Lay-up

Causes for Flame Failure in a


Boiler and Operator Action
Energy & Power Plants / By Dr V T Sathyanathan / Mechanical Engin

Maintaining a good flame in a boiler is the key to a good boiler perfor


Unstable flame is always a threat for boiler furnace explosion, which
lead to a large outage of the boiler and economic loss. When a flame
report this ad occurs in a boiler, the boiler desk operator and the local operators w
MORE INFO to act immediately and bring the boiler back on line with all safety ta
consideration. It is always seen that the greatest number of explosio
Recent boilers takes place during start-up and shutdown. It is during this pe
the probability for unburned to accumulate in flue gas path of the bo
Biomass Pellets – A More very high. Hence it has become a practice of all boiler designers to i
Portable And Flexible Fuel purging the boiler with boiler start-up. Flame failure in a boiler can be
Is Antimatter Real? many reasons.
https://www.brighthubengineering.com/power-plants/52543-flame-failure-causes-in-boiler-and-operator-action/ 1/9
9/15/2019 Causes for Flame Failure in a Boiler and Operator Action

How to Remove Water from


Flue Gas
All About Natural Gas:
Transmission Plants and
Storage Solutions
Boiler Water Treatment – Why
is It Important ?
Natural Gas Leak Survey
Equipment The specific causes
Heavy oil or warm-up oil trip valve closing
Popular Sudden reduction in mill feeder speed to a minimum
Loss of ignition energy
Flame scanner trip due to poor and unstable flame
Malfunctioning of flame scanner
Scanner air fan trip and slag build-up
Sudden coal hang-up in one or more mills
Coal feeder trip
Advantages and Electrical supply failure
Disadvantages of Natural Gas Air flow below 30% of total air flow
The Efficiency of Power Tripping of all forced draft air fan
Plants of Different Types Tripping of all induced draft air fan
Very high furnace pressure
These causes lead to flame failure individually or in a few a combina
This will depend upon when the flame quality becomes unacceptab
The plant response
AC and DC Electric Shock In many cases it is possible to see fluctuation in furnace pres
Effects Compared

https://www.brighthubengineering.com/power-plants/52543-flame-failure-causes-in-boiler-and-operator-action/ 2/9
9/15/2019 Causes for Flame Failure in a Boiler and Operator Action

How to Determine Electrical Flickering of the flame scanner can be seen when flame quali
Shock Hazard Boundaries deteriorates
Reverse Osmosis vs. Multi Tripping of the primary air fan or very low primary air header p
Stage Flash Distillation: A is more probable to occur just before flame failure
Comparison Between
Different Desalination After flame failure immediately the unit trips
Methods
The boiler desk operator immediate action
The boiler desk operator will have to start boiler purge
Assess the reason for flame failure
Light-up the boiler after the purge is complete and local oper
gives clearance
How Power Plant Boiler Local operator immediate action
Works?
Check furnace and report to boiler control room
Related Check flame scanners for any possible slag accumulation
CAD and AutoCAD Check mills and restore them for starting
Check oil trip valves for proper function
Energy & Power Plants Make sure oil guns are in position for light up of boiler
Fluid Mechanics & How it
Relates to Mechanical
Engineering
HVAC: Heating, Ventilation &
Air-Conditioning
https://www.brighthubengineering.com/power-plants/52543-flame-failure-causes-in-boiler-and-operator-action/ 3/9
9/15/2019 Causes for Flame Failure in a Boiler and Operator Action

Power Transmission and Sponsored Content


Distribution
Thermodynamics

Sponsored Content
Giant Mistakes In Historical Films Explore PayPal Checkout [Gallery] Genius Russ
That Never Should Have PayPal - Merchant Shares A Prediction A
Happened That's Making Experts
Offbeat Money Versed
Recommended by

It has to be remembered that delay in lighting up the boiler will decay


Savvy Americans Are Opening High Yield boiler pressure and temperature. Depending upon the duty of the bo
Savings Accounts
Yahoo Search time taken to come back on line will vary.

Flame Failure in Boiler


Explore PayPal Checkout
PayPal - Merchant

Find Your Sanctuary


Tualatin Valley

If You Like to Play, this City-Building Game is


Addictive. No Install.
Forge of Empires
Recommended by

https://www.brighthubengineering.com/power-plants/52543-flame-failure-causes-in-boiler-and-operator-action/ 4/9
9/15/2019 Causes for Flame Failure in a Boiler and Operator Action

The

SHOP OUR LAMINATE SELECTION

report this ad

9 Comments Bright Hub Media 

 Recommend t Tweet f Share Sort

Join the discussion…

LOG IN WITH OR SIGN UP WITH DISQUS ?

Name
https://www.brighthubengineering.com/power-plants/52543-flame-failure-causes-in-boiler-and-operator-action/ 5/9
9/15/2019 Causes for Flame Failure in a Boiler and Operator Action

Gentian Buzi • 10 months ago


The flame is unstable after the ignition and stop the boiler. what might be the probl
△ ▽ • Reply • Share ›

James Iszatt • 4 years ago


Hi y'all. Recently i had a huge gas leak. We experienced a power cut whilst the gas
operating. Therefore the electronic valve did not close and we had a large gas leak
chimney loosing about 2 weeks worth of gas for hot water use here.
I was lucky that there was no explosion as there was a wood stove burning in the h
the time and they share the same chimney pot (separate flues side by side).
I decided to do a search to see if it is recommended to shut off the gas during a po
but i don't see this information anywhere.
I'm surprised that this is not common knowledge. Was i unlucky that the valve did
Should it not have a safety which would stop this from happening?
As far as i am aware there is a gas valve which is operated by a solenoid or a moto
Once the power was restored and the flue was clear the boiler operates as normal
△ ▽ • Reply • Share ›

Parag Agrawal • 4 years ago


In one of our case---Unit was running at 96 MW with 3 mills in service and one gun
elevation, all 3 mill got tripped on loss of PA.unit was not tripped on flame failure is
logically correct.
△ ▽ • Reply • Share ›

S.Rajanarsu > Parag Agrawal • 3 years ago


yaa correct, it depends on the quality of flame being maintained in the furna
when the mills trips, the furnace pessure will go to nagative which lead the
flame to become unstable. The maximum chance is there that the unit trips
failure but how u r boiler have saved. You please see the furnace pressure t
the time of mill trips out. It means furnace draft control system working fine
△ ▽ • Reply • Share ›

Dr V T Sathyanathan Mod • 9 years ago


It has been seen that with 30% air flow we are able create adequate scavenging of
fuel in the furnace. Increasing this further did not help much. As you are purging w
large volumes also take away the heat without any advantage.
1△ ▽ • Reply • Share ›

Rajapandian • 9 years ago


Dear Sir,
I have doubt regarding the furnace purge air flow.May i know why in most of the bo
minimum air flow is 30%?.Is any specific reason for that?.On what basis we are giv
air flow.
Thank u
△ ▽ • Reply • Share ›

pk pradip > Rajapandian • 4 years ago


2 stage starting air compressor inter stage pressure reading reason for this
bar
△ ▽ • Reply • Share ›

pk pradip > pk pradip • 4 years ago


2 stage start air compressor inter stage pressure reading 5 bar reaso
keeing.
△ ▽ • Reply • Share ›

Kaushalgambhire > Rajapandian • 8 years ago


Minimum air flow is depend on the furnace size and area.
△ ▽ • Reply • Share ›

https://www.brighthubengineering.com/power-plants/52543-flame-failure-causes-in-boiler-and-operator-action/ 6/9
9/15/2019 Causes for Flame Failure in a Boiler and Operator Action

ALSO ON BRIGHT HUB MEDIA

Stages of Osteoarthritis: What Everyone Wondering How to Break Up with


Should Know About the Three Stages Asperger's Partner Kindly? Let Br
1 comment • 10 months ago 2 comments • 10 months ago
arejaye — I have osteoarthritis(osteonecrosis) Michael King — I’m the partner wit
in both of my shoulders. There is absolutely feel touch deprived. My neurotypic
NO relief from the pain unless I take my pain has multiple sclerosis and fibromy

Optic Nerve Anatomy Includes a Meninges What to Expect After Cardiac Abl
Sheath and Extends to the … Results, Complications and Reco
1 comment • 9 months ago 2 comments • 10 months ago
my — external sheath of optic nerve is from Voco_Veritas — Dear Janet, I had 3
sclera, then, where is inner sheath of optic with ablations due to supra-ventric
nerve from. tachycardia located in an unusual

✉ Subscribe d Add Disqus to your siteAdd DisqusAdd 🔒 Disqus' Privacy PolicyPrivacy PolicyPrivacy

← Previous Post Next P

Copyright © 2019 Bright Hub About | Copyright Po


Engineering. All Rights Reserved. Policy | T

https://www.brighthubengineering.com/power-plants/52543-flame-failure-causes-in-boiler-and-operator-action/ 7/9
9/15/2019 Causes for Flame Failure in a Boiler and Operator Action

Sponsored Content

Explore PayPal Checkout Savvy Americans Are Opening 60 Rare Vietnam W


PayPal - Merchant High Yield Savings Accounts Discretion Advise
Yahoo Search Groovy History

[Pics] NFL Teammates Are California, Our $5 wines are 43 Rare Photos of
Terrified To Even Practice Against better than most $50 wines and the Summer o
Him Firstleaf CelebsPulse
Tie Breaker
Recommende

SEARCH N AV I G AT I O N FOLLOW US

Civil
Custom Search  TWITTER

E l e c trical
 FA C E B O O K
M e c hanical

M a rin e

https://www.brighthubengineering.com/power-plants/52543-flame-failure-causes-in-boiler-and-operator-action/ 8/9
9/15/2019 Causes for Flame Failure in a Boiler and Operator Action

© brighthubengineering.com. All rights reserved. | Privacy Policy

https://www.brighthubengineering.com/power-plants/52543-flame-failure-causes-in-boiler-and-operator-action/ 9/9

You might also like