Summary Performance Report For Air Cooled Chiller

Project: MKM 12/10/2018


Prepared By: PT Berca Carrier Indonesia 02:25PM

PackagedChillerReport:DoNotEdit

AquaSnap TM Air-Cooled Scroll Chiller

Unit Information Performance Information


Tag Name: Air Cooled Chiller Cooling Capacity: 39,68 kW
Model Number: 30RB039S Total Compressor Power: 13,00 kW
Quantity: 1 Total Fan Motor Power: 0,7621 kW
Manufacturing Source: Shanghai, China Total Unit Power (without pump): 13,76 kW
Refrigerant: R410A Efficiency (without pump): 2,884 kW/kW
Operating Weight: 458 kg A-Weighted Sound Power Level: 80 dbA
Unit Length: 2109 mm A-Weighted Sound Pressure Level: 57 dBA
Unit Width: 1090 mm
Unit Height: 1321 mm Accessories and Installed Options
Standard Unit
Evaporator Information Opt. 116D Without Hydronic Module
Fluid Type: Fresh Water Standard Unit
Fouling Factor: 0,0180 (sqm-K)/kW
Leaving Temperature: 7,00 °C Electrical Information
Entering Temperature: 12,00 °C Unit Voltage: 400-3-50 V-Ph-Hz
Fluid Flow: 1,891 L/s Standby Power: 0,2420 kW
Pressure Drop: 42,5 kPa Minimum Voltage: 360, Volts
Maximum Voltage: 440, Volts
Condenser Information
Altitude: 0,000 m Electrical Electrical
Number of Fans: 1 Amps (Un) Circuit 1 Circuit 2
Total Condenser Fan Air Flow at 20°C: 3800 L/s Max Unit Current 32,9 ---
Entering Air Temperature: 35,0 °C Draw (RLA)
Max Start Up 112,7 ---
Integrated Pump Information Current (ICF)
No Pump Selected Nominal Unit 25,7 ---
Current Draw (A)

Sound Power Lw according to ISO 9614-1 and EUROVENT standard 8/1.

Packaged Chiller Builder China Export 3.39P Page 1 of 1