Download as pdf or txt
Download as pdf or txt
You are on page 1of 60

2018 Catalog

PIX RoF
Air Insulated Switchgear up to 17.5  kV
Now with roll-on-floor EasyPact EXE vacuum circuit breaker

Medium Voltage Distribution

schneider-electric.com/PIX RoF
Whether you generate, distribute or
PE91012

use electric power, in today’s economic


climate you need an optimized and
effective solution which provides
reliability, safety and ease of use.

2 | PIX Easy Catalog schneider-electric.com


Contents

Overview 6

PIX RoF range 22

Functions and characteristics 28

Components 36

Installation and connection 52

schneider-electric.com PIX RoF Catalog | 3


PIX RoF Your requirements

Safety

Simplicity

Efficiency

Reliability

4 | PIX RoF Catalog schneider-electric.com


PIX RoF Our solutions

Safety
•• Designed using the latest tools and techniques ensuring that the
highest level of operator safety is always provided
•• Fully type tested according to the latest IEC standards for
50 and 60 Hz
•• Internal arc tested up to 31.5 kA with AFLR
•• Full metal partition PM class switchgear
•• Embedded mechanical and electrical interlock provides
operator safety

Simplicity
•• PIX RoF has been designed for easy access to all compartments
and is simple to operate and maintain
•• PIX RoF design provides effortless rack-in/rack-out circuit
breaker feature, closed-door circuit breaker operation, inspection
window indicating circuit breaker status
•• The intuitive HMI guides the operator to perform various
operations and indicates the current status of the components
•• VPIS on the front door can instantly indicate voltage presence on
a given cable
•• Fast access via QR codes to products' technical documentation
(cubicles, breakers, relays), stored in the "digital safe repository"

Efficiency
•• Compact dimensions start with a 600 mm wide cubicle for ratings
up to 1250 A and a 800 mm wide cubicle for ratings up to
2 500 A, for up to 17.5  kV rated voltage
••The bus metering and earthing functions are coupled in a single
cubicle to optimize space

Reliability
•• Maximizing service continuity to minimize downtime thanks to
LSC-2B IEC classification
•• Busbar segregation between cubicles (option)
•• It is designed to have a 30 year service life in relation to
installation, operation and environmental conditions

schneider-electric.com PIX RoF Catalog | 5


Overview

6 | PIX RoF Catalog schneider-electric.com


Overview

Field of application 8

Safety 9

Simplicity 10

Efficiency 11

Reliability 12

EcoStruxureTM ready solutions 14

Schneider Electric services 20

Quality assurance 21

schneider-electric.com PIX RoF Catalog | 7


Overview Field of application

PIX RoF offers you: A versatile solution


• An engineered solution tailored to your The PIX RoF Air Insulated Switchgear adapts to all electrical power distribution
specific requirements requirements up to 17.5 kV. It is an indoor metal enclosed switchgear intended for
• A solution with low ownership costs Medium Voltage applications such as those found in HV/MV or MV/MV substations,
thanks to reduced maintenance and the buildings and industries.
highest levels of service continuity
Energy Buildings - Industry - MMM - O&G
• Enhanced safety for your staff and
Primary substation (>20 MVA) Heavy industry primary substation
operators (10-50 MVA)
• Advanced control and monitoring options
• A network of our global support centers

Large switching substation (>4 MVA) Large MV consumers site (10-50 MVA)

MV/LV substation (<4 MVA) MV consumers site (1-5 MVA)


PE91015

Applications
Buildings
• Healthcare
• Hotels
• Airports
• Banking & Finance
PE91013

Energy & Infrastructure


• Electrical utilities
• Smart cities

Industry
PM106611

• Food & Beverage


• Automotive
• Water and Wastewater
• Small industries
• Life sciences

8 | PIX RoF Catalog schneider-electric.com


Overview Safety
High level of operational safety

Internal Arc tunnel for enhanced ALFR


Notes
protection
LSC2B (Loss of Service Continuity

PM106614
IEC 62272-200)

PM106613
This category defines the possibility of keeping
other compartments energised (in service) when
opening a main circuit compartment.

IAC (Internal Arc Classification)

PM106615
The metal-enclosed switchgear is classified
for internal arc protection in accordance with
IEC 62271-200 where AFLR is defined as follows:
Type of accessibility
• A: Restricted access to authorized personnel
only. Sides of the enclosure which meet the
criteria of the internal arc test
• F: Front side This internal arc solution protects the operator when in the vicinity of switchgear
• L: Lateral side under normal operating conditions.
• R: Rear side
• The internal arc classification is an option in accordance with IEC 62271-
200 and EN 62271-200. It refers to the effect of internal excess pressure on
covers, doors, inspection ports, vents etc. Moreover, the thermal effects of the
internal arc and its origins on the enclosure, as well as escaping hot gases or
incandescent particles, are taken into account.
• As a reminder, metal-enclosed switchgear and controlgear are granted Internal
PM106636

Arc Classification if all the following criteria are met:


-- No 1: Correctly secured doors and covers cannot be opened
-- No 2: No enclosure fragmentation occurs during the arc fault
-- No 3: Arcing does not cause holes by burning through the classified sides
up to a height of 2 000 mm
-- No 4: Indicators do not ignite due to the effect of hot gases
-- No 5: The enclosure remains connected to the earthing point
• Internal Arc Classification IAC has been conducted successfully for PIX Easy

Operator safety
• Enhanced protection against unintended contact provided by a complete metal
enclosure around the switchgear components
• PIX RoF, equipped with a digital bay controller, provides enhanced operator
safety for control, monitoring and complete automation of the switchgear from a
remote control room
• For safety reasons, the switchgear cubicle can only be operated with the
enclosure door closed and the operator facing the front
• For protection against operating errors, the PIX RoF features a logically
designed, continuous mechanical and electrical interlock system
• Capacitive voltage testing system for zero voltage verification
• PIX RoF has been tested for Internal Arc Classification AFLR in accordnace with
IEC 62271-200 up to 31.5 kA 1s

schneider-electric.com PIX RoF Catalog | 9


Overview Simplicity
Easy operation providing service continuity

Easy to install
PM106616

PIX RoF architecture has been designed to accomodate a wide range of installation
requirements:
• Face to face
• Connections can be accessed from the bottom
• Easy to access with plenty of space for cable connection and/or to terminate
bulky and rigid 3 core cables:
- 600 mm for 1 250 A
- 570 mm for 2 500 A

Easy to operate
• Intuitive single line diagrams on the front door of each functional unit provide
a clear description of the cubicle components and power flows. This helps to
optimize operations
PM106617

• With the EasyPact EXE breaker, PIX RoF features direct access to an opening
pushbutton on the front door: this ensures better service continuity
• Voltage Presence Indicators (VPIS) are present on the front door of each
functional unit: this can instantly indicate voltage presence on a given cable!
• A floor rolling trolley provides quick and easy rack-in/rack-out operation for
withdrawable devices

Easily access technical documentation


PIX RoF uses Schneider Electric digital innovation to optimize the customer
experience:
• A QR code is on the front door of each cubicle: scanning it provides access to a
web page displaying technical information
• Safe Repository: it also provides access to a "digital safe" containing customized
data related to each cubicle : e.g.: manuals, brochures, reports, maintenance
procedures
PM106465

Safe repository

10 | PIX RoF Catalog schneider-electric.com


Overview Efficiency
OPEX optimization

Compact design = space efficiency


PM106619

• Thanks to the ingenious design of PIX RoF, many functions can be housed in a
compact cubicle
• Outgoing with currents up to 1 250 A are housed in 600 mm wide cubicles.
2 000 and 2 500 A are installed in 800 mm wide cubicles
• Incomers up to 1 250 A are installed in 600 mm cubicles. 800 mm cubicles
house these between 1 250 A and 2 500 A maximum
• Bus couplers and risers are installed in 600 mm cubicles for ratings up to
1 250 A and 800 mm cubicle for beyond and up to 2 500 A
• Functions for incomers and feeders are housed in compact cubicles:
600 mm for ratings up to 1 250 A and 800 mm for ratings up to 2 500 A
• With heights of between 2 300 mm and 2 800 mm (in line with the Internal Arc
solution), the cubicles can be installed in any building
• The busmetering and earthing functions are coupled in a single cubicle to
optimize space
• All cubicles provide energy with natural cooling with no need of forced
ventilation

PIX RoF with EasyPact EXE:

Smaller footprint
Less volume
PM106635

schneider-electric.com PIX RoF Catalog | 11


Overview Reliability
Systematic Testing

Loss of service continuity


PM106620

The cubicle is a LSC2B (Loss of Service Continuity Category) type as defined


by IEC standard 62271-200; in other words, the medium voltage parts are
compartmented using metal partitions (PM class) which are connected to earth and
which separate:
• The busbars
• The withdrawable part (circuit breaker, disconnector truck or metering truck)
• The MV connections, earthing switch, current sensors and voltage transformers,
as required
• The LV cabinet
In terms of personnel, PIX RoF with EasyPact EXE provides to a high level of
protection; when a compartment containing a main circuit is open, the other
compartments and/or functional units may remain energised.
The low voltage auxiliaries and monitoring unit are in a control cabinet separated
from the medium voltage section.
Four basic cubicle layouts are offered:
• Incomer or feeder
• Busbar coupler
• Busbar riser
• Busbar metering

Strength of experience
• Fully compliant with IEC standards for AC metal-enclosed switchgear for rated
voltages above 1 kV and up to 53 kV

• More than 50 years experience in medium voltage switchgear design

High quality design


PIX RoF with EasyPact EXE switchgear only uses key Schneider components
that are designed in-house: full breaker (mechanisms, VI bottles), instrument
transformers, relays.

12 | PIX RoF Catalog schneider-electric.com


Overview Reliability
Systematic Testing

A major asset
PM106622

In each of its business units or manufacturing plants, Schneider Electric integrates a


functional organization whose main role is to check quality and monitor compliance
with standards.
This procedure is:
• Uniform throughout all departments
• Recognized by many customers and approved organizations
But above all, its strict application has allowed us to obtain the recognition
of an independent organization: Bureau Veritas.
The design and manufacturing quality system is certified in accordance with the
ISO 9001:2008 standard for quality management systems.

Strict and systematic checks


During manufacturing, each functional unit is subject to systematic, routine testing
with the aim of checking the quality and conformity of the following features:
• Measurement of the opening and closing speeds
• Dielectric test
• Testing of the safety systems and interlocks
• Testing of the low voltage components
• Conformity with drawings and diagrams
The results are recorded and approved by the quality control department on the
test report of each device, thereby ensuring product traceability.

Type tested
The electrical and mechanical ratings of the PIX RoF with EasyPact EXE switchgear
and controlgear have been proven by comprehensive type tests.
The type tests were performed in independent and accredited test laboratories in
accordance with international norms and standards. The results are recorded in the
appropriate test records and are made available on request.

schneider-electric.com PIX RoF Catalog | 13


Overview EcoStruxure ready solutions
What is EcoStruxure ?

The EcoStruxure™ architecture and interoperable technology platform bring


together energy, automation, and software. It provides enhanced value around
safety, reliability, efficiency, sustainability and connectivity.
EcoStruxureTM systems deployed since
2007 with the support of our 9 000 system
integrators. Turn data into action
EcoStruxure™ architecture lets customers maximize the value of data.
Specifically, it helps them:
• Translate data into actionable intelligence and better business decisions
Efficient asset
• Make informed decisions to secure uptime & operational efficiency thanks to
management
real-time control platforms
Greater efficiency with
predictive maintenance • Provide complete electrical distribution visibility by measuring, collecting,
aggregating and communicating data
helping to reduce downtime.

Connect Collect Analyze Take action


24/7 connectivity
Real-time data everywhere,
anytime to make better
informed decisions.
Connect Capture critical Convert data into Drive action
everything data at every level, meaningful through real-time
from shop floor from sensor analytics information and
to top floor to cloud business logic
Increased safety
Proven design and experience
combined with fast embedded
CLOSE THE LOOP
arc detection to enhance
people's safety and equipment
protection.

EcoStruxure Platform

Building Data Center Industry Infrastructure

Apps, Analytics and Services


Cybersecurity

Cloud and/or
On-Premise
End to End

Edge control

Connected products

EcoStruxure EcoStruxure EcoStruxure EcoStruxure EcoStruxure EcoStruxure


Building Power IT Machine Plant Grid

14 | PIX RoF Catalog schneider-electric.com


Overview EcoStruxure ready solutions
Core technologies for embedded
connectivity and intelligence

Enable local control,

PB11768
Arc fault detection
ensure safety and uptime
All the Schneider Electric protection, metering and
control devices can be connected to our Substation
monitoring device.
The HMI can be installed anywhere within the

PM106275
substation to provide local control and monitoring, Bay controller
and power meter
independent of any external systems.
The monitoring information and control functions

PM106278
can be scaled to the needs of each customer.
Optionally the Magelis control and monitoring
functions can be mirrored on a tablet through Wifi
PM106619

connection thanks to our Vijeo Design Air application.


The technician can operate the switchgear remotely,
while maintaining visual contact.
Substation
monitoring device

PE56366
PM106279

Insulation and voltage


Thermal sensor presence indication

Ecostruxure Asset Advisor


Analytics Ecostruxure Facility Advisor
 …

Ecostruxure Substation Operation


Edge control Ecostruxure Power Monitoring Expert

PM106281

PM106282
PM106283

Local control
Substation monitoring

Connected
products
PM105623b

PM106336

PB113683

PE56366

...

Protection/Metering/Condition Monitoring

schneider-electric.com PIX RoF Catalog | 15


Overview EcoStruxure ready solutions
Smart protection for distribution networks

Easergy P3 Easergy Sepam


The Easergy P3 protection relay family has been The Easergy Sepam series digital protection relays take full advantage of Schneider
developed to cover standard protection needs for Electric’s experience in electrical network protection.
industrial and commercial building applications.
Thanks to its cost-effective and flexible design,
Easergy P3 provides an excellent alternative for
Easergy Sepam range
various protection applications.

PM106624
User-friendliness has always been a value of
Schneider Electric products, and the Easergy P3 is
not an exception, with the unique option to operate
through your smartphone or tablet with “Easergy
SmartApp”.
Rapid setup is achieved using the unique “eSetup
Easergy Pro” software which improves usability.
They provide the following essential functions:
• Effective fault diagnosis and protection planning
Easergy P3 standard
PM106284

Universal application • Accurate measurements and detailed diagnosis


• Integral equipment control
PM106336

• Local or remote indication and operation


• Easy upgrading: communication, digital I/O, analog outputs, or temperature
acquisition systems can be added, thanks to its modular design

• Feeder and Transformer




Motor
Voltage
Easergy MiCOM
• Frequency
Offers scalable levels of functionality and hardware options to suit your protection
• Capacitor
requirements, and allows you to choose a cost-effective solution for your
application.
Easergy P3 advanced
Advanced applications with
PM106625

arc flash fault detection


PM106284
PM106340

Easergy MiCOM range

• P3F30 Feeder and Transformer


• P3M30 Motor
• P3G30 Generator This versatile hardware and common relay management software (Easergy MiCOM
• P3L30 Line differential and Distance S1 Studio) provides simple configuration and installation for different applications.
• P3T32 Transformer differential
A standard and simple user interface across the entire range makes Easergy
• P3M32 Motor differential
MiCOM ideal in any environment, from the more complex bay level control with
• P3G32 Generator differential
mimic, to the most simple LCD display with menu interrogation.

16 | PIX RoF Catalog schneider-electric.com


Overview EcoStruxure ready solutions
Enhance the safety with the arc fault
mitigation relays

Modern society relies on an uninterrupted supply of electric power. Prolonged


power outages may cause significant damage, cwhich may potentially lead to loss
of life and interruption to service continuity.
An arc flash protection unit is a protective device used to enhance availability to the
power system and assets.
Schneider Electric covers a wide range of applications, from stand alone protection
to a complete system.

Integrated
Protection relay with arc interface

• Integrated arc detection in a 1-box solution with protection relay


PM106340

• SCADA connectivity via the protection relay


PM106277

• Small footprint

Easergy P3 advanced

Standalone
PM106276

PM106277

• Single stand-alone VAMP125 unit, protects busbar connections, circuit breakers,


CTs

V125

Simple system
V125
PM106276

• “Master-trip” function, to allow simple selectivity in arc detection without strong


PM106277

configuration
PM106276

PM106276

PM106276
PM106277

PM106277

PM105447

V125 V125 V125

High-end system
• Scalable and Customized Arc Detection system tailored to your needs
• Extended possibilities (number of inputs/outputs, logics, selectivity, etc.)
• Open to several serial & Ethernet communication protocols, including IEC 61850
• Multiple technologies (point sensors, loop sensors, fiber optic, etc.)

schneider-electric.com PIX RoF Catalog | 17


Overview EcoStruxure ready solutions
Extend protection to the entire substation

• Possible to retrofit non-arc-restistant installations


• Integration in all products for new projects
• Connected to upper levels or stand alone system

PM106340
Power SCADA
PM105099

PM106285
PM106619

MV Distribution MV/LV Transformer MLV Distribution

Easy retrofit! Easy to retrofit!

18 | PIX RoF Catalog schneider-electric.com


Overview EcoStruxure ready solutions
Real-time condition monitoring to optimize
asset availability

Easergy CL110 ambient Easergy TH110 thermal monitoring


monitoring Easergy TH110 is part of the new generation of wireless smart sensors that ensure
continuous thermal monitoring of all the off-site critical connections allowing to:
This Schneider Electric ambient monitoring system will
• Prevent unscheduled downtimes
continuosly:
• Increase operator and equipment safety
• Monitor ambient moisture and pollution which are
detrimental to the switchgear, by automatically • Optimize and forecast maintenance
calculating the condensation cycle, and combining Thanks to its very compact footprint and wireless communication, Easergy TH110
it with the mission profile conditions, the system has a simple and global installation for a wide range of critical points without
will recommend adjustments to the maintenance impacting on the performance of MV switchgear.
and cleaning frequency in order to maintain the By using the Zigbee Green Power communication protocol, Easergy TH110 ensures
switchgear in its nominal status a robust communication that can be used to create interoperable solutions which
are evolving in the age of the Industrial Internet of Things (IIoT).
Easergy TH110 is self-powered by the network current that ensures high
performance thereby providing accurate thermal monitoring.

Characteristics
Power supply Self-powered.
Energy harvested from power circuit.
Accuracy +/- 1 °C
Range -25 °C/+115 °C
Wireless communication ZigBee Green Power 2.4 GHz
Dimensions - Weight 31 x 31 x 13 mm - 15 g
PM106619

PM106286

PM106287
PM106279

PM105623b

PM105623b

PM106288

TH110 TH110 TH110 CL110

schneider-electric.com PIX RoF Catalog | 19


Overview Schneider Electric services
Peace of mind throughout your
installation life cycle

How can you cut costs and Plan


improve performance at the Schneider Electric helps you plan the full design and execution of your solution,
same time? looking at how to improve your processes and optimize your time:
• Technical feasibility studies: Design a solution for your environment
When it comes to your electrical distribution
• Preliminary design: Improve turnaround time to reach a final solution design
infrastructure, the answer is straightforward:
get professional expertise.

Install
Life Cycle Services
Life Cycle Services Schneider Electric will help you to install solutions based on your plans improving
efficiency, reliability and safety.
DB408843

• Project management: Complete your projects on time and within budget


Plan
What are my options? • Commissioning: Ensure your actual performance matches the design, through
on-site testing and commissioning, to tools and procedures

Install
How do I install and commission? Operate
Schneider Electric helps you improve your installation uptime and control your
Operate capital expenditure through its service offer.
How do I operate and maintain?
• Asset operation solutions: Provide the information you need to increase
safety, enhance installation performance, and optimize asset maintenance and
investment
Optimize • Advantage service plans: Customize service plans that cover preventive,
How do I optimize?
predictive and corrective maintenance
• On-site maintenance services: Deliver extensive knowledge and experience
in electrical distribution maintenance
Renew
• Spare parts management: Ensure availability of spare parts and provide an
How do I renew my solution?
optimized maintenance budget for your spare parts
• Technical training: Build the necessary skills and expertise to properly and
safely operate your installations

When it comes to your electrical


distribution installation, we can Optimize
help you:
Schneider Electric can make recommendations for improved safety, availability,
• Increase productivity, reliability, and reliability and quality.
safety • MP4 electrical assessment: Define an improvement and risk management
• Mitigate risk and limit downtime program
• Keep equipment up to date and extend
lifespan
• Cut costs and increase savings Renew
• Improve your return on investment
Schneider Electric extends the life of your system (under installation, operation and
environmental conditions) while providing upgrades.
CONTACT US! • ECOFIT™: Keep up to date and improve the performance of your electrical
installations (LV, MV, protection relays, etc.)
www.schneider-electric.com/b2b/
• MV product end of life: Recycle and recover outdated equipment with end-of-
en/services/
life services

20 | PIX RoF Catalog schneider-electric.com


Overview Quality assurance
Quality certified to ISO 9001

The Quality Management System for Certified quality: ISO 9001


development, production, sales and At Schneider Electric, customer satisfaction is the Number One priority for
servicing of PIX RoF has been certified everybody:
in accordance with ISO 9001:2008
requirements. • We find the ideal solution for each of our customers
• We are enthusiastic about our customers; our thinking and actions are customer-
oriented
• We encourage and train our staff to always meet quality requirements
Each Schneider Electric production site has an established functional organization
PM106626

which ensures, monitors and improves quality in line with respective norms and
standards.

This process is:

• Uniform across all sites


• Acknowledged by many customers and recognized organizations
Most importantly, there is a strict Quality Management System which is audited on a
regular basis by the international independent certification company Bureau Veritas.
PM106628
PM106627

PM106629

schneider-electric.com PIX RoF Catalog | 21


PIX RoF range

22 | PIX RoF Catalog schneider-electric.com


PIX RoF range

General characteristics 24

General overview 25

Operating conditions and standards 26

Arc fault 27

schneider-electric.com PIX RoF Catalog | 23


PIX RoF range General characteristics

Technical characteristics
Rated voltage (kV) 12 17.5
Rated power frequency withstand voltage (kV r ms) 28 38
Rated lightning impulse withstand voltage (kV peak) 75(2) 95
Rated frequency (Hz) 50/60 50/60

Rated short time withstand current (1) (kA/3 s) 25 - 31.5 25 - 31.5 


Rated peak withstand current (kA peak) 65 - 82 65 - 82 
Rated continuous current
Busbar (A) Up to 2 500 Up to 2 500
Cubicle (A) Up to Up to
2 500 (2) 2 500 (2)
Earthing switch making capacity (kA peak) 82 82
Internal arc classification according (kA/1 s) 31.5 31.5 
to IEC 62271-200 AFLR
Degree of protection IP4X IP4X
(1) The short time withstand current capability of the current transformers must be considered
separately.
(2) Other values available on request.

Dimensions and weights


Rated current (1) (A) 800 - 1 250 2 000 - 2 500

Width (mm) 600 800


Depth (mm) 1 650 (Foundation depth with/without
voltage transformer)
Note: with voltage transformer, panel depth increases at
the top, while the foundation depth remains unchanged.

Height (mm) 2 300 (Low voltage cabinet 735 mm) (3)

Feeder panel with vacuum circuit breaker & bus coupler with vacuum
circuit breaker

Panel width (mm) 600 800

Weight approx. (2) (kg) 800 1 200

Bus Riser Panel

Panel width (mm) 600 800

Weight approx. (2) (kg) 650 1 000

Busbar Metering Panel

Panel width (mm) 600

Weight approx. (2) (kg) 650 - 1 000


(1) The rated current refers to the feeder circuit
(2) 3 x voltage transformer (optional): + approx. 120 kg
(3) With internal arc tunnel with internal exhaust - 2800 mm

24 | PIX RoF Catalog schneider-electric.com


PIX RoF range General overview
Panel design

Pix Roll on Floor with EasyPact EXE


vacuum circuit breaker
1. Low-voltage cabinet with control device

DM105730
2. M
 etallic shutter for bus bar side arm of breaker
connecting to molded seal-off spouts
1
3. Vacuum circuit breaker truck
4. Front door 16
5. M
 etallic shutter for line side arm of breaker
15
connecting to molded seal-off spouts
6. Breaker guiding rails
7. Earthing switch position indicator 2
8. Insertion opening for operating lever of the
earthing switch
9. M
 echanical interrogation interlock of insertion port
3
for the earthing switch
10. Cable compartment cover 4
14
11. Cable compartment 5
12. Earth switch with making capacity 6
13
13. Cable connections
7
14. Current transformers 8 12
15. Busbars 9

16. Voltage transformer with primary fuse


11

10
Cubicle view without Internal Arc accessories.

PIX RoF with EasyPact EXE


operating facia

2
DM105731

1 3

5 4

1. Orifice to insert rod for breaker opening


2. Knob for door lock
3. Orifice to insert rod for breaker closing
4. Glass window to inspect circuit breaker
5. Space for the panel rating label
6. Pad locking facility
7. Rack-in/rack-out lever insertion

7 6

schneider-electric.com PIX RoF Catalog | 25


PIX RoF range Operating conditions and
standards

Operating conditions
PIX RoF has been developed to meet
the following conditions: Normal operating conditions, according to the IEC International Standards listed
below, for indoor switchgear.
• Ambient temperature up to 40 °C, without
derating and natural cooling
Ambient air temperature
• Corrosive atmospheres
• Less than or equal to 40 °C (other values available on request)
(possible adaptation)
• Less than or equal to 35 °C on average over 24 hours
• Storage conditions
• Greater than or equal to – 5 °C
In order to retain all of the functional unit’s
qualities when stored for prolonged periods,
Altitude
we recommend that the equipment is stored in
its original packaging, in dry conditions, and • Less than or equal to 1000 m;
sheltered. • Above 1000 m, a derating coefficient is applied (please contact us)

Atmosphere
• No dust, smoke or corrosive or inflammable gas and vapor, or salt

Humidity
• Average relative humidity over a 24 hour period ≤ 95%
• Average relative humidity over a 1 month period ≤ 90%
• Average vapor pressure over a 24 hour period ≤ 2.2 kPa
• Average vapor pressure over a 1 month period ≤ 1.8 kPa

Specific operating conditions (please contact us).

Standards
The PIX RoF meets the following international
standards:

• IEC 62271-1: High-voltage switchgear and controlgear: common specifications


• IEC 62271-200: AC metal-enclosed switchgear and controlgear for rated
voltages above 1 kV and up to and including 52 kV
• IEC 62271-100: High-voltage switchgear and controlgear - Alternating current
circuit breakers
• IEC 62271-103: High-voltage switchgear and controlgear - Switches for rated
voltages above 1 kV up to and including 52 kV
• IEC 62271-102: High-voltage switchgear and controlgear - Alternating current
disconnectors and earthing switches
• IEC 60255: Measuring relays and protection equipment - Common requirements
• IEC 61869-2: Instrument transformers - Current transformers
• IEC 61869-3: Instrument transformers - Inductive voltage transformers
• IEC 60044-8: Instrument transformers - Electronic current transformers

26 | PIX RoF Catalog schneider-electric.com


PIX RoF range Arc fault
Internal arc fault withstand

Integrating many of the proven components of the PIX RoF range, it has all the
intrinsic features of the standard version i.e. very reliable and of high quality.
PIX RoF has been fully tested according to the latest IEC 62271-100 & 200, by
internationally accredited test laboratories.
Switchgear units of the PIX RoF series are:
• M
 etal-enclosed; loss of service continuity category according to
IEC 62271-200: LSC 2B-PM
• Type-tested
• Tested for internal arc faults (Internal Arc Classification AFLR)
• Dimensioned for indoor installation

Internal exhaust duct


An intenal arc exhaust duct can be provided to discharge the hot gases inside the
room in the controlled manner.
DM105754

External exhaust and deflector solutions can also be implemented.


Please contact us for more details.

Notes
LSC2B (Loss of Service Continuity
IEC 62272-200)
This category defines the possibility of keeping other compartments
energised (in service) when opening a main circuit compartment.

IAC (Internal Arc Classification)


The metal-enclosed switchgear is classified for internal arc protection in
accordance with IEC 62271-200 where AFLR is defined as follows:

Type of accessibility
• A: Restricted access to authorized personnel only. Sides of the enclosure
which meet the criteria of the internal arc test
• F: Front side
• L: Lateral side
• R: Rear side

schneider-electric.com PIX RoF Catalog | 27


Functions and
characteristics

28 | PIX RoF Catalog schneider-electric.com


Functions and
characteristics
Functional overview 30
Choice of functional units 30
IC or FD type cubicle - Incomer or feeder 31
BC type cubicles - Bus section 32
BR type cubicle - Bus riser 33
BM type cubicles - Metering busbar earthing 34

schneider-electric.com PIX RoF Catalog | 29


Functions and Functional overview
characteristics
Choice of functional units

PIX RoF with withdrawable vacuum circuit breaker has a comprehensive range of
functions to suit all requirements for multiple applications.

Selection guide
The following guide will help you to define the most appropriate protection
coresponding to the type of applications you want to energize.
The equipment shown below are the main functions.
For specific requirements, additional functions are available upon request.

Function Incomer Feeder Busbar coupler Bus riser Metering

Cubicle IC FD BC BR BM

Device Branch-circuit panel Branch-circuit panel Bus section coupler panel Bus riser panel Bus voltage transformer/
• Vacuum • Vacuum • Vacuum • Optional voltage bus earthing switch panel
Circuit Breaker Circuit Breaker Circuit Breaker transformers • Voltage transformers
• Voltage transformers • Optional current • Bus earthing switch
transformers
• Optional earthing switch

Single line
D102_654

DM105734

D102_655

D102_656

D102_657
diagram

30 | PIX RoF Catalog schneider-electric.com


Functions and Functional overview
characteristics
IC or FD type cubicle - Incomer or feeder

DM105735

DM105736
7

2
D102_654

H
5

4 3

W D

1 Busbars
2 Main switching device
3 Cable connections (rear access)
4 Earthing switch
5 Current Transformers
6 Voltage Transformers (optional)
7 Low voltage equipment

IC or FD
Rated voltage Ur (kV) 12 17.5
Breaking capacity (kA) 25 31.5 25 31.5
Rated current - Vacuum circuit breaker (A)
Ir 800 (3) (3) (3) (3)

Ir 1 250 (3) (3) (3) (3)

Ir 2 000 (4) (4) (4) (4)

Ir 2 500 (4) (4) (4) (4)

Rated peak withstand current Ip (kA) 65 82 65 82


Short-time withstand current Ik (kA) 25 31.5 25 31.5
Duration (s) 3 3 3 3
Dimensions H (1) (mm) 2 300
D (2) (mm) 1 650
Approximate mass (kg) 800  - 1 200
(1) With the standard LV cabinet
(2) Add 500 mm for Line VTs/other values for extra cables or CTs
(3) Width 600 mm
(4) Width 800 mm

schneider-electric.com PIX RoF Catalog | 31


Functions and Functional overview
characteristics
BC type cubicles - Bus coupler

DM105737

DM105738
6

1
D102_655

H 2
5

4 3

W D

1 Busbars
2 Main switching device
3 Lateral connections (connection to/
from adjacent bus riser cubicle)
4 Earthing switch
5 Current transformers
6 Low voltage equipment

BC
Rated voltage Ur (kV) 12 17.5
Breaking capacity (kA) 25 31.5 25 31.5
Rated current - Vacuum circuit breaker (A)
Ir 800 (3) (3) (3) (3)

Ir 1 250 (3) (3) (3) (3)

Ir 2 000 (4) (4) (4) (4)

Ir 2 500 (4) (4) (4) (4)

Rated peak withstand current Ip (kA) 65 82 65 82


Short-time withstand current Ik (kA) 25 31.5 25 31.5
Duration (s) 3 3 3 3
Dimensions H (1) (mm) 2 300
D (mm) 1 650
Approximate mass (kg) 800  - 1 200
(1) With the standard LV cabinet
(3) Width 600 mm
(4) Width 800 mm

32 | PIX RoF Catalog schneider-electric.com


Functions and
characteristics Functional overview
BR type cubicle - Bus riser

DM105739

DM105740
4

1
D102_656

H 2

W D

1 Busbars
2 Withdrawable voltage transformer (optional)
3 Lateral connections (connection to/from
adjacent bus section cubicle)
4 Low Voltage equipment

BR
Rated voltage Ur (kV) 12 17.5
Breaking capacity (kA)
Rated current (A)
Ir 800 (3) (3) (3) (3)

Ir 1 250 (3) (3) (3) (3)

Ir 2 000 (4) (4) (4) (4)

Ir 2 500 (4) (4) (4) (4)

Rated peak withstand current Ip (kA) 65 82 65 82


Short-time withstand current Ik (kA) 25 31.5 25 31.5
Duration (s) 3 3 3 3
Dimensions H (1) (mm) 2 300
D (mm) 1 650
Approximate mass (kg) 650  - 1 000
(1) With the standard LV cabinet
(3) Width 600 mm
(4) Width 800 mm

schneider-electric.com PIX RoF Catalog | 33


Functions and Functional overview
characteristics
BM type cubicles - Busbar metering

DM105741

DM105742
4
1

D102_657

H 2

W D

1 Busbars
2 Withdrawable voltage transformer
3 Earthing switch
4 Low voltage equipment

BM
Rated voltage Ur (kV) 12 17.5
Breaking capacity (kA)
Rated current (A)
Ir 800 (3) (3) (3) (3)

Ir 1 250 (3) (3) (3) (3)

Ir 2 000 (4) (4) (4) (4)

Ir 2 500 (4) (4) (4) (4)

Rated peak withstand current Ip (kA) 65 82 65 82


Short-time withstand current Ik (kA) 25 31.5 25 31.5
Duration (s) 3 3 3 3
Dimensions H (1) (mm) 2 300
D (mm) 1 650
Approximate mass (kg) 650  - 1 200
(1) With the standard LV cabinet
(3) Width 600 mm
(4) Width 800 mm

34 | PIX RoF Catalog schneider-electric.com


Notes

schneider-electric.com PIX RoF Catalog | 35


Components

36 | PIX RoF Catalog schneider-electric.com


Components

Panel components 38

EasyPact EXE circuit breaker 39


General characteristics 39
Remote control mandatory auxiliaries 41
Remote control optional auxiliaries 42
Remote control indication auxiliaries 43

HVX-C circuit breaker 44

Interlocking Systems 45

Protection, monitoring and control 46


Easergy P3 protection relays 46
Easergy Sepam protection system 47
Easergy MiCOM protection system 48
Arc fault protection 49

Current and voltage transformers 51

schneider-electric.com PIX RoF Catalog | 37


Components Panel components

The withdrawable parts:


PM106630

• The circuit breaker, the disconnector device or the metering device


• The lever-type propulsion mechanism for racking in-out
• Interlocks to fix the withdrawable parts onto the fixed part

Circuit breaker
A circuit breaker is a safety device enabling the switching and protection of
electrical distribution networks. It protects all components connected to the
downstream network by opening the circuit during a fault.
The withdrawable EasyPact EXE vacuum circuit breaker is mounted on an
integrated floor rolling trolley enabling easy handling.

Disconnector
A withdrawable disconnector with an integrated floor rolling trolley means
disconnection between the busbar and the cables is feasible by racking it out from
EasyPact EXE circuit breaker on an extraction table the service position to the test position.
It is inserted in place of the circuit breaker in the circuit breaker compartment.

Metering device
A withdrawable metering device with voltage transformers mounted on an
integrated floor rolling trolley means measurement of the circuit voltage for
metering purposes is feasible.
It can be disconnected from the main circuit by racking it out from the service
position to the test position.
PM106631

Earthing switch
The integrated earth switch with fault making capacity makes it possible to earth
the cables or the Busbar (depending on the cubicle) and ensures safety during
maintenance.
In accordance with IEC 62271-102 the integrated earth switch is Class E1 M0.

Earthing switch

38 | PIX RoF Catalog schneider-electric.com


Components EasyPact EXE circuit breaker
General characteristics
PM106400

EasyPact EXE is our latest range of state-of-the-art vacuum circuit breakers. Its
design is the result of more than 40 years of Schneider Electric experience in
switching devices. Its wide geographical deployment makes it a key PIX Easy
equipment component.
It has been designed to suit specific applications such as: Infrastructure,
Commercial and Industrial buildings, Industrial plants and Distribution substations.
The materials used to manufacture this circuit breaker have been selected and
designed to operate 10 000 cycles.

Mechanism
PM106412

The operating mechanism gives the device an opening and closing speed that is
independent of the operator whether the order is electrical or manual. It carries out
reclosing cycles and it is automatically recharged by a geared motor after each
closing.

Vacuum interrupter
This component is the heart of the circuit breaker. This specific Schneider designed
component breaks the rated short circuit and this is achieved by:
• Choosing materials that are specifically intended for this application (metals and
ceramics)
• Choosing an appropriate assembly process (vacuum, high temperature brazing)
• The use of a "getter" material to absorb the residual gas inside the enclosure

Racking device
PM106402

The racking device moves the circuit breaker from the disconnected position to the
service position and vice versa.
The EasyPact EXE racking device has a robust interlocking system with the
switchgear door, the LV plug, the circuit breaker and the earthing switch.
The materials used to manufacture EasyPact EXE racking trolley sub-assemblies
have been selected and designed to operate 2 000 cycles under the conditions
Racking device defined by the IEC standard.

According to IEC 62271-100 According to IEC 62271-100


Cubicle width Rated voltage Ur kV 12
integrated EasyPact EXE Rated frequency fr Hz 50/60
breaker
Rated short duration power frequency withstand voltage Ud kV 28
600 mm 800 mm
Rated normal Rated lightning impulse withstand voltage Up kV 75
Ir A 800 p
current Rated short-circuit breaking current Isc kA 20
1 250 p
25
2 000 p
31.5
2 500 p
Rated duration of short-circuit tk s 3

schneider-electric.com PIX RoF Catalog | 39


Components EasyPact EXE circuit breaker
General characteristics

According to IEC 62271-100


PM1053882

Common characteristics 12 kV

Rated short-time withstand kA/3s (50/60 Hz) = Isc


current (Ik/tk)
Rated operating sequence O-3 min - CO-3 min - CO p

O-0.3 s - CO-3 min - CO p

O-0.3 s - CO-15 s - CO p

Operating times Opening < 51 ms


Breaking < 66 ms
Closing < 71 ms
Mechanical endurance Class M2
Electrical endurance Class E2
Rated line-charging A-class 10-C2
breaking current
Rated cable-charging A-class 25-C2
breaking current

Mechanical endurance
EasyPact EXE installed under normal service conditions with a preventive
maintenance program is designed to :

Circuit MCH MX/XF/MN Mechanical


Breaker release interlocks
10 000 operation 10 000 charging 10 000 operations 2 000 operation
cycles/30 years operations cycles

40 | PIX RoF Catalog schneider-electric.com


Components EasyPact EXE circuit breaker
Remote control mandatory auxiliaries

Shunt opening Shunt closing The remote control auxiliaries comprise an electric motor (MCH), a shunt closing
release MX1 release XF release (XF) and a shunt opening release (MX1).

Electric motor (MCH)


PM106427

The electric motor operates by charging the closing spring as soon as it is


connected to the auxiliary power supply. This allows the circuit breaker to close
after opening according to the rated operating sequence.
A lever is located on the front of the circuit breaker that enables the closing spring
to be charged manually if the auxiliary power supply is unavailable.
The electric motor is equipped with an electrical contact to indicate the "spring
charged" status of the mechanism.
The electric motor includes a gear reducer.

Power supply • DC: 24-30 V, 48-60 V, 110-130 V, 200-250 V


• AC (50 Hz / 60 Hz): 48-60 V, 100-130 V, 200-240 V
Operating range 0.85 to 1.1 Ua
Consumption (VA or W) 180
Motor overcurrent 2 to 3 In for 0.1 s
Charging time ≤7 s
Electric
CH contact 10 A / 240 V
motor MCH
PM106428

Shunt closing release (XF)


A shunt closing release operates by closing the circuit breaker when the voltage
at the terminals of the release is between 85% and 110% of its rated voltage. The
closing release is designed to withstand a permanent power supply.

Electric Characteristics
motor MCH Power supply • DC: 24-30 V, 48-60 V, 100-130 V, 200-250 V
• AC (50Hz / 60Hz): 24 V, 48 V, 100-130 V, 200-250 V
Operating range 0.85 to 1.1 Ua
PM105391

Consumption (VA or W) Triggering 200 (for 200 ms)


Latched 4.5

Shunt closing Shunt opening release (MX1)


release XF
A shunt opening release operates by opening the circuit breaker when the voltage
at the terminals of the release is between 70% and 110% (for a direct current)-
or between 85% and 110% (for an alternative current)- of its rated voltage. The
opening release is designed to withstand a permanent power supply and to lock
PM105391

the circuit breaker in the "open" position as long as the voltage is maintained at its
terminals.

Characteristics
Power supply • DC: 24-30 V, 48-60 V, 100-130 V, 200-250 V
Shunt opening
release MX1 • AC (50 Hz / 60 Hz): 24 V, 48 V, 100-130 V, 200-250 V
Operating range • DC: 0.7 to 1.1 Ua
• AC: 0.85 to 1.1 Ua
Consumption (VA or W) Triggering 200 (for 200 ms)
Latched 4.5

schneider-electric.com PIX RoF Catalog | 41


Components EasyPact EXE circuit breaker
Remote control optional auxiliaries

EasyPact EXE can be equipped with a second Second shunt opening release (MX2)
opening release that can be either a shunt
The second shunt opening release operates by opening the circuit breaker when
opening release or an undervoltage release.
the voltage at the terminals of the release is between 70% and 110% (for a direct
current)- or between 85% and 110% (for an alternative current)- of its rated voltage.
The opening release is designed to withstand a permanent power supply and to
PM106427

lock the circuit breaker in the "open" position as long as the voltage is maintained
at its terminals.

Characteristics
Power supply • DC: 24-30 V, 48-60V, 100-130 V, 200-250 V
• AC (50Hz / 60Hz): 24 V, 48 V, 100-130 V, 200-250 V
Operating range • DC: 0.7 to 1.1 Ua
• AC: 0.85 to 1.1 Ua
Consumption (VA or W) Triggering 200 (for 200 ms)
Latched 4.5

Undervoltage release (MN)


The undervoltage release operates by opening the circuit breaker when the voltage
at the terminals of the release falls below 35% of its rated voltage, even if the fall
is slow and gradual.
Shunt opening
The undervoltage release does not operate the circuit breaker when the voltage at
release MX2 or
Under voltage its terminals exceeds 70% of its rated supply voltage. The area between 35% and
release MN 70% is uncertain, and the undervoltage release might operate to open the circuit
breaker.
Circuit breaker closure is possible when the voltage at the terminals of
the release is equal to or exceeds 85% of its rated voltage. On the other hand,
circuit breaker closure is impossible when the voltage at the terminals is below 35%
PM105391

of the rated supply voltage.

Characteristics
Shunt opening Power supply • DC: 24-30 V, 48-60 V, 100-130 V, 200-250 V
release MX2
• AC (50 Hz / 60 Hz): 24 V, 48 V, 100-130 V, 200-250 V
Operating range Opening 0.35 to 0.7 Ua
Closing 0.85 Ua
Consumption (VA or W) Triggering 200 (for 200 ms)
Latched 4.5
PM105391

Release combination table


Undervoltage
release MN MCH p p p
XF p p p
MX1 p p p
MX2 p
MN p

42 | PIX RoF Catalog schneider-electric.com


Components EasyPact EXE circuit breaker
Remote control indication auxiliaries

Position contacts (OC)


PM106429

EasyPact EXE is equipped with one block of four position contacts as standard,
and the Panel Builder may add one or two additional blocks of four contacts.
Rotary type The maximum number of position contacts is twelve.
contacts (OC)
Characteristics
Standard delivery 1 (1 block of 4 contacts)
Maximum quantity 3 (3 blocks of 4 contacts)
Breaking capacity (A) Standard Min. load: 100 mA / 24 V
Cos : 0.3 V AC 240 / 380 10 / 6
V DC 24 / 48 10 / 6 *
125 10 / 6
250 3
* standard contacts : 10 A; optional contacts : 6 A (temperature derating)
PM106430

"Ready to close" contact (PF)


A "ready to close" contact (PF) indicates that the circuit breaker is ready to close
in the following conditions:
• The circuit breaker contacts are open

"Ready to close" • The operating mechanism closing spring is charged


PF contact • The opening pushbutton is not activated (by a keylock or manually)
• The opening shunt release is not energized
• The undervoltage release, if present, is energized

EasyPact EXE is always equipped with 1 "ready to close" contact (PF) for
remote control.

Characteristics
Standard delivery 1
Maximum quantity 1
Breaking capacity (A) Standard Min. load: 100 mA / 24 V
Cos : 0.3 V AC 240 / 380 5
V DC 24 / 48 3
125 0.3
250 0.15

Operation counter (CDM)


PM106431

Operation counter An operation counter counts the number of operating cycles (close-open) that
(CDM) the device has carried out.
EasyPact EXE is always delivered with an operation counter showing the number
of close-open cycles that have been performed for the factory routine test
(usually 50).

schneider-electric.com PIX RoF Catalog | 43


Components HVX-C Vacuum circuit breaker

HVX is our latest range of vacuum circuit breakers. It offers a proven state-of-the
art design to meet your specifications for power switching devices in air-insulated
PE910018

switchgear up to 36 kV. HVX provides a valuable solution for you projects. Thanks to
their improved contact design, our interrupters provide unrivalled performance.

Operating mechanisms have been simplified to increase reliability and service life
with very low maintenance. Instead of the traditional spring operating mechanism,
HVX has implemented a single-shaft system with only one torsion spring, reducing
the number of parts and increasing reliability.

Application
HVX is designed to suit all types of applications (utilities, power generation, O&G,
industry, etc.) and for breaking short-circuit currents.

Standard
HVX-C used in PIX Roll on Floor has been fully tested according to IEC 62271-100
and belongs to the M2, C2, E2 class of circuit breakers as defined by the standard.

Electrical characteristics HVX 17


Rated voltage (kV) 17.5
Rated current (A) Up to 2500 (1)
Rated frequency (Hz) 50 (2)
Short-circuit current (kA) 25 - 31.5
Cable charging current (A) 31.5
Rated breaking capacity
Line charging current (A) 10
Single capacitor bank (A) -
Rated making capacity (kA peak) 65 - 82
Opening (ms/max) 50
Breaking (ms/max) 60
Rated operating time
Arcing (ms/max) 10
Closing (ms/max) 60
O-0.3s-CO-3 min-CO p
Rated operating sequence
O-3min-CO-3 min-CO p

Mechanical (C/O) for switching 30 000


chamber
Endurance Mechanical (C/O) for mechanism 10 000
Electrical (C/O at In) 10 000
Electrical (C/O at Isc) 100
(1) Contact us for higher values
(2) Contact us for other values

44 | PIX RoF Catalog schneider-electric.com


Components Interlocking systems

In order to maximize operator safety and minimize erroneous operations, PIX


RoF provides a large number of integral interlocks. All mandatory interlocks in
accordance with IEC are available and in addition, there are several optional
interlocks that can be chosen to enhance operator safety.

A list of basic interlocks to enhance operator safety are described below:

Interlock Function of interlock Method of operation of interlock

Between truck and low The truck cannot be actuated unless the low-voltage Rack in handle can not be inserted for operation.
voltage connector connector is inserted.

The low voltage plug cannot be removed when the MV compartment door cannot be opened in transit/
truck is not in the test position. service position.

Between truck and The truck cannot be racked in if the earthing switch The opening in the front door for the truck crank is
earthing switch is ON. locked.

The earthing switch can no longer be switched on if the The interrogation slide below the earthing switch is
truck has left its test position. locked.
The insertion of the earthing switch lever is blocked.

Between the circuit Circuit breaker cannot be racked in or out while it is Rack in handle can not be inserted for operation.
breaker and the truck switched on.

Circuit breaker cannot be switched on/off unless the The circuit breaker cannot be switched ON or OFF.
truck is completely in its test or service position.

Between truck and If the truck front frame is not locked in the cubicle, the The crank cannot be inserted to the truck if both truck
cubicle truck cannot be actuated. handles in the front frame are not moved outwards.

If the truck has left its test position the truck front frame Both truck handles in the front frame are locked.
cannot be unlocked in the cubicle.

Between the truck and The front door can only be opened if the truck is in its The double-bit key cannot be turned.
the front door (optional) test position. Provision available in the front door to open the inerlock

If the front door is open, the truck cannot be moved into The crank cannot be inserted into the truck if the front
the service position. This interlock is standard. door is open.

If the front door is not locked, the truck cannot be The opening in the front door for the truck crank is
actuated. locked.

For the truck in a CB can only be moved into the service position when Rack in access is available only after insertion of the
disconnected position the key is inserted in the lock. key.
(optional key lock) Key is blocked in the lock when the circuit breaker is in
the service position.

schneider-electric.com PIX RoF Catalog | 45


Components Protection, monitoring
and control
Easergy P3 protection relays

Easergy P3 standard Solid protection meets unparralleled

PM106284
Universal applications
eficiency
PM106572

The Easergy P3 protection relay family is based on proven technology designs


developed in close cooperation with our customers. Easergy products have been
designed around user-friendliness, a feature which is highlighted in our customers
feedback.
The Easergy P3 feeder manager has been developed to cover basic protection
needs for OEMs, utilities and industrial applications. Thanks to its cost-effective
and flexible design, the Easergy P3 provides an excellent alternative for various
P3U10/20/30 = Universal protection
protection applications.
• Feeder and Transformer Easergy P3 combines additional protection functions such as directional earth fault
• Motor for feeder and motor protection.
• Voltage
• Frequency Unparralleled efficiency
• Capacitor • Simple selection and ordering with EcoReal MV
• Faster delivery with instant availability for standard configurations
Easergy P3 advanced • Simplified configuration with the new eSetup Easergy Pro setting tool
PM106284

Advanced applications with


arc flash fault detection
Better Connectivity
• Simpler operation and maintenance with the Easergy P3 SmartApp
• All communication protocols included as standard, including IEC 61850
PM106574

• Option to use two active communication protocols at the same time


• Increased number of inputs and outputs gives you more options

Enhanced safety
• Embedded arc protection
• P3F30 Feeder and Transformer
• Built-in virtual injection testing
• P3M30 Motor
• Compliant to international standards (e.g. IEC 60255-1)
• P3G30 Generator
• P3L30 Line differential and Distance
• P3T32 Transformer differential
• P3M32 Motor differential
• P3G32 Generator differential Ease of use
User-friendliness is a key benefit to Easergy P3, made to save time at every
step of your project's life-cycle.
PM106637

A great deal of effort has gone into designing the operational aspects of
our new products. Set up and download/upload are much faster thanks to
the unique eSetup Easergy Pro setting software which significantly improves
usability.
The informative human machine interface provides the information the user
needs, in addition to customized legend texts.

Enhanced usability
The Easergy P3 protection relay design has been enhanced with a number of
features that make relay installation and testing even more efficient and user-
friendly, like the virtual injection testing is accessible with our eSetup Easergy
Pro setting software.

46 | PIX RoF Catalog schneider-electric.com


Components Protection, monitoring
and control
Easergy Sepam protection system

Easergy Sepam: protection digital relays


PM106624

Easergy Sepam is a range of digital monitoring protection and control units.


Easergy Sepam is the centre of the protection, monitoring and control system
functional units: all the necessary protection, metering, control, monitoring and
signalling functions are carried out by Easergy Sepam.
The Easergy Sepam range is a range of units designed to provide an optimal
solution for each application, and includes, for example:
• Easergy Sepam S, substation incomer and feeder
• Easergy Sepam B, bus sectioning
• Easergy Sepam T, transformer feeder
• Easergy Sepam M, motor feeder
• Easergy Sepam G, generator feeder
• Easergy Sepam C, capacitor feeder
The Easergy Sepam range consists of the Easergy Sepam series 20, series 40,
Each functional unit can be equipped series 60 and series 80, a range of modular protection relays that can be adapted
with a comprehensive protection, to your specific requirements.
monitoring and control system
comprising:
• Instrument transformers to measure the
necessary electrical values (phase current,
Protection chain
residual current, voltages, etc.) The Easergy Sepam protection units combined with innovative current sensors,
• P
 rotection relays, providing functions adapted provide a comprehensive measurement, protection and energy management
to the part of the network to be protected chain .*
• Metering equipment, to inform operators
• L
 ow voltage relaying, to provide control of the A high-performance, economical solution
breaking device and the withdrawable part The modular Easergy Sepam offer provides a cost-effective solution tailored to
• V
 arious auxiliaries: secondary circuit test units, every requirement.
etc.

Easy to order and install


All the components of the protection chain are referenced and can be delivered
very quickly.

The power of a multi-functional digital unit


Easergy Sepam is more than a simple protection relay; it is a truly multi-functional
unit offering, in particular:
• C
 ircuit breaker diagnosis functions (switching counter and time, rearming time,
cumulated broken A2)
• Direct circuit breaker control, whatever the type of release unit
• Remote equipment operation using the communication option
(*) Please check in the Sepam catalogue which sensor to use with each Sepam version.

schneider-electric.com PIX RoF Catalog | 47


Components Protection, monitoring
and control
Easergy MiCOM protection system

Easergy MiCOM protection relays


PM106625

Easergy MiCOM protection provides the user with a choice of cost-effective


solutions for specific protection requirements within the distribution network.
The Easergy MiCOM relay series offers comprehensive protective function solutions
for all power supply systems, as well as for various functional and hardware project
stages.
With their modular design, the Easergy MiCOM device platforms provide the user
with multifunctional equipment that can act as :
• Grid protection equipment, and
• Combined protection and control systems
• E
 asergy MiCOM devices integrate most standard communication protocols
used in station control systems and SCADA systems
• Thanks to the continuous development of these products, compatibility with
technical progress in the field of switchgear and controlgear communication
is guaranteed
Easergy MiCOM offers varying levels
of functionality and hardware
• Series 30 is designed to meet the rigorous
requirements of MV & HV applications with
particular focus on feeder and transformer
protection and control.
• S
 eries 40 fulfills the protection requirements
for a wide market of utility and industrial
systems and offers a complete range of
protection functions.

48 | PIX RoF Catalog schneider-electric.com


Components Protection, monitoring
and control
Arc fault protection

Arc fault detectors selection guide


Vamp 125 Vamp 121 Vamp 321 (+I/0 units)*

PM106632
PM106411

PE90502

Functions
The arc protection unit detects an arc flash in an installation and trips the feeding breaker.
An arc flash protection maximises personnel safety and minimizes material damage caused by arc faults.
System features
• Typical operation on light only principle • Operation light only • Flexible and modular system can be adapted
-- Input for current criteria for I> and • Up to 10 arc or smoke sensors to different targets requiring arc protection
L> operation • Single trip contact • Central unit and modular units engineer a
-- Integrated 19 - 256 V AC/DC aux. supply • Straightforward installation scheme to your requirements
• Optimised for wind power and other • Operation time 9 ms • Continuous system self-supervision
small applications (including the output relay) • 3-phase curent, zero-sequence voltage and
• Up to 4 arc sensors • Cost-effective solution current
• Selective trip for 2 zones • Self-supervision • Event logs, disturbance recording and real-
• Operation time 1 ms with high speed output • Binary input for blocking or resetting time clock
and 8 ms with a trip relay the unit (programmable) • Operation on simultaneous current and light
• Non-volatile trip status • Option for double arc channel or on light only
• Self-supervision activation trip criteria • Direct connection of arc sensors in the
• Straightforward installation • BIO light transfer option to other central unit without using I/O units
• Cost-effective solution Vamp devices • 7 ms operation time with trip contact and 2
ms with high speed output (HSO)
• Programmable operation zones
• Communication protocol support for SCADA
and automation interfacing
• Supports a maximum of 6 Digital Inputs and
8 Digital Outputs for object (CB) status and
control (order option dependent)
Sensors
Point sensor - surface
• Arc detection from two compartments simultaneously
• Self-monitored
• Cable length adjustable from 6 m to 20 m
Point sensor - pipe
• S
 elf-monitored
• Cable length adjustable from 6 m to 20 m
Loop sensor
• Monitors various compartments
• Small bending radius for easy installation
Benefits
• Reduces production losses
• Extended switchgear life cycle
• Reduced insurance costs
• Low investment costs and fast installation
• Enhanced personnel safety

IEC standards IEC standards IEC standards


* I/0 units: 4 references available (VAM 3L, VAM 10L/LD, VAM 12L/LD, VAM 4C/CD). The choice is made according to the needs in relation to the type
and number of sensors. Please contact us.

schneider-electric.com PIX RoF Catalog | 49


Components Protection, monitoring
and control
Arc fault protection

The arc protection unit detects an arc Vamp arc flash range
flash in an installation and trips the
feeding breaker

PM106633
An arc flash protection system
minimizes material damage caused by
arc faults. Vamp 321

Arc flash protection minimizes material damage to the


installation in the most hazardous power system fault
situations.
Minimized damage also minimizes repair work which
means the power supply can be restored as quickly
as possible.

Advantages

Enhanced personnel safety


The shorter the operating time of the arc flash protection unit, the smaller the
damage caused by the arc fault thereby minimizing possible power outages..

Extended switchgear life cycle


The arc protection unit increases the lifecycle expectancy of switchgear
installations, so that investment in new switchgear installations can be postponed
and money can be saved by re-Vamping existing switchgear systems.

Reduced insurance costs


The faster and better the protection system of a power installation, the more
generous the insurance terms and costs.

Low investment costs and fast installation


A comprehensive arc protection system is characterized by low investment costs
and fast installation and commissioning times. One successful arc flash protection
unit operation provides an immediate return on your investment.

Reliable Operation
Operation is based on the appearance of light or alternatively on the appearance of
light and current from an external device. The system is immune to faulty trippings
due to dual tripping criteria: light & current.

50 | PIX RoF Catalog schneider-electric.com


Components Current and voltage
transformers

PE91022
Block type current transformers
• Single, Double or Triple primary
• 1 A or 5  A secondary current
• Class 0.2, 0.5 or 1 for measurement
• 5P10, 5P15 or 5P20 for protection

For specific burdens or accuracy class please contact us.

Window type current transformers


PE91021

• Single, Double or Triple primary


• 1 A or 5  A secondary current
• Class 0.2, 0.5 or 1 for measurement
• 5P10, 5P15 or 5P20 for protection

For specific burdens or accuracy class please contact us.

Ring type Current transformer


PE58444

• Single, Double or Triple primary


• 1 A or 5  A secondary current
• Class 0.2, 0.5 or 1 for measurement
• 5P10, 5P15 or 5P20 for protection

For specific burdens or accuracy class please contact us.

Voltage transformers
PE91020

• Primary voltage from 3/√3 up to 15/√3 kV


• F
 irst secondary voltage available in different ratios with burden up to 100  VA
and accuracy class 0.5
• Secondary voltage available with burden up to 50 VA and protection class 3P

For specific burdens or accuracy class please contact us.

schneider-electric.com PIX RoF Catalog | 51


Installation
and connection

52 | PIX RoF Catalog schneider-electric.com


Installation
and connection
Room Planning 54
Installation non IAC 54
Installation IAC internal tunnel 55

Layout 56
Back-to-the-wall installation - IAC AFL 56

Civil Engineering 57
Standard foundation/Ground plan for
57
PIX Roll-on-Floor switchgear

Accessories 58

schneider-electric.com PIX RoF Catalog | 53


Installation Room planing
and connection
Installation non-IAC

Switchgear Room

DM105743
≥ 100
25 25

800 600 600 800


DM105743

≥ 1 400 ≥ 600

500
2 300

All dimensions are in mm

1 650

54 | PIX RoF Catalog schneider-electric.com


Installation Room planing
and connection
Installation IAC internal tunnel

Switchgear room

DM105744
≥ 100
25 25

800 600 600 800


DM105745

≥ 400
≥ 1 400
500
2 800

All dimensions are in mm

1 660

schneider-electric.com PIX RoF Catalog | 55


Installation Layout
and connection
Back-to-the-wall installation - IAC AFL

Space allocation plan


Installation example top view
PIX RoF with 2 incomers, 1 bus coupler, 1 bus riser, 1 metering,
5 feeders up to 1 250 A:
DM105746

Incomer Incomer
1 250 A 1 250 A

≥ 900 mm
Feeder Feeder Feeder Bus coupler Bus riser Feeder Feeder Bus PT
1 250 A 1 250 A 1 250 A 1 250 A 1 250 A 1 250 A 1 250 A 1 250 A
2 150 mm

1 650 mm

600 mm 600 mm 600 mm 600 mm 600 mm 600 mm 600 mm 600 mm 600 mm 600 mm
25 mm 25 mm

≥ 100 mm

Installation example top view


PIX RoF with 2 incomers, 1 bus coupler, 1 bus riser up to 2 500 A,
5 feeders up to 1 250 A and 1 bus voltage metering panel:
DM105747

Incomer Incomer
2500 A 2500 A ≥ 900 mm

Feeder Feeder Feeder Bus coupler Bus riser Feeder Feeder Bus PT
1250 A 1250 A 1250 A 2 500 A 2 500 A 1250 A 1250 A 1250 A
2150 mm

1650 mm

800 mm 600 mm 600 mm 600 mm 800 mm 800 mm 600 mm 600 mm 600 mm 800 mm
25 mm 25 mm

≥ 100 mm

56 | PIX RoF Catalog schneider-electric.com


Installation Civil engineering
and connection
Standard foundation/ground plan for
PIX Roll-on-Floor switchgear 

600 mm width 800 mm width

2* 12.5 68 664
DM105748

DM105749
68 464 2* 12.5
372.5*

485*
831

831
410*

610*

2* 12.5 2* 12.5
1650
1566

1650
1566

78 444 73.5 653


1184

1071.5

35 35 35
9 35 9
732

732
270

270
113

113

27
27

309 145.5 454 173


2* 12.5
2* 12.5

600 800

schneider-electric.com PIX RoF Catalog | 57


Installation Accessories
and connection

Operation accessories
These accessories are supplied with the switchboard.

The switchboard switchgears may be operated using these accessories.

Double-bit key
DM105750

• Standard double-bit key is provided to lock/unlock the door of the low-voltage


cabinet where applicable

Earthing switch operating lever


DM105751

• Operating lever to operate the earth switch of the switchgear on the front of
panel
• Thanks to its ergonomic design, minimum effort is required by the operator to
operate the earth switch
DM105752

Breaker operating rod


• Breaking operation rod is provided along with switchboard to operate the
breaker inside the switchgear with the door closed
• The operator can close or open the breaker by inserting this rod into the
respective orifice provided on the front door of each switchgear

Crank for breaker trolley


DM105753

• This crank is provided along with switchboard to rack-in and rack-out the HVX
breaker along with trolley inside the switchgear
• This handle is also used to rack-in and rack-out the voltage transformer's
disconnecting link, housed at the rear of Incomer cubicle
• The operation of racking-in and racking-out the breaker is performed with the
door closed, by inserting the crank in the respective slot, which is provided on
the front door of each switchgear

Crank for EasyPact EXE breaker trolley


• This crank is provided along with switchboard to rack-in and rack-out the
Easypact EXE breaker along with trolley inside the switchgear.
DM103805-b

• The operation of racking-in and racking-out the breaker is performed with the
door closed, by inserting the crank in the respective slot, which is provided on
the front door of each switchgear

58 | PIX RoF Catalog schneider-electric.com


TOOLS
Training
This international web site allows you to access all the
Schneider Electric solutions and product information via: Training allows you to acquire the
expertise (installation design, work
• Comprehensive descriptions
with power on, etc.) to increase
• Range datasheets efficiency and improve customer
• A download area service.
• Product selectors
For example, the training catalog
You can also access information for your business and
includes a beginner’s courses in
contact your respective Schneider Electric in-country
electrical distribution, knowledge
support.
of MV and LV switchgear, operation
and maintenance of installations,
PM103687

and design of LV installations.

Web selector

This site allows you to access the Schneider Electric products in just two clicks via a
comprehensive range of datasheets, with direct links to:
• Complete libraries: technical documents, catalogs, FAQs, brochures
• Selection guides from the e-catalog
• Product discovery sites with animations
You will also find illustrated overviews, news subscription, and a list of country contacts.

schneider-electric.com PIX RoF Catalog | 59


Schneider Electric Industries SAS

35 rue Joseph Monier


92500 Rueil-Malmaison, France
Tel : +33 (0)1 41 29 70 00

www.schneider-electric.com

20, April, 2018


NRJCAT17780EN
©2018 Schneider Electric SE. All Rights Reserved.
All Schneider Electric trademarks and service marks are the property of Schneider Electric SE, its subsidiaries and affiliated companies.