Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 5

ELECTRICAL POWER SYSTEM DIVISION

TEST REPORT

Customer Name & Address: M/s. Ritis Meera Infra LLP


M/R. Clean Solar (Gulbarga) Pvt.
Village- Jonnakeri
Taluk - Aurad
Pin code-585326
Dist. - Bidar (Karnataka)

Customer’s Reference: SRF No. 033 Date

TEST REPORT NO. TESTED ON RECOMMENDED TEST DUE PAGE NO.


TSC / 19 - 20 / 033-01 10 May 2019 ---- 1 of 2

Details of device under testing (DUT):


DUT : Bus Bar Testing Cable Mate
: Power : Aluminium - XLPE
Make : Siemens Cable Cross Section : 11 kv .1R-3*400 SP.MM Armournd Cable
Dept : RMU - 9 Loc : Incomer Transformer

Standards used:

Sl. No. Nomenclature Make & Model Sl. No Traceable to

5 kV Insulation
1 Motwane / IT-51 A08197L18 Transcal
Tester
Contact
2 Resistance Scope / CRM-100B 2301.02AD1312 Transcal
Meter
Note:
1. The Testing Report. relates only to the above DUT
2. Publication or reproduction of this report in any form other than by complete set of the whole
report & in the language, written, is not permitted without the written consent of Transcal.
3. Corrections/erasing, invalidate the Testing Report.
4. Testing of the DUT are traceable to National standards/International Standards
5. Any error in this report should be brought to our knowledge within 45 days from the date of this Report.
6. Results Reported are valid at the time of and under the stated conditions of measurements.

Tested By Authorised By

M.S.Siva C.S Koushal


(Testing Engineer) (Testing In-Charge)
N

: 10 May 2019

PAGE NO.
1 of 2

nium - XLPE
00 SP.MM Armournd Cable

Validity

01 Dec 2019

26 April 2020

f the whole

he date of this Report.


surements.

Authorised By

C.S Koushal
(Testing In-Charge)
TEST REPORT NO. TSC / 19 - 20 / 033-01 Page No: 2 of 2

Transformer Testing Results :

1 . Insulation Resistance Test :


Circuit Reference Megger Used Resistance Measured in GΩ

R-N 5000 > 1000


Y-N 5000 > 352
B-N 5000 > 1000
R-Y 5000 > 1000
Y-B 5000 > 1000
B-R 5000 > 1000
R-R' 5000 > 1000
Y-Y' 5000 0.0
B-B' 5000 0.0

2. Contact Resistance Measurement :

Circuit Reference Source Used Resistance Measured in μΩ

R-R' 100 A DC Infinity


Y-Y' 100 A DC 247.0
B-B' 100 A DC 274.0

3. Remarks : R-Phase Found Faulty

Tested By Authorised By

M.S.Siva Koushal C.S


(Testing Engineer) (Testing in charge)