the winter, the warm exhaust air from the building is transferred to the
circulating fluid, which warms the
supply airstream containing incoming
cold ventilation air. In summer, the
cool exhaust is transferred to the
circulating fluid, which then cools the
warmer supply air.
The supply air coil may be
installed in an air handler in a pre-
cool and pre-heat position. There
may also be multiple coil locations in
multiple exhaust and supply ducts.
The runaround loop piping connects
all the coils together. This is the major
Figure 70
advantage of this approach to heat
recovery. Runaround Loop
The major components of the system are: a pump, expansion tank, interconnecting piping,
exhaust and supply coils, and controls, which include a 3-way valve.
Runaround loops are very flexible and well suited to industrial applications or comfort-to-
comfort applications with remote supply and exhaust ductwork. The airstreams do not need to be
next to one another. There are no cross contamination issues.
Runaround loops have an effectiveness of approximately 50 to 60 percent in transferring
sensible heat.
accordance with construction codes and the generally accepted IAQ standards (ASHRAE
Standard 62.1-2004, Ventilation for Acceptable Indoor Air Quality).
In this section, we will discuss various topics that affect indoor air quality for a WSHP
system.
See TDP-902, Indoor Air Quality for detailed discussion of this topic.
The ventilation air system should deliver the recommended amounts from ASHRAE Standard
62.1. If a ceiling plenum is used to distribute ventilation air, design the ductwork so that the
ventilation air is as evenly distributed as possible. Ducting the ventilation air directly to the return
duct of each WSHP or directly to the conditioned space ensures the proper distribution of fresh
air throughout the building.
Unit Filters
Use the best filter the unit can safely accommodate. On many WSHP units, this means
upgrading to a 2-in. filter. Confirm that unit fans can accomplish the required static pressure of
the system with thicker filters. On the ventilation system unit, extended surface filters like bag
filters or cartridge filters can be used to accomplish greater efficiencies. Many WSHP thermostats
include a dirty filter light option. This is a good feature since it is often difficult to track filter
loading on systems with hundreds of units.
The dirty filter light on a standard water source heat pump wall thermostat is usually lit after
a cumulative number of fan run hours has been surpassed. The number of run hours before the
light is activated is usually adjustable on programmable thermostats. This does not take into
account the actual filter loading condition. Filter loading can vary depending on airflow and
environmental conditions. On some control systems, the filter may be equipped with a pressure
switch or differential pressure sensor that measures actual filter pressure drop. Filter pressure
drop is an actual indication of filter loading. The building control system can post an alarm when
filters need to be changed out.
If a ducted return is used, provide a suitable slot in the duct for filter access.
Condensate Removal
Humidity control is not typically a problem at full load. The WSHP unit refrigerant-to-air
exchanger will be at its coldest temperature and moisture is being removed from the space. Most
humidity problems occur at part-load. If the WSHP has one stage of cooling and is cycled on/off
to control room temperature, the room relative humidity may rise during the off cycle. This
phenomenon is common to all standard WSHP units up to approximately 8 tons in capacity since
they all typically have one compressor and use on/off control to maintain room temperature.
Units above 10 tons usually have multiple compressors to provide better part-load humidity
control.
Some new WSHP units
incorporate a single scroll compressor
with unloading capability. An internal
unloading mechanism provides an
unloading step of 67 percent of full
capacity. The compressor modulates
between the two capacity steps. The
result of this technology is better
overall unit and system efficiency and
control of humidity at part-load
conditions. See Figure 73.
Some manufacturers provide an
optional electronic fan speed control Figure 73
matched to thermostat or to a Compressor Unloading Technology
humidistat demand. Varying the fan speed in this manner keeps the cooling coil active for much
longer periods of time and significantly improves part-load humidity control.
Reheat capability with each WSHP unit is an excellent way to control space relative
humidity. The air is initially cooled by the refrigerant-to-air heat exchanger, then the air heated as
required to the desired space dry bulb and relative humidity. ASHRAE Standard 90.1 allows for
reheat as long as the source is site-recovered energy. This is the case with hot gas or loop water
reheat.
Lastly, the ventilation air handler can pre-cool the outdoor air to a neutral condition using
recovery coupled with an on board cooling coil as required. If outdoor air is ducted, it can be
conditioned to the unit supply air temperature and sent directly to the unit for mixing with return
air. This relieves the WSHP unit of any latent outdoor air loads and helps with part load humidity
and control.
The design ventilation airflow for each space in the building is established by ASHRAE
Standard 62.1. The design rates ensure adequate dilution of room contaminants and a healthy
occupant environment. The ventilation equipment is then set to provide the design airflow rate as
long as the building is occupied.
However, the occupancy rate for individual spaces, as well as the building as a whole, varies
throughout the day. For example, there can be a large drop in building occupancy around noon as
people leave for lunch. If the current occupancy is lower than the design occupancy, then a lower
ventilation airflow can be used. Operating at a lower ventilation airflow during these times can
save significant operating cost dollars, while maintaining adequate building IAQ.
Direct digital control systems are capable of utilizing CO2 sensors to track the occupant
density in the building and match the ventilation rate to occupancy needs. See Figure 74. This can
be done on a space-by-space level, and the
ventilation source is continually adjusted to
match space needs.
With a WSHP system, the ventilation air
duct from the dedicated ventilation air unit
can be routed into the unit inlet duct. The
inlet duct is a small length of ductwork
provided by the contractor. An internally
lined elbow is often used. This scheme
directs the correct amount of ventilation air
to each WSHP zone instead of just spilling it
in the proximity of the unit.
Certain areas of a multi-unit WSHP Figure 74
system can be designed for DCV usage, such CO2 Sensor
as conference rooms, cafeterias, or other
large zones where heavy ventilation amounts
may exist.
Acoustics Considerations
Following are recommendations for three major types of WSHP units with respect to sound.
Manufacturers offer software programs to assist in detailed analysis. Measured sound power
ratings on the equipment and a software program can be used to determine the sound attenuation
effect of the ceiling and room. In addition to the software analysis, there are many suggestions
that, if followed, can minimize unwanted noise reaching the conditioned space. See TDP-901,
Acoustics for detailed information on this subject.
Horizontal Units
Vertical Units
Vertical units tend to be installed in small equipment rooms or closets. To minimize sound
from vertical WSHP installations:
• Mount the unit on a pad made of high-density sound absorbing material such as rubber or cork.
• Prevent line-of-sight noise into the space if there is a grille mounted in the closet door for non-
ducted return applications.
• Use an elbow with turning vanes in the direction of the fan rotation to minimize discharge
turbulence.
Console Units
With console units, the fan and compressor are located within the space, and only the unit casing
design attenuates the transmission of these sound sources. The designer should review the decision to
utilize console units in general, and if concerned, use lowest fan speed to make unit selections.
Refrigerants
As of this writing, most manufacturers of WSHP units utilize R-22 refrigerant. R-22 has been the
refrigerant of choice for many years; however, this situation is in transition. R-22 contains chlorine,
which, if released to the atmosphere, has detrimental environmental effects. Therefore R-22 is being
phased out under current legislation. By the year 2010, R-22 cannot be used in new equipment.
Consequently, newer WSHP designs will utilize new blends like R-410A (Puron®) and R-407c.
With the year 2010 in mind, manufacturers are modifying their products in phases to use new
environmentally sound refrigerants. It should be understood that it is not possible to replace R-22
with R-410A in an existing WSHP unit. R-410A has far different pressure, temperature, and heat
of vaporization characteristics than R-22.
It is acceptable to have WSHP units of
different refrigerants on the same water loop.
For instance, new R-410A units can share the
same water loop as R-22 units. Please consult
TDP-402, Refrigerants for a full discussion
concerning refrigerants. See Figure 76.
Refrigerants
The phase out date for R-22 is 2010
when supplied in new equipment and
Figure 76 2020 for service.
Refrigerants Not Scheduled for Phase-Out
Airside Economizer
An airside economizer is a standard energy saving feature on most commercial air-handling
units, rooftop units, and indoor packaged units. ASHRAE Standard 90.1 mandates the application
of economizers in most regions of the country (with exceptions).
An airside economizer provides
“free” cooling with outdoor air
whenever the temperature and relative
humidity conditions outside are
acceptable. One type of economizer
control is a simple dry bulb changeover
economizer that uses outdoor air for
cooling whenever it is approximately
55° F or colder outside. At this
changeover temperature, the compres-
sors are turned off to save energy.
Shown in Figure 77 is an arrangement
for an airside economizer with water Figure 77
source heat pumps. Economizer for Horizontal WSHP Units
On a WSHP system, however, the use of an airside economizer is not required and might
actually result in greater overall energy consumption. Water source heat pump units providing
cooling with an economizer are not operating their compressors and, therefore, not rejecting heat
into the loop. The potential exists for the loop temperature to drop below the lower limit, since
some perimeter units may be absorbing heat from the loop. This may require the boiler to be
activated to maintain loop temperature. Running the boiler and consuming “new” energy may
cost more than is saved from shutting off the compressors.
If the loop water temperature during the economizer
Economizers mode of operation stays above the boiler loop water
activation temperature (approximately 60 to 65° F), then
If the loop water temperature
airside economizer operation with WSHP units is acceptable.
during the economizer mode
of operation stays above the In a WSHP system, the economizer would have to be
boiler activation temperature locked out to allow for the normal operation of the heat
(approximately 60 to 65° F), recovery from the interior zone cooling units to the perimeter
the air side economizer zone heating units. Coupled with the additional cost of duct
operation with WSHP units
outlets to each WSHP unit sized for full unit airflow (and the
is acceptable.
cost of controls), an economizer is not often utilized.
Water-Regulating Valves
A water-regulating valve can be used to maintain the proper head pressure for WSHP units
installed on widely fluctuating entering water temperature applications such as open loops. For
closed-loop applications, water-regulating valves are not typically necessary since the loop
temperature is maintained by the boiler and tower through the system controls. The water-
regulating valve responds to rising and falling refrigerant pressure and controls the flow through
the refrigerant-to-water heat exchanger for proper unit operation.
Maintenance
Some designers feel the maintenance aspects of a WSHP system are a disadvantage because a
typical commercial installation has many units positioned throughout the building. Some may be
under windows, while some may be
above ceilings, while others may be in
utility closets. However, WSHP units
are designed to operate while
requiring no greater amount of
maintenance than any other water-
cooled air-conditioning unit. See
Figure 78.
The components of a WSHP that
require maintenance are the
refrigerant-to-air coil, the blower
assembly, the filters, the refrigerant-
to-water heat exchanger, and the drain
pan. Let’s discuss maintenance Figure 78
requirements of each of the Maintenance of Ceiling-Mounted Unit
components.
Refrigerant-to-Air Coil
The coil should be inspected yearly and any lint or dirt should be removed from the fins. The
drain pan should be kept clean and free of any bacteria producing growth. The condensate drain
line must be open for the complete removal of any water that condenses on the coil in the cooling
mode.
Blower Assembly
Most units have direct drive blower assemblies so maintenance of belts is not an issue. Larger
units with belt drive blowers should have an annual inspection.
Filters
Filters must be changed at regular intervals in order to promote good IAQ. Dirty filters
restrict the airflow and degrade fan performance. Overall unit efficiency is affected. Using a dirty
filter warning light on the unit thermostat can help the operating staff maintain clean filters.
Since most closed-loop systems use a closed-circuit cooling tower, sediment inside the loop
after initial commissioning is generally not an issue. However, the individual refrigerant-to-water
heat exchangers should be inspected and chemically cleaned if waterside fouling has occurred.
Since all units are on the same loop, a representative unit can be inspected for film formation or
deposits inside the tubing.
The strainers in a system loop require cleaning if the water source is a well, river, or pond.
This is discussed in the geothermal section. A water quality test must be conducted prior to using
well, river, or pond water with a WSHP refrigerant-to-water exchanger. The services of a water
treatment specialist are recommended on systems where an open tower has been used. Deposits
of minerals and contaminants must be kept at an acceptable level.
Since some WSHP systems incorporate an antifreeze mixture, the mixture should be checked
periodically to maintain the desired solution percentage. Major pieces of equipment like boilers,
cooling towers, and pumps have manufacturer’s procedures that should be followed.
Geothermal Systems
Up to now we have been discussing closed-loop WSHP Limited Applications
systems where the loop piping is run inside a commercial
building. With closed-loop systems, a heat adder and heat Geothermal systems are
rejecter are used to keep the loop within a normal operating often used for residential
and medium to small
range of 60 to 90° F. This is the majority of applications for
commercial applications.
WSHP systems.
However, some WSHP systems can be designed to take advantage of the fact that the Earth’s
resources (ground or water) remain at a relatively constant temperature at a certain depth all year
long. Instead of using a conventional heat adder like a boiler and a conventional heat rejecter like
a closed circuit tower, the ground or water can be used as the heat sink for absorption or rejection
of heat.
The term geothermal is used to describe using the Earth’s ground or water as a heat sink for
WSHP systems.
Geothermal systems tend to be used for residential and medium to small commercial
applications. This is because land areas, boring costs, and once-thru water quantities are limited
on most applications.
Geothermal heat pumps can work with closed loops or open loops. Open loops are used with
well, river, or lake water applications. Open-loop designs are also known as ground water
systems. Closed-loop designs are often called ground-coupled or ground-loop systems.
Most manufacturers offer extended range WSHP units for use in geothermal applications.
These extended range units can handle entering fluid temperatures from 20 to 120° F (instead of
the standard 60 to 90° F range) and incorporate factory-installed insulation on the coaxial coil and
refrigerant and water piping to prevent condensate from dripping. The units also have field-
selectable freeze protection for well or loop application. Units used with ground water are usually
available with an optional cupro-nickel coaxial heat exchanger when there is concern about the
water quality. Thermostatic expansion valves are the required metering device. Extended range
water source heat pumps typically are used for all geothermal applications.
There are several factors that affect the design of a geothermal WSHP system. For instance,
assuming the same soil type, a small capacity system will require a relatively small ground-source
loop, while a larger capacity system will require a larger ground-source loop length.
Some of the application factors that are evaluated prior to designing a geothermal system are:
• Ground water availability and quality
• Loop installation costs
• Land area availability
• Subsoil conditions
• Local codes
• Owner preferences
Many regions have contractors specializing in the installation of the ground loop portion of
the earth-coupled system. Most heating and air conditioning contractors are not experts at soil
identification. There are two choices available: become proficient at soil identification through
study and field experience or have an independent soil testing laboratory or geologist perform the
identification. For the contractor not familiar with earth-coupled comfort systems, this second
choice will remove any doubt about this aspect of system design.
Closed-Loop Systems
Closed-loop systems consist of an underground (or underwater) heat exchange network of
sealed, high-strength, polyethylene plastic pipes and a pumping module. When in the cooling
mode, the loop fluid temperature will rise, and rejected heat is dissipated into the ground or water.
Conversely, while heating, the loop fluid temperatures fall, and heat is absorbed from the
ground or water. The pump module circulates the water/anti-freeze fluid within the piping
system. Closed loops do not require a ground water supply or drain, and they are not subject to
mineral build-up.
Closed loops can be installed in vertical or horizontal ground configurations, or submerged in
a pond or lake. When designed properly, all three alternatives operate with similar efficiency.
Typically high-density polyethylene (HDPE) pipe is used for all closed loop installations. Pipe
connections are heat fused to form strong joints. The heat-fusion process requires special tools
and training and should not be attempted without these items. The pipe manufacturer can provide
additional literature and training on this subject.
Loop piping has a life expectancy in excess
of 50 years. High-density polyethylene is the Life Expectancy
recommended pipe material that should be used Loop piping has a life expectancy in
in the ground-source loop. Materials such as excess of 50 years. High-density
PVC should not be used for a ground-source polyethylene is the recommended pipe
loop. material that should be used in the
ground-source loop
Polyethylene pipe is available in a variety of
diameters in straight lengths and coils. Fittings to perform various functions are also available.
For closed-loop systems, if the fluid may reach freezing temperatures, an antifreeze solution
is used instead of fresh water in the pipes. Refer to the Freeze Protection section of this TDP.
Horizontal Loops
Figure 80
Horizontal System Trench
Vertical Loops
Figure 82
Vertical Loop Installation
Figure 83
Pond and Lake Loops
This system utilizes two independent refrigerant circuits on the heat pump unit. A closed loop
of approximately 60 percent of the typical length is installed as the source for the first stage
refrigerant circuit with ground or city water as the source for the second stage refrigerant circuit.
See Figure 86. The unit will operate the majority of the time on the earth loop and only use the
well or city water a small percentage of the time. Benefits include a reduction in required land
area, less expensive earth loop, increased overall cooling and heating capacity and efficiency, and
much lower water usage than a standard once-thru ground water system. The annual well/city
water consumption is approximately 20 percent of a typical ground water application.
High Efficiency
The extremely high levels of efficiency are possible because a geothermal heat pump only
uses power to move heat, not produce it. A geothermal WSHP unit typically supplies about
4 kilowatts of heat for every kilowatt of electricity used. Three of these kilowatts of heat come
directly from the earth itself, and are clean, free and
Hot Water Generator renewable. Some geothermal units can also include
a hot water generator, which diverts a portion of the
Some geothermal units also include
supplied heat to the domestic water heater. This
a hot water generator, which diverts
a portion of the supplied heat to the option is used for residential systems and can
domestic water heater. provide a substantial portion of a family’s hot water
needs at a very low cost.
Geothermal heat pumps can provide high comfort levels for the conditioned space. By using a
relatively warm source of heat such as the Earth, supply air temperatures are maintained.
Geothermal heat pumps may also cycle less often than other forms of heat like fossil fuel boilers,
creating a more consistent indoor temperature.
Environmentally Sound
Attractive life-cycle costs are provided by the low operating and maintenance costs of
geothermal systems, even when the higher initial installation costs are considered. Life
expectancy of the WSHP unit exceeds 20 years. Electric utilities, recognizing the dual benefits of
high efficiency and low electric peak demand, often provide incentives to purchase these systems.
Standard 13256-1 uses different operating rating conditions than the previous standards. The
standard also uses a consistent methodology for including fan and pump energy to calculate
cooling capacity, heating capacity and energy efficiency ratio (EER). Tables 2 and 3 compare
ARI and ISO rating and performance test conditions.
Table 2
Comparison of ARI ISO Rating Test Conditions
Water-Loop Heat Pumps Ground-Water Heat Pumps Ground-Loop Pumps
Rating Tests
ARI/ISO ARI 320 ARI/ISO ARI 325 Hi ARI 325 Lo ARI/ISO ARI 330
Standard Cooling
Air dry bulb, °F 80.6 80 80.6 80 80 80.6 80
Air wet bulb, °F 66.2 67 66.2 67 67 66.2 67
Airflow rate, cfm per mfr per mfr per mfr per mfr per mfr per mfr per mfr
Liquid full load, °F 86.0 85 59.0 70 50 77.0 77
Liquid part load, °F 86.0 75 59.0 70 50 68.0 70
Liquid flow rate, gpm per mfr per mfr per mfr per mfr per mfr per mfr per mfr
Standard Heating
Air dry bulb, °F 68.0 70 68.0 70 70 68.0 70
Air wet bulb, °F 59.0 60 59.0 60 60 59.0 60
Airflow rate, cfm per mfr std clg std clg std clg std clg per mfr std clg
Liquid full load, °F 68.0 70 50.0 70 50 32.0 32
Liquid part load, °F 68.0 75 50.0 70 50 41.0 41
Liquid flow rate, gpm per mfr std clg per mfr per mfr per mfr per mfr std clg
External Static
Air H2O 0 0.1-0.3 0 0.1-0.3 0.1-0.3 0 0.1-0.3
Liquid, ft H2O 0 na 0 50 50 0 17
Table 3
Comparison of ARI ISO Performance Test Conditions
Water-Loop Heat Pumps Ground-Water Heat Pumps Ground-Loop Pumps
Performance Tests
ARI/ISO ARI 320 ARI/ISO ARI 325 ARI/ISO ARI 330
Maximum Cooling
Air dry bulb, °F 89.6 95 89.6 95 89.6 95
Air wet bulb, °F 73.4 71 73.4 71 73.4 71
Liquid, °F 104.0 95 77.0 75 104.0 100
Maximum Heating
Air dry bulb, °F 80.6 80 80.6 80 80.6 80
Liquid, °F 86.0 90 77.0 75 77.0 75
Minimum Cooling
Air dry bulb,° 69.8 67 69.8 na 69.8 80
Air wet bulb, °F 59.0 57 59.0 na 590 67
Liquid, °F 68.0 65 50.0 na 50.0 32
Minimum Heating
Air dry bulb, °F 59.0 NA 59.0 60 59.0 60
Liquid, °F 59.0 NA 41.0 45 23.0 25
Enclosure Sweat
Air dry bulb, °F 80.6 80 80.6 80 80.6 80
Air wet bulb, °F 75.2 75 75.2 75 75.2 75
Liquid, °F 68.0 80 50.0 50 50.0 50
Notes:
All ratings based upon 208v operation
Ground loop heat pump ratings based upon 15% antifreeze solution
For ease of comparison, most of the U.S. manufacturers list ARI/ISO performance for their
WSHP units. Please note that a rating based on ARI conditions will not compare equally with a
rating based on ARI/ISO conditions.
The ASHRAE (American Society of Heating, Refrigerating, and Air Conditioning Engineers)
organization establishes and maintains standards for the industry. ASHRAE Standard 90.1
defines minimum energy efficiency standards for a variety of building components, including air
conditioning equipment. This standard also applies to water source heat pumps. The standard
defines the minimum EER, IPLV (integrated part load value), and COP of the units. Below in
Table 4 are the current water source heat pump efficiency requirements.
Table 4
WSHP Efficiency Requirements
Subcategory ASHRAE 90.1 ASHRAE 90.1
or Minimum Efficiency Minimum Efficiency
Rating (1989) (2004 Code)
Size Category Standard Condition OBSOLETE APPROVED
ARI 320 85° F EWT 9.3 EER —
<17,000 Btuh
ISO-13256-1 86° F EWT — 11.2 EER
≥17,000 Btuh and 210/240 85° F EWT 9.3 EER —
< 135,000 Btuh ISO-13256-1 86° F EWT — 12.0 EER
70° F EWT 11.0 EER —
<135,000 Btuh 210/240
59° F EWT — 16.2 EER
77° F EWT 10.0 EER —
<135,000 Btuh 210/240
77° F EWT — 13.4 EER
Standard efficiency WSHP units have an EER range (which varies by size) of about 12.0 to
13.0 for closed water loop (boiler/tower) applications. Premium efficiency R-22 models have an
EER range of about 12.5 to 16.0. Premium efficiency Puron® refrigerant two-stage models have
full-load EERs from 15.0 to 16.0 and part-load EERs from 17.5 to 18.5 when used in closed-
water loop applications.
All of the EERs are higher for geothermal applications. That is because the entering water
temperature for EER calculations in geothermal systems (set by the ISO 13256-1 Standard) are
cooler than for conventional boiler/tower systems.
Energy Star
Energy Star is a voluntary labeling program of the U.S. Environmental Protection Agency
(EPA) and the U.S. Department of Energy that identifies energy efficient products. Qualified
water source heat pump products exceed minimum federal standards for energy consumption by a
certain amount, or where no federal standards exist, have certain energy saving features. These
units may display the Energy Star label.
Energy Star models exceed all levels of legislated efficiency and are designed for utility
and/or local and federal government rebate and energy-driven incentive programs.
As an example, a state energy agency may offer $140/ton for 14.0 SEER units up to 5 tons
and $500/ton for using Energy Star rated units on a geothermal application. These figures are for
illustration only. Actual rebate programs will vary based on the local situation.
ASHRAE Standard 90.1 was developed to establish building efficiency requirements in the
U.S.A. Energy Star efficiency standards exceed ASHRAE 90.1.
Several safety standards apply to water source heat pumps. Agencies such as Underwriters’
Laboratories, Inc., Canadian Standards Association, and ETL Testing Laboratories, test for
compliance to those standards. When a water source heat pump is approved by these agencies
from the required testing, it will bear a mark or label from the certifying agency.
UL (Underwriters’ Laboratories, Inc.) is an independent nonprofit organization that tests
products for safety and certifies them. The Canadian Standards Association (CSA) is a non-profit
association serving business, industry, government, and consumers in Canada. Among many
other activities, CSA develops standards that enhance public safety. For heating, ventilating, and
air conditioning, UL/CSA Standard UL 1995 / CSA C22, Heating and Cooling Equipment
applies.
The ETL Testing Laboratories, like UL, conducts electrical performance and reliability
testing. OSHA (Occupation Safety and Health Administration) recognizes ETL and UL as
nationally recognized testing laboratories. The ETL Listed Mark and Canadian-ETL Listed Mark
are accepted throughout the United States and Canada as compliance with nationally recognized
standards such as ANSI (American National Standards Institute), UL, and CSA. This
certification mark indicates that:
• The product has been tested to and has met the minimum requirements of a widely recognized
U.S. product safety standard.
• The manufacturing site has been audited.
• The applicant has agreed to a program of periodic factory follow-up inspections to verify
continued conformance.
If the mark includes a small “US” and/or “C,” it follows product safety standards of United
States and/or Canada respectively.
WSHP Units
Most manufacturers offer computerized selection programs to aid in the selection of
individual WSHP types. See Figure 88. Manual selection can also be made from product catalogs.
Regardless of the method
involved, the following
information is required to
make a selection for a water-
to-air WSHP unit:
• Total capacity required
• Voltage
• Airflow or static pressure
• Entering dry bulb and
wet bulb temperature
• Loop entering water
temperature during
cooling and heating
• Flow rate
• Unit configuration
The final selection of the
unit should ensure that it
meets the zone sensible heat
and latent heat loads. See Figure 88
Figure 89. Office applications
Selection Program Base Unit Screen
typically have an 85 percent
sensible heat ratio (15 percent
latent, 85 percent sensible),
and WSHP units are well
suited for this need.
Applications with a lower
sensible heat factor (higher
latent load) require selection
at a lower cfm per ton in order
to meet the sensible and latent
needs of the space. Oversizing
of units by more than
20 percent is discouraged
since the units will cycle more
often and lose control of zone
relative humidity at part load.
When the unit’s sensible
capacity is close to the
required zone sensible load, Figure 89
minimal cycling is assured. Unit Performances Screen
Many selections for WSHP units are based on a relatively low external static pressure of
about 0.25 in. wg for each unit. This is because the WSHP units are located close to the area they
serve and have minimal duct lengths. The final duct layout is usually not known at time of
selection. When the final duct design is finished, the unit fan can be checked. Since most units are
direct drive, different fan speeds are
available. If the unit selections are
based on low fan speed, and slightly
more capacity is required, the unit
can always be switched to higher
fan speed. See Figure 90.
The following water temp-
erature assumptions are often used
to select the units. During cooling,
the loop can rise to as high as 90° F.
Thus, for cooling duty, the WSHP
units can be selected to make
capacity at 90° F entering water
temperature. During the design
heating load, the building will be
unoccupied, and the loop
temperature could drop to 60° F as
an operational low temperature.
Thus, the units heating performance Figure 90
can be based on 60° F entering Final Selection Screen
water temperature.
On larger jobs, the cooling tower size is typically selected based on the following inputs (as
shown in Figure 91):
• Fluid type (fresh water, propylene glycol, etc.)
• Water flow (gpm) – this is the total loop water flow for all the units in the system.
• Entering fluid temperature – calculated as follows:
Figure 92
Tower Computer Selection Screen
(Photo courtesy of Baltimore Air Coil)
Figure 93
Boiler
To simplify the boiler selection and avoid under-sizing, three assumptions are often made:
1. There is no ventilation air load at start-up, and no heat gain credit from lights, people, or any
other zones.
2. The cooling tower is a closed-circuit type. It is installed indoors and does not contribute heat
loss to the loop.
3. There is no storage tank.
For systems without night set-back, the installed boiler capacity should sized between 70 and
90 percent of the block heating load. This varies based on the building configuration and amount
of perimeter space versus core space. Buildings with greater areas of perimeter spaces use the
90 percent rule.
For systems with night set-back, the boiler capacity should be
Boiler Sizing sized for the heat of absorption of all connected WSHP units. This
assumes that all units will be in heating mode simultaneously.
A second method for
boiler sizing with night Please note that a staggered start would avoid all the units starting
setback is to multiply simultaneously.
the block heating load A second method for boiler sizing with night setback is to
of the building by 1.25. multiply the block heating load of the building by 1.25. The
25 percent extra is to account for morning heating allowance.
Ventilation System
The ventilation air load contains
both a sensible and a latent
component. This load is best handled
by a dedicated ventilation air unit. See
Figure 94. If the load is handled by
the ventilation air system, then the
individual WSHP units only need to
be sized for their space loads. Since
the outdoor air load is variable, a
dedicated system can be selected to
maintain reasonably close control of
the ventilation air exit conditions. The
heat pumps will handle their
individual space loads leading to
better humidity control. The units will Figure 94
also be smaller to save valuable space. Dedicated Ventilation System
The ventilation system fan should be sized to supply the required outdoor air necessary based
on building occupancy and use per ASHRAE 62.1-2004 Standards. The cooling capacity for the
ventilation air unit typically is sized to deliver neutral air. The cooling capacity of the ventilation
air unit can be downsized by the use of energy recovery. For an example of this procedure, see
TDP-910, Energy Recovery.
A typical ventilation air unit design incorporates an energy recovery device such as an energy
wheel to precondition the outdoor air. Another popular design uses an indirect gas-fired heat
exchanger with modulating blowers and discharge air control to maintain a neutral discharge air
temperature of about 65 to 70° F in the cold weather months.
During the cooling season, a separate DX cooling system in the ventilation air unit takes the
preconditioned air from the energy recovery device and cools it to about 50 to 60° F for delivery
to the individual WSHP units. Other methods of delivery are used and they are discussed next.
The WSHP unit in the space handles the room sensible and latent loads, while the separate
ventilation air unit handles the ventilation air sensible and latent loads.
In applications involving open floor plans, it may be acceptable to supply ventilation air for
the entire floor through interior WSHP units. In this arrangement, large vertical WSHP units are
located in central mechanical rooms on each floor and utilized to condition the interior spaces.
Smaller WSHP units located in ceiling cavities are utilized to condition the perimeter spaces.
With open floor plans, supply air has a chance to mix and spread the ventilation air throughout
the entire floor. With a large vertical WSHP located in a mechanical room on each floor, a
centrally located vertical building shaft is used to provide ventilation air to the mechanical room.
In this design, the mechanical room itself is used as a mixture plenum. Outdoor air is brought
into the room and mixed with return air entering the room through grilles from adjacent ceiling
plenum returns. The vertical WSHP units condition the mixture of untreated fresh air and return
air.
Should the interior spaces have floor-to-ceiling partitions, this method will not prove feasible,
and ventilation air must be ducted to the perimeter horizontal WSHP units.
This method requires less installation cost. It is used with horizontal WSHP units that are
located in a ceiling return air plenum. The outdoor air is ducted in close proximity of each
horizontal WSHP unit’s return air
inlet. The WSHP unit fan draws the
fresh air in along with return air from
the plenum and delivers it to the
conditioned space. See Figure 96.
During summer operation the
outside air will be cooled and
dehumidified by the central unit. Care
should be taken to ensure that this
cold air does not enter in an
uncontrolled manner into the
conditioned space through ceiling tiles
or return air grilles.
During winter operation, the air
should be heated to neutral Figure 96
temperatures (about 65° F). Ceiling Plenum Return
Some designs deliver untreated outdoor air directly to the ceiling plenum. This approach is
not recommended as it can introduce warm moist air or very cold air into the building and the
WSHP units must then be sized to handle the outdoor air load along with the local space loads. A
better solution would be to utilize energy recovery in the dedicated ventilation air unit to provide
preconditioning of the outdoor air.
Ventilation air ductwork should be designed and sized based on standard low velocity duct
design. Use an equal friction rate of 0.10 in. wg per 100 ft. Maintain duct velocities of 1000 to
1400 fpm to keep the system quiet and the static drop low.
If the fans of vertical WSHP units located at each floor have to pull the fresh air down the
ventilation shaft, the shaft should be designed with a very low pressure drop. This can be
accomplished by sizing the shaft between 1000 and 1200 fpm for sheet metal ductwork.
Piping Systems
Loop Piping
As discussed earlier in this TDP, loop risers should be arranged for reverse return. In some
installations, this will be the natural layout. In other systems, reverse return will require an
additional length of vertical pipe, but will eliminate the need for balancing valves and balancing
work.
Typically the piping used in a WSHP system is schedule 40 black steel. Type L copper or
threaded schedule 40 black steel pipe is normally used for 2-in. diameter and smaller. In some
closed-loop water source heat pump applications, schedule 40 PVC piping has been used where
local codes and inspectors permit.
The procedure for sizing the pipe and determining pump horsepower is as outlined below. For
a complete example problem, refer to the TDP-502, Water Piping and Pumps. A pipe sizing chart
is shown in Table 5.
Table 5
Water Pipe Sizing
Pipe Size Design Parameters
Basic Design: Pressure Loss of 1 to 4 ft wg/100 ft
2” and smaller Velocity Limit: 2 to 4 fps
Can exceed 4 fps only is system has good air eliminator and low turbulence
Basic Design: Pressure Loss of 1 to 4 ft wg/100 ft
Over 2”
Upper Limit: 4 ft/100 ft
Condensate Piping
In the cooling mode, the evaporator coil will condense moisture from the airstream into the
drain pan. This condensate must be collected from each unit and removed. Since the condensate
piping often runs above finished ceilings, it is important to maintain a clean, debris-free path for
the water to flow to a central disposal point.
Disposal of condensate is regulated by local codes. In some locations, the condensate lines
from the individual WSHP units can be run into the storm drain system. In other areas it is
permissible to connect into the building sanitary system. In either case, a design practice that is
recommended is the use of an air gap between the unit condensate discharge and the building
drain system. This prevents the possible entrance of vapors from the building system into the
WSHP unit drain pan.
If condensate is not free to flow, the backup of water could lead to damaged ceilings and
walls. Therefore, all piping runs must be sloped to drain properly. Any areas where gravity
drainage is not possible should be equipped with a condensate pump.
Often, PVC piping is used for the condensate system. Insulation is required if the pipe surface
temperature may drop below the dewpoint of the air in the ceiling plenum. Insulation extending 6 to
8 ft from the trap is common practice. Copper piping may be required depending on local codes.
Pump catalogs, with pump performance curves, allow the proper pump to be selected. Most pump
manufacturers also have software programs that can select the optimal pump for your
application. Figure 98 shows the selection of a pump producing 150 gpm at 66 feet of head pressure.
The total head pressure of the pump will consist of the following: pipe friction loss, valves
including control valves, any accessories, equipment such as closed circuit coolers and boiler, the
WSHP unit that establishes the highest pressure drop circuit, air separators, etc.
Liquid Horsepower
Liquid horsepower is obtained by the formula, gpm ∗ head ∗ specific gravity ÷ 3960 (for
standard water sp gr = 1.0), where 3960 converts the equation units into horsepower (33,000 ft ∗
lb per minute, divided by 8.33 lb per gallon).
Brake Horsepower
Brake horsepower (bhp) is the power required to drive the pump and equals the liquid
horsepower divided by the overall efficiency of the pump. As a rule of thumb, the efficiency is
usually about 65 percent.
Controls
This section covers basic principles and general guidelines that apply to the design and
selection of controls for WSHP systems. See the Carrier System Design Guide Water Source
Heat Pumps for additional information.
The following control system components and functions will be discussed in this section.
• WSHP thermostats and unit controllers
• Loop control panels
• Water sensors and switches
• Pump controls
• Cooling tower and boiler controls
• Ventilation systems
• System safety and alarms
• Methods of reducing operating costs
• Overall system controls
Controllers
Two basic unit-mounted WSHP controllers are typically available. The first type of controller
is non-communicating and can be wired to a standard thermostat, a programmable thermostat, or
a communicating thermostat. A non-communicating thermostat is not capable of being connected
to a building-wide network communications bus. A non-communicating thermostat is the normal
choice for many WSHP applications where internal operational and safety information about the
WSHP unit is not needed on a building-wide basis.
The other type of WSHP controller
is capable of communicating on a
building-wide network bus and may be
connected to a space sensor, a
thermostat, a communicating sensor, a
linkage thermostat, or a CO2 sensor for
indoor air quality monitoring and
control. See Figure 100. The WSHP
controller’s ability to communicate
allows all internal operational and
safety information of the WSHP to be
available to an overall building
management system. This is useful for
report gathering, tracking, service and Figure 100
maintenance activities, and energy PremierLink™ Communicating Controller
management options.
Linkage Thermostat
New technology has led to a “linkage thermostat.” A linkage thermostat is a programmable
communicating thermostat designed to control multiple WSHP units equipped with communicating
controllers. With functionality similar to a programmable thermostat, the linkage thermostat can
control up to eight WSHP units.
Linkage is a term used to describe a sophisticated “handshake” between the major components that
comprise a total system. This connection actually passes packets of information back and forth between the
players, such as the WSHP units and the loop controller. The WSHP system utilizes linkage software to
“link” the other system components with their source of air (WSHP units) to form a coordinated system.
The panel can work with variable speed pumping arrangements. It also has control of loop alarms,
safeties, and can signal an energy management system for central shutdown on system fault. See
Figure 102 for a
system schematic.
Figure 102
Loop Control Panel Schematic
Summer Operation
During the summer, the loop water temperature is maintained between 60 and 90° F for
efficient system operation. The loop controller sequences the heat rejector when loop water
temperature rises to about 83° F and provides full tower operation with high fan speed if loop
water temperature continues to rise to 90° F.
Winter Operation
In winter, the loop controller sequences the heat adder when loop water temperature falls to
about 65° F and provides full boiler capacity if loop water temperature continues to fall to 60° F.
Alarms
The loop controller can also provide an alarm and emergency shutdown signal as follows:
• Alarm if loop temperature rises to 100° F, shutdown at 105° F (high limit)
• Alarm if loop temperature falls to 55° F, shutdown at 50° F (low limit)
• Alarm and shutdown for lack of loop water flow.
Pump Control
It is normal practice is to have the circulating pump Standby Pump
in operation 24 hours per day. The pumps should be
The use of a standby pump is
automatically sequenced by the loop control panel. If the highly recommended. Water
main pump does not start or produce adequate flow, the source heat pump systems
standby would be energized. In the event of no flow, a cannot cool or heat without flow
shutdown signal is sent to all WSHP units. This prevents unless each unit has an
the WSHP units from tripping on a safety device. auxiliary electric heater.
The boiler control depends on the type of boiler used. For instance, many fossil fuel boilers
require isolation from the WSHP loop because they operate at higher temperatures. Condensation
inside the heat exchanger is prevented by regulating a valve to divert sufficient water through the
boiler to maintain inlet water temperature at approximately 140° F while allowing the WSHP
loop to operate at normal temperatures. A water temperature controller will energize the boiler
and a separate boiler-circulating pump, if provided. The on-board boiler control regulates the
burner. Hot water will be blended into the loop as required to maintain loop temperature.
If the heat adder is electric, the heating element is staged by the water temperature controller
to maintain loop temperature.
Most loop control systems have a temperature reset option that automatically raises the
minimum loop water temperature during periods of extremely cold weather. This allows the
WSHP units in heating mode to deliver more capacity during extreme conditions.
Ventilation System
There are several ventilation air unit types that can be used, such as: DX packaged units, gas-
fired make-up units with cooling, or central station air-handling units with heating and cooling.
Regardless of the unit type, the objective of the ventilation unit in summer is to deliver outdoor
air that has the sensible and latent load (moisture) removed. That way, the outdoor air does not
impose a load on the heat pumps units and they can be sized for the loads in the spaces they
serve. In winter the objective is to deliver neutral air. To help accomplish this, the ventilation air
unit may incorporate sensible or latent recovery, which preconditions the outdoor air in both
summer and winter.
A separate ventilation air unit controller that maintains discharge air temperature is required.
The controller modulates or stages the cooling and heating to maintain a ventilation air
temperature of approximately 60° F. At the onset of the occupied mode, the ventilation system
remains inoperative for a pre-determined period of time (during building warm-up). Then the
outdoor damper opens and the fan starts. Conditioned air is sent to the heat pump inlets, or
conditioned space. Details on these three most common methods of delivery are discussed earlier
in this TDP. Reheat, if available from an onsite energy source may be used to temper the air.
When the WSHP system switches to the Unoccupied Mode, the cooling or heating mode is
deenergized, the fan stops, and the air damper closes. Two-speed fan motors or VFDs can be used
to adjust outdoor air amounts based on schedule or occupancy rates.
against possible malfunctions. In case of malfunctions of either the boiler or the tower, the
temperature limit controls (high and low) will initiate an emergency shutdown of the system. The
cooling tower dampers are of the positive shutoff type, and will drive to the closed position in
case of power failure to protect against coil freeze-
up at low ambient temperature.
Loop Flow Alarms
For WSHP units, in the event of a system
Loss-of-system loop flow is critical
fault, the general shutdown should be made from a and interlocks should result in
central control point. If this is not done, the WSHP stoppage of boiler and tower
units will continue to operate until each one goes operation. An alarm should notify
off on its own safeties. This would require manual building personnel so corrective
resetting of each unit when the system fault has action can be initiated as the system
been corrected. may now be using the standby pump.
Reduced Demand
The starting of individual WSHP units should be staggered upon start-up or after an
emergency shutdown, to reduce peak simultaneous demand. A random start timer in the on-board
WSHP controls typically accomplishes this. Also, a storage tank can assist in the heating the loop
at morning start-up, reducing demand if an electric heat adder is used.
Optimal Start/Stop
Optimal Start/Stop calculates the WSHP start and stop times to match anticipated
occupied/unoccupied times based upon load conditions, previous start/stop history, outdoor air
temperature and how long the building has been unoccupied. This reduces the amount of energy used.
The Master Control Panel provides centralized control for the entire WSHP system in the
building. See Figure 104. The panel coordinates and monitors all these functions:
• Occupied or unoccupied mode
• Pumps
• Ventilation system.
• Individual unit thermostats
• Night setback
• Manual override, when in the
unoccupied mode
• Alarms and emergency
shutdowns
• Staggered start of the WSHP
units (this function may be
handled by random timers in the
WSHP controllers and not needed
in the master control panel)
• Outdoor air and loop water
temperature
• Status of all equipment
• System emergency shut down
• Optimized start and stop of the
building
Computer Access
Figure 104
The highest level of system control includes the utilization of building and WSHP system
management functions.
Control of building lighting, parking lot lights, and other miscellaneous equipment not
already controlled by the loop controller and master panel controller is possible. A data collection
module can time and record building temperatures, pressures, etc. The module can also keep track
of building consumables like kWh and gpm and can record equipment runtimes for service
operations. A loadshed function can monitor and control building electrical demand by shedding
electrical loads as pre-programmed. Tenant billing modules can monitor and record any use of the
thermostat override buttons in the building and assigns after hours usage charges to tenants
accordingly.
Summary
Water source heat pump systems have become a very popular choice for use in commercial
buildings where individual zones of control are required to maintain comfort conditions. Building
types that exhibit a simultaneous cooling and heating load are ideal candidates. This is because the
water loop can transfer heat of rejection from the cooling units to the heating units. This provides
heat recovery, which leads to low system operating costs. However, WSHP systems have other
desirable characteristics like zoning capability, ease of design, and reliability so that buildings
where little or no reclaim will take place are often still considered for using a WSHP system.
There are several WSHP unit types available. The more popular units types are consoles,
horizontal ducted (above the ceiling), vertical (for use in a utility closet), stacked (one above the
other), and rooftop models. A single WSHP system may utilize several types of units all connected
to the same water loop.
The WSHP system is configurable by adding or deleting some of the major components as
required to best fit the application. Typical systems used in commercial buildings incorporate a heat
adder and a heat rejecter to maintain the water loop within the 60 to 90° F range. Earth coupled
WSHP systems utilize buried loop piping, which acts as the heat sink and heat source since the
temperature of the ground is constant. This allows for the elimination of the heat adder and rejecter
in most cases. The piping can be buried in a vertical, horizontal, or spiral pattern depending on soil
conditions and surface area available.
Another WSHP configuration uses lakes, rivers, or a well to serve as the heat sink. These
systems may not recirculate the water. They can be a once-thru design, so proper straining of the
water is important in these applications. The designer must be sure proper water flow is available as
WSHP units require approximately 3 gpm per ton.
Water source heat pump systems are often designed with a dedicated outdoor air unit to supply
ventilation air per ASHRAE 62.1 requirements. Often, heat recovery devices like heat pipes, energy
recovery wheels or runaround loops are incorporated into the unit to precondition the outdoor air.
Other ventilation air alternatives include using a motorized damper in the outdoor air wall box if
using console units or utilizing a separate rooftop WSHP unit as the ventilation air unit. In all cases,
the outdoor air should be filtered and conditioned so as not to introduce dust and humidity into the
building.
Lastly, there are a variety of control options that are offered with WSHP systems. Most often,
the manufacturer of heat pump units can supply a complete control system that ranges from a
simple programmable thermostat to a complete DDC network that incorporates computer access,
energy management and building automation control functions.
Work Session
2. List the six types of water source heat pumps that are available.
_____________________________ _____________________________
_____________________________ _____________________________
_____________________________ _____________________________
3. True or False? Water source heat pumps have more problems with moisture control during
full-load conditions than with part-load conditions. ____________________
4. Name the advantages of a WSHP system for each of the four customer types: owners,
architects, facility staff, and the utility company.
Owners: _________________________________________________________________
________________________________________________________________________
Architects: _______________________________________________________________
________________________________________________________________________
Facility Staff: ____________________________________________________________
________________________________________________________________________
Utility Company: _________________________________________________________
________________________________________________________________________
5. What is the typical WSHP loop temperature range and how is it maintained?
________________________________________________________________________
________________________________________________________________________
6. An earth-coupled WSHP system often eliminates what typical components from a standard
closed-loop WSHP system?
________________________________________________________________________
________________________________________________________________________
7. What kind of heat rejection unit is normally used in a closed-loop WSHP system and why?
________________________________________________________________________
________________________________________________________________________
8. What is an alternative to using the heat rejecter type described in question 7 above?
________________________________________________________________________
________________________________________________________________________
____________________________ _______________________________
____________________________ _______________________________
____________________________
10. Name the three conditions for which the WSHP controls must provide a signal for emergency
shutdown.
________________________________________
______________________________________
________________________________________
12. Which type of piping configuration utilizes the least amount of land area in an earth coupled
WSHP design and why?
________________________________________________________________________
________________________________________________________________________
13. Explain how an airside economizer can be incorporated into a WSHP system. Define any
limitations and explain why.
________________________________________________________________________
________________________________________________________________________
14. Explain why it is important to install a standby pump for a WSHP system.
________________________________________________________________________
________________________________________________________________________
16. Name three common methods of supplying outdoor air preconditioning using heat recovery
from the building exhaust on a WSHP ventilation system. Which require the exhaust and
ventilation airstreams to be close together?
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
17. Name four methods of ventilation and delivery design for WSHP systems.
________________________________________
________________________________________
________________________________________
________________________________________
18. Explain the purpose and function of adding a storage tank to a WSHP system.
________________________________________________________________________
________________________________________________________________________
19. What is the current performance standard for WSHP units in the industry and what standards
did it replace?
________________________________________________________________________
________________________________________________________________________
20. Describe why an electric heater might be used on a WSHP unit and how it works in the system.
________________________________________________________________________
________________________________________________________________________
21. List the seven components of a WSHP system and a brief description of their function.
_______________________________________________________________________
_______________________________________________________________________
_______________________________________________________________________
_______________________________________________________________________
_______________________________________________________________________
_______________________________________________________________________
_______________________________________________________________________
Notes
3. False, Water source heat pumps have more problems with moisture control during part-load
conditions than with full-load conditions. That is because at full load the unit will run for
longer periods of time and remove moisture from the air. During part-load operation, single-
stage WSHP units will cycle on and off and can lose control of relative humidity in the space.
4. Owners and developers: WSHP systems offer low first cost, zoning flexibility, operating cost
savings, and ease of design.
Architects: WSHP systems provide design flexibility and require minimal building space.
Facility Staff: WSHP systems offer low maintenance costs and minimal downtime.
Utility Company: WSHP systems offer low electrical usage and generating costs through
electrical demand limiting and control.
5. The circulating loop temperature is maintained between 60° F and 90° F. When more zones
require heat than those needing cooling, the loop temperature drops (approaching 60° F), and
the boiler is activated to make up the heat deficit. When more zones need cooling than those
needing heat, the loop temperature rises (approaching 90° F), and the cooling tower is
activated to reject unwanted heat.
6. The boiler and the cooling tower. That is because the earth serves as the heat sink and heat
source in an earth coupled system.
7. The most cost effective and popular choice for systems under approximately 250 tons is the
closed-circuit cooling tower. In this design, the heat exchanger is an integral part of the
cooling tower – isolating loop water from the atmosphere and thus minimizing the potential
for corrosion and scaling of the individual heat pump heat exchangers.
8. An open cooling tower can be used but must incorporate a plate heat exchanger and a pump
to isolate the WSHP loop from the open tower loop.
10. Loop temperature rises past 100°F (shut down at 105° F – the high limit)
Loop temperature falls to 55°F (shut down at 50° F – the low limit)
No loop water flow detected in the system
11. The selection of controls for a WSHP system should fulfill the following major objectives:
Ability to alter the operating mode (Occupied/Unoccupied)
Control of indoor temperature conditions
Control of loop water temperature
Control of the ventilation system
Provide equipment and system safety
Reduced operating and maintenance cost
12. An earth coupled system that utilizes vertical piping loops occupies the least area because it
accomplishes most of the required heat sink requirements beneath the ground’s surface, not
parallel to it.
13. An airside economizer can be utilized with a WSHP system. However, since the economizer
will be taking the place of operating the compressors on cooling duty, the potential exists to
draw the water loop temperature down too low. That is because there is no heat being rejected
into the loop by units in cooling mode while perimeter units are absorbing heat while in the
heating mode. A heat adder would be required to keep the loop temperature up. The boiler
energy consumed may offset the economizer savings. To prevent this, controls can lock out
the airside economizer operation, and activate the heat pumps in mechanical cooling mode if
the loop temperature approaches 60° F.
14. A WSHP system requires water flow in order to maintain set points during both the occupied
and unoccupied modes. The compressors cannot be operative with no water flow. Since the
loop should be operative whenever a compressor requires flow, a standby pump is a practical
design.
15. A VFD controls the main loop pump. Each WSHP unit should be fitted with a two-position
valve to close automatically if the compressor cycles off. In fact, this arrangement is
becoming more common than constant flow systems.
18. A storage tank can store excess heated loop water and use it during the morning warm up
period in the morning. That way, the boiler does not have to be sized for the total warm up
load which involves all units simultaneously requiring heating.
20. Electric heaters can be added to WSHP units as a way of avoiding the installation of a central
heat adder like a boiler. When spaces require heat the WSHP units can operate as normal
absorbing loop water heat to the point where the loop temperature drops to near 60° F. At that
point instead of activating the boiler, the WSHP units requiring heat will turn off their
compressors and turn on the electric heat coil. Eventually, if some units are operating in the
cooling mode the loop temperature will rise. Installations not requiring a lot of supplementary
heat or those where the electric costs are not the concern of the owner may use this scheme.
21. Heat pumps – provide cooling and heating to the conditioned space
Boiler – maintains 60° F minimum loop temperature by adding heat
Cooling tower – maintains 90° F maximum loop temperature by rejecting heat
Circulation pumps – maintain loop flow to all components
Expansion tank and air separator – allow expansion of loop volume and remove entrained air
Controls – maintain lop water temperature and zone set points
Air distribution ductwork – delivers air to zones
References
AEXUSA, Kalamazoo, MI. www.aexusa.com
Andrew Chiasson, P.E., Research Engineer at Geo-Heat Center Oregon Institute of
Technology, Klamath Falls, OR (provided review of geothermal chapter)
Air Conditioning and Refrigeration Institute (ARI), Arlington, VA. www.ari.org
ASHRAE, Atlanta, GA. www.ashrae.org
Carrier System Design Guide – Water Source Heat Pumps
Hays Fluid Controls, Dallas, NC. www.haysfluidcontrols.com
Heat Pipe Technologies., Gainesville, FL. www.heatpipe.com
International Ground Source Heat Pump Association (IGSHPA), Stillwater, OK.
www.oksate.edu
Learning Objectives:
After reading this module, participants will be able to:
• Demonstrate how a WSHP unit works in the cooling and the heating mode.
• Review the six types of WSHP units and explain the application of each.
• Describe the function of the internal components of a typical WSHP unit.
• Show how WSHP units function together in a complete system for summer, winter, and
intermediate season.
• Describe the function of each component that comprises a WSHP system.
• List the advantages and the disadvantages of a WSHP system.
• Compare the differences between a closed loop, earth coupled, pond and well water
WSHP system.
• Describe various WSHP system variations such as variable speed pumping, systems
without a boiler, and use of a storage tank.
• Explain WSHP application topics like freeze protection, refrigerants, economizers, and
maintenance of WSHP systems.
• Describe typical WSHP controls and how they control individual units, the water loop, and
the WSHP system.
Supplemental Material:
Book Instructor CD
TDP No. Cat. No. Cat. No. Title
TDP-703 06-796-068 06-797-068 Variable Air Volume Systems
TDP-631 796-056 797-056 Rooftops, Level 1: Constant Volume
-- 811-10088 -- Carrier Demand Controlled Ventilation Design Guide
-- 795-202 -- Carrier System Design Guide – Water Source Heat Pumps
Instructor Information
Each TDP topic is supported with a number of different items to meet the specific needs of the
user. Instructor materials consist of a CD-ROM disk that includes a PowerPoint™ presentation
with convenient links to all required support materials required for the topic. This always includes:
slides, presenter notes, text file including work sessions and work session solutions, quiz and
quiz answers. Depending upon the topic, the instructor CD may also include sound, video,
spreadsheets, forms, or other material required to present a complete class. Self-study or student
material consists of a text including work sessions and work session answers, and may also
include forms, worksheets, calculators, etc.
Carrier Corporation
Technical Training
800 644-5544
www.training.carrier.com