PVSYST V6.

85 Vikram Solar Private Limited (India) 05/12/19 Page 1/5

Grid-Connected System: Simulation parameters


Project : 10MW Solar Project,WBSEDCL Asansol-SolarGIS
Geographical Site Asansol-SolarGIS Country India
Situation Latitude 23.64° N Longitude 87.00° E
Time defined as Legal Time Time zone UT+5.5 Altitude 92 m
Albedo 0.20
Meteo data: Asansol-SolarGIS SolarGIS Monthly aver. , period not spec. - Synthetic

Simulation variant : New simulation variant


Simulation date 05/12/19 19h58

Simulation parameters System type Unlimited sheds


Collector Plane Orientation Tilt 15° Azimuth 0°
Sheds configuration Nb. of sheds 50 Unlimited sheds
Sheds spacing 6.00 m Collector width 3.92 m
Inactive band Top 0.02 m Bottom 0.02 m
Shading limit angle Limit profile angle 24.9° Ground cov. Ratio (GCR) 65.3 %
Shadings electrical effect Cell size 15.6 cm Strings in width 1

Models used Transposition Perez Diffuse Perez, Meteonorm


Horizon Free Horizon
Near Shadings Mutual shadings of sheds Electrical effect
User's needs : Unlimited load (grid)

PV Arrays Characteristics (2 kinds of array defined)

Sub-array "330Wp" Si-poly Model Eldora VSP.72.330.05


Custom parameters definition Manufacturer Vikram Solar
Number of PV modules In series 30 modules In parallel 818 strings
Total number of PV modules Nb. modules 24540 Unit Nom. Power 330 Wp
Array global power Nominal (STC) 8098 kWp At operating cond. 7339 kWp (50°C)
Array operating characteristics (50°C) U mpp 1023 V I mpp 7173 A
Sub-array "325Wp" Si-poly Model Eldora VSP.72.325.05
Original PVsyst database Manufacturer Vikram Solar
Number of PV modules In series 30 modules In parallel 206 strings
Total number of PV modules Nb. modules 6180 Unit Nom. Power 325 Wp
Array global power Nominal (STC) 2009 kWp At operating cond. 1817 kWp (50°C)
Array operating characteristics (50°C) U mpp 1019 V I mpp 1783 A
Total Arrays global power Nominal (STC) 10107 kWp Total 30720 modules
Module area 59608 m²

Inverter Model PVS980-58-2000kVA-K


Custom parameters definition Manufacturer ABB
Characteristics Operating Voltage 935-1500 V Unit Nom. Power 2000 kWac
Max. power (=>35°C) 2200 kWac
Sub-array "330Wp" Nb. of inverters 4 units Total Power 8000 kWac
Pnom ratio 1.01
Sub-array "325Wp" Nb. of inverters 1 units Total Power 2000 kWac
Pnom ratio 1.00
Total Nb. of inverters 5 Total Power 10000 kWac

PV Array loss factors


PVsyst Licensed to Vikram Solar Private Limited (India)
PVSYST V6.85 Vikram Solar Private Limited (India) 05/12/19 Page 2/5

Grid-Connected System: Simulation parameters


Array Soiling Losses Loss Fraction 2.0 %
Thermal Loss factor Uc (const) 29.0 W/m²K Uv (wind) 0.0 W/m²K / m/s
Wiring Ohmic Loss Array#1 2.4 mOhm Loss Fraction 1.5 % at STC
Array#2 9.6 mOhm Loss Fraction 1.5 % at STC
Global Loss Fraction 1.5 % at STC
LID - Light Induced Degradation Loss Fraction 2.0 %
Module Quality Loss Loss Fraction 0.0 %
Module Mismatch Losses Array#1, Loss Fraction 0.00 % at MPP
Array#2, Loss Fraction 1.00 % at MPP
Incidence effect (IAM): User defined profile
10° 20° 30° 40° 50° 60° 70° 80° 90°
1.000 1.000 1.000 1.000 1.000 1.000 0.930 0.730 0.000

System loss factors


AC loss, transfo to injection Grid Voltage 33 kV
Wires: 3x300.0 mm² 17528 m Loss Fraction 1.0 % at STC
External transformer Iron loss (24H connexion) 9914 W Loss Fraction 0.1 % at STC
Resistive/Inductive losses 1208.3 mOhm Loss Fraction 1.1 % at STC
Unavailability of the system 1.0 days, 3 periods Time fraction 0.3 %

Auxiliaries loss Proportionnal to Power 6.0 W/kW ... from Power thresh. 0.0 kW

PVsyst Licensed to Vikram Solar Private Limited (India)


PVSYST V6.85 Vikram Solar Private Limited (India) 05/12/19 Page 3/5

Grid-Connected System: Main results


Project : 10MW Solar Project,WBSEDCL Asansol-SolarGIS
Simulation variant : New simulation variant
Main system parameters System type Unlimited sheds
PV Field Orientation Sheds disposition, tilt 15° azimuth 0°
PV modules Model Eldora VSP.72.330.05 Pnom 330 Wp
PV modules Model Eldora VSP.72.325.05 Pnom 325 Wp
PV Array Nb. of modules 30720 Pnom total 10107 kWp
Inverter Model PVS980-58-2000kVA-K Pnom 2000 kW ac
Inverter pack Nb. of units 5.0 Pnom total 10000 kW ac
User's needs Unlimited load (grid)

Main simulation results


System Production Produced Energy 15272 MWh/year Specific prod. 1511 kWh/kWp/year
Performance Ratio PR 80.22 %

Normalized productions (per installed kWp): Nominal power 10107 kWp Performance Ratio PR

8 1.0
Lc : Collection Loss (PV-array losses) 0.81 kWh/kWp/day PR : Performance Ratio (Yf / Yr) : 0.802
0.9
7 Ls : System Loss (inverter, ...) 0.21 kWh/kWp/day
Yf : Produced useful energy (inverter output) 4.14 kWh/kWp/day
0.8
[kWh/kWp/day]

6
0.7
Performance Ratio PR

5
0.6
Energy

4 0.5

0.4
3
Normalized

0.3
2
0.2

1
0.1

0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

New simulation variant


Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² MWh MWh
January 124.0 61.00 17.40 146.7 139.6 1286 1234 0.833
February 139.0 59.00 21.30 158.7 151.6 1381 1277 0.797
March 185.0 76.00 26.10 199.8 190.8 1693 1579 0.782
April 195.0 84.00 31.20 199.0 189.7 1648 1536 0.764
May 188.0 100.00 33.80 183.3 173.8 1503 1446 0.781
June 152.0 95.00 32.20 145.8 137.5 1217 1171 0.795
July 137.0 92.00 29.20 132.7 125.0 1124 1080 0.805
August 139.0 90.00 28.30 138.0 130.2 1168 1121 0.804
September 136.0 81.00 27.30 141.1 133.6 1204 1156 0.811
October 144.0 74.00 24.90 159.5 151.5 1372 1318 0.818
November 125.0 64.00 21.30 144.5 137.6 1260 1210 0.828
December 114.0 61.00 17.89 134.7 128.3 1190 1142 0.839
Year 1778.0 937.00 25.92 1883.7 1789.3 16046 15272 0.802

Legends: GlobHor Horizontal global irradiation GlobEff Effective Global, corr. for IAM and shadings
DiffHor Horizontal diffuse irradiation EArray Effective energy at the output of the array
T_Amb T amb. E_Grid Energy injected into grid
GlobInc Global incident in coll. plane PR Performance Ratio

PVsyst Licensed to Vikram Solar Private Limited (India)


PVSYST V6.85 Vikram Solar Private Limited (India) 05/12/19 Page 4/5

Grid-Connected System: Special graphs


Project : 10MW Solar Project,WBSEDCL Asansol-SolarGIS
Simulation variant : New simulation variant
Main system parameters System type Unlimited sheds
PV Field Orientation Sheds disposition, tilt 15° azimuth 0°
PV modules Model Eldora VSP.72.330.05 Pnom 330 Wp
PV modules Model Eldora VSP.72.325.05 Pnom 325 Wp
PV Array Nb. of modules 30720 Pnom total 10107 kWp
Inverter Model PVS980-58-2000kVA-K Pnom 2000 kW ac
Inverter pack Nb. of units 5.0 Pnom total 10000 kW ac
User's needs Unlimited load (grid)

Daily Input/Output diagram

70000
Values from 01/01 to 31/12
60000
[kWh/day]

50000
grid

40000
into

30000
injected

20000
Energy

10000

0
0 1 2 3 4 5 6 7 8
Global incident in coll. plane [kWh/m².day]

System Output Power Distribution

500000
Values from 01/01 to 31/12
Bin]

400000
/
[kWh

300000
grid
into
injected

200000
Energy

100000

0
0 2000 4000 6000 8000
Power injected into grid [kW]

PVsyst Licensed to Vikram Solar Private Limited (India)


PVSYST V6.85 Vikram Solar Private Limited (India) 05/12/19 Page 5/5

Grid-Connected System: Loss diagram


Project : 10MW Solar Project,WBSEDCL Asansol-SolarGIS
Simulation variant : New simulation variant
Main system parameters System type Unlimited sheds
PV Field Orientation Sheds disposition, tilt 15° azimuth 0°
PV modules Model Eldora VSP.72.330.05 Pnom 330 Wp
PV modules Model Eldora VSP.72.325.05 Pnom 325 Wp
PV Array Nb. of modules 30720 Pnom total 10107 kWp
Inverter Model PVS980-58-2000kVA-K Pnom 2000 kW ac
Inverter pack Nb. of units 5.0 Pnom total 10000 kW ac
User's needs Unlimited load (grid)

Loss diagram over the whole year

1778 kWh/m² Horizontal global irradiation


+5.9% Global incident in coll. plane

-0.05% Global incident below threshold


-1.80% Near Shadings: irradiance loss
-1.29% IAM factor on global
-2.00% Soiling loss factor

1789 kWh/m² * 59608 m² coll. Effective irradiation on collectors


efficiency at STC = 16.98% PV conversion

18110 MWh Array nominal energy (at STC effic.)


-0.54% PV loss due to irradiance level

-7.84% PV loss due to temperature

-0.17% Shadings: Electrical Loss , sheds1 strings in width


-2.00% LID - Light induced degradation
-0.22% Module array mismatch loss
-0.98% Ohmic wiring loss
16046 MWh Array virtual energy at MPP

-1.68% Inverter Loss during operation (efficiency)


0.00% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
0.00% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
-0.03% Night consumption
15772 MWh Available Energy at Inverter Output

-0.59% Auxiliaries (fans, other)


-0.94% System unavailability
-0.53% AC ohmic loss
-1.15% External transfo loss
15272 MWh Energy injected into grid

PVsyst Licensed to Vikram Solar Private Limited (India)