Professional Documents
Culture Documents
PIX Rof - NRJCAT17780EN - 0418 PDF
PIX Rof - NRJCAT17780EN - 0418 PDF
PIX RoF
Air Insulated Switchgear up to 17.5 kV
Now with roll-on-floor EasyPact EXE vacuum circuit breaker
schneider-electric.com/PIX RoF
Whether you generate, distribute or
PE91012
Overview 6
Components 36
Safety
Simplicity
Efficiency
Reliability
Safety
•• Designed using the latest tools and techniques ensuring that the
highest level of operator safety is always provided
•• Fully type tested according to the latest IEC standards for
50 and 60 Hz
•• Internal arc tested up to 31.5 kA with AFLR
•• Full metal partition PM class switchgear
•• Embedded mechanical and electrical interlock provides
operator safety
Simplicity
•• PIX RoF has been designed for easy access to all compartments
and is simple to operate and maintain
•• PIX RoF design provides effortless rack-in/rack-out circuit
breaker feature, closed-door circuit breaker operation, inspection
window indicating circuit breaker status
•• The intuitive HMI guides the operator to perform various
operations and indicates the current status of the components
•• VPIS on the front door can instantly indicate voltage presence on
a given cable
•• Fast access via QR codes to products' technical documentation
(cubicles, breakers, relays), stored in the "digital safe repository"
Efficiency
•• Compact dimensions start with a 600 mm wide cubicle for ratings
up to 1250 A and a 800 mm wide cubicle for ratings up to
2 500 A, for up to 17.5 kV rated voltage
••The bus metering and earthing functions are coupled in a single
cubicle to optimize space
Reliability
•• Maximizing service continuity to minimize downtime thanks to
LSC-2B IEC classification
•• Busbar segregation between cubicles (option)
•• It is designed to have a 30 year service life in relation to
installation, operation and environmental conditions
Field of application 8
Safety 9
Simplicity 10
Efficiency 11
Reliability 12
Quality assurance 21
Applications
Buildings
• Healthcare
• Hotels
• Airports
• Banking & Finance
PE91013
Industry
PM106611
PM106614
IEC 62272-200)
PM106613
This category defines the possibility of keeping
other compartments energised (in service) when
opening a main circuit compartment.
PM106615
The metal-enclosed switchgear is classified
for internal arc protection in accordance with
IEC 62271-200 where AFLR is defined as follows:
Type of accessibility
• A: Restricted access to authorized personnel
only. Sides of the enclosure which meet the
criteria of the internal arc test
• F: Front side This internal arc solution protects the operator when in the vicinity of switchgear
• L: Lateral side under normal operating conditions.
• R: Rear side
• The internal arc classification is an option in accordance with IEC 62271-
200 and EN 62271-200. It refers to the effect of internal excess pressure on
covers, doors, inspection ports, vents etc. Moreover, the thermal effects of the
internal arc and its origins on the enclosure, as well as escaping hot gases or
incandescent particles, are taken into account.
• As a reminder, metal-enclosed switchgear and controlgear are granted Internal
PM106636
Operator safety
• Enhanced protection against unintended contact provided by a complete metal
enclosure around the switchgear components
• PIX RoF, equipped with a digital bay controller, provides enhanced operator
safety for control, monitoring and complete automation of the switchgear from a
remote control room
• For safety reasons, the switchgear cubicle can only be operated with the
enclosure door closed and the operator facing the front
• For protection against operating errors, the PIX RoF features a logically
designed, continuous mechanical and electrical interlock system
• Capacitive voltage testing system for zero voltage verification
• PIX RoF has been tested for Internal Arc Classification AFLR in accordnace with
IEC 62271-200 up to 31.5 kA 1s
Easy to install
PM106616
PIX RoF architecture has been designed to accomodate a wide range of installation
requirements:
• Face to face
• Connections can be accessed from the bottom
• Easy to access with plenty of space for cable connection and/or to terminate
bulky and rigid 3 core cables:
- 600 mm for 1 250 A
- 570 mm for 2 500 A
Easy to operate
• Intuitive single line diagrams on the front door of each functional unit provide
a clear description of the cubicle components and power flows. This helps to
optimize operations
PM106617
• With the EasyPact EXE breaker, PIX RoF features direct access to an opening
pushbutton on the front door: this ensures better service continuity
• Voltage Presence Indicators (VPIS) are present on the front door of each
functional unit: this can instantly indicate voltage presence on a given cable!
• A floor rolling trolley provides quick and easy rack-in/rack-out operation for
withdrawable devices
Safe repository
• Thanks to the ingenious design of PIX RoF, many functions can be housed in a
compact cubicle
• Outgoing with currents up to 1 250 A are housed in 600 mm wide cubicles.
2 000 and 2 500 A are installed in 800 mm wide cubicles
• Incomers up to 1 250 A are installed in 600 mm cubicles. 800 mm cubicles
house these between 1 250 A and 2 500 A maximum
• Bus couplers and risers are installed in 600 mm cubicles for ratings up to
1 250 A and 800 mm cubicle for beyond and up to 2 500 A
• Functions for incomers and feeders are housed in compact cubicles:
600 mm for ratings up to 1 250 A and 800 mm for ratings up to 2 500 A
• With heights of between 2 300 mm and 2 800 mm (in line with the Internal Arc
solution), the cubicles can be installed in any building
• The busmetering and earthing functions are coupled in a single cubicle to
optimize space
• All cubicles provide energy with natural cooling with no need of forced
ventilation
Smaller footprint
Less volume
PM106635
Strength of experience
• Fully compliant with IEC standards for AC metal-enclosed switchgear for rated
voltages above 1 kV and up to 53 kV
A major asset
PM106622
Type tested
The electrical and mechanical ratings of the PIX RoF with EasyPact EXE switchgear
and controlgear have been proven by comprehensive type tests.
The type tests were performed in independent and accredited test laboratories in
accordance with international norms and standards. The results are recorded in the
appropriate test records and are made available on request.
EcoStruxure Platform
Cloud and/or
On-Premise
End to End
Edge control
Connected products
PB11768
Arc fault detection
ensure safety and uptime
All the Schneider Electric protection, metering and
control devices can be connected to our Substation
monitoring device.
The HMI can be installed anywhere within the
PM106275
substation to provide local control and monitoring, Bay controller
and power meter
independent of any external systems.
The monitoring information and control functions
PM106278
can be scaled to the needs of each customer.
Optionally the Magelis control and monitoring
functions can be mirrored on a tablet through Wifi
PM106619
PE56366
PM106279
PM106282
PM106283
Local control
Substation monitoring
Connected
products
PM105623b
PM106336
PB113683
PE56366
...
Protection/Metering/Condition Monitoring
PM106624
User-friendliness has always been a value of
Schneider Electric products, and the Easergy P3 is
not an exception, with the unique option to operate
through your smartphone or tablet with “Easergy
SmartApp”.
Rapid setup is achieved using the unique “eSetup
Easergy Pro” software which improves usability.
They provide the following essential functions:
• Effective fault diagnosis and protection planning
Easergy P3 standard
PM106284
Integrated
Protection relay with arc interface
• Small footprint
Easergy P3 advanced
Standalone
PM106276
PM106277
V125
Simple system
V125
PM106276
configuration
PM106276
PM106276
PM106276
PM106277
PM106277
PM105447
High-end system
• Scalable and Customized Arc Detection system tailored to your needs
• Extended possibilities (number of inputs/outputs, logics, selectivity, etc.)
• Open to several serial & Ethernet communication protocols, including IEC 61850
• Multiple technologies (point sensors, loop sensors, fiber optic, etc.)
PM106340
Power SCADA
PM105099
PM106285
PM106619
Characteristics
Power supply Self-powered.
Energy harvested from power circuit.
Accuracy +/- 1 °C
Range -25 °C/+115 °C
Wireless communication ZigBee Green Power 2.4 GHz
Dimensions - Weight 31 x 31 x 13 mm - 15 g
PM106619
PM106286
PM106287
PM106279
PM105623b
PM105623b
PM106288
Install
Life Cycle Services
Life Cycle Services Schneider Electric will help you to install solutions based on your plans improving
efficiency, reliability and safety.
DB408843
Install
How do I install and commission? Operate
Schneider Electric helps you improve your installation uptime and control your
Operate capital expenditure through its service offer.
How do I operate and maintain?
• Asset operation solutions: Provide the information you need to increase
safety, enhance installation performance, and optimize asset maintenance and
investment
Optimize • Advantage service plans: Customize service plans that cover preventive,
How do I optimize?
predictive and corrective maintenance
• On-site maintenance services: Deliver extensive knowledge and experience
in electrical distribution maintenance
Renew
• Spare parts management: Ensure availability of spare parts and provide an
How do I renew my solution?
optimized maintenance budget for your spare parts
• Technical training: Build the necessary skills and expertise to properly and
safely operate your installations
which ensures, monitors and improves quality in line with respective norms and
standards.
PM106629
General characteristics 24
General overview 25
Arc fault 27
Technical characteristics
Rated voltage (kV) 12 17.5
Rated power frequency withstand voltage (kV r ms) 28 38
Rated lightning impulse withstand voltage (kV peak) 75(2) 95
Rated frequency (Hz) 50/60 50/60
Feeder panel with vacuum circuit breaker & bus coupler with vacuum
circuit breaker
DM105730
2. M
etallic shutter for bus bar side arm of breaker
connecting to molded seal-off spouts
1
3. Vacuum circuit breaker truck
4. Front door 16
5. M
etallic shutter for line side arm of breaker
15
connecting to molded seal-off spouts
6. Breaker guiding rails
7. Earthing switch position indicator 2
8. Insertion opening for operating lever of the
earthing switch
9. M
echanical interrogation interlock of insertion port
3
for the earthing switch
10. Cable compartment cover 4
14
11. Cable compartment 5
12. Earth switch with making capacity 6
13
13. Cable connections
7
14. Current transformers 8 12
15. Busbars 9
10
Cubicle view without Internal Arc accessories.
2
DM105731
1 3
5 4
7 6
Operating conditions
PIX RoF has been developed to meet
the following conditions: Normal operating conditions, according to the IEC International Standards listed
below, for indoor switchgear.
• Ambient temperature up to 40 °C, without
derating and natural cooling
Ambient air temperature
• Corrosive atmospheres
• Less than or equal to 40 °C (other values available on request)
(possible adaptation)
• Less than or equal to 35 °C on average over 24 hours
• Storage conditions
• Greater than or equal to – 5 °C
In order to retain all of the functional unit’s
qualities when stored for prolonged periods,
Altitude
we recommend that the equipment is stored in
its original packaging, in dry conditions, and • Less than or equal to 1000 m;
sheltered. • Above 1000 m, a derating coefficient is applied (please contact us)
Atmosphere
• No dust, smoke or corrosive or inflammable gas and vapor, or salt
Humidity
• Average relative humidity over a 24 hour period ≤ 95%
• Average relative humidity over a 1 month period ≤ 90%
• Average vapor pressure over a 24 hour period ≤ 2.2 kPa
• Average vapor pressure over a 1 month period ≤ 1.8 kPa
Standards
The PIX RoF meets the following international
standards:
Integrating many of the proven components of the PIX RoF range, it has all the
intrinsic features of the standard version i.e. very reliable and of high quality.
PIX RoF has been fully tested according to the latest IEC 62271-100 & 200, by
internationally accredited test laboratories.
Switchgear units of the PIX RoF series are:
• M
etal-enclosed; loss of service continuity category according to
IEC 62271-200: LSC 2B-PM
• Type-tested
• Tested for internal arc faults (Internal Arc Classification AFLR)
• Dimensioned for indoor installation
Notes
LSC2B (Loss of Service Continuity
IEC 62272-200)
This category defines the possibility of keeping other compartments
energised (in service) when opening a main circuit compartment.
Type of accessibility
• A: Restricted access to authorized personnel only. Sides of the enclosure
which meet the criteria of the internal arc test
• F: Front side
• L: Lateral side
• R: Rear side
PIX RoF with withdrawable vacuum circuit breaker has a comprehensive range of
functions to suit all requirements for multiple applications.
Selection guide
The following guide will help you to define the most appropriate protection
coresponding to the type of applications you want to energize.
The equipment shown below are the main functions.
For specific requirements, additional functions are available upon request.
Cubicle IC FD BC BR BM
Device Branch-circuit panel Branch-circuit panel Bus section coupler panel Bus riser panel Bus voltage transformer/
• Vacuum • Vacuum • Vacuum • Optional voltage bus earthing switch panel
Circuit Breaker Circuit Breaker Circuit Breaker transformers • Voltage transformers
• Voltage transformers • Optional current • Bus earthing switch
transformers
• Optional earthing switch
Single line
D102_654
DM105734
D102_655
D102_656
D102_657
diagram
DM105735
DM105736
7
2
D102_654
H
5
4 3
W D
1 Busbars
2 Main switching device
3 Cable connections (rear access)
4 Earthing switch
5 Current Transformers
6 Voltage Transformers (optional)
7 Low voltage equipment
IC or FD
Rated voltage Ur (kV) 12 17.5
Breaking capacity (kA) 25 31.5 25 31.5
Rated current - Vacuum circuit breaker (A)
Ir 800 (3) (3) (3) (3)
DM105737
DM105738
6
1
D102_655
H 2
5
4 3
W D
1 Busbars
2 Main switching device
3 Lateral connections (connection to/
from adjacent bus riser cubicle)
4 Earthing switch
5 Current transformers
6 Low voltage equipment
BC
Rated voltage Ur (kV) 12 17.5
Breaking capacity (kA) 25 31.5 25 31.5
Rated current - Vacuum circuit breaker (A)
Ir 800 (3) (3) (3) (3)
DM105739
DM105740
4
1
D102_656
H 2
W D
1 Busbars
2 Withdrawable voltage transformer (optional)
3 Lateral connections (connection to/from
adjacent bus section cubicle)
4 Low Voltage equipment
BR
Rated voltage Ur (kV) 12 17.5
Breaking capacity (kA)
Rated current (A)
Ir 800 (3) (3) (3) (3)
DM105741
DM105742
4
1
D102_657
H 2
W D
1 Busbars
2 Withdrawable voltage transformer
3 Earthing switch
4 Low voltage equipment
BM
Rated voltage Ur (kV) 12 17.5
Breaking capacity (kA)
Rated current (A)
Ir 800 (3) (3) (3) (3)
Panel components 38
Interlocking Systems 45
Circuit breaker
A circuit breaker is a safety device enabling the switching and protection of
electrical distribution networks. It protects all components connected to the
downstream network by opening the circuit during a fault.
The withdrawable EasyPact EXE vacuum circuit breaker is mounted on an
integrated floor rolling trolley enabling easy handling.
Disconnector
A withdrawable disconnector with an integrated floor rolling trolley means
disconnection between the busbar and the cables is feasible by racking it out from
EasyPact EXE circuit breaker on an extraction table the service position to the test position.
It is inserted in place of the circuit breaker in the circuit breaker compartment.
Metering device
A withdrawable metering device with voltage transformers mounted on an
integrated floor rolling trolley means measurement of the circuit voltage for
metering purposes is feasible.
It can be disconnected from the main circuit by racking it out from the service
position to the test position.
PM106631
Earthing switch
The integrated earth switch with fault making capacity makes it possible to earth
the cables or the Busbar (depending on the cubicle) and ensures safety during
maintenance.
In accordance with IEC 62271-102 the integrated earth switch is Class E1 M0.
Earthing switch
EasyPact EXE is our latest range of state-of-the-art vacuum circuit breakers. Its
design is the result of more than 40 years of Schneider Electric experience in
switching devices. Its wide geographical deployment makes it a key PIX Easy
equipment component.
It has been designed to suit specific applications such as: Infrastructure,
Commercial and Industrial buildings, Industrial plants and Distribution substations.
The materials used to manufacture this circuit breaker have been selected and
designed to operate 10 000 cycles.
Mechanism
PM106412
The operating mechanism gives the device an opening and closing speed that is
independent of the operator whether the order is electrical or manual. It carries out
reclosing cycles and it is automatically recharged by a geared motor after each
closing.
Vacuum interrupter
This component is the heart of the circuit breaker. This specific Schneider designed
component breaks the rated short circuit and this is achieved by:
• Choosing materials that are specifically intended for this application (metals and
ceramics)
• Choosing an appropriate assembly process (vacuum, high temperature brazing)
• The use of a "getter" material to absorb the residual gas inside the enclosure
Racking device
PM106402
The racking device moves the circuit breaker from the disconnected position to the
service position and vice versa.
The EasyPact EXE racking device has a robust interlocking system with the
switchgear door, the LV plug, the circuit breaker and the earthing switch.
The materials used to manufacture EasyPact EXE racking trolley sub-assemblies
have been selected and designed to operate 2 000 cycles under the conditions
Racking device defined by the IEC standard.
Common characteristics 12 kV
O-0.3 s - CO-15 s - CO p
Mechanical endurance
EasyPact EXE installed under normal service conditions with a preventive
maintenance program is designed to :
Shunt opening Shunt closing The remote control auxiliaries comprise an electric motor (MCH), a shunt closing
release MX1 release XF release (XF) and a shunt opening release (MX1).
Electric Characteristics
motor MCH Power supply • DC: 24-30 V, 48-60 V, 100-130 V, 200-250 V
• AC (50Hz / 60Hz): 24 V, 48 V, 100-130 V, 200-250 V
Operating range 0.85 to 1.1 Ua
PM105391
the circuit breaker in the "open" position as long as the voltage is maintained at its
terminals.
Characteristics
Power supply • DC: 24-30 V, 48-60 V, 100-130 V, 200-250 V
Shunt opening
release MX1 • AC (50 Hz / 60 Hz): 24 V, 48 V, 100-130 V, 200-250 V
Operating range • DC: 0.7 to 1.1 Ua
• AC: 0.85 to 1.1 Ua
Consumption (VA or W) Triggering 200 (for 200 ms)
Latched 4.5
EasyPact EXE can be equipped with a second Second shunt opening release (MX2)
opening release that can be either a shunt
The second shunt opening release operates by opening the circuit breaker when
opening release or an undervoltage release.
the voltage at the terminals of the release is between 70% and 110% (for a direct
current)- or between 85% and 110% (for an alternative current)- of its rated voltage.
The opening release is designed to withstand a permanent power supply and to
PM106427
lock the circuit breaker in the "open" position as long as the voltage is maintained
at its terminals.
Characteristics
Power supply • DC: 24-30 V, 48-60V, 100-130 V, 200-250 V
• AC (50Hz / 60Hz): 24 V, 48 V, 100-130 V, 200-250 V
Operating range • DC: 0.7 to 1.1 Ua
• AC: 0.85 to 1.1 Ua
Consumption (VA or W) Triggering 200 (for 200 ms)
Latched 4.5
Characteristics
Shunt opening Power supply • DC: 24-30 V, 48-60 V, 100-130 V, 200-250 V
release MX2
• AC (50 Hz / 60 Hz): 24 V, 48 V, 100-130 V, 200-250 V
Operating range Opening 0.35 to 0.7 Ua
Closing 0.85 Ua
Consumption (VA or W) Triggering 200 (for 200 ms)
Latched 4.5
PM105391
EasyPact EXE is equipped with one block of four position contacts as standard,
and the Panel Builder may add one or two additional blocks of four contacts.
Rotary type The maximum number of position contacts is twelve.
contacts (OC)
Characteristics
Standard delivery 1 (1 block of 4 contacts)
Maximum quantity 3 (3 blocks of 4 contacts)
Breaking capacity (A) Standard Min. load: 100 mA / 24 V
Cos : 0.3 V AC 240 / 380 10 / 6
V DC 24 / 48 10 / 6 *
125 10 / 6
250 3
* standard contacts : 10 A; optional contacts : 6 A (temperature derating)
PM106430
EasyPact EXE is always equipped with 1 "ready to close" contact (PF) for
remote control.
Characteristics
Standard delivery 1
Maximum quantity 1
Breaking capacity (A) Standard Min. load: 100 mA / 24 V
Cos : 0.3 V AC 240 / 380 5
V DC 24 / 48 3
125 0.3
250 0.15
Operation counter An operation counter counts the number of operating cycles (close-open) that
(CDM) the device has carried out.
EasyPact EXE is always delivered with an operation counter showing the number
of close-open cycles that have been performed for the factory routine test
(usually 50).
HVX is our latest range of vacuum circuit breakers. It offers a proven state-of-the
art design to meet your specifications for power switching devices in air-insulated
PE910018
switchgear up to 36 kV. HVX provides a valuable solution for you projects. Thanks to
their improved contact design, our interrupters provide unrivalled performance.
Operating mechanisms have been simplified to increase reliability and service life
with very low maintenance. Instead of the traditional spring operating mechanism,
HVX has implemented a single-shaft system with only one torsion spring, reducing
the number of parts and increasing reliability.
Application
HVX is designed to suit all types of applications (utilities, power generation, O&G,
industry, etc.) and for breaking short-circuit currents.
Standard
HVX-C used in PIX Roll on Floor has been fully tested according to IEC 62271-100
and belongs to the M2, C2, E2 class of circuit breakers as defined by the standard.
Between truck and low The truck cannot be actuated unless the low-voltage Rack in handle can not be inserted for operation.
voltage connector connector is inserted.
The low voltage plug cannot be removed when the MV compartment door cannot be opened in transit/
truck is not in the test position. service position.
Between truck and The truck cannot be racked in if the earthing switch The opening in the front door for the truck crank is
earthing switch is ON. locked.
The earthing switch can no longer be switched on if the The interrogation slide below the earthing switch is
truck has left its test position. locked.
The insertion of the earthing switch lever is blocked.
Between the circuit Circuit breaker cannot be racked in or out while it is Rack in handle can not be inserted for operation.
breaker and the truck switched on.
Circuit breaker cannot be switched on/off unless the The circuit breaker cannot be switched ON or OFF.
truck is completely in its test or service position.
Between truck and If the truck front frame is not locked in the cubicle, the The crank cannot be inserted to the truck if both truck
cubicle truck cannot be actuated. handles in the front frame are not moved outwards.
If the truck has left its test position the truck front frame Both truck handles in the front frame are locked.
cannot be unlocked in the cubicle.
Between the truck and The front door can only be opened if the truck is in its The double-bit key cannot be turned.
the front door (optional) test position. Provision available in the front door to open the inerlock
If the front door is open, the truck cannot be moved into The crank cannot be inserted into the truck if the front
the service position. This interlock is standard. door is open.
If the front door is not locked, the truck cannot be The opening in the front door for the truck crank is
actuated. locked.
For the truck in a CB can only be moved into the service position when Rack in access is available only after insertion of the
disconnected position the key is inserted in the lock. key.
(optional key lock) Key is blocked in the lock when the circuit breaker is in
the service position.
PM106284
Universal applications
eficiency
PM106572
Enhanced safety
• Embedded arc protection
• P3F30 Feeder and Transformer
• Built-in virtual injection testing
• P3M30 Motor
• Compliant to international standards (e.g. IEC 60255-1)
• P3G30 Generator
• P3L30 Line differential and Distance
• P3T32 Transformer differential
• P3M32 Motor differential
• P3G32 Generator differential Ease of use
User-friendliness is a key benefit to Easergy P3, made to save time at every
step of your project's life-cycle.
PM106637
A great deal of effort has gone into designing the operational aspects of
our new products. Set up and download/upload are much faster thanks to
the unique eSetup Easergy Pro setting software which significantly improves
usability.
The informative human machine interface provides the information the user
needs, in addition to customized legend texts.
Enhanced usability
The Easergy P3 protection relay design has been enhanced with a number of
features that make relay installation and testing even more efficient and user-
friendly, like the virtual injection testing is accessible with our eSetup Easergy
Pro setting software.
PM106632
PM106411
PE90502
Functions
The arc protection unit detects an arc flash in an installation and trips the feeding breaker.
An arc flash protection maximises personnel safety and minimizes material damage caused by arc faults.
System features
• Typical operation on light only principle • Operation light only • Flexible and modular system can be adapted
-- Input for current criteria for I> and • Up to 10 arc or smoke sensors to different targets requiring arc protection
L> operation • Single trip contact • Central unit and modular units engineer a
-- Integrated 19 - 256 V AC/DC aux. supply • Straightforward installation scheme to your requirements
• Optimised for wind power and other • Operation time 9 ms • Continuous system self-supervision
small applications (including the output relay) • 3-phase curent, zero-sequence voltage and
• Up to 4 arc sensors • Cost-effective solution current
• Selective trip for 2 zones • Self-supervision • Event logs, disturbance recording and real-
• Operation time 1 ms with high speed output • Binary input for blocking or resetting time clock
and 8 ms with a trip relay the unit (programmable) • Operation on simultaneous current and light
• Non-volatile trip status • Option for double arc channel or on light only
• Self-supervision activation trip criteria • Direct connection of arc sensors in the
• Straightforward installation • BIO light transfer option to other central unit without using I/O units
• Cost-effective solution Vamp devices • 7 ms operation time with trip contact and 2
ms with high speed output (HSO)
• Programmable operation zones
• Communication protocol support for SCADA
and automation interfacing
• Supports a maximum of 6 Digital Inputs and
8 Digital Outputs for object (CB) status and
control (order option dependent)
Sensors
Point sensor - surface
• Arc detection from two compartments simultaneously
• Self-monitored
• Cable length adjustable from 6 m to 20 m
Point sensor - pipe
• S
elf-monitored
• Cable length adjustable from 6 m to 20 m
Loop sensor
• Monitors various compartments
• Small bending radius for easy installation
Benefits
• Reduces production losses
• Extended switchgear life cycle
• Reduced insurance costs
• Low investment costs and fast installation
• Enhanced personnel safety
The arc protection unit detects an arc Vamp arc flash range
flash in an installation and trips the
feeding breaker
PM106633
An arc flash protection system
minimizes material damage caused by
arc faults. Vamp 321
Advantages
Reliable Operation
Operation is based on the appearance of light or alternatively on the appearance of
light and current from an external device. The system is immune to faulty trippings
due to dual tripping criteria: light & current.
PE91022
Block type current transformers
• Single, Double or Triple primary
• 1 A or 5 A secondary current
• Class 0.2, 0.5 or 1 for measurement
• 5P10, 5P15 or 5P20 for protection
Voltage transformers
PE91020
Layout 56
Back-to-the-wall installation - IAC AFL 56
Civil Engineering 57
Standard foundation/Ground plan for
57
PIX Roll-on-Floor switchgear
Accessories 58
Switchgear Room
DM105743
≥ 100
25 25
500
2 300
1 650
Switchgear room
DM105744
≥ 100
25 25
≥ 400
≥ 1 400
500
2 800
1 660
Incomer Incomer
1 250 A 1 250 A
≥ 900 mm
Feeder Feeder Feeder Bus coupler Bus riser Feeder Feeder Bus PT
1 250 A 1 250 A 1 250 A 1 250 A 1 250 A 1 250 A 1 250 A 1 250 A
2 150 mm
1 650 mm
600 mm 600 mm 600 mm 600 mm 600 mm 600 mm 600 mm 600 mm 600 mm 600 mm
25 mm 25 mm
≥ 100 mm
Incomer Incomer
2500 A 2500 A ≥ 900 mm
Feeder Feeder Feeder Bus coupler Bus riser Feeder Feeder Bus PT
1250 A 1250 A 1250 A 2 500 A 2 500 A 1250 A 1250 A 1250 A
2150 mm
1650 mm
800 mm 600 mm 600 mm 600 mm 800 mm 800 mm 600 mm 600 mm 600 mm 800 mm
25 mm 25 mm
≥ 100 mm
2* 12.5 68 664
DM105748
DM105749
68 464 2* 12.5
372.5*
485*
831
831
410*
610*
2* 12.5 2* 12.5
1650
1566
1650
1566
1071.5
35 35 35
9 35 9
732
732
270
270
113
113
27
27
600 800
Operation accessories
These accessories are supplied with the switchboard.
Double-bit key
DM105750
• Operating lever to operate the earth switch of the switchgear on the front of
panel
• Thanks to its ergonomic design, minimum effort is required by the operator to
operate the earth switch
DM105752
• This crank is provided along with switchboard to rack-in and rack-out the HVX
breaker along with trolley inside the switchgear
• This handle is also used to rack-in and rack-out the voltage transformer's
disconnecting link, housed at the rear of Incomer cubicle
• The operation of racking-in and racking-out the breaker is performed with the
door closed, by inserting the crank in the respective slot, which is provided on
the front door of each switchgear
• The operation of racking-in and racking-out the breaker is performed with the
door closed, by inserting the crank in the respective slot, which is provided on
the front door of each switchgear
Web selector
This site allows you to access the Schneider Electric products in just two clicks via a
comprehensive range of datasheets, with direct links to:
• Complete libraries: technical documents, catalogs, FAQs, brochures
• Selection guides from the e-catalog
• Product discovery sites with animations
You will also find illustrated overviews, news subscription, and a list of country contacts.
www.schneider-electric.com