FIRE PUMP CONTROLS

Standard Catalog

Catalog Sections:

General Information
Diesel Engine Controllers
Electric Fire Pump Controllers
Transfer Switches
Limited Service Controllers
Jockey Pump, Alarm Panels

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
GENERAL
INFORMATION
SECTION CONTENTS:

Representatives
Recommended Long Term Storage
Approximate Controller Shipping Weights

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
METRON SERVICE REPRESENTATIVES
ALABAMA Cybertronic Coatings LLC CONNECTICUT
1905 West Thomas Street Walter E. Dawson
Suite D-181 dba E J Enterprises
Hammond, LA 70401 33 Bartlett Loop
(985) 351-5681 Warner, NH 03278-4500
Mr. Glenn Bradshaw (603) 456-3014
Fax (603) 456-3013
ALASKA Metron, Inc. Mr. Walt Dawson
1505 W. Third Avenue
Denver, CO 80223 DELAWARE GDS Controls
(303) 592-1903 5301 Carlisle Road
Fax (303) 534-1947 Dover, PA 17315
Service Department (717) 292-9403
Fax (717) 292-5746
ARIZONA Ken Cramer Co. Mr. Dave Stephens
4733 Torrance Blvd. #296
Torrance, CA 90503 DISTRICT OF COLUMBIA
(310) 375-6356 GDS Controls
Fax (310) 375-6356 + 5301 Carlisle Road
Mr. Tom Stolarski Dover, PA 17315
(717) 292-9403
ARKANSAS J.A. Controls Inc. Fax (717) 292-5746
13118 Suzanne Mr. Dave Stephens
Stanford, TX 77477
(281) 530-2500 FLORIDA Horton & Company
Fax (281) 530-9202 Tampa & 3421 San Jose Street
Mr. Jim Adams Central Tampa, FL 33629
(813) 871-2393
CALIFORNIA Fax (813) 839-3292
Northern Control Central, Inc. Mr. Lee Horton
12 La Serena Court Mr. Bob Horton
Alamo, CA 94507
(925) 743-8994 Southern Metron, Inc
Fax (925) 743-8437 1505 W. Third Avenue
Mr. Kenneth Pearce Denver, CO 80223
(303) 592-1903
Southern Ken Cramer Co. Fax (303) 534-1947
4733 Torrance Blvd. #296 Service Department
Torrance, CA 90503
(310) 375-6356 Panhandle Cybertronic Coatings LLC
Fax (310) 375-6356 + 1905 West Thomas Street
Mr. Tom Stolarski Suite D-181
Hammond, LA 70401
COLORADO Metron, Inc. (985) 351-5681
1505 W. Third Avenue Mr. Glenn Bradshaw
Denver, CO 80223
(303) 592-1903 GEORGIA Aqua Flow Service
Fax (303) 534-1947 4220 Steve Reynolds Blvd, Suite 16
Service Department Norcross, GA 30093
(770) 935-8443
Fax (770) 935-8443
Mr. James Girsch
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
METRON SERVICE REPRESENTATIVES
HAWAII Introl Hawaii, Inc. KANSAS Custom Enterprises
2020 A Kahai Street 93 10 Wenonga
Honolulu, HI 96817 Leawood, KS 66206
(808) 845-7471 (913) 383-2545
Fax (808) 847-2734 Mr. Dick Kerr
Mr. Les Lum
KENTUCKY Metron, Inc.
IDAHO Metron, Inc. 1505 W. Third Avenue
1505 W. Third Avenue Denver, CO 80223
Denver, CO 80223 (303) 592-1903
(303) 592-1903 Fax (303) 534-1947
Fax (303) 534-1947 Service Department
Service Department
LOUISIANA Cybertronic Coatings LLC
ILLINOIS 1905 West Thomas Street
North- Metron, Inc. Suite D-181
Southeast 3600 Woodgate Drive Hammond, LA 70401
Wheatfield, IN 46392 (985) 351-5681
(219) 765-7645 Mr. Glenn Bradshaw
Fax (219) 956-2788
Dana Everett
MAINE Walter E. Dawson
Southwest Custom Enterprises dba E J Enterprises
93 10 Wenonga 33 Bartlett Loop
Leawood, KS 66206 Warner, NH 03278-4500
(913) 383-2545 (603) 456-3014
Mr. Dick Kerr Fax (603) 456-3013
Mr. Walt Dawson
Northwest Metron, Inc.
3600 Woodgate Drive MARYLAND GDS Controls
Wheatfield, IN 46392 5301 Carlisle Road
(219) 765-7645 Dover, PA 17315
Fax (219) 956-2788 (717) 292-9403
Dana Everett Fax (717) 292-5746
Mr. Dave Stephens
IOWA East Metron, Inc.
3600 Woodgate Drive MASSACHUSETTS
Wheatfield, IN 46392 Walter E. Dawson
(219) 765-7645 dba E J Enterprises
Fax (219) 956-2788 33 Bartlett Loop
Dana Everett Warner, NH 03278-4500
(603) 456-3014
IOWA West Custom Enterprises Fax (603) 456-3013
93 10 Wenonga Mr. Walt Dawson
Leawood, KS 66206
(913) 383-2545 MICHIGAN
Mr. Dick Kerr So. Central Metron, Inc.
1505 W. Third Avenue
Denver, CO 80223
(303) 534-1947
Fax (303) 592-1903
Service Department
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
METRON SERVICE REPRESENTATIVES

North Ainslie Co. NEVADA


26501 Fremont Dr Las Vegas Ken Cramer Co.
Zimmerman, MN 55398 4733 Torrance Blvd. #296
(612) 920-2996 Torrance, CA 90503
Fax (612) 395-5577 (310) 375-6356
Mr. Bill Book Fax (310) 375-6356 +
Mr. Tom Stolarski
MINNESOTA Ainslie Co.
26501 Fremont Dr NEW HAMPSHIRE
Zimmerman, MN 55398 Walter E. Dawson
(612) 920-2996 dba E J Enterprises
Fax (612) 395-5577 33 Bartlett Loop
Mr. Bill Book Warner, NH 03278-4500
(603) 456-3014
MISSISSIPPI Cybertronic Coatings LLC Fax (603) 456-3013
1905 West Thomas Street Mr. Walt Dawson
Suite D-181
Hammond, LA 70401 NEW JERSEY
(985) 351-5681 GDS Controls
Mr. Glenn Bradshaw 5301 Carlisle Road
Dover, PA 17315
MISSOURI Custom Enterprises (717) 292-9403
93 10 Wenonga Fax (717) 292-5746
Leawood, KS 66206 Mr. Dave Stephens
(913) 383-2545
Mr. Dick Kerr NEW MEXICO
Metron, Inc.
MONTANA Metron, Inc. 1505 W. Third Avenue
1505 W. Third Avenue Denver, CO 80223
Denver, CO 80223 (303) 592-1903
(303) 592-1903 Fax (303) 534-1947
Fax (303) 534-1947 Service Department
Service Department
NEW YORK Walter E. Dawson
NEBRASKA Custom Enterprises Except dba E J Enterprises
93 10 Wenonga New York City 33 Bartlett Loop
Leawood, KS 66206 Long Island Warner, NH 03278-4500
(913) 383-2545 (603) 456-3014
Mr. Dick Kerr Fax (603) 456-3013
Mr. Walt Dawson
NEVADA Control Central, Inc.
12 La Serena Court New York City Metron, Inc.
Alamo, CA 94507 Long Island 1505 W. Third Avenue
(925) 743-8994 Denver, CO 80223
Fax (925) 743-8437 (303) 534-1947
Mr. Kenneth Pearce Fax (303) 592-1903
Service Department

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
METRON SERVICE REPRESENTATIVES

NORTH CAROLINA PENNSYLVANIA


E. H. Walters & Assoc., Inc. Western Metron, Inc.
4303 Tabernacle Rd. 1505 W. Third Avenue
Lancaster, SC 29720 Denver, CO 80223
(803) 286-4777, Fax same (303) 534-1947
Mr. Eustice Walters Fax (303) 592-1903
Mr. Van Walters Service Department
PENNSYLVANIA
NORTH DAKOTA Eastern GDS Controls
Ainslie Co. 5301 Carlisle Road
26501 Fremont Dr Dover, PA 17315
Zimmerman, MN 55398 (717) 292-9403
(612) 920-2996 Fax (717) 292-5746
Fax (612) 395-5577 Mr. Dave Stephens
Mr. Bill Book
RHODE ISLAND
OHIO Walter E. Dawson
Northern Metron, Inc. dba E J Enterprises
1505 West Third Avenue 33 Bartlett Loop
Denver, CO 80223-2811 Warner, NH 03278-4500
(303) 592-1903 (603) 456-3014
Fax (303) 534-1947 Fax (603) 456-3013
Service Department Mr. Walt Dawson

Southern Metron, Inc. SOUTH CAROLINA


1505 West Third Avenue E. H. Walters & Assoc.
Denver, CO 80223-2811 4303 Tabernacle Rd.
(303) 592-1903 Lancaster, SC 29720
Fax (303) 534-1947 (803) 286-4777, Fax same
Service Department Mr. Eustice Walters
Mr. Van Walters
OKLAHOMA Metron, Inc.
1505 West Third Avenue SOUTH DAKOTA
Denver, CO 80223-2811 Ainslie Co.
(303) 592-1903 26501 Fremont Dr
Fax (303) 534-1947 Zimmerman, MN 55398
Service Department (612) 920-2996
Fax (612) 395-5577
OREGON Metron, Inc. Mr. Bill Book
1505 W. Third Avenue
Denver, CO 80223 TENNESSEE Metron, Inc.
(303) 592-1903 1505 W. Third Avenue
Fax (303) 534-1947 Denver, CO 80223
Service Department (303) 592-1903
Fax (303) 534-1947
Service Department

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
METRON SERVICE REPRESENTATIVES

TEXAS J.A. Controls Inc. WEST VIRGINIA


13118 Suzanne GDS Controls
Stanford, TX 77477 5301 Carlisle Road
(281) 530-2500 Dover, PA 17315
Fax (281) 530-9202 (717) 292-9403
Mr. Jim Adams Fax (717) 292-5746
Mr. Dave Stephens
UTAH Metron, Inc.
1505 W. Third Avenue WISCONSIN Metron, Inc.
Denver, CO 80223 3600 Woodgate Drive
(303) 592-1903 Wheatfield, IN 46392
Fax (303) 534-1947 (219) 765-7645
Service Department Fax (219) 956-2788
Dana Everett
VERMONT Walter E. Dawson
dba E J Enterprises WYOMING Metron, Inc.
33 Bartlett Loop 1505 W. Third Avenue
Warner, NH 03278-4500 Denver, CO 80223
(603) 456-3014 (303) 592-1903
Fax (603) 456-3013 Fax (303) 534-1947
Mr. Walt Dawson Service Department

VIRGINIA
Southern E. H. Walters & Assoc.
4303 Tabernacle Rd.
Lancaster, SC 29720
(803) 286-4777, Fax same
Mr. Eustice Walters
Mr. Van Walters

Northern GDS Controls


5301 Carlisle Road
Dover, PA 17315
(717) 292-9403
Fax (717) 292-5746
Mr. Dave Stephens

WASHINGTON
Metron, Inc.
1505 W. Third Avenue
Denver, CO 80223
(303) 592-1903
Fax (303) 534-1947
Service Department

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
METRON INTERNATIONAL SERVICE REPRESENTATIVES
LATIN AMERICA

Bolivia Guatemala
TERVAP Ltda Hidromaq, Ltda
Ing Rolando Cerezo C. Ing Boris Llamas
Av. 3 Pasos al Frente No.13 5ta. Calle 7-23 Zona 17
Santa Cruz de la Sierra Guatemala C.A.
Bolivia Email: hidromaq1@yahoo.com
E-Mail: rcerezo@tervap.com Tel: 2255-8017
Tel: 591 33466118 / 591 33465842 Fax: 2259-5826
Fax: 591 33493121 Cell: 5632-8173
Cell: 591 75008087 / 72189245
Panama
Brazil Firetech Corp
Sao Paulo Ing Abraham Guilbe
Coenger Comercio, Engenharia Ltda. E-mail: aguilbe@firetechcorp.com
Ing. Luiz Alberto Benedetti Tel: 507-392-1039 x 101
Ing. Joao de Moraes Barbosa Fax: 507-392-1040
Rua Martim Bruchard, 310 Cell: 507-6619-9143
Sao Paulo, CEP 03043-020
Brazil Peru
E-Mail: coenger@ig.com.br Baustelle S.A.
Tel: 55 11 5571 4867 Ing Willman Baustelle
Fax: 55 11 3209 1384 Mama Ocllo #1853-B
Cell: 55 11 9761 8003 Lince, Lima 14, Lima
Chile Peru
Macam Ltda E-mail: willman.gonzalez@baustelle-sa.com
Ing. Carlos Sarquis Tel: 51 1 265-0112
Aracena Infanta No 188 Fax: 51 1 9657-9102
San Joaquin Cell: 51 1 470-5330
Santiago, Chile
Email: commacam@entelchile.net ICR Peru S.A.
Tel: 56 2 555 0959 Ing. Armando Atencio Pizarro
Fax: 56 2 556 1397 Jiron San Martin
Ecuador M2. E Lot 6 Los Huertos de Huachipa
LEVO, Ltda Districto Lurigancho
Sergio Marcel Lima 15, Peru
Centro ejecutivo Espacia – Oficina #212 E-Mail: icrperu@terra.com.pe
Interoceanica Km 10.5 Cumbaya Tel: 51 1371 0443
Quito, Ecuador Fax: 51 1371 0443
Email: ingenerialevo@cablemodem.com.ec Cell: 51 1 9816 5655
Tel: 2 041 487/204 0761
Fax: 2 040 856 Venezuela
Cell: 098 912 434 SAPORITI Equipos y Sistemas II C.A
Ing. Pedro Saporiti, NFPA Cert
Mariperez, Calle Trujillo #12
Caracas,Venezuela 10501
Email:pruebasbombascontraincendio@gmail.com
Cell: 58 414 3275991
Fax 58 212 6352240

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
METRON INTERNATIONAL SERVICE REPRESENTATIVES

MEXICO
México City
Avila y Hijos Asociados
Ing. Francisco Avila
Av. Hidalgo No. 118
Col. Miguel Hidalgo
Tlalnepantla, Edo. De Mexico C.P. 54060
Mexico
E-Mail: franavil@aol.com
Tel: 52 555 397 7489
Fax: 52 555 397 7489
Cell: 52 1 44 553 134 9796

México City/Monterrey
VIPE INTERNACIONAL SA DE CV
Ing Sabas Villegas
Escobedo 613 A Pte Zona Centro
San Nicolas de los Garza
N.L. Mexico CP 66400
E-Mail:svillegas@vipeinternacional.com
Tel: (81) 84794979
Cell: (81) 84797226

Global Technologies and Supplies, S.A. de C.V


Ing. Alfredo Coronado
Gardenia 3011 Col. Moderna
Monterrey, N.L. 64350
Mexico
E-Mail: alfredo.global@prodigy.net.mx
Tel: 52 81 8371 0629
Fax: 52 81 8354 6005
Cell: 52 81 8259 9951

Guadalajara
FTECH S. A. de C. V.
IME. Luis Felipe Serrano V.
NFPA Member
Volcán Momotombo 2714, El Colli Urbano
Zapopan, Jalisco, Mexico. C. P. 45070
Email: luis.serrano@ftech.com.mx
Tel: 33 37930470, Ext. 116
Cell: 33 11665631

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
METRON INTERNATIONAL SERVICE REPRESENTATIVES

MIDDLE EAST
CARIBBEAN
Egypt
Puerto Rico
Arabian Engineering Business
Omar Burgos
12 Amierlay Khalil Kamel st.
Urb. Colina Del Plata
Heliopolis, Cairo
3-E17 Camino del Monte
202-26341296
Toa Alta, Puerto Rico 00953
Mr. Essam ABD El- Hamid
E-Mail: omarburgos43@yahoo.com
Tel: (787) 210-8265
Israel
Trinidad & Tobago
E. Shlomi Services
All Purpose Diesel Limited
Eliezer Shlomi
Dwayne Yawching
Gonot 73
Allenyne Anthony
Israel 50293
#20 Amber Drive Diamond Vale Diego Martin
Tel: 972 3 690 4260
Carenage, Trinidad, West Indies
Fax: 972 3 960 4327
E-Mail: allpurposediesel@hotmail.com
Work: (868) 695 1551 United Arab Emirates
Fax: (868) 695-1551 Alaman
Cell: (868) 721-2725 Dubai- United Emerates
971-4 2580090
Fax 971-4-2580098
Mr. Qais Khader
ASIA

China Martyn Clarke


NKH Technology PO Box 36811
Thomas Ng Al Ramoul Post Office
Block 1048 Eunos Avenue 6 Dubai, UAE
#01 – 143 E-mail: mjclarke2000@yahoo.com
SINGAPORE, Singapore 409627 Tel: 971 4882 0342
Tel: 65 841 7088 Fax: 971 4882 0342
Fax: 65 841 7077

Singapore
NKH Technology
Thomas Ng
Block 1048 Eunos Avenue 6 PLEASE CONSULT FACTORY FOR
#01 – 143 LOCATIONS/REGIONS NOT LISTED.
SINGAPORE, Singapore 409627
Tel: 65 841 7088
Fax: 65 841 7077

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
RECOMMENDED LONG TERM STORAGE

It is recommended that controllers be inspected upon receipt at job or storage facility for any damage that may
have incurred during shipment.

Metron should be notified of any long term storage requirements, so the controllers can be shipped in plywood
crates (completely enclosed). It is recommended that the controller be returned to its crate after inspection,
resealed and stored in an environmentally controlled atmosphere (room temperature) free of moisture, splashing
liquids or dust.

It is also recommended when controllers are to be stored in excess of two (2) months that a moisture inhibitor
(desiccant) be installed in various points within the shipping crate and replaced periodically.

Prior to installation, another visual inspection should be made to insure that moisture or excessive dirt is not
present within the controller.

When installing conduit for wiring, extra care should be taken to insure that metal particles, cut wires, etc. do not
fall into any of the components.

Should a Metron serviceperson be required for repair due to inadequate storage or handling, the customer will
assume all expenses for PARTS, FOOD, LODGING along with STANDARD SERVICE DEPARTMENT
LABOR CHARGES for repair.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
METRON CONTROLLER SHIPPING WEIGHTS

Weight with
Weight Transfer Switch
Controller Model Pounds Kilograms Pounds Kilograms
FD4 193 88
FD4 with legs 220 100
MP600 1210 549
M15 Jockey Pump 42 19
M30 (limited service) 180 82 404 183
MP300
208VAC up to 75 HP 248 112 407 185
380VAC up to 125 HP 248 112 407 185
460VAC up to 125 HP 248 112 407 185
208VAC 100-150 HP 365 166 703 319
380VAC 150-300 HP 365 166 703 319
460VAC 200-400 HP 365 166 703 319
208VAC 200-250 HP 496 225 768 348
380VAC 350 HP 496 225 768 348
460VAC 500 HP 496 225 768 348
MP400
208VAC up to 75 HP 298 135 450 204
380VAC up to 125 HP 298 135 450 204
460VAC up to 125 HP 298 135 450 204
208VAC 100-150 HP 415 188 743 337
380VAC 150 HP 415 188 743 337
MP420
208VAC up to 75 HP 288 131 438 199
380VAC up to 125 HP 288 131 438 199
460VAC up to 125 HP 288 131 438 199
208VAC 100-150 HP 395 179 746 338
380VAC 150-300 HP 395 179 746 338
460VAC 200-400 HP 395 179 746 338
208VAC 200-250 HP 553 251 NA NA
380VAC 350 HP 553 251 NA NA
460VAC 500 HP 553 251 NA NA
MP430
208VAC up to 75 HP 302 137 468 212
380VAC up to 125 HP 302 137 468 212
460VAC up to 150 HP 302 137 468 212
208VAC 100-150 HP 409 186 575 261
380VAC 150-300 HP 409 186 575 261

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
METRON CONTROLLER SHIPPING WEIGHTS

Weight with
Weight Transfer Switch
Controller Model Pounds Kilograms Pounds Kilograms
460VAC 200-400 HP 409 186 575 261
208VAC 200-250 HP 573 260 930 422
380VAC 300-400 HP 573 260 930 422
460VAC 500 HP 573 260 930 422
MP435
208VAC up to 75 HP 342 155 509 231
380VAC up to 125 HP 342 155 509 231
460VAC up to 150 HP 342 155 509 231
208VAC 100 HP 449 204 557 253
380VAC 150 HP 449 204 557 253
460VAC 200 HP 449 204 557 253
208VAC 125-150 HP 573 260 658 298
380VAC 200-300 HP 573 260 658 298
460VAC 250-450 HP 573 260 658 298
208VAC 200-250 HP 641 291 882 400
380VAC 350-400 HP 641 291 882 400
460VAC 500 HP 641 291 882 400
MP450
208VAC up to 20 HP 352 160 518 235
380VAC up to 40 HP 352 160 518 235
460VAC up to 50 HP 352 160 518 235
208VAC 25-75 HP 385 175 567 257
380VAC 50-125 HP 385 175 567 257
460VAC 60-150 HP 385 175 567 257
208VAC 100 HP 452 205 623 283
380VAC 150-200 HP 452 205 623 283
460VAC 200-250 HP 452 205 623 283
208VAC 125-150 HP 750 340 984 446
380VAC 250-300 HP 750 340 984 446
460VAC 300-400 HP 750 340 984 446
MP700
208VAC 15-75 HP 365 166 527 239
380VAC 15-125 HP 365 166 527 239
460VAC 15-150 HP 365 166 527 239
208VAC 100-150 HP 624 283 796 361
380VAC 150-300 HP 624 283 796 361
460VAC 200-400 HP 624 283 796 361

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
DIESEL
ENGINE
CONTROLLERS
Contents:
SECTION CONTENTS:
FD4 Bulletin
FD4 Price Sheets
FD4 Bulletin
FD4 Drawings
Liquid Level Switch, AA10519E
FD4 Price Sheets
FD4 Drawings

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Fire Pump Controller
For Diesel Driven Fire Pumps

5GTKGU(&


The Metron Model FD4 controller is designed to specifically


meet the latest NFPA 20 and UL 218 standards for Diesel
Engine Fire Pump Controllers.
This controller implements the latest component and
microprocessor logic technology available. It incorporates
years of experience in the design and manufacture of fire
pump control systems.
The components are installed in a NEMA 2 dust and drip
proof enclosure with optional NEMA 3R, 4, 4X, or 12 ratings
available. The Operator Interface Device (OlD), manual start
pushbuttons, stop push button and Auto-Off-Manual selector
switch are located on the exterior door for easy access. The
battery disconnect switches are located on the main
mounting panel inside the enclosure.
The controller’s logic is based on discrete components using
the latest technology with high quality, highly reliable printed
circuit boards (PCBs) and PCB mounted relays. The
controller uses a microprocessor to control automatic engine
and alternation between batteries during cranking. It also
monitors and records system alarms and pressure, battery
voltage and engine functions. This controller is suitable for
all engine types with either ‘energized to run’ or ‘energize to
stop’ fuel solenoids.
Inside the controller are two independent fully automatic
microprocessor controlled battery chargers rated at 10 Amps
each. The battery chargers operate in such a manner as to
ensure that the engine batteries are fully charged within 24
hours. PCB mounted LED’s are provided for indication of
AC Power On, and Battery Power On.
The controller is supplied with wall mounting brackets as
standard. It may be supplied with optional 24” (609.6 mm)
legs for free standing floor or skid mounting.

FD4 Fire Pump Controller


0212
Standard and Optional Features

• The OlD includes 12 pushbuttons for easy screen navigation,


Standard Features system mode changes, alarm reset, horn silencing, and lamp
test.
Operator Interface Device (OID) with LED Annunciator and
Digital Display: • The built in annunciator includes multicolored LED’s for alarm
and mode indications. The annunciation LED’s have
removable labels that allow the user to easily make changes, if
additional alarms and/or language changes are needed.
• All controller settings are programmable through the OlD.
Programming changes are protected by two levels of
passwords to prevent unauthorized modification.
• All features are enabled or disabled through the OlD, so no
jumpers or external wires are needed, making control logic
field modification very easy.
• The OlD displays System Pressure, Start Pressure, Battery 1
Voltage, Battery 2 Voltage, Battery 1 Charger Amps, and
Battery 2 Charger Amps providing the operator instant system
status, Status of Automatic Stop Setting. LED indication of
Loss of DC Power. A detailed Battery Voltage and Charging
Current screen is also supplied. Current time and date,
Number of starts, Total engine run hours, Displayed
countdown timers for: Sequential engine start and engine stop,
and Time until AC Power fail start.
• The state of the art microprocessor based logic includes a real
time/date clock that can operate for a minimum of 14 days
without DC power connected to controller.
• An SD Memory card is used to record pressure log, event log,
and auxiliary user programs. The pressure log is stored in
separate comma delimited ASCII text files with each file
containing data for one day. The SD card is removable and
can be read by any PC equipped with an SD card reader.
• One RS485 data port is included as standard.
General Controller Description • MODBUS Communication Protocol via RS485 port
The Fire Pump Controller conforms to all requirements of the • If there is ever a need to change the internal components all
latest edition of NFPA 20, NFPA 70 and is Listed by wiring to the internal board is removable without the use of any
Underwriters Laboratories (UL) and Approved by Factory Mutual special tools or soldering.
(FM). Auxiliary alarms and contacts
The controller is available for either 12VDC or 24VDC operation. As standard the controller includes 6 discrete auxiliary inputs, 8
Included as standard, the controller is suitable for 120VAC or form ‘C’ auxiliary relay outputs. These auxiliary inputs and
208/240VAC input power at no additional cost. outputs are in addition to those mandated by NFPA 20. All
auxiliary inputs, outputs, and OlD LED’s are field programmable
Controller Standard Features
making it very easy to make changes to the controller in the field.
• The controller includes two 10 Amp battery chargers that are
Through the OlD the operator can select any 8 of the following
temperature compensated and includes integral LED’s for
auxiliary alarms which will be recorded in the event/alarm logs
indication of charge AC Failure, and Battery Power On.
and annunciated with an LED and/or output relay contact:
• Two outer door mounted manual crank pushbuttons and two
battery on/off switches located on the interior back panel. ENGINE QUIT FAULT HIGH ENGINE OIL TEMP
PRESSURE TRANSDUCER FAULT LOW JACKET WATER FLOW
• Outer door mounted AUTO, OFF, MANUAL selector switch PUMP ON DEMAND LOW JACKET WATER LEVEL
with mode condition illuminated on OID with colored LED's LOW DISCHARGE PRESSURE LOW HYDRAULIC PRESSURE
• Operator Interface Device (OlD) with 4 lines by 20 character HIGH DISCHARGE PRESSURE GAS DETECTION
display with large character backlit LCD capable of being read REMOTE START SIGNAL LOW FIREWATER PRESSURE
in both direct sunlight or dark lighting conditions. English or DELUGE VALVE START AIR DAMPER CLOSED
Spanish languages are standard and selectable through the HIGH FUEL LEVEL AIR DAMPER OPEN
OlD. Additional languages available upon request.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
FUEL SPILL LOW PURGE PRESSURE Controller Operation
FUEL TANK RUPTURE LOW GEAR OIL PRESSURE Automatic Mode:
LOW PUMP ROOM TEMP LOW COOLANT LEVEL Starting conditions such as pressure drop, and deluge valve start,
RESERVOIR LOW HIGH GEAR OIL TEMP will cause the user adjustable sequential start delay timer to begin
RESERVOIR EMPTY HIGH VIBRATION operation. After start delay is completed the engine will start and
RESERVOIR HIGH LOW FUEL PRESSURE the operation will be recorded in the event log. In addition to the
FLOW METER ON HIGH EXHAUST TEMP sequential start timer the Automatic Weekly Test Start, AC Power
RELIEF VALVE OPEN HIGH FUEL TEMP Fail Start are programmable by the user through the OlD. All
LOW SUCTION PRESSURE PUMP ON DEMAND system statistics are continuously monitored and changes are
logged into the internal logs. System statistics include, but are not
Data logging: limited to, battery charger volts/amps, battery voltage, and system
Pressure Log: The Pressure log provides a continuous pressure pressure are continuously monitored and changes are logged.
recording for one month of data. Each time the pressure log
records a pressure it includes the time and date of the reading and Stopping conditions: Auto engine stop delay, engine lockout, low
is stored on the SD memory card. suction shutdown, automatic stop during automatic weekly test for
low oil pressure and high water temperature are all OlD user
The data recorded in the pressure log can be searched by each programmable features.
sample, by minute, or by hour allowing for easy access to specific
data. Manual Mode:
If a control logic failure occurs, two crank pushbuttons are provided
Event Log: The event log is also stored on the SD memory card. It that will bypass all internal logic and allow manual operation of the
will hold a maximum of 3000 events. These events include any of engine.
the following events/alarms:
BATTERY 1 FAULT
BATTERY 2 FAULT
SYSTEM AUTO MODE
ENGINE LOCKOUT SIGNAL
Options
BATTERY 1 LOW VOLTAGE SYSTEM AUTO MODE Option H: Space Heater
BATTERY 2 LOW VOLTAGE SYSTEM MANUAL MODE If the ambient atmosphere is especially damp or humid, a space
CHARGER 1 FAULT SYSTEM OFF MODE heater rated at 100 watts may be supplied to reduce moisture in the
CHARGER 2 FAULT SYSTEM TEST RUN cabinet. A thermostat is supplied as standard with this option. A
AC POWER FAIL ALARM RESET humidistat may be substituted at no additional charge.
ENGINE OVERSPEED LOW PRESSURE CONDITION
ENGINE FAILED TO START LOW PRESSURE START Option N: Step-down Transformer
ENGINE QUIT DELUGE START When AC voltage exceeds 240 VAC single phase, an integral
ENGINE LOW OIL PRESSURE REMOTE START transformer may be provided for operation from 380 to 600 VAC
ENGINE HIGH WATER TEMP AC POWER FAIL START 50/60 Hz input. Exact voltage and frequency must be specified
PRESSURE DROP HORN SILENCED when ordering.
STOP PUSHBUTTON PRESSURE TRANSDUCER Option W: 24 Inch (609.6 mm) Legs
PRESSED FAULT Provided for free standing installations when wall mounting is not
SPEED SWITCH FAILURE CONTACTOR COIL FAILURE practical. If specified, lifting eyes may also be supplied.
Plus any of the 8 programmable auxiliary alarms listed above
Enclosure
Every event or alarm that is recorded includes the following data The following NEMA type enclosures are also available: 3R, 4, 4X
with the recorded event or alarm: (Painted Cold Rolled Steel), 4X (304 or 316 Stainless Steel), and
• Time and Date of Event or Alarm 12.
• System Pressure
• Descriptive Text Message of the Event/Alarm
• System Auto Mode Status
• Engine Running Status
• Charger 1 Status
• Charger 2 Status
• Battery 1 Status
• Battery 2 Status

0212
Fire Pump Controller
For Diesel Driven Fire Pumps

clock capable of running a minimum of 14 days Data logging:


Specifications without DC power connected to controller and
non-volatile flash memory to permanently store
The controller shall have separate data logs for
storing system event and pressure data that is
General Controller Description the continuous pressure log, event log, alarm readable through the OlD or printable on the
log and all user changeable set points and internal printer. The data logs shall be stored on
The Fire Pump Controller shall be factory system data. Battery backup of any kind not a removable SD memory card. The file format
assembled, wired and tested as a unit and shall allowed. shall be standard ASCII text. These logs shall be
conform to all requirements of the latest edition of • Input and output status LED’s to provide visual as follows:
NFPA 20, NFPA 70 and be Third Party Listed by indication of each discrete input’s or output’s Pressure Log: The controller shall have a
Underwriters Laboratories (UL) and Approved by on/off status Pressure log with continuous pressure recording
Factory Mutual (FM). The controller shall be • One RS485 Serial Port one month of data. Each day’s data shall be in a
available for either 12VDC or 24VDC systems. • MODBUS Communication Protocol via RS485 separate file. The pressure log samples shall be
port time and date stamped and stored in permanent
Controller Equipment Features • All wiring terminals on PCB’s shall be non-volatile flash memory. The pressure log shall
The controller shall include the following standard removable type be searchable by each sample, by minute, or by
features: Auxiliary alarms: hour.
• NEMA Type 2 drip proof metal wall mount As standard the controller shall include 6 discrete Event Log: The event log shall be capable of
enclosure auxiliary inputs, 8 form ‘C’ auxiliary relay outputs. storing no less than 3000 events. These events
• Dual Battery chargers, 10 amp microprocessor These auxiliary inputs and outputs are in addition shall include any of the following events/alarms:
temperature compensated with integral to those mandated by NFPA 20. All auxiliary BATTERY 1 FAULT SYSTEM AUTO MODE
volt/amp digital display and integral LEDs for inputs, outputs, and OlD LED’s shall be field ENGINE LOCKOUT
indication of AC Power On and Battery Power BATTERY 2 FAULT
programmable through the OlD. This permits a SIGNAL
On multitude of customizable controller configurations BATTERY 1 LOW
SYSTEM AUTO MODE
• Two outer door mounted crank pushbuttons VOLTAGE
to meet each installations unique needs without BATTERY 2 LOW SYSTEM MANUAL
and two inner panel mounted battery on/off adding cost to the controller. The use of jumpers, VOLTAGE MODE
switches soldering, or other external components is not CHARGER 1 FAULT SYSTEM OFF MODE
• Outer door mounted key operated AUTO, OFF, allowed. CHARGER 2 FAULT SYSTEM TEST RUN
MANUAL, mode selector switch AC POWER FAIL ALARM RESET
• Operator Interface Device (OID) with 4 lines by The user can select any 8 of the following
ENGINE OVERSPEED LOW PRESSURE
20 character display with large character auxiliary alarms that can be programmed and CONDITION
backlit LCD capable of being read in both recorded in the event/alarm logs and annunciated ENGINE FAILED TO LOW PRESSURE
direct sunlight or dark lighting conditions with an LED and output relay contact: START START
• 12 pushbuttons for easy screen navigation, HIGH ENGINE OIL ENGINE QUIT DELUGE START
ENGINE QUIT FAULT
TEMPERATURE ENGINE LOW OIL
alarm reset, and horn silencing PRESSURE
REMOTE START
PRESSURE
• Multicolored LED’s for alarm and mode LOW JACKET WATER ENGINE HIGH WATER AC POWER FAIL
TRANSDUCER
annunciation FLOW TEMP START
FAULT
• LEDs shall be labeled with removable labels to LOW JACKET WATER PRESSURE
allow for easy field modification if additional PUMP ON DEMAND TRANSDUCER HORN SILENCED
LEVEL
alarms and/or language changes LOW DISCHARGE LOW HYDRAULIC FAULT
• All controller settings shall be programmable PRESSURE PRESSURE STOP PUSHBUTTON
PRESSURE DROP
through the OlD and shall be protected by two HIGH DISCHARGE PRESSED
GAS DETECTION SPEED SWITCH CONTACTOR COIL
password levels PRESSURE
FAILURE FAILURE
• All features shall be enabled or disabled REMOTE START LOW FIREWATER
(PLUS ANY OF THE 8 PROGRAMMABLE
through the OlD, no jumpers or external wires SIGNAL PRESSURE
AUXILIARY ALARMS LISTED ABOVE)
shall be needed or allowed to activate or de- AIR DAMPER
DELUGE VALVE START
CLOSED
Each event or alarm recorded in the either event
activate a feature log or alarm logs shall have the following data
• The system status data shall be displayed on HIGH FUEL LEVEL AIR DAMPER OPEN
LOW PURGE recorded with the event/alarm:
the OlD. The displayed items shall include: FUEL SPILL
Speed Switch Failure, Contactor Coil Failure, PRESSURE • Time and Date of Event or Alarm
LOW GEAR OIL • System Pressure
System pressure, Battery 1 Voltage, Battery 2 FUEL TANK RUPTURE
PRESSURE
Voltage, Battery 1 Charger Amps, Battery 2 • Descriptive Text Message of the Event/Alarm
LOW PUMP ROOM LOW COOLANT
Charger Amps, Current time and date, Number • System Auto Mode Status
TEMPERATURE LEVEL
of starts, Total engine run hours, Displayed HIGH GEAR OIL • Engine Running Status
countdown timers for: RESERVOIR LOW • Charger 1 Status
TEMPERATURE
Sequential engine start and engine stop, and RESERVOIR EMPTY HIGH VIBRATION • Charger 2 Status
Time until AC Power fail start, Status of LOW FUEL • Battery 1 Status
RESERVOIR HIGH • Battery 2 Status
Automatic Stop Setting. LED indication of Loss PRESSURE
of DC Power. HIGH EXHAUST The internal logic of the controller shall be
FLOW METER ON
• Audible horn with horn silence feature for TEMPERATURE capable of operation in a temperature range of
silenceable alarms HIGH FUEL 4.4°C to 40°C and high, non-condensing,
RELIEF VALVE OPEN
• Lamp test feature TEMPERATURE humidity levels.
• English or Spanish languages selectable LOW SUCTION
PUMP ON DEMAND
through the OlD PRESSURE The controller shall be manufactured by Metron
• Microprocessor based logic with real time/date Inc.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
DIESEL ENGINE FIRE PUMP CONTROLLER
SELECTION CHART MODEL FD4

BASE PRICE includes built-in 12 or 24 Quantity


VDC, Negative Ground Battery chargers $6,289 Form C of
VOLTAGE (PLEASE SPECIFY) Dry Contacts
Description LED Contacts Required
[ ] 12 VDC NEGATIVE GROUND ENGINE QUIT FAULT [■] [■]
[ ] 24 VDC NEGATIVE GROUND PRESSURE TRANSDUCER FAULT [■] [■]
PUMP ON DEMAND [■] [■]
[ ] 60 HZ OPERATION (DEFAULT) LOW DISCHARGE PRESSURE [■] [■]
[ ] 50 HZ OPERATION HIGH DISCHARGE PRESSURE [■] [■]
(All items below require a N.O. or N.C. contact provided by the customer)
[ ] 120 VAC / 1 PHASE OPERATION ENGINE LOCKED OUT [■] [■]
[ ] 240 VAC / 1 PHASE OPERATION REMOTE START SIGNAL [■] [■]
[ ] ALL OTHER VOLTAGES (OPTION N DELUGE VALVE START [■] [■]
REQUIRED) (A maximum of six of the following can be chosen below)
HIGH FUEL LEVEL [■] [■]
DIESEL ENGINE TYPE FUEL SPILL [■] [■]
FUEL TANK RUPTURE [■] [■]
[ ] UL/FM LISTED ENGINE LOW FUEL PRESSURE [■] [■]
[ ] NON-UL/NON-FM LISTED ENGINE HIGH FUEL TEMPERATURE [■] [■]
Specify __________________________ RESERVOIR LOW [■] [■]
RESERVOIR HIGH [■] [■]
STANDARD FEATURE SELECTION RESERVOIR EMPTY [■] [■]
Price of controller includes the following local visual LOW PUMP ROOM TEMPERATURE [■] [■]
LED indications: System Fault, Battery #1 Healthy, FLOW METER ON [■] [■]
Battery #2 Healthy, Charger #1 Failure, Charger #2 RELIEF VALVE OPEN [■] [■]
Failure, AC Power Loss, Engine Running, Engine LOW SUCTION PRESSURE [■] [■]
Failed to Start, Engine Low Oil Pressure, Engine High HIGH ENGINE OIL TEMPERATURE [■] [■]
Water Temp., Engine Overspeed, Low Fuel, Speed LOW JACKET WATER FLOW [■] [■]
Switch Failure, Contactor Coil Failure, Loss of DC LOW JACKET WATER LEVEL [■] [■]
LOW HYDRAULIC PRESSURE [■] [■]
Power, Switch in Auto, Switch in Manual, and Test
LOW FIREWATER PRESSURE [■] [■]
Operation
AIR DAMPER CLOSED [■] [■]
Standard Default Volt Free (Dry) Contacts include: AIR DAMPER OPEN [■] [■]
Controller not in Auto, System Fault, Engine Running LOW PURGE PRESSURE [■] [■]
(two (2) sets), and Battery Fault LOW GEAR OIL PRESSURE [■] [■]
In addition to the above LED indications a maximum of LOW COOLANT LEVEL [■] [■]
ten (10) user specified alarm conditions can be HIGH GEAR OIL TEMPERATURE [■] [■]
displayed. A maximum of six (6) additional volt free HIGH VIBRATION [■] [■]
(dry) contacts can be added. In the next column is a HIGH EXHAUST TEMPERATURE [■] [■]
list of suggested alarm conditions. Consult factory for Maximum number of additional LEDs is 10
alarm conditions not listed.
Maximum Number of contacts, including default
contacts, can not exceed 9. Each Alarm Condition
can have a maximum 3 contacts.

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
DIESEL ENGINE FIRE PUMP CONTROLLER
SELECTION CHART MODEL FD4

OPTIONS [ ] MODBUS COMMUNICATION via RS485 Standard

[ ] H SPACE HEATER (100 WATT) PLUMBING


[ ] THERMOSTAT $250
[ ] HUMIDISTAT $250 [ ] 300PSI FRESH WATER PLUMBING Standard
[ ] J INTEGRAL BATTERY [ ] 600PSI FRESH WATER PLUMBING $350
CHARGERS
(Included in base price) [ ] 300 PSI SALTWATER / FOAM $550
[ ] JJ INTEGRAL BATTERY [ ] 600 PSI SALTWATER / FOAM $750
CHARGERS CONSULT FACTORY
This option required for engines with
high capacity starting batteries that ENCLOSURE
exceed 220 Ampere Hours
[ ] NEMA 2 Standard
[ ] N STEP DOWN TRANSFORMER
All voltages above 240 VAC [ ] NEMA 3R $ 350
Specify Voltage_____________ $492 [ ] NEMA 4 (PAINTED STEEL) $ 600
[ ] W 24” (609.6mm) LEGS FOR FREE [ ] NEMA 4X (PAINTED STEEL) $ 600
STANDING (FLOOR)
INSTALLATION $220 [ ] NEMA 4X (UNPAINTED 304
STAINLESS STEEL) $3447
[ ] W 24” (609.6mm) STAINLESS STEEL
LEGS FOR FREE STANDING [ ] NEMA 4X 304 PAINTED STAINLESS
(FLOOR) INSTALLATION $880 STEEL
CONSULT FACTORY
[ ] REMOVABLE GLAND PLATE $250
[ ] NEMA 4X (UNPAINTED 316
[ ] FUEL LEVEL SWITCH WITH ONE
STAINLESS STEEL) $3500
ALARM POINT † $290
[ ] NEMA 4X 316 PAINTED STAINLESS
[ ] FUEL LEVEL SWITCH WITH TWO
STEEL
ALARM POINTS † $1248
CONSULT FACTORY
[ ] PUMP ROOM TEMPERATURE
THERMOSTAT MOUNTED ON [ ] NEMA 12 (SPECIFY) N/C
EXTERIOR OF ENCLOSURE [ ] LIFTING EYES N/C
[ ] NEMA 2 RATED $42
[ ] NEMA 4 RATED $160
† Device shipped loose for Customer Installation
[ ] LOW SUCTION CUT OFF PRESSURE
SWITCH (externally mounted) $500
[ ] EXPORT CRATING (Suitable for below
deck or airfreight) $600
[ ] PURGE SYSTEM, Type Z System, per
NFPA 496 suitable for Class I, Division 2,
Group C/D CONSULT FACTORY

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
ELECTRIC
FIRE PUMP
CONTROLLERS
SECTION CONTENTS:
Electric Controller Option Details
Across the Line Start, Type MP300 Bulletin
Model MP300 Price Sheets
MP300 Drawings
High Voltage Across the Line Start, Type MP600 Bulletin
Model MP600 Price Sheets
MP600 Drawings
Primary Resistance Reduced Voltage Start, Type MP400 Bulletin
Model MP400 Price Sheets
Model MP400 Drawings
Part Winding Reduced Voltage, Type MP420 Bulletin
Model MP420 Price Sheets
Model MP420 Drawings
Wye-Delta Reduced Current, Type MP430 / MP435 Bulletin
Model MP430 Price Sheets
Model MP435 Price Sheets
Model MP430 Drawings
Model MP435 Drawings
Autotransformer Closed-Transition Reduced Voltage, Type MP450 Bulletin
Model MP450 Price Sheets
Model MP450 Drawings
Solid State Reduced Voltage, Type MP700 Bulletin
Model MP700 Price Sheets
Model MP700 Drawings
Solid State Reduced Voltage, Type MP800 Bulletin
Model MP800 Price Sheets

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
TYPE ‘MP’ FULL SERVICE CONTROLLERS

(See Individual Bulletins For Various Motor Starting Methods)

The following features are standard on all Type ‘MP’ Full Service Electric Controllers:

NEMA Type 2 Drip-proof Enclosure


Microprocessor Control Logic
Data Logging
Operator Interface Device (OID)
Pressure Transducer
Automatic Weekly Test Solenoid
Starting Contactor(s)
Manual Start and Stop Pushbuttons
Minimum Running Period Timer
Remote Start Circuit
Deluge Start Circuit
Weekly Test Solenoid Drain Valve
Dry set of form “C” N.O. and N.C. contacts and visual indication of PUMP RUNNING, PHASE REVERSAL, PRIMARY
POWER AVAILABLE, and CONTROLLER NOT IN AUTO
Voltage Surge Arrester
Service Entrance Rated

OPTION H: SPACE HEATER


With Thermostat $320
With Humidistat $320

If the ambient atmosphere is especially damp, a space heater rated at 100 watts may be supplied
to reduce moisture in the cabinet. A thermostat is supplied as standard with this option. A
humidistat may be substituted if specified.

OPTION W: OMIT LEGS (specify) N/C

For systems where the controller is mounted on a common skid with the pump and engine, the legs of the
controller may be omitted, and 3” mounting channels or wall mounting brackets can be supplied. If
specified lifting eyes may also be supplied.

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Fire Pump Controller
For Electric Motor Driven Fire Pumps

#ETQUU6JG.KPG6[RG


5GTKGU/2Ä%QODKPGF
/CPWCNCPF#WVQOCVKE
Metron Fire Pump Controllers conform to the latest
requirements of Chapter 10, National Fire
Protection Association Pamphlet 20, Standard for
Centrifugal Fire Pumps as adopted by
Underwriters Laboratories and Factory Mutual.
They are withstand rated and listed by
Underwriters’ Laboratories and approved by
Factory Mutual Research Corporation.

Sizes range from 15 to 600 horsepower, 200 to


600 volts, 60 Hz. These controllers are for use on
Across-the-Line type installations.

Only the highest quality components, all UL listed


or UL recognized, are used throughout to assure
the best possible reliability. The cabinet is
fabricated of heavy gauge reinforced steel with
drip-proof hood. All field wiring and service
connections may be made from the front, allowing
the controller to be mounted flush against a wall.

The controller is completely wired, assembled, and


tested at the factory before shipment, and ready
for immediate installation.


MP300 Fire Pump Controller


0212
Standard and Optional Features

x Auxiliary alarm functions displayed on the OID LCD


Standard Features screen
Operator Interface Device (OID) with LED x Audible horn with silence feature for silencable
Annunciator and Digital Display alarms
x Lamp test feature
x Foreign languages selectable through the OID
x Microprocessor based logic with real time/date
clock capable of running a minimum of 14 days
without AC power connected to controller
x SD Memory card used to record pressure log, event
and log, and auxiliary user programs. Pressure log
is stored in separate comma delimited ASCII text
files with each file containing data for one day. The
SD card is removable and can be read by any PC
equipped with an SD card reader.
x Input and output status LED's provide visual
indication of each discrete input's or output's on/off
status
x One RS485 Serial Port
x MODBUS Communication Protocol via RS485 port
x Service Entrance Rated
x NEMA Type 2 drip proof metal freestanding Standard Auxiliary alarms:
enclosure The controller includes as standard six (6) discrete
x Operator Interface Device (OID) with 4 lines by 20 auxiliary inputs, nine (9) form 'C' auxiliary relay
character display with large character backlit Liquid outputs. These auxiliary inputs and outputs are in
Crystal Display (LCD) capable of being read in both addition to those mandated by NFPA 20. All auxiliary
direct sunlight or dark lighting conditions inputs, outputs, and OID Display can be field
x 10 pushbuttons for easy screen navigation, LED programmed through the OID.
lamp test, alarm reset, controller test and horn Nine (9) of the following auxiliary alarms can be
silencing programmed and recorded in the event/alarm logs
x Removable labels to allow for easy field language and annunciated on the OID display screen and/or
changes output relay contact(s). These alarm conditions
x All controller settings are programmable through the include:
OID. All features are enabled or disabled through LOW PUMP ROOM TEMP
the OID, no jumpers or external wires are needed RESERVOIR LOW
allowing easy field modification RESERVOIR EMPTY
x The system status data is displayed on the OID. RESERVOIR HIGH
The displayed items include: System pressure, FLOW METER ON
Phase to Phase (AB, BC, AC) voltage, Phase RELIEF VALVE OPEN
current (A, B, C), Current time and date, System LOW SUCTION PRESSURE
Events and Notifications such as Remote Start, HIGH PUMP ROOM TEMPERATURE
Local Start etc., Number of starts, Total motor run LOW FIREWATER PRESSURE
hours, Time remaining on sequential motor start LOW PURGE PRESSURE
and motor stop timers, Status of automatic stop LOW GEAR OIL PRESSURE
setting. HIGH GEAR OIL TEMPERATURE

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
GAS DETECTION
HIGH VIBRATION Options
EMERGENCY POWER ON
PUMP ROOM DOOR OPEN Option H: Space Heater
If the ambient atmosphere is especially damp, a
Data logging: space heater rated at 100 watts may be supplied to
The controller includes two (2) separate data logs for reduce moisture in the cabinet. A thermostat is
storing system data that is readable through the OID supplied as standard with this option. A humidistat
or copied to a computer equipped with an SD card may be substituted if specified.
reader. The 2 data logs are as follows:
Option W: Omit Legs
Pressure Log: The pressure log provides a For systems where the controller is mounted on a
continuous pressure record for 30 days. The common skid with the pump and motor, the legs of
pressure log samples shall be time and date stamped the controller may be omitted, 3” (76.2mm) channels
and stored in permanent non-volatile SD memory or wall mounting brackets can be supplied. If
card. The pressure log can be searched by each specified, lifting eyes may also be supplied.
sample, by minute, or by hour through the OID.
Enclosure
Event Log: The event log will store up to 300 of the The following NEMA type enclosures are also
most current events. These events can include, but is available: 3R, 4, 4X (Painted Cold Rolled Steel), 4X
not limited to, any of the following events/alarms: (304 or 316 Stainless Steel), and 12
PUMP RUNNING
POWER AVAILABLE
PHASE REVERSAL
MOTOR OVERLOAD
REMOTE START
LOCAL START
PUMP ON DEMAND
SYSTEM FAULT
PRESSURE TRANSDUCER FAULT
PUMP FAILED TO START
LOW INTAKE SHUTDOWN ALARM
SUPERVISORY POWER FAILURE
LOW PRESSURE
AUTO WEEKLY TEST START
UNDER FREQUENCY
OVER FREQUENCY
LOW ZONE / HIGH ZONE
CONTACTS
HIGH DISCHARGE PRESSURE
NO LOAD CONDITION

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Fire Pump Controller
For Electric Motor Driven Fire Pumps
Model MP300 Across-the-line Start Microprocessor Electric Motor Fire Pump Controller
event log, alarm log and all user changeable shall be searchable by each sample, by minute, or
Specifications set points and system data. Battery backup of
any kind not allowed.
by hour. Each day’s entries shall be stored in a
separate file on the SD card. SD memory shall be
Input and output status LED's to provide visual readable by any PC equipped with an SD
General Controller Description indication of each discrete input's or output's memory card reader.
The Fire Pump Controller shall be factory on/off status
Event Log: The event log shall be capable of
assembled, wired and tested as a unit and shall One RS485 Serial Port
storing no less than 3000 events. These events
conform to all requirements of the latest edition MODBUS Communication Protocol via shall include, but is not limited to, any of the
of NFPA 20, NFPA 70 and be Third Party Listed RS485 port following events/alarms:
by Underwriters Laboratories (UL) and All wiring terminals on PCB's shall be PUMP RUNNING
Approved by Factory Mutual (FM). The removable type POWER AVAILABLE
controller shall be available for 208, 230, 380- Service Entrance Rated PHASE REVERSAL
415, or 480 volt three phase power. MOTOR OVERLOAD
Auxiliary alarms
Controller Equipment Features REMOTE START
As standard the controller shall include 6 discrete LOCAL START
The controller shall include the following auxiliary inputs, 9 form 'C' auxiliary relay PUMP ON DEMAND
standard features: outputs. These auxiliary inputs and outputs are SYSTEM FAULT
NEMA Type 2 drip proof metal freestanding in addition to those mandated by NFPA 20. All PRESSURE TRANSDUCER FAULT
enclosure auxiliary inputs, outputs, and OID screens shall PUMP FAILED TO START
Operator Interface Device (OID) with 4 lines be field programmable through the OID. This LOW INTAKE SHUTDOWN ALARM
by 20 character display with large character permits a multitude of customizable controller SUPERVISORY POWER FAILURE
backlit LCD capable of being read in both configurations to meet each installations unique LOW PRESSURE
direct sunlight or dark lighting conditions needs without adding cost to the controller. The AUTO WEEKLY TEST START
10 pushbuttons for easy screen navigation, use of jumpers, soldering, or other external UNDER FREQUENCY
system test, lamp test, alarm reset, and horn components are not allowed. OVER FREQUENCY
silencing LOW ZONE / HIGH ZONE CONTACTS
The user can select any 9 of the following
Multicolored LED's for alarm and mode HIGH DISCHARGE PRESSURE
auxiliary alarms that can be programmed and
annunciation NO LOAD CONDITION
recorded in the event log and annunciated with
LEDs shall be labeled with removable labels an OID screen and output relay contact for Each event or alarm recorded in the event log
to allow for easy field modification of conditions such as but not limited to: shall have the following data recorded with the
language changes LOW PUMP ROOM TEMP event/alarm:
All controller settings shall be programmable RESERVOIR LOW Time and Date of Event or Alarm
through the OID and shall be protected by two RESERVOIR EMPTY System Pressure
password levels RESERVOIR HIGH Descriptive Text Message of the Event/Alarm
All features shall be enabled or disabled FLOW METER ON Motor Running Status
through the OID, no jumpers or external wires RELIEF VALVE OPEN Phase to Phase Volts
shall be needed or allowed to activate or de- LOW SUCTION PRESSURE
Phase Amps
activate a feature HIGH PUMP ROOM TEMPERATURE
The system status data shall be displayed on LOW FIREWATER PRESSURE The internal logic of the controller shall be
the OID. The displayed items shall include: LOW PURGE PRESSURE capable of operation in a temperature range of
System pressure, Phase to Phase (AB, BC, LOW GEAR OIL PRESSURE 4.4ºC to 40ºC and high, non-condensing,
AC) voltage, Phase current (A, B, C), System HIGH GEAR OIL TEMPERATURE humidity levels.
Events and Notifications, Current time and GAS DETECTION
date, Number of starts, Total motor run hours, HIGH VIBRATION The controller shall be manufactured by Metron.
Displayed countdown timers for: Sequential EMERGENCY POWER ON
motor start and motor stop, Status of PUMP ROOM DOOR OPEN
Automatic Stop Setting.
Data logging
Audible horn with silence feature for
silencable alarms The controller shall have separate data logs for
Lamp test feature storing system data that is readable through the
Foreign languages selectable through the OID OID.
Microprocessor based logic with real time/date
Pressure Log: The controller shall have a
clock capable of running a minimum of 14
Pressure log with continuous pressure recording
days without AC power connected to
of 30 days of data. The pressure log samples
controller and non-volatile flash memory to
shall be time and date stamped and stored on a
permanently store the continuous pressure log,
removable SD card memory. The pressure log

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP300 ACROSS THE LINE
FULL SERVICE FIRE PUMP CONTROLLER
Model Options Hp Volts Withstand
MP300

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 6260 6260 6260 6260 6260 ‡
20 6260 6260 6260 6260 6260 ‡
25 6260 6260 6260 6260 6260 ‡
30 6260 6260 6260 6260 6260 ‡
40 7300 7300 6260 6260 6260 ‡
50 7300 7300 6260 6260 6260 ‡
60 8360 8360 7300 7300 7300 ‡
75 8360 8360 7300 7300 7300 ‡
100 10100 10100 8360 7300 7300 ‡
125 13020 13020 8360 8360 8360 ‡
150 13020 13020 8360 8360 8360 ‡
200 13020 * ‡ 13020 13020 10100 8360 ‡
250 16360 * ‡ 16360 * ‡ 13020 13020 13020 ‡
300 20020 * ‡ 13020 13020 13020 ‡
350 15880 * ‡ 15880 15880 ‡
400 15880 15880 ‡
500 19300 * ‡
600 21360 * ‡
700

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL
575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL
200-480VAC STD
‡ Available with “B” Breaker only [C] 100,000 AMPS RMS SYMMETRICAL
* Oversized Enclosure 200-480VAC STD

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP300 ACROSS THE LINE
FULL SERVICE FIRE PUMP CONTROLLER

STANDARD FEATURE SELECTION [ ] PUMP ROOM TEMPERATURE


Price of controller includes the following local visual THERMOSTAT MOUNTED ON
LED indications: Power On, Phase Reversal, EXTERIOR OF ENCLOSURE
System Fault, and Test Operation. [ ] NEMA 2 RATED $42
Standard Default Volt Free (Dry) Contacts include: [ ] NEMA 4 RATED $160
Power Available, Phase Reversal, Pump Running, [ ] LOW SUCTION CUT OFF PRESSURE
and Controller not in Auto. SWITCH (externally mounted) $500
In addition to the above LED indications a [ ] MODBUS COMMUNICATION via RS485
maximum of twelve (12) user specified alarm STANDARD
conditions can be displayed on the Liquid Crystal
ENCLOSURES
Display (LCD) display of the Operator Interface
[ ] NEMA 2 STANDARD
Display (OID). A maximum of nine (9) additional
[ ] NEMA 3R $375
volt free (dry) contacts can be added. Below is a
[ ] NEMA 3R (Oversized Enclosure, denoted
list of possible alarm conditions. Consult factory for
by asterisk (*) on page 1) $640
alarm conditions not listed.
Quantity
[ ] NEMA 4 $1200
Alarm Dry of [ ] NEMA 4 (Oversized Enclosure, denoted
Displayed Cont Contacts by asterisk (*) on page 1) $2200
Description on OID acts Required
LOW PUMP ROOM TEMP [Ŷ] [Ŷ] [ ] NEMA 4X PAINTED STEEL $1600
RESERVOIR LOW [Ŷ] [Ŷ] [ ] NEMA 4X PAINTED STEEL (Oversized
RESERVOIR EMPTY [Ŷ] [Ŷ] Enclosure, denoted by asterisk (*) on
RESERVOIR HIGH [Ŷ] [Ŷ] page 1) $2600
FLOW METER ON [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 304
RELIEF VALVE OPEN [Ŷ] [Ŷ] STAINLESS STEEL) $2500
GAS DETECTION [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 304
LOW SUCTION PRESSURE [Ŷ] [Ŷ] STAINLESS STEEL) (Oversized
LOW FIREWATER PRESSURE [Ŷ] [Ŷ] Enclosure, denoted by asterisk (*) on
LOW PURGE PRESSURE [Ŷ] [Ŷ] page 1) $3750
HIGH GEAR OIL TEMP [Ŷ] [Ŷ] [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
LOW GEAR OIL PRESSURE [Ŷ] [Ŷ] CONSULT FACTORY
HIGH VIBRATION [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316
EMERGENCY POWER ON [Ŷ] [Ŷ] STAINLESS STEEL) $4500
PUMP ROOM DOOR OPEN [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316
Maximum number of additional Alarms is 12 STAINLESS STEEL) (Oversized
Maximum Number of contacts, including Enclosure, denoted by asterisk (*) on
default contacts, can not exceed 9. Each page 1) $6875
Alarm Condition can have a maximum 3
contacts. [ ] NEMA 4X (316 PAINTED STAINLESS STEEL)

OPTIONS CONSULT FACTORY


[ ]H SPACE HEATER [ ] NEMA 12 $25
[ ] WITH THERMOSTAT $320 [ ] REMOVABLE GLAND PLATE $250
[ ] WITH HUMIDISTAT $320 [ ] PURGE SYSTEM, Type Z System, per
[ ]W OMIT LEGS, WITH 3" (76.2 mm) NFPA 496 suitable for Class I, Division 2,
CHANNELS N/C Group C/D CONSULT FACTORY
[ ] EXPORT CRATING – SUITABLE FOR
BELOW DECK STORAGE $997 PLUMBING
[ ] 300 PSI FOR FRESH WATER STANDARD
[ ] 600 PSI FOR FRESH WATER $120
[ ] 300 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $670
[ ] 600 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $790

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Fire Pump Controller
For Electric Motor Driven Fire Pumps

*KIJ8QNVCIG%QPVTQNNGTU



5GTKGU/2Ä%QODKPGF
/CPWCNCPF#WVQOCVKE

The Metron Series MP600 High Voltage Fire Pump Controllers
are a modular concept system, which utilize “state-of-the-art”
vacuum bottle technology. The primary control element in the
MP600 is a fixed mount style vacuum bottle contactor with
isolating disconnect switch. Integral to the disconnect switch are
“R” rated current limiting cartridge style fuses. Space is provided
for storage of three spare fuses on the rear of the outer door.
Two fused potential/control transformers (PTs) are also
contained within the cabinet. These transformers provide both
input signals to the monitor circuits as well as control power for
the MP600. For testing purposes, it is possible to supply
120VAC power directly to the control section through a built-in
test receptacle and test switch.
The MP600 has both front and rear access. Front access is for
easy access to the control circuits. Rear access is provided for
termination of the incoming power and termination of the motor
connections. Incoming power and motor connections enter
through the bottom of the controller enclosure.
Locked rotor motor protection is provided by the microprocessor
control unit per the requirements of NFPA 20, Chapter 10.
The microprocessor control unit also provides contacts for
remote alarm of phase reversal, low voltage, single phase, loss
of voltage, motor tripped, and motor overload. The Operator
Interface Device (OID) has LED lamps for Power On, Power
Failure, System Failure, Motor Overload, and Motor Tripped. The
OID also displays three phase voltage and current along with
system water pressure.
The standard MP600 is supplied in a NEMA type 2 enclosure
which is fabricated from 12 gauge steel. Minimum floor
clearance of 12 inches (304.8 mm) is provided with allowances
for floor anchoring. The MP600 is protected with two hinged
removable, gasketed doors, equipped with a 3-point latch, one
door for the control section and one door for the high voltage
section. Access to the vacuum contactor is provided by a
lockable and interlocked second door, which requires the
contactor to be disengaged from the bus prior to opening the
door. Control wiring and components are accessible behind their
own access door. Access to control components does not
require motor de-energization.
A solid copper ground bus is provided through the incoming high
voltage and motor termination compartments.

MP600 Fire Pump Controller


0212 v12
Standard and Optional Features

x The system status data is displayed on the OID. The


Standard Features displayed items include: System pressure, Phase to
Operator Interface Device (OID) with LED Phase (AB, BC, AC) voltage, Phase current (A, B,
Annunciator and Digital Display C), Current time and date, System Events and
Notifications such as Remote Start, Local Start etc.,
Number of starts, Total motor run hours, Time
remaining on sequential motor start and motor stop
timers.
x Auxiliary alarm functions displayed on the OID LCD
screen
x Audible horn with silence feature for silencable
alarms
x Lamp test feature
x Foreign languages selectable through the OID
x Microprocessor based logic with real time/date clock
capable of running a minimum of 14 days without AC
power connected to controller
x SD Memory card used to record pressure log, event
and log, and auxiliary user programs. Pressure log
is stored in separate comma delimited ASCII text
files with each file containing data for one day. The
SD card is removable and can be read by any PC
x NEMA Type 2 drip proof metal freestanding equipped with an SD card reader.
enclosure x Input and output status LED's provide visual
x Vacuum Bottle Contactor indication of each discrete input's or output's on/off
x “R” Rated Current Limiting Fuses status
x Emergency Mechanical Start Mechanism x RS485 Communications Port
x Rated Voltage 2300-6600 x MODBUS Communication Protocol via RS485 port
x Rated Current 400A Standard Auxiliary alarms:
x Built-in Spare Fuse Storage The controller includes as standard six (6) discrete
x UL Listed to 7.2Kv auxiliary inputs, seven (7) form 'C' auxiliary relay
x Operator Interface Device (OID) with 4 lines by 20 outputs. These auxiliary inputs and outputs are in
character display with large character backlit Liquid addition to those mandated by NFPA 20. All auxiliary
Crystal Display (LCD) capable of being read in both inputs, outputs, and OID Display can be field
direct sunlight or dark lighting conditions programmed through the OID.
x 10 pushbuttons for easy screen navigation, LED
Seven (7) of the following auxiliary alarms can be
lamp test, alarm reset, controller test and horn
programmed and recorded in the event/alarm logs and
silencing
annunciated on the OID display screen and/or output
x Removable labels to allow for easy field language
relay contact(s). These alarm conditions include:
changes
LOW PUMP ROOM TEMP
x All controller settings are programmable through the RESERVOIR LOW
OID. All features are enabled or disabled through RESERVOIR EMPTY
the OID, no jumpers or external wires are needed RESERVOIR HIGH
allowing easy field modification FLOW METER ON
RELIEF VALVE OPEN

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
LOW SUCTION PRESSURE
HIGH PUMP ROOM TEMP. Options
LOW FIREWATER PRESSURE
LOW PURGE PRESSURE Option H: Space Heater
LOW GEAR OIL PRESSURE If the ambient atmosphere is especially damp, a space
HIGH GEAR OIL TEMP. heater rated at 100 watts may be supplied to reduce
GAS DETECTION moisture in the cabinet. A thermostat is supplied as
HIGH VIBRATION standard with this option. A humidistat may be
PUMP ROOM DOOR OPEN substituted if specified.
LOW INTAKE Option T: Weekly Test Start Solenoid
In some cases it may be desirable to have the electric
Data logging:
motor run at a preset time each week for approximately
The controller includes two (2) separate data logs for
30 minutes. The controller includes a built in weekly
storing system data that is readable through the OID or
test function. This option complements the standard
copied to a computer equipped with an SD card reader.
function by simulating a loss of pressure. Simulation of
The 2 data logs are as follows:
pressure loss is accomplished by opening a solenoid
Pressure Log: The pressure log provides a continuous valve, which reduces the system pressure below the
pressure record for 30 days. The pressure log samples starting pressure of the controller.
shall be time and date stamped and stored in
permanent non-volatile SD memory card. The Option W: Omit Legs
pressure log can be searched by each sample, by For systems where the controller is mounted on a
minute, or by hour through the OID. common skid with the pump and motor, the legs of the
controller may be omitted, 3” (76.2mm) channels may
Event Log: The event log will store up to 3000 of the be substituted in lieu of standard legs. If specified,
most current events. These events can include, but is lifting eyes may also be supplied.
not limited to, any of the following events/alarms:
PUMP RUNNING Enclosure
POWER AVAILABLE The following NEMA type enclosures are also
PHASE REVERSAL available: 3R, 4, 4X (Painted Cold Rolled Steel), 4X
MOTOR OVERLOAD (304 or 316 Stainless Steel), and 12
MOTOR TRIPPED
REMOTE START
LOCAL START
PUMP ON DEMAND
SYSTEM FAULT
AUTO MODE
PRESSURE TRANSDUCER FAULT
PUMP FAILED TO START
LOW INTAKE SHUTDOWN ALARM
SUPERVISORY POWER FAILURE
LOW PRESSURE
AUTO WEEKLY TEST START
UNDER FREQUENCY
OVER FREQUENCY
LOW ZONE / HIGH ZONE CONTACTS
HIGH DISCHARGE PRESSURE
NO LOAD CONDITION

0212 v12
Fire Pump Controller
For Electric Motor Driven Fire Pumps
Model MP600 Across-the-line Start Microprocessor Electric Motor Fire Pump Controller
Lamp test feature Data logging
Specifications Foreign languages selectable through the OID
Microprocessor based logic with real
The controller shall have separate data logs for
storing system data that is readable through the
General Controller Description time/date clock capable of running a OID.
The fire pump controller shall be listed by minimum of 14 days without AC power
Underwriters Laboratories and approved by Pressure Log: The controller shall have a
connected to controller and non-volatile flash Pressure log with continuous pressure recording
Factory Mutual for fire pump service. The fire memory to permanently store the continuous
pump shall be completely factory wired, of 30 days of data. The pressure log samples
pressure log, event log, alarm log and all user shall be time and date stamped and stored on a
assembled, and tested prior to shipment. changeable set points and system data. removable SD card memory. The pressure log
The motor contactor shall be rated at least 400 Battery backup of any kind not allowed shall be searchable by each sample, by minute,
amps, 7200 VAC, be of the vacuum type, and Input and output status LED's to provide or by hour. Each days entries shall be stored in
shall be suitable for use on a circuit capable of visual indication of each discrete input's or a separate file on the SD card. SD memory shall
delivering not more than 50KA at 7200 VAC output's on/off status be readable by any PC equipped with an SD
short circuit current. The contactor shall be RS485 Communications Port memory card reader.
interlocked with the controller door to prohibit MODBUS Communication Protocol via
the door from being opened while the contactor RS485 port Event Log: The event log shall be capable of
is racked in. The main disconnect switch shall All wiring terminals on PCB's shall be storing no less than 3000 events. These events
contain integral fuse clips capable of holding removable type shall include, but is not limited to, any of the
“R” rated motor protection type fuses. Suitable following events/alarms:
Auxiliary alarms PUMP RUNNING
high voltage fuses shall be supplied and sized to
As standard the controller shall include 6 POWER AVAILABLE
hold motor locked rotor current as per NFPA 20.
discrete auxiliary inputs, 7 form 'C' auxiliary PHASE REVERSAL
Internal space shall be provided for spare fuse
relay outputs. These auxiliary inputs and MOTOR OVERLOAD
storage.
outputs are in addition to those mandated by MOTOR TRIPPED
Controller Equipment Features NFPA 20. All auxiliary inputs, outputs, and REMOTE START
The controller shall include the following OID screens shall be field programmable LOCAL START
standard features: through the OID. This permits a multitude of PUMP ON DEMAND
NEMA Type 2 drip proof metal freestanding customizable controller configurations to meet SYSTEM FAULT
enclosure each installations unique needs without adding AUTO MODE
Operator Interface Device (OID) with 4 lines cost to the controller. The use of jumpers, PRESSURE TRANSDUCER FAULT
by 20 character display with large character soldering, or other external components are not PUMP FAILED TO START
backlit LCD capable of being read in both allowed. LOW INTAKE SHUTDOWN ALARM
direct sunlight or dark lighting conditions The user can select any 7 of the following SUPERVISORY POWER FAILURE
10 pushbuttons for easy screen navigation, auxiliary alarms that can be programmed and LOW PRESSURE
system test, lamp test, alarm reset, and horn recorded in the event log and annunciated with AUTO WEEKLY TEST START
silencing an OID screen and output relay contact for UNDER FREQUENCY
LED's for alarm and status annunciation conditions such as, but not limited to: OVER FREQUENCY
LEDs shall be labeled with removable labels LOW PUMP ROOM TEMP LOW ZONE / HIGH ZONE CONTACTS
to allow for easy field modification of RESERVOIR LOW HIGH DISCHARGE PRESSURE
language changes RESERVOIR EMPTY NO LOAD CONDITION
All controller settings shall be programmable RESERVOIR HIGH Each event or alarm recorded in the event log
through the OID and shall be protected by FLOW METER ON shall have the following data recorded with the
two password levels RELIEF VALVE OPEN event/alarm:
All features shall be enabled or disabled LOW SUCTION PRESSURE Time and Date of Event or Alarm
through the OID, no jumpers or external wires HIGH PUMP ROOM TEMPERATURE System Pressure
shall be needed or allowed to activate or de- LOW FIREWATER PRESSURE Descriptive Text Message of the Event/Alarm
activate a feature LOW PURGE PRESSURE Motor Running Status
The system status data shall be displayed on LOW GEAR OIL PRESSURE
Phase to Phase Volts
the OID. The displayed items shall include: HIGH GEAR OIL TEMPERATURE
Phase Amps
System pressure, Phase to Phase (AB, BC, GAS DETECTION
AC) voltage, Phase current (A, B, C), System HIGH VIBRATION The internal logic of the controller shall be
Events and Notifications, Current time and PUMP ROOM DOOR OPEN capable of operation in a temperature range of
date, Number of starts, Total motor run hours, LOW INTAKE 4.4ºC to 40ºC and high, non-condensing,
Displayed countdown timers for: Sequential humidity levels.
motor start and motor stop
Audible horn with silence feature for The controller shall be manufactured by Metron.
silencable alarms

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP600 ACROSS THE LINE
FULL SERVICE FIRE PUMP CONTROLLER
Model Options Hp Volts UL Listed and FM Approved to 7.2kV
MP600 WITHSTAND RATING CLASS E-2 CONTROLLER
2400V 50KA @ 2500V
SEE PAGE FOR OPTIONS 3300V 50KA @ 5000V
4160V 50KA @ 5000V
6600V 50KA @ 7200V

Horsepower Voltage
2400 3300 4160 6000 6600
100 28,429 28,429
125 28,585 28,429 28,429
150 28,585 28,429 28,429
175 28,455 28,585 28,429 32,326
200 28,455 28,585 28,429 32,326 32,326
225 28,455 28,585 28,585 32,326 32,326
250 29,000 28,455 28,585 32,326 32,326
300 30,101 28,455 28,455 32,354 32,326
350 30,101 29,000 28,455 32,354 32,354
400 30,101 30,101 29,000 32,354 32,354
450 30,101 30,101 29,000 32,354 32,354
500 30,101 30,101 30,101 32,354 32,354
550 29,946 30,101 30,101 32,354 32,354
600 29,946 30,101 30,101 33,072 32,354
650 29,946 30,101 30,101 33,072 33,072
700 29,946 30,101 30,101 33,887 33,072
750 29,946 30,101 33,887 33,072
800 29,946 30,101 33,887 33,887
850 29,946 30,101 33,887 33,887
900 29,946 29,946 35,172 33,887
950 29,946 29,946 35,172 33,887
1000 29,946 35,172 35,172
1100 29,946 35,172 35,172
1200 29,946 35,172 35,172
1300 33,821 35,172
1400 33,821 35,172
1500 33,821 33,821
1600 33,821 33,821
1700 33,821 33,821
1800 33,821
1900 33,821

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
OPTIONS FOR FULL SERVICE FIRE PUMP CONTROLLERS
Applies to Model: MP600
[ ] PUMP ROOM TEMPERATURE
STANDARD FEATURE SELECTION THERMOSTAT MOUNTED ON EXTERIOR
Price of controller includes the following local OF ENCLOSURE
visual LED indications: Power On, Phase [ ] NEMA 2 RATED $42
Reversal, System Fault, and Test Operation. [ ] NEMA 4 RATED $160
Standard Default Volt Free (Dry) Contacts include: [ ] LOW SUCTION CUT OFF PRESSURE
Power Available, Phase Reversal, Pump Running, SWITCH (externally mounted) $500
and Controller not in Auto. [ ] MODBUS COMMUNICATION via RS485
In addition to the above LED indications a STANDARD
maximum of ten (10) user specified alarm ENCLOSURES:
conditions can be displayed on the Liquid Crystal [ ] NEMA 2 STANDARD
Display (LCD) display of the Operator Interface [ ] NEMA 3R $375
Display (OID). A maximum of seven (7) additional [ ] NEMA 4 $930
volt free (dry) contacts can be added. Below is a [ ] NEMA 4X PAINTED STEEL $930
list of possible alarm conditions. Consult factory [ ] NEMA 4X (UNPAINTED 304 STAINLESS
for alarm conditions not listed. STEEL) $8213
Quantity
Alarm Dry of [ ] NEMA 4X (304 PAINTED STAINLESS
Displayed Cont Contacts STEEL)
Description on OID acts Required
LOW PUMP ROOM TEMP
CONSULT FACTORY
[■] [■]
RESERVOIR LOW
[ ] NEMA 4X (UNPAINTED 316 STAINLESS
[■] [■]
RESERVOIR EMPTY STEEL) $12666
[■] [■]
RESERVOIR HIGH [■] [■]
[ ] NEMA 4X (316 PAINTED STAINLESS
FLOW METER ON [■] [■] STEEL)
RELIEF VALVE OPEN [■] [■] CONSULT FACTORY
GAS DETECTION [■] [■] [ ] NEMA 12 (SPECIFY) $840
LOW SUCTION PRESSURE [■] [■] [ ] PURGE SYSTEM, Type Z System, per
NFPA 496 suitable for Class I, Division 2,
LOW FIREWATER [■] [■]
PRESSURE Group C/D CONSULT FACTORY
LOW PURGE PRESSURE [■] [■] PLUMBING:
HIGH GEAR OIL TEMP [■] [■]
[ ] 300 psi FOR FRESH WATER STANDARD
LOW GEAR OIL PRESSURE [■] [■]
HIGH VIBRATION
[ ] 600 psi FOR FRESH WATER $120
[■] [■]
EMERGENCY POWER ON
[ ] 300 psi STAINLESS STEEL FOR
[■] [■]
PUMP ROOM DOOR OPEN [■] [■]
SALTWATER/FOAM $670
[ ] 600 psi STAINLESS STEEL FOR
Maximum number of additional Alarms is 12 SALTWATER/FOAM $790
Maximum Number of contacts, including
default contacts, can not exceed 7. Each
Alarm Condition can have a maximum 3
contacts.

OPTIONS
[ ]H SPACE HEATER
[ ]WITH THERMOSTAT $320
[ ]WITH HUMIDISTAT $320
[ ]W OMIT LEGS, WITH 3" (76.2 mm)
CHANNELS N/C
[ ] EXPORT CRATING – SUITABLE FOR
BELOW DECK STORAGE $1659

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Fire Pump Controller
For Electric Motor Driven Fire Pumps

2TKOCT[4GUKUVCPEG4GFWEGF
8QNVCIG6[RG


5GTKGU/2Ä%QODKPGF
/CPWCNCPF#WVQOCVKE

Metron Fire Pump Controllers conform to the latest
requirements of Chapter 10, National Fire
Protection Association Pamphlet 20, Standard for
Centrifugal Fire Pumps as adopted by
Underwriters Laboratories and Factory Mutual.
They are withstand rated and listed by
Underwriters’ Laboratories and approved by
Factory Mutual Research Corporation.

Sizes range from 15 to 600 horsepower, 200 to


600 volts, 60 Hz. These controllers are for use on
Reduced Voltage type installations.

Only the highest quality components, all UL listed


or UL recognized, are used throughout to assure
the best possible reliability. The cabinet is
fabricated of heavy gauge reinforced steel with
drip-proof hood. All field wiring and service
connections may be made from the front, allowing
the controller to be mounted flush against a wall.

The controller is completely wired, assembled, and


tested at the factory before shipment, and ready
for immediate installation.


MP400 Fire Pump Controller


0212 v12
Standard and Optional Features

x The system status data is displayed on the OID. The


Standard Features displayed items include: System pressure, Phase to
Primary Resistance Fire Pump controllers incorporate Phase (AB, BC, AC) voltage, Phase current (A, B, C),
heavy-duty resistors which reduce inrush current to Current time and date, System Events and Notifications
approximately 50% of normal. An adjustable timing relay is such as Remote Start, Local Start etc., Number of starts,
provided to control time between reduced voltage start and Total motor run hours, Time remaining on sequential
full voltage operation. An emergency start lever to close motor start and motor stop timers, Status of automatic
starting contactor independent of automatic control circuits stop setting.
is also supplied as standard. When used, this lever will x Auxiliary alarm functions displayed on the OID LCD
bypass the reduced voltage start features and start the screen
motor with full inrush current drawn from the power source. x Audible horn with silence feature for silencable alarms
x Lamp test feature
Operator Interface Device (OID) with LED Annunciator
x Foreign languages selectable through the OID
and Digital Display
x Microprocessor based logic with real time/date clock
capable of running a minimum of 14 days without AC
power connected to controller
x SD Memory card used to record pressure log, event and
log, and auxiliary user programs. Pressure log is stored
in separate comma delimited ASCII text files with each
file containing data for one day. The SD card is
removable and can be read by any PC equipped with an
SD card reader.
x Input and output status LED's provide visual indication of
each discrete input's or output's on/off status
x One RS485 Serial Port
x MODBUS Communication Protocol via RS485 port
x Service Entrance Rated
Standard Auxiliary alarms:
The controller includes as standard six (6) discrete
auxiliary inputs, nine (9) form 'C' auxiliary relay outputs.
These auxiliary inputs and outputs are in addition to those
mandated by NFPA 20. All auxiliary inputs, outputs, and
OID Display can be field programmed through the OID.
Nine (9) of the following auxiliary alarms can be
programmed and recorded in the event/alarm logs and
annunciated on the OID display screen and/or output relay
x NEMA Type 2 drip proof metal freestanding enclosure
contact(s). These alarm conditions include:
x Operator Interface Device (OID) with 4 lines by 20
LOW PUMP ROOM TEMP
character display with large character backlit Liquid
RESERVOIR LOW
Crystal Display (LCD) capable of being read in both
RESERVOIR EMPTY
direct sunlight or dark lighting conditions
RESERVOIR HIGH
x 10 pushbuttons for easy screen navigation, LED lamp FLOW METER ON
test, alarm reset, controller test and horn silencing RELIEF VALVE OPEN
x Removable labels to allow for easy field language LOW SUCTION PRESSURE
changes HIGH PUMP ROOM TEMPERATURE
x All controller settings are programmable through the LOW FIREWATER PRESSURE
OID. All features are enabled or disabled through the LOW PURGE PRESSURE
OID, no jumpers or external wires are needed allowing LOW GEAR OIL PRESSURE
easy field modification HIGH GEAR OIL TEMPERATURE
GAS DETECTION

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
HIGH VIBRATION
EMERGENCY POWER ON Options
PUMP ROOM DOOR OPEN
Option H: Space Heater
Data logging: If the ambient atmosphere is especially damp, a space
The controller includes two (2) separate data logs for heater rated at 100 watts may be supplied to reduce
storing system data that is readable through the OID or moisture in the cabinet. A thermostat is supplied as
copied to a computer equipped with an SD card reader. standard with this option. A humidistat may be substituted
The 2 data logs are as follows: if specified.
Pressure Log: The pressure log provides a continuous Option W: Omit Legs
pressure record for 30 days. The pressure log samples For systems where the controller is mounted on a common
shall be time and date stamped and stored in permanent skid with the pump and motor, the legs of the controller
non-volatile SD memory card. The pressure log can be may be omitted, 3” (76.2mm) channels or wall mounting
searched by each sample, by minute, or by hour through brackets can be supplied. If specified, lifting eyes may also
the OID. be supplied.
Event Log: The event log will store up to 300 of the most Enclosure
current events. These events can include, but is not limited The following NEMA type enclosures are also available:
to, any of the following events/alarms: 3R, 4, 4X (Painted Cold Rolled Steel), 4X (304 or 316
PUMP RUNNING Stainless Steel), and 12
POWER AVAILABLE
PHASE REVERSAL
MOTOR OVERLOAD
REMOTE START
LOCAL START
PUMP ON DEMAND
SYSTEM FAULT
PRESSURE TRANSDUCER FAULT
PUMP FAILED TO START
LOW INTAKE SHUTDOWN ALARM
SUPERVISORY POWER FAILURE
LOW PRESSURE
AUTO WEEKLY TEST START
UNDER FREQUENCY
OVER FREQUENCY
LOW ZONE / HIGH ZONE CONTACTS
HIGH DISCHARGE PRESSURE
NO LOAD CONDITION

0212 v12
Fire Pump Controller
For Electric Motor Driven Fire Pumps
Model MP400 Primary Resistance Start Microprocessor Electric Motor Fire Pump Controller
Microprocessor based logic with real time/date Data logging
Specifications clock capable of running a minimum of 14
days without AC power connected to
The controller shall have separate data logs for
storing system data that is readable through the
controller and non-volatile flash memory to
General Controller Description OID.
permanently store the continuous pressure log,
The Fire Pump Controller shall be factory event log, alarm log and all user changeable Pressure Log: The controller shall have a
assembled, wired and tested as a unit and shall set points and system data. Battery backup of Pressure log with continuous pressure recording
conform to all requirements of the latest edition any kind not allowed. of 30 days of data. The pressure log samples
of NFPA 20, NFPA 70 and be Third Party Listed Input and output status LED's to provide visual shall be time and date stamped and stored on a
by Underwriters Laboratories (UL) and indication of each discrete input's or output's removable SD card memory. The pressure log
Approved by Factory Mutual (FM). The on/off status shall be searchable by each sample, by minute, or
controller shall be available for 208, 230, 380- One RS485 Serial Port by hour. Each days entries shall be stored in a
415, or 480 volt three phase power. MODBUS Communication Protocol via separate file on the SD card. SD memory shall be
RS485 port readable by any PC equipped with an SD
Controller Equipment Features
All wiring terminals on PCB's shall be memory card reader.
The controller shall include the following removable type
Event Log: The event log shall be capable of
standard features: Service Entrance Rated storing no less than 3000 events. These events
NEMA Type 2 drip proof metal freestanding Auxiliary alarms shall include, but is not limited to, any of the
enclosure following events/alarms:
The controller shall be designed for Primary As standard the controller shall include 6 discrete PUMP RUNNING
Resistance starting. The controller shall start auxiliary inputs, 9 form 'C' auxiliary relay POWER AVAILABLE
outputs. These auxiliary inputs and outputs are PHASE REVERSAL
the motor in two steps, using heavy-duty
in addition to those mandated by NFPA 20. All MOTOR OVERLOAD
starting resistors to reduce the inrush current to
approximately 50% of normal. auxiliary inputs, outputs, and OID screens shall REMOTE START
be field programmable through the OID. This LOCAL START
Operator Interface Device (OID) with 4 lines
permits a multitude of customizable controller PUMP ON DEMAND
by 20 character display with large character
configurations to meet each installations unique SYSTEM FAULT
backlit LCD capable of being read in both
needs without adding cost to the controller. The PRESSURE TRANSDUCER FAULT
direct sunlight or dark lighting conditions
use of jumpers, soldering, or other external PUMP FAILED TO START
10 pushbuttons for easy screen navigation,
components are not allowed. LOW INTAKE SHUTDOWN ALARM
system test, lamp test, alarm reset, and horn
silencing The user can select any 9 of the following SUPERVISORY POWER FAILURE
Multicolored LED's for alarm and mode auxiliary alarms that can be programmed and LOW PRESSURE
annunciation recorded in the event log and annunciated with an AUTO WEEKLY TEST START
UNDER FREQUENCY
LEDs shall be labeled with removable labels to OID screen and output relay contact for
conditions such as but not limited to: OVER FREQUENCY
allow for easy field modification of language
LOW PUMP ROOM TEMP LOW ZONE / HIGH ZONE CONTACTS
changes
RESERVOIR LOW HIGH DISCHARGE PRESSURE
All controller settings shall be programmable
RESERVOIR EMPTY NO LOAD CONDITION
through the OID and shall be protected by two
password levels RESERVOIR HIGH Each event or alarm recorded in the event log
All features shall be enabled or disabled FLOW METER ON shall have the following data recorded with the
through the OID, no jumpers or external wires RELIEF VALVE OPEN event/alarm:
shall be needed or allowed to activate or de- LOW SUCTION PRESSURE Time and Date of Event or Alarm
activate a feature HIGH PUMP ROOM TEMPERATURE System Pressure
The system status data shall be displayed on LOW FIREWATER PRESSURE Descriptive Text Message of the Event/Alarm
the OID. The displayed items shall include: LOW PURGE PRESSURE Motor Running Status
System pressure, Phase to Phase (AB, BC, LOW GEAR OIL PRESSURE
Phase to Phase Volts
AC) voltage, Phase current (A, B, C), System HIGH GEAR OIL TEMPERATURE
Phase Amps
Events and Notifications, Current time and GAS DETECTION
date, Number of starts, Total motor run hours, HIGH VIBRATION The internal logic of the controller shall be
Displayed countdown timers for: Sequential EMERGENCY POWER ON capable of operation in a temperature range of
motor start and motor stop, Status of PUMP ROOM DOOR OPEN 4.4ºC to 40ºC and high, non-condensing,
Automatic Stop Setting. humidity levels.
Audible horn with silence feature for The controller shall be manufactured by Metron.
silencable alarms
Lamp test feature
Foreign languages selectable through the OID

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP400 PRIMARY RESISTANCE
FULL SERVICE FIRE PUMP CONTROLLER

Model Options Hp Volts Withstand


MP400

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 7440 7440 7440 7440 7440 ‡
20 7440 7440 7440 7440 7440 ‡
25 7440 7440 7440 7440 7440 ‡
30 7440 7440 7440 7440 7440 ‡
40 9280 9280 7520 7520 7520‡
50 9320 9320 7560 7560 7560 ‡
60 10620 10620 9340 9340 9340 ‡
75 10640 10640 9360 9360 9360 ‡
100 13400 13400 10860 10380 10380 ‡
125 19620 19620 12560 12560 12560 ‡
150 20540 20540 15820 13480 13480 ‡
200 21140 * ‡ 21140 21880 15820 14080 ‡
250 23340 * ‡ 23340 * ‡ 21880 21180 21880 ‡
300 25560 * ‡ 22580 22580 22580 ‡
350 25860 * ‡ 25400 25400 ‡
400 25400 25400 ‡
500 28760 * ‡
600 33580 * ‡
700

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL
575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL
Effective August 1, 2010 / Cat v10 200-480VAC STD
Prices subject to change without notice [C] 100,000 AMPS RMS SYMMETRICAL
‡ Available with “B” Breaker only 200-480VAC STD
* Oversized Enclosure

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP400 PRIMARY RESISTANCE
FULL SERVICE FIRE PUMP CONTROLLER

STANDARD FEATURE SELECTION [ ] LOW SUCTION CUT OFF PRESSURE


Price of controller includes the following local visual SWITCH (externally mounted) $500
LED indications: Power On, Phase Reversal, [ ] MODBUS COMMUNICATION via RS485
System Fault, and Test Operation. STANDARD
Standard Default Volt Free (Dry) Contacts include:
ENCLOSURES
Power Available, Phase Reversal, Pump Running,
[ ] NEMA 2 STANDARD
and Controller not in Auto.
[ ] NEMA 3R $375
In addition to the above LED indications a
[ ] NEMA 3R (Oversized Enclosure, denoted
maximum of twelve (12) user specified alarm
by asterisk (*) on page 1) $640
conditions can be displayed on the Liquid Crystal
[ ] NEMA 4 $1200
Display (LCD) display of the Operator Interface
[ ] NEMA 4 (Oversized Enclosure, denoted
Display (OID). A maximum of nine (9) additional
by asterisk (*) on page 1) $2200
volt free (dry) contacts can be added. Below is a
[ ] NEMA 4X PAINTED STEEL $1600
list of possible alarm conditions. Consult factory for
[ ] NEMA 4X PAINTED STEEL (Oversized
alarm conditions not listed.
Quantity
Enclosure, denoted by asterisk (*) on
Alarm Dry of page 1) $2600
Displayed Cont Contacts [ ] NEMA 4X (UNPAINTED 304
Description on OID acts Required
LOW PUMP ROOM TEMP [Ŷ] [Ŷ] STAINLESS STEEL) $2667
RESERVOIR LOW [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 304 STAINLESS
RESERVOIR EMPTY [Ŷ] [Ŷ] STEEL) (Oversized Enclosure, denoted
RESERVOIR HIGH [Ŷ] [Ŷ] by asterisk (*) on page 1) $4000
FLOW METER ON [Ŷ] [Ŷ] [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
RELIEF VALVE OPEN [Ŷ] [Ŷ] CONSULT FACTORY
GAS DETECTION [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
LOW SUCTION PRESSURE [Ŷ] [Ŷ] STEEL) $4800
LOW FIREWATER PRESSURE [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
LOW PURGE PRESSURE [Ŷ] [Ŷ] STEEL) (Oversized Enclosure, denoted
HIGH GEAR OIL TEMP [Ŷ] [Ŷ] by asterisk (*) on page 1) $7333
LOW GEAR OIL PRESSURE [Ŷ] [Ŷ] [ ] NEMA 4X (316 PAINTED STAINLESS
HIGH VIBRATION [Ŷ] [Ŷ] STEEL)
EMERGENCY POWER ON [Ŷ] [Ŷ] CONSULT FACTORY
PUMP ROOM DOOR OPEN [Ŷ] [Ŷ] [ ] NEMA 12 $25
Note: Resistor Bank Enclosure Maximum Rating is NEMA 3R when NEMA 4, 4X or 12 Enclosure is supplied
Maximum number of additional Alarms is 12
[ ] REMOVABLE GLAND PLATE $250
Maximum Number of contacts, including
default contacts, can not exceed 9. Each
[ ] PURGE SYSTEM, Type Z System, per
Alarm Condition can have a maximum 3 NFPA 496 suitable for Class I, Division 2,
contacts. Group C/D CONSULT FACTORY
[ ] MODBUS COMMUNICATION via RS485
OPTIONS CONSULT FACTORY
[ ]H SPACE HEATER PLUMBING
[ ] WITH THERMOSTAT $320 [ ] 300 PSI FOR FRESH WATER STANDARD
[ ] WITH HUMIDISTAT $320 [ ] 600 PSI FOR FRESH WATER $120
[ ]W OMIT LEGS, WITH 3" (76.2 mm) [ ] 300 PSI STAINLESS STEEL FOR
CHANNELS N/C SALTWATER/FOAM $670
[ ] EXPORT CRATING – SUITABLE FOR [ ] 600 PSI STAINLESS STEEL FOR
BELOW DECK STORAGE $997 SALTWATER/FOAM $790
[ ] PUMP ROOM TEMPERATURE
THERMOSTAT MOUNTED ON
EXTERIOR OF ENCLOSURE
[ ] NEMA 2 RATED $42
[ ] NEMA 4 RATED $160 Effective: January 1, 2011. Replaces all previous prices.
Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Fire Pump Controller
For Electric Motor Driven Fire Pumps

2CTV9KPFKPI4GFWEGF
%WTTGPV6[RGU


5GTKGU/2Ä%QODKPGF
/CPWCNCPF#WVQOCVKE

Metron Fire Pump Controllers conform to the latest
requirements of Chapter 10, National Fire
Protection Association Pamphlet 20, Standard for
Centrifugal Fire Pumps as adopted by
Underwriters Laboratories and Factory Mutual.
They are withstand rated and listed by
Underwriters’ Laboratories and approved by
Factory Mutual Research Corporation.

Sizes range from 15 to 700 horsepower, 200 to


600 volts, 60 Hz. These controllers are for use on
Reduced Voltage type installations.

Only the highest quality components, all UL listed


or UL recognized, are used throughout to assure
the best possible reliability. The cabinet is
fabricated of heavy gauge reinforced steel with
drip-proof hood. All field wiring and service
connections may be made from the front, allowing
the controller to be mounted flush against a wall.

The controller is completely wired, assembled, and


tested at the factory before shipment, and ready
for immediate installation.


MP420 Fire Pump Controller


0212 v12
Standard and Optional Features

jumpers or external wires are needed allowing easy field


Standard Features modification
Series M420 x The system status data is displayed on the OID. The
Part Winding Fire Pump controllers can be used when full displayed items include: System pressure, Phase to
voltage starting may not be desired or practical. Starting Phase (AB, BC, AC) voltage, Phase current (A, B, C),
contactors operate in sequence to energize a portion of the Current time and date, System Events and Notifications
motor windings on start which reduces inrush current to such as Remote Start, Local Start etc., Number of starts,
approximately 65% of normal. An adjustable timing relay is Total motor run hours, Time remaining on sequential
provided to control time between reduced current start and motor start and motor stop timers, Status of automatic
normal running operation. An emergency start lever to stop setting.
close starting contactor independent of automatic control x Auxiliary alarm functions displayed on the OID LCD
circuits is also supplied as standard. When used, this lever screen
will bypass the reduced voltage start feature and start the x Audible horn with silence feature for silencable alarms
motor with full inrush current drawn from the power source. x Lamp test feature
Operator Interface Device (OID) with LED Annunciator x Foreign languages selectable through the OID
and Digital Display x Microprocessor based logic with real time/date clock
capable of running a minimum of 14 days without AC
power connected to controller
x SD Memory card used to record pressure log, event and
log, and auxiliary user programs. Pressure log is stored
in separate comma delimited ASCII text files with each
file containing data for one day. The SD card is
removable and can be read by any PC equipped with an
SD card reader.
x Input and output status LED's provide visual indication of
each discrete input's or output's on/off status
x One RS485 Serial Port
x MODBUS Communication Protocol via RS485 port
x Service Entrance Rated
Standard Auxiliary alarms:
The controller includes as standard six (6) discrete
auxiliary inputs, nine (9) form 'C' auxiliary relay outputs.
These auxiliary inputs and outputs are in addition to those
mandated by NFPA 20. All auxiliary inputs, outputs, and
OID Display can be field programmed through the OID.
Nine (9) of the following auxiliary alarms can be
programmed and recorded in the event/alarm logs and
annunciated on the OID display screen and/or output relay
contact(s). These alarm conditions include:
x NEMA Type 2 drip proof metal freestanding enclosure LOW PUMP ROOM TEMP
x Operator Interface Device (OID) with 4 lines by 20 RESERVOIR LOW
character display with large character backlit Liquid RESERVOIR EMPTY
Crystal Display (LCD) capable of being read in both RESERVOIR HIGH
direct sunlight or dark lighting conditions FLOW METER ON
x 10 pushbuttons for easy screen navigation, LED lamp RELIEF VALVE OPEN
test, alarm reset, controller test and horn silencing LOW SUCTION PRESSURE
x Removable labels to allow for easy field language HIGH PUMP ROOM TEMPERATURE LOW
changes FIREWATER PRESSURE
x All controller settings are programmable through the OID. LOW PURGE PRESSURE
All features are enabled or disabled through the OID, no LOW GEAR OIL PRESSURE

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
HIGH GEAR OIL TEMPERATURE
GAS DETECTION Options
HIGH VIBRATION
EMERGENCY POWER ON Option H: Space Heater
PUMP ROOM DOOR OPEN If the ambient atmosphere is especially damp, a space
heater rated at 100 watts may be supplied to reduce
Data logging: moisture in the cabinet. A thermostat is supplied as
The controller includes two (2) separate data logs for standard with this option. A humidistat may be substituted
storing system data that is readable through the OID or if specified.
copied to a computer equipped with an SD card reader.
The 2 data logs are as follows: Option W: Omit Legs
For systems where the controller is mounted on a common
Pressure Log: The pressure log provides a continuous skid with the pump and motor, the legs of the controller
pressure record for 30 days. The pressure log samples may be omitted, 3” (76.2mm) channels or wall mounting
shall be time and date stamped and stored in permanent brackets can be supplied. If specified, lifting eyes may also
non-volatile SD memory card. The pressure log can be be supplied.
searched by each sample, by minute, or by hour through
the OID. Enclosure
The following NEMA type enclosures are also available:
Event Log: The event log will store up to 300 of the most 3R, 4, 4X (Painted Cold Rolled Steel), 4X (304 or 316
current events. These events can include, but is not Stainless Steel), and 12
limited to, any of the following events/alarms:
PUMP RUNNING
POWER AVAILABLE
PHASE REVERSAL
MOTOR OVERLOAD
REMOTE START
LOCAL START
PUMP ON DEMAND
SYSTEM FAULT
PRESSURE TRANSDUCER FAULT
PUMP FAILED TO START
LOW INTAKE SHUTDOWN ALARM
SUPERVISORY POWER FAILURE
LOW PRESSURE
AUTO WEEKLY TEST START
UNDER FREQUENCY
OVER FREQUENCY
LOW ZONE / HIGH ZONE CONTACTS
HIGH DISCHARGE PRESSURE
NO LOAD CONDITION

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Fire Pump Controller
For Electric Motor Driven Fire Pumps
Model MP420 Part Winding Start Microprocessor Electric Motor Fire Pump Controller
Audible horn with silence feature for Data logging
Specifications silencable alarms
Lamp test feature
The controller shall have separate data logs for
storing system data that is readable through the
Foreign languages selectable through the OID OID.
General Controller Description
The Fire Pump Controller shall be factory Microprocessor based logic with real time/date Pressure Log: The controller shall have a
assembled, wired and tested as a unit and shall clock capable of running a minimum of 14 Pressure log with continuous pressure recording
conform to all requirements of the latest edition days without AC power connected to of 30 days of data. The pressure log samples
of NFPA 20, NFPA 70 and be Third Party Listed controller and non-volatile flash memory to shall be time and date stamped and stored on a
by Underwriters Laboratories (UL) and permanently store the continuous pressure log, removable SD card memory. The pressure log
Approved by Factory Mutual (FM). The event log, alarm log and all user changeable shall be searchable by each sample, by minute, or
controller shall be available for 208, 230, 380- set points and system data. Battery backup of by hour. Each days entries shall be stored in a
415, or 480 volt three phase power. any kind not allowed. separate file on the SD card. SD memory shall be
Input and output status LED's to provide visual readable by any PC equipped with an SD
Controller Equipment Features indication of each discrete input's or output's memory card reader.
The controller shall include the following on/off status
standard features: One RS485 Serial Port Event Log: The event log shall be capable of
MODBUS Communication Protocol via storing no less than 3000 events. These events
NEMA Type 2 drip proof metal freestanding shall include, but is not limited to, any of the
enclosure RS485 port
All wiring terminals on PCB's shall be following events/alarms:
The Controller shall be designed for Part removable type PUMP RUNNING
Winding starting. The starting contactors shall Service Entrance Rated POWER AVAILABLE
operate in sequence to energize a portion of PHASE REVERSAL
the motor windings on start which reduces Auxiliary alarms MOTOR OVERLOAD
inrush current to approximately 65% of As standard the controller shall include 6 discrete REMOTE START
normal. An adjustable timing relay shall be auxiliary inputs, 9 form 'C' auxiliary relay LOCAL START
provided to control time between reduced outputs. These auxiliary inputs and outputs are PUMP ON DEMAND
current start and normal running operation. in addition to those mandated by NFPA 20. All SYSTEM FAULT
auxiliary inputs, outputs, and OID screens shall PRESSURE TRANSDUCER FAULT
Operator Interface Device (OID) with 4 lines be field programmable through the OID. This PUMP FAILED TO START
by 20 character display with large character permits a multitude of customizable controller LOW INTAKE SHUTDOWN ALARM
backlit LCD capable of being read in both configurations to meet each installations unique SUPERVISORY POWER FAILURE
direct sunlight or dark lighting conditions needs without adding cost to the controller. The LOW PRESSURE
10 pushbuttons for easy screen navigation, use of jumpers, soldering, or other external AUTO WEEKLY TEST START
system test, lamp test, alarm reset, and horn components are not allowed. UNDER FREQUENCY
silencing OVER FREQUENCY
The user can select any 9 of the following
Multicolored LED's for alarm and mode LOW ZONE / HIGH ZONE CONTACTS
auxiliary alarms that can be programmed and
annunciation HIGH DISCHARGE PRESSURE
recorded in the event log and annunciated with
LEDs shall be labeled with removable labels NO LOAD CONDITION
an OID screen and output relay contact for
to allow for easy field modification of
conditions such as but not limited to: Each event or alarm recorded in the event log
language changes
LOW PUMP ROOM TEMP shall have the following data recorded with the
All controller settings shall be programmable
RESERVOIR LOW event/alarm:
through the OID and shall be protected by two
RESERVOIR EMPTY Time and Date of Event or Alarm
password levels
RESERVOIR HIGH System Pressure
All features shall be enabled or disabled FLOW METER ON
through the OID, no jumpers or external wires Descriptive Text Message of the Event/Alarm
RELIEF VALVE OPEN Motor Running Status
shall be needed or allowed to activate or de- LOW SUCTION PRESSURE
activate a feature Phase to Phase Volts
HIGH PUMP ROOM TEMPERATURE Phase Amps
The system status data shall be displayed on LOW FIREWATER PRESSURE
the OID. The displayed items shall include: LOW PURGE PRESSURE The internal logic of the controller shall be
System pressure, Phase to Phase (AB, BC, LOW GEAR OIL PRESSURE capable of operation in a temperature range of
AC) voltage, Phase current (A, B, C), System HIGH GEAR OIL TEMPERATURE 4.4ºC to 40ºC and high, non-condensing,
Events and Notifications, Current time and GAS DETECTION humidity levels.
date, Number of starts, Total motor run hours, HIGH VIBRATION
Displayed countdown timers for: Sequential The controller shall be manufactured by Metron.
EMERGENCY POWER ON
motor start and motor stop, Status of PUMP ROOM DOOR OPEN
Automatic Stop Setting.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP420 PART WINDING
FULL SERVICE FIRE PUMP CONTROLLER

Model Options Hp Volts Withstand


MP420

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 6860 6860 6860 6860 6860 ‡
20 6860 6860 6860 6860 6860 ‡
25 6860 6860 6860 6860 6860 ‡
30 6860 6860 6860 6860 6860 ‡
40 8280 8280 7160 6860 6860 ‡
50 8280 8280 7160 7160 7160 ‡
60 9620 9620 8280 8280 8280 ‡
75 9620 9620 8280 8280 8280 ‡
100 12600 12600 9620 9620 9620 ‡
125 16620 16620 9620 9620 9620 ‡
150 16620 16620 13300 9620 9620 ‡
200 19120 * ‡ 19120 13300 13300 11560 ‡
250 21280 * ‡ 21280 * ‡ 16620 16620 16620 ‡
300 24160 * ‡ 24160 * ‡ 16620 16620 16620 ‡
350 16620 * ‡ 16620 16620 ‡
400 19620 * ‡ 19120 19120 ‡
500 22560 *‡ 22560 * ‡
600 25860 * ‡ 25600 * ‡
700 29120 * ‡

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL
575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL
Effective August 1, 2010 / Cat v10 200-480VAC STD
Prices subject to change without notice [C] 100,000 AMPS RMS SYMMETRICAL
‡ Available with “B” Breaker only 200-480VAC STD
* Oversized Enclosure

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP420 PART WINDING
FULL SERVICE FIRE PUMP CONTROLLER

STANDARD FEATURE SELECTION [ ] PUMP ROOM TEMPERATURE


Price of controller includes the following local visual THERMOSTAT MOUNTED ON
LED indications: Power On, Phase Reversal, EXTERIOR OF ENCLOSURE
System Fault, and Test Operation. [ ] NEMA 2 RATED $42
Standard Default Volt Free (Dry) Contacts include: [ ] NEMA 4 RATED $160
Power Available, Phase Reversal, Pump Running, [ ] LOW SUCTION CUT OFF PRESSURE
and Controller not in Auto. SWITCH (externally mounted) $500
In addition to the above LED indications a [ ] MODBUS COMMUNICATION via RS485
maximum of twelve (12) user specified alarm STANDARD
conditions can be displayed on the Liquid Crystal
Display (LCD) display of the Operator Interface ENCLOSURES
Display (OID). A maximum of nine (9) additional [ ] NEMA 2 STANDARD
volt free (dry) contacts can be added. Below is a [ ] NEMA 3R $375
list of possible alarm conditions. Consult factory for [ ] NEMA 3R (Oversized Enclosure, denoted
alarm conditions not listed. by asterisk (*) on page 1) $640
Quantity [ ] NEMA 4 $1200
Alarm Dry of
Displayed Cont Contacts [ ] NEMA 4 (Oversized Enclosure, denoted
Description on OID acts Required by asterisk (*) on page 1) $2200
LOW PUMP ROOM TEMP [Ŷ] [Ŷ] [ ] NEMA 4X PAINTED STEEL $1600
RESERVOIR LOW [Ŷ] [Ŷ] [ ] NEMA 4X PAINTED STEEL (Oversized
RESERVOIR EMPTY [Ŷ] [Ŷ] Enclosure, denoted by asterisk (*) on
RESERVOIR HIGH [Ŷ] [Ŷ] page 1) $2600
FLOW METER ON [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 304
RELIEF VALVE OPEN [Ŷ] [Ŷ]
STAINLESS STEEL) $2667
GAS DETECTION [Ŷ] [Ŷ]
LOW SUCTION PRESSURE
[ ] NEMA 4X (UNPAINTED 304 STAINLESS
[Ŷ] [Ŷ]
LOW FIREWATER PRESSURE [Ŷ] [Ŷ]
STEEL) (Oversized Enclosure, denoted
LOW PURGE PRESSURE [Ŷ] [Ŷ] by asterisk (*) on page 1) $4000
HIGH GEAR OIL TEMP [Ŷ] [Ŷ] [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
LOW GEAR OIL PRESSURE [Ŷ] [Ŷ] CONSULT FACTORY
HIGH VIBRATION [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
EMERGENCY POWER ON [Ŷ] [Ŷ] STEEL) $4800
PUMP ROOM DOOR OPEN [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
Maximum number of additional Alarms is 12
STEEL) (Oversized Enclosure, denoted by
asterisk (*) on page 1) $7333
Maximum Number of contacts, including
default contacts, can not exceed 9. Each [ ] NEMA 4X (316 PAINTED STAINLESS STEEL)
Alarm Condition can have a maximum 3
contacts. CONSULT FACTORY
[ ] NEMA 12 $25
OPTIONS
[ ] REMOVABLE GLAND PLATE $250
[ ]H SPACE HEATER
[ ] PURGE SYSTEM, Type Z System, per
[ ] WITH THERMOSTAT $320
NFPA 496 suitable for Class I, Division 2,
[ ] WITH HUMIDISTAT $320
Group C/D CONSULT FACTORY
[ ]W OMIT LEGS, WITH 3" (76.2 mm)
CHANNELS N/C
PLUMBING
[ ] EXPORT CRATING – SUITABLE FOR
[ ] 300 PSI FOR FRESH WATER STANDARD
BELOW DECK STORAGE $997
[ ] 600 PSI FOR FRESH WATER $120
[ ] 300 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $670
[ ] 600 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $790
Effective: January 1, 2011. Replaces all previous prices.
Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Fire Pump Controller
For Electric Motor Driven Fire Pumps

9[GÄ&GNVC4GFWEGF
%WTTGPV6[RGU


5GTKGU/2CPF
5GTKGU/2Ä%QODKPGF
/CPWCNCPF#WVQOCVKE

Metron Fire Pump Controllers conform to the latest
requirements of Chapter 10, National Fire
Protection Association Pamphlet 20, Standard for
Centrifugal Fire Pumps as adopted by
Underwriters Laboratories and Factory Mutual.
They are withstand rated and listed by
Underwriters’ Laboratories and approved by
Factory Mutual Research Corporation.

Sizes range from 15 to 700 horsepower, 200 to


600 volts, 60 Hz. These controllers are for use on
Reduced Voltage type installations.

Only the highest quality components, all UL listed


or UL recognized, are used throughout to assure
the best possible reliability. The cabinet is
fabricated of heavy gauge reinforced steel with
drip-proof hood. All field wiring and service
connections may be made from the front, allowing
the controller to be mounted flush against a wall.

The controller is completely wired, assembled, and


tested at the factory before shipment, and ready
for immediate installation.


MP430 Fire Pump Controller


0212 v12
Standard and Optional Features

x NEMA Type 2 drip proof metal freestanding enclosure


Standard Features x Operator Interface Device (OID) with 4 lines by 20 character
display with large character backlit Liquid Crystal Display (LCD)
Series MP430/MP435 capable of being read in both direct sunlight or dark lighting
Wye- Delta motors have all six leads brought out to the motor conditions
terminal box. These leads are connected by the controller first in x 10 pushbuttons for easy screen navigation, LED lamp test,
the Wye configuration which draws only 33% of normal starting alarm reset, controller test and horn silencing
current and develops 33% of normal starting torque. After a short x Removable labels to allow for easy field language changes
time delay, the controller then connects the motor winding in a x All controller settings are programmable through the OID. All
Delta configuration, applying full voltage and drawing full load features are enabled or disabled through the OID, no jumpers
running current and developing full running torque. or external wires are needed allowing easy field modification
With the MP430 open transition types, there is a very short period x The system status data is displayed on the OID. The displayed
of time where no voltage is applied to the motor during transition items include: System pressure, Phase to Phase (AB, BC, AC)
from Wye to Delta connections. This condition can cause current voltage, Phase current (A, B, C), Current time and date,
surges or disturbances being fed back into the main power System Events and Notifications such as Remote Start, Local
source. The magnitude of the surges is proportional to the phase Start etc., Number of starts, Total motor run hours, Time
difference between the voltage generated by the running motor remaining on sequential motor start and motor stop timers,
and the power source. These transients can in some instances, Status of automatic stop setting.
affect other equipment which are sensitive to current surges. x Auxiliary alarm functions displayed on the OID LCD screen
x Audible horn with silence feature for silencable alarms
The MP435 closed transition types provide a smoother transition x Lamp test feature
from Wye to Delta by keeping the motor continuously energized x Foreign languages selectable through the OID
during the transition period. This is accomplished by means of x Microprocessor based logic with real time/date clock capable of
resistors which are connected in the circuit during the momentary running a minimum of 14 days without AC power connected to
period of transition from Wye to Delta. controller
Metron Wye-Delta Controllers incorporate a mechanical as well x SD Memory card used to record pressure log, event and log,
as electrical interlock to prevent the Wye connecting contactor and auxiliary user programs. Pressure log is stored in separate
from being energized at the same time as the Delta contactor. comma delimited ASCII text files with each file containing data
for one day. The SD card is removable and can be read by any
An emergency start lever to close starting contactor independent PC equipped with an SD card reader.
of automatic control circuits. When used, this lever will bypass x Input and output status LED's provide visual indication of each
the reduced current start feature and start the motor with full discrete input's or output's on/off status
inrush current drawn from the power source. x One RS485 Serial Port
Operator Interface Device (OID) with LED Annunciator and x MODBUS Communication Protocol via RS485 port
Digital Display x Service Entrance Rated
Standard Auxiliary alarms:
The controller includes as standard six (6) discrete auxiliary
inputs, nine (9) form 'C' auxiliary relay outputs. These auxiliary
inputs and outputs are in addition to those mandated by NFPA
20. All auxiliary inputs, outputs, and OID Display can be field
programmed through the OID.
Nine (9) of the following auxiliary alarms can be programmed and
recorded in the event/alarm logs and annunciated on the OID
display screen and/or output relay contact(s). These alarm
conditions include:
LOW PUMP ROOM TEMP
RESERVOIR LOW
RESERVOIR EMPTY
RESERVOIR HIGH
FLOW METER ON
RELIEF VALVE OPEN
LOW SUCTION PRESSURE
HIGH PUMP ROOM TEMPERATURE
LOW FIREWATER PRESSURE LOW PURGE PRESSURE
LOW GEAR OIL PRESSURE

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
HIGH GEAR OIL TEMPERATURE
GAS DETECTION Options
HIGH VIBRATION
EMERGENCY POWER ON Option H: Space Heater
PUMP ROOM DOOR OPEN If the ambient atmosphere is especially damp, a space heater
rated at 100 watts may be supplied to reduce moisture in the
Data logging:
cabinet. A thermostat is supplied as standard with this option. A
The controller includes two (2) separate data logs for storing
humidistat may be substituted if specified.
system data that is readable through the OID or copied to a
computer equipped with an SD card reader. The 2 data logs are Option W: Omit Legs
as follows: For systems where the controller is mounted on a common skid
Pressure Log: The pressure log provides a continuous pressure with the pump and motor, the legs of the controller may be
record for 30 days. The pressure log samples shall be time and omitted, 3” (76.2mm) channels or wall mounting brackets can be
date stamped and stored in permanent non-volatile SD memory supplied. If specified, lifting eyes may also be supplied.
card. The pressure log can be searched by each sample, by Enclosure
minute, or by hour through the OID. The following NEMA type enclosures are also available: 3R, 4, 4X
Event Log: The event log will store up to 300 of the most current (Painted Cold Rolled Steel), 4X (304 or 316 Stainless Steel), and
events. These events can include, but is not limited to, any of the 12
following events/alarms:
PUMP RUNNING
POWER AVAILABLE
PHASE REVERSAL
MOTOR OVERLOAD
REMOTE START
LOCAL START
PUMP ON DEMAND
SYSTEM FAULT
PRESSURE TRANSDUCER FAULT
PUMP FAILED TO START
LOW INTAKE SHUTDOWN ALARM
SUPERVISORY POWER FAILURE
LOW PRESSURE
AUTO WEEKLY TEST START
UNDER FREQUENCY
OVER FREQUENCY
LOW ZONE / HIGH ZONE CONTACTS
HIGH DISCHARGE PRESSURE
NO LOAD CONDITION

0212 v12
Fire Pump Controller
For Electric Motor Driven Fire Pumps
Model MP430/435 Wye-Delta Start Microprocessor Electric Motor Fire Pump Controller
Microprocessor based logic with real time/date Data logging
Specifications clock capable of running a minimum of 14
days without AC power connected to
The controller shall have separate data logs for
storing system data that is readable through the
General Controller Description controller and non-volatile flash memory to OID.
permanently store the continuous pressure log,
The Fire Pump Controller shall be factory Pressure Log: The controller shall have a
event log, alarm log and all user changeable
assembled, wired and tested as a unit and shall Pressure log with continuous pressure recording
set points and system data. Battery backup of
conform to all requirements of the latest edition of 30 days of data. The pressure log samples
any kind not allowed.
of NFPA 20, NFPA 70 and be Third Party Listed shall be time and date stamped and stored on a
by Underwriters Laboratories (UL) and Input and output status LED's to provide visual
removable SD card memory. The pressure log
Approved by Factory Mutual (FM). The indication of each discrete input's or output's
shall be searchable by each sample, by minute, or
controller shall be available for 208, 230, 380- on/off status
by hour. Each days entries shall be stored in a
415, or 480 volt three phase power. One RS485 Serial Port separate file on the SD card. SD memory shall be
MODBUS Communication Protocol via readable by any PC equipped with an SD
Controller Equipment Features RS485 port memory card reader.
The controller shall include the following All wiring terminals on PCB's shall be
removable type Event Log: The event log shall be capable of
standard features:
Service Entrance Rated storing no less than 3000 events. These events
NEMA Type 2 drip proof metal freestanding shall include, but is not limited to, any of the
enclosure Auxiliary alarms following events/alarms:
The controller shall be designed for Wye-Delta As standard the controller shall include 6 discrete PUMP RUNNING
starting and shall start the motor in the Wye auxiliary inputs, 9 form 'C' auxiliary relay POWER AVAILABLE
configuration drawing 33% of normal current, outputs. These auxiliary inputs and outputs are PHASE REVERSAL
then connect the motor in the Delta in addition to those mandated by NFPA 20. All MOTOR OVERLOAD
configuration applying full voltage. auxiliary inputs, outputs, and OID screens shall REMOTE START
Operator Interface Device (OID) with 4 lines be field programmable through the OID. This LOCAL START
by 20 character display with large character permits a multitude of customizable controller PUMP ON DEMAND
backlit LCD capable of being read in both configurations to meet each installations unique SYSTEM FAULT
direct sunlight or dark lighting conditions needs without adding cost to the controller. The PRESSURE TRANSDUCER FAULT
10 pushbuttons for easy screen navigation, use of jumpers, soldering, or other external PUMP FAILED TO START
system test, lamp test, alarm reset, and horn components are not allowed. LOW INTAKE SHUTDOWN ALARM
silencing SUPERVISORY POWER FAILURE
The user can select any 9 of the following LOW PRESSURE
Multicolored LED's for alarm and mode
auxiliary alarms that can be programmed and AUTO WEEKLY TEST START
annunciation
recorded in the event log and annunciated with UNDER FREQUENCY
LEDs shall be labeled with removable labels
an OID screen and output relay contact for OVER FREQUENCY
to allow for easy field modification of
conditions such as but not limited to: LOW ZONE / HIGH ZONE CONTACTS
language changes
LOW PUMP ROOM TEMP HIGH DISCHARGE PRESSURE
All controller settings shall be programmable
RESERVOIR LOW NO LOAD CONDITION
through the OID and shall be protected by two RESERVOIR EMPTY
password levels RESERVOIR HIGH Each event or alarm recorded in the event log
All features shall be enabled or disabled FLOW METER ON shall have the following data recorded with the
through the OID, no jumpers or external wires RELIEF VALVE OPEN event/alarm:
shall be needed or allowed to activate or de- LOW SUCTION PRESSURE Time and Date of Event or Alarm
activate a feature HIGH PUMP ROOM TEMPERATURE System Pressure
The system status data shall be displayed on LOW FIREWATER PRESSURE Descriptive Text Message of the Event/Alarm
the OID. The displayed items shall include: LOW PURGE PRESSURE Motor Running Status
System pressure, Phase to Phase (AB, BC, LOW GEAR OIL PRESSURE Phase to Phase Volts
AC) voltage, Phase current (A, B, C), System HIGH GEAR OIL TEMPERATURE Phase Amps
Events and Notifications, Current time and GAS DETECTION
date, Number of starts, Total motor run hours, The internal logic of the controller shall be
HIGH VIBRATION
Displayed countdown timers for: Sequential capable of operation in a temperature range of
EMERGENCY POWER ON
motor start and motor stop, Status of 4.4ºC to 40ºC and high, non-condensing,
PUMP ROOM DOOR OPEN
Automatic Stop Setting. humidity levels.
Audible horn with silence feature for The controller shall be manufactured by Metron.
silencable alarms
Lamp test feature
Foreign languages selectable through the OID

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP430 WYE-DELTA OPEN TRANSITION
FULL SERVICE FIRE PUMP CONTROLLER

Model Options Hp Volts Withstand


MP430

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 7120 7120 7120 7120 7120 ‡
20 7120 7120 7120 7120 7120 ‡
25 7120 7120 7120 7120 7120 ‡
30 7120 7120 7120 7120 7120 ‡
40 8670 8670 7360 7360 7360 ‡
50 9140 9140 7360 7360 7360 ‡
60 10480 10480 8670 8670 8670 ‡
75 10480 10480 8670 8670 8670 ‡
100 13340 13340 10180 10180 10180 ‡
125 17640 17640 11260 11260 11260 ‡
150 17640 17640 13640 11260 11260 ‡
200 20500 * ‡ 20140 14240 14240 14240 ‡
250 20500 * ‡ 22670 * ‡ 17640 17640 17640 ‡
300 24360 * ‡ 24360 * ‡ 20740 18240 18240 ‡
350 20790 * ‡ 20740 20740 ‡
400 22670 * ‡ 20740 20740 ‡
500 24670 * ‡ 24670 * ‡
600 27180 * ‡ 27220 * ‡
700 31240 * ‡

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL
575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL
Effective August 1, 2010 / Cat v10 200-480VAC STD
Prices subject to change without notice [C] 100,000 AMPS RMS SYMMETRICAL
‡ Available with “B” Breaker only 200-480VAC STD
* Oversized Enclosure

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP430 WYE-DELTA OPEN TRANSITION
FULL SERVICE FIRE PUMP CONTROLLER

STANDARD FEATURE SELECTION [ ] PUMP ROOM TEMPERATURE


Price of controller includes the following local visual THERMOSTAT MOUNTED ON
LED indications: Power On, Phase Reversal, EXTERIOR OF ENCLOSURE
System Fault, and Test Operation. [ ] NEMA 2 RATED $42
Standard Default Volt Free (Dry) Contacts include: [ ] NEMA 4 RATED $160
Power Available, Phase Reversal, Pump Running, [ ] LOW SUCTION CUT OFF PRESSURE
and Controller not in Auto. SWITCH (externally mounted) $500
In addition to the above LED indications a [ ] MODBUS COMMUNICATION via RS485
maximum of twelve (12) user specified alarm STANDARD
conditions can be displayed on the Liquid Crystal
ENCLOSURES
Display (LCD) display of the Operator Interface
[ ] NEMA 2 STANDARD
Display (OID). A maximum of nine (9) additional
[ ] NEMA 3R $375
volt free (dry) contacts can be added. Below is a
[ ] NEMA 3R (Oversized Enclosure, denoted
list of possible alarm conditions. Consult factory for
by asterisk (*) on page 1) $640
alarm conditions not listed.
Quantity
[ ] NEMA 4 $1200
Alarm Dry of [ ] NEMA 4 (Oversized Enclosure, denoted
Displayed Cont Contacts by asterisk (*) on page 1) $2200
Description on OID acts Required
LOW PUMP ROOM TEMP [Ŷ] [Ŷ] [ ] NEMA 4X PAINTED STEEL $1600
RESERVOIR LOW [Ŷ] [Ŷ] [ ] NEMA 4X PAINTED STEEL (Oversized
RESERVOIR EMPTY [Ŷ] [Ŷ] Enclosure, denoted by asterisk (*) on
RESERVOIR HIGH [Ŷ] [Ŷ] page 1) $2600
FLOW METER ON [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 304
RELIEF VALVE OPEN [Ŷ] [Ŷ] STAINLESS STEEL) $2667
GAS DETECTION [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 304 STAINLESS
LOW SUCTION PRESSURE [Ŷ] [Ŷ] STEEL) (Oversized Enclosure, denoted
LOW FIREWATER PRESSURE [Ŷ] [Ŷ] by asterisk (*) on page 1) $4000
LOW PURGE PRESSURE [Ŷ] [Ŷ] [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
HIGH GEAR OIL TEMP [Ŷ] [Ŷ] CONSULT FACTORY
LOW GEAR OIL PRESSURE [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
HIGH VIBRATION [Ŷ] [Ŷ] STEEL) $4800
EMERGENCY POWER ON [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
PUMP ROOM DOOR OPEN [Ŷ] [Ŷ] STEEL) (Oversized Enclosure, denoted by
Maximum number of additional Alarms is 12 asterisk (*) on page 1) $7333
Maximum Number of contacts, including [ ] NEMA 4X (316 PAINTED STAINLESS STEEL)
default contacts, can not exceed 9. Each
Alarm Condition can have a maximum 3
contacts. CONSULT FACTORY
[ ] NEMA 12 $25
OPTIONS [ ] REMOVABLE GLAND PLATE $250
[ ]H SPACE HEATER [ ] PURGE SYSTEM, Type Z System, per
[ ] WITH THERMOSTAT $320 NFPA 496 suitable for Class I, Division 2,
[ ] WITH HUMIDISTAT $320 Group C/D CONSULT FACTORY
[ ]W OMIT LEGS, WITH 3" (76.2 mm)
CHANNELS N/C PLUMBING
[ ] EXPORT CRATING – SUITABLE FOR [ ] 300 PSI FOR FRESH WATER STANDARD
BELOW DECK STORAGE $997 [ ] 600 PSI FOR FRESH WATER $120
[ ] 300 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $670
[ ] 600 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $790

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP435 WYE-DELTA CLOSED TRANSITION
FULL SERVICE FIRE PUMP CONTROLLER

Model Options Hp Volts Withstand


MP435

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 9220 9220 9520 9520 9520 ‡
20 9220 9220 9520 9520 9520 ‡
25 9220 9220 9520 9520 9520 ‡
30 9620 9620 9520 9520 9520 ‡
40 11170 11170 9760 9520 9520 ‡
50 11720 11720 9760 9760 9760 ‡
60 12980 12980 11070 11070 11070 ‡
75 14680 14680 11070 11070 11070 ‡
100 17540 17540 13580 13580 13580 ‡
125 21840 21840 14660 14660 14660 ‡
150 21840 21840 17040 14660 14660 ‡
200 24340 * ‡ 24340 17640 17640 17640 ‡
250 26760 * ‡ 26760 * ‡ 22240 22240 22240 ‡
300 28860 * ‡ 28680 * ‡ 24740 22840 22840 ‡
350 25340 * ‡ 25340 25340 ‡
400 28760 * ‡ 25340 25340 ‡
500 31860 * ‡ 28760 * ‡
600 35540 * ‡ 31860 * ‡
700 36070 * ‡

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL
575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL
Effective August 1, 2010 / Cat v10 200-480VAC STD
Prices subject to change without notice [C] 100,000 AMPS RMS SYMMETRICAL
‡ Available with “B” Breaker only 200-480VAC STD
* Oversized Enclosure
Effective: January 1, 2011. Replaces all previous prices.
Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP435 WYE-DELTA CLOSED TRANSITION
FULL SERVICE FIRE PUMP CONTROLLER

STANDARD FEATURE SELECTION [ ] PUMP ROOM TEMPERATURE


Price of controller includes the following local visual THERMOSTAT MOUNTED ON
LED indications: Power On, Phase Reversal, EXTERIOR OF ENCLOSURE
System Fault, and Test Operation. [ ] NEMA 2 RATED $42
Standard Default Volt Free (Dry) Contacts include: [ ] NEMA 4 RATED $160
Power Available, Phase Reversal, Pump Running, [ ] LOW SUCTION CUT OFF PRESSURE
and Controller not in Auto. SWITCH (externally mounted) $500
In addition to the above LED indications a [ ] MODBUS COMMUNICATION via RS485
maximum of twelve (12) user specified alarm STANDARD
conditions can be displayed on the Liquid Crystal
ENCLOSURES
Display (LCD) display of the Operator Interface
[ ] NEMA 2 STANDARD
Display (OID). A maximum of nine (9) additional
[ ] NEMA 3R $375
volt free (dry) contacts can be added. Below is a
[ ] NEMA 3R (Oversized Enclosure, denoted
list of possible alarm conditions. Consult factory for
by asterisk (*) on page 1) $640
alarm conditions not listed.
Quantity
[ ] NEMA 4 $1200
Alarm Dry of [ ] NEMA 4 (Oversized Enclosure, denoted
Displayed Cont Contacts by asterisk (*) on page 1) $2200
Description on OID acts Required
LOW PUMP ROOM TEMP [Ŷ] [Ŷ] [ ] NEMA 4X PAINTED STEEL $1600
RESERVOIR LOW [Ŷ] [Ŷ] [ ] NEMA 4X PAINTED STEEL (Oversized
RESERVOIR EMPTY [Ŷ] [Ŷ] Enclosure, denoted by asterisk (*) on
RESERVOIR HIGH [Ŷ] [Ŷ] page 1) $2600
FLOW METER ON [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 304
RELIEF VALVE OPEN [Ŷ] [Ŷ] STAINLESS STEEL) $2667
GAS DETECTION [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 304 STAINLESS
LOW SUCTION PRESSURE [Ŷ] [Ŷ] STEEL) (Oversized Enclosure, denoted
LOW FIREWATER PRESSURE [Ŷ] [Ŷ] by asterisk (*) on page 1) $4000
LOW PURGE PRESSURE [Ŷ] [Ŷ] [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
HIGH GEAR OIL TEMP [Ŷ] [Ŷ] CONSULT FACTORY
LOW GEAR OIL PRESSURE [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
HIGH VIBRATION [Ŷ] [Ŷ] STEEL) $4800
EMERGENCY POWER ON [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
PUMP ROOM DOOR OPEN [Ŷ] [Ŷ] STEEL) (Oversized Enclosure, denoted
Maximum number of additional Alarms is 12 by asterisk (*) on page 1) $7333
Maximum Number of contacts, including [ ] NEMA 4X (316 PAINTED STAINLESS STEEL)
default contacts, can not exceed 9. Each
Alarm Condition can have a maximum 3
contacts. CONSULT FACTORY
[ ] NEMA 12 $25
Note: Resistor Bank Enclosure Maximum Rating is NEMA 3R when NEMA 4, 4X or 12 Enclosure is supplied
OPTIONS [ ] REMOVABLE GLAND PLATE $250
[ ]H SPACE HEATER
[ ] PURGE SYSTEM, Type Z System, per
[ ] WITH THERMOSTAT $320
NFPA 496 suitable for Class I, Division 2,
[ ] WITH HUMIDISTAT $320
Group C/D CONSULT FACTORY
[ ]W OMIT LEGS, WITH 3" (76.2 mm)
CHANNELS N/C
PLUMBING
[ ] EXPORT CRATING – SUITABLE FOR
[ ] 300 PSI FOR FRESH WATER STANDARD
BELOW DECK STORAGE $997
[ ] 600 PSI FOR FRESH WATER $120
[ ] 300 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $670
[ ] 600 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $790

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Fire Pump Controller
For Electric Motor Driven Fire Pumps

#WVQVTCPUHQTOGT
%NQUGFÄ6TCPUKVKQP
4GFWEGF8QNVCIG6[RG


5GTKGU/2Ä%QODKPGF
/CPWCNCPF#WVQOCVKE

Metron Fire Pump Controllers conform to the latest
requirements of Chapter 10, National Fire
Protection Association Pamphlet 20, Standard for
Centrifugal Fire Pumps as adopted by
Underwriters Laboratories and Factory Mutual.
They are withstand rated and listed by
Underwriters’ Laboratories and approved by
Factory Mutual Research Corporation.

Sizes range from 15 to 600 horsepower, 200 to


600 volts, 60 Hz. These controllers are for use on
Reduced Voltage type installations.

Only the highest quality components, all UL listed


or UL recognized, are used throughout to assure
the best possible reliability. The cabinet is
fabricated of heavy gauge reinforced steel with
drip-proof hood. All field wiring and service
connections may be made from the front, allowing
the controller to be mounted flush against a wall.

The controller is completely wired, assembled, and


tested at the factory before shipment, and ready
for immediate installation.


MP450 Fire Pump Controller


MSC0212 v11
Standard and Optional Features

x 10 pushbuttons for easy screen navigation, LED lamp


Standard Features test, alarm reset, controller test and horn silencing
x Removable labels to allow for easy field language
Series MP450
changes
Autotransformer Fire Pump Controllers incorporate a
heavy-duty autotransformer with taps available at 50%, x All controller settings are programmable through the
65%, and 80% to reduce the starting voltage to the motor. OID. All features are enabled or disabled through the
The autotransformer is factory wired to the 65% taps OID, no jumpers or external wires are needed allowing
unless specified otherwise. easy field modification
x The system status data is displayed on the OID. The
The starting inrush current drawn from the power source is displayed items include: System pressure, Phase to
reduced to approximately 25% of normal when using the Phase (AB, BC, AC) voltage, Phase current (A, B, C),
50% tap, 42% of normal on 65% tap, and 64% of normal Current time and date, System Events and Notifications
on 80% tap. such as Remote Start, Local Start etc., Number of starts,
Taps other than listed above are also available. Consult Total motor run hours, Time remaining on sequential
factory for information. motor start and motor stop timers, Status of automatic
stop setting.
An adjustable timing relay is provided to control time x Auxiliary alarm functions displayed on the OID LCD
between reduced voltage start and full voltage operation. screen
An emergency start handle to close starting contactor x Audible horn with silence feature for silencable alarms
independent of automatic control circuits is also supplied x Lamp test feature
as standard. When used, this handle will bypass the x Foreign languages selectable through the OID
reduced voltage start feature and start the motor with full x Microprocessor based logic with real time/date clock
inrush current drawn from the power source. capable of running a minimum of 14 days without AC
Operator Interface Device (OID) with LED Annunciator power connected to controller
and Digital Display x SD Memory card used to record pressure log, event and
log, and auxiliary user programs. Pressure log is stored
in separate comma delimited ASCII text files with each
file containing data for one day. The SD card is
removable and can be read by any PC equipped with an
SD card reader.
x Input and output status LED's provide visual indication of
each discrete input's or output's on/off status
x RS485 Communications Port
x MODBUS Communication Protocol via RS485 port
x Service Entrance Rated
Standard Auxiliary alarms:
The controller includes as standard six (6) discrete
auxiliary inputs, nine (9) form 'C' auxiliary relay outputs.
These auxiliary inputs and outputs are in addition to those
mandated by NFPA 20. All auxiliary inputs, outputs, and
OID Display can be field programmed through the OID.
Nine (9) of the following auxiliary alarms can be
programmed and recorded in the event/alarm logs and
annunciated on the OID display screen and/or output relay
contact(s). These alarm conditions include:
x NEMA Type 2 drip proof metal freestanding enclosure
LOW PUMP ROOM TEMP
x Operator Interface Device (OID) with 4 lines by 20
RESERVOIR LOW
character display with large character backlit Liquid
RESERVOIR EMPTY
Crystal Display (LCD) capable of being read in both
RESERVOIR HIGH
direct sunlight or dark lighting conditions

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
FLOW METER ON
RELIEF VALVE OPEN Options
LOW SUCTION PRESSURE
HIGH PUMP ROOM TEMPERATURE Option H: Space Heater
LOW FIREWATER PRESSURE If the ambient atmosphere is especially damp, a space
LOW PURGE PRESSURE heater rated at 100 watts may be supplied to reduce
LOW GEAR OIL PRESSURE moisture in the cabinet. A thermostat is supplied as
HIGH GEAR OIL TEMPERATURE standard with this option. A humidistat may be substituted
GAS DETECTION if specified.
HIGH VIBRATION Option W: Omit Legs
EMERGENCY POWER ON For systems where the controller is mounted on a common
PUMP ROOM DOOR OPEN skid with the pump and motor, the legs of the controller
Data logging: may be omitted, 3” (76.2mm) channels or wall mounting
The controller includes two (2) separate data logs for brackets can be supplied. If specified, lifting eyes may also
storing system data that is readable through the OID or be supplied.
copied to a computer equipped with an SD card reader. Enclosure
The 2 data logs are as follows: The following NEMA type enclosures are also available:
Pressure Log: The pressure log provides a continuous 3R, 4, 4X (Painted Cold Rolled Steel), 4X (304 or 316
pressure record for 30 days. The pressure log samples Stainless Steel), and 12
shall be time and date stamped and stored in permanent
non-volatile SD memory card. The pressure log can be
searched by each sample, by minute, or by hour through
the OID.
Event Log: The event log will store up to 300 of the most
current events. These events can include, but is not limited
to, any of the following events/alarms:
PUMP RUNNING
POWER AVAILABLE
PHASE REVERSAL
MOTOR OVERLOAD
REMOTE START
LOCAL START
PUMP ON DEMAND
SYSTEM FAULT
PRESSURE TRANSDUCER FAULT
PUMP FAILED TO START
LOW INTAKE SHUTDOWN ALARM
SUPERVISORY POWER FAILURE
LOW PRESSURE
AUTO WEEKLY TEST START
UNDER FREQUENCY
OVER FREQUENCY
LOW ZONE / HIGH ZONE CONTACTS
HIGH DISCHARGE PRESSURE
NO LOAD CONDITION

MSC0212 v11
Fire Pump Controller
For Electric Motor Driven Fire Pumps
Model MP450 Autotransformer Start Microprocessor Electric Motor Fire Pump Controller
Microprocessor based logic with real time/date Data logging
Specifications clock capable of running a minimum of 14
days without AC power connected to
The controller shall have separate data logs for
storing system data that is readable through the
General Controller Description controller and non-volatile flash memory to OID.
The Fire Pump Controller shall be factory permanently store the continuous pressure log,
Pressure Log: The controller shall have a
assembled, wired and tested as a unit and shall event log, alarm log and all user changeable
Pressure log with continuous pressure recording
conform to all requirements of the latest edition set points and system data. Battery backup of
of 30 days of data. The pressure log samples
of NFPA 20, NFPA 70 and be Third Party Listed any kind not allowed.
shall be time and date stamped and stored on a
by Underwriters Laboratories (UL) and Input and output status LED's to provide visual
removable SD card memory. The pressure log
Approved by Factory Mutual (FM). The indication of each discrete input's or output's
shall be searchable by each sample, by minute, or
controller shall be available for 208, 230, 380- on/off status
by hour. Each days entries shall be stored in a
415, or 480 volt three phase power. RS485 Communications Port separate file on the SD card. SD memory shall be
Controller Equipment Features MODBUS Communication Protocol via readable by any PC equipped with an SD
RS485 port memory card reader.
The controller shall include the following
All wiring terminals on PCB's shall be
standard features: Event Log: The event log shall be capable of
removable type
storing no less than 3000 events. These events
NEMA Type 2 drip proof metal freestanding Service Entrance Rated
shall include, but is not limited to, any of the
enclosure Auxiliary alarms following events/alarms:
The controller shall be designed for PUMP RUNNING
As standard the controller shall include 6 discrete
Autotransformer starting and shall start the POWER AVAILABLE
auxiliary inputs, 9 form 'C' auxiliary relay
motor using a heavy-duty motor starting outputs. These auxiliary inputs and outputs are PHASE REVERSAL
autotransformer, reducing inrush current to in addition to those mandated by NFPA 20. All MOTOR OVERLOAD
42% of normal using the 65% tap. Taps of REMOTE START
auxiliary inputs, outputs, and OID screens shall
25% and 80% shall be supplied. LOCAL START
be field programmable through the OID. This
Operator Interface Device (OID) with 4 lines permits a multitude of customizable controller PUMP ON DEMAND
by 20 character display with large character configurations to meet each installations unique SYSTEM FAULT
backlit LCD capable of being read in both needs without adding cost to the controller. The PRESSURE TRANSDUCER FAULT
direct sunlight or dark lighting conditions use of jumpers, soldering, or other external PUMP FAILED TO START
10 pushbuttons for easy screen navigation, components are not allowed. LOW INTAKE SHUTDOWN ALARM
system test, lamp test, alarm reset, and horn SUPERVISORY POWER FAILURE
silencing The user can select any 9 of the following
auxiliary alarms that can be programmed and LOW PRESSURE
Multicolored LED's for alarm and mode AUTO WEEKLY TEST START
recorded in the event log and annunciated with
annunciation UNDER FREQUENCY
an OID screen and output relay contact for
LEDs shall be labeled with removable labels OVER FREQUENCY
conditions such as but not limited to:
to allow for easy field modification of LOW ZONE / HIGH ZONE CONTACTS
LOW PUMP ROOM TEMP
language changes HIGH DISCHARGE PRESSURE
RESERVOIR LOW
All controller settings shall be programmable NO LOAD CONDITION
RESERVOIR EMPTY
through the OID and shall be protected by two RESERVOIR HIGH Each event or alarm recorded in the event log
password levels FLOW METER ON shall have the following data recorded with the
All features shall be enabled or disabled RELIEF VALVE OPEN event/alarm:
through the OID, no jumpers or external wires LOW SUCTION PRESSURE Time and Date of Event or Alarm
shall be needed or allowed to activate or de- HIGH PUMP ROOM TEMPERATURE System Pressure
activate a feature LOW FIREWATER PRESSURE Descriptive Text Message of the Event/Alarm
The system status data shall be displayed on LOW PURGE PRESSURE Motor Running Status
the OID. The displayed items shall include: LOW GEAR OIL PRESSURE Phase to Phase Volts
System pressure, Phase to Phase (AB, BC, HIGH GEAR OIL TEMPERATURE
AC) voltage, Phase current (A, B, C), Phase Amps
GAS DETECTION
System Events and Notifications, Current The internal logic of the controller shall be
HIGH VIBRATION
time and date, Number of starts, Total motor capable of operation in a temperature range of
EMERGENCY POWER ON
run hours, Displayed countdown timers for: 4.4ºC to 40ºC and high, non-condensing,
PUMP ROOM DOOR OPEN
Sequential motor start and motor stop, humidity levels.
Status of Automatic Stop Setting. The controller shall be manufactured by Metron.
Audible horn with silence feature for
silencable alarms
Lamp test feature
Foreign languages selectable through the OID

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP450 AUTOTRANSFORMER
FULL SERVICE FIRE PUMP CONTROLLER

Model Options Hp Volts Withstand


MP450

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 11680 11680 11680 11680 11680 ‡
20 11680 11680 11680 11680 11680 ‡
25 11680 11680 11680 11680 11680 ‡
30 11680 11680 11680 11680 11680 ‡
40 13760 13760 11680 11680 11680 ‡
50 13760 13760 11680 11680 11680 ‡
60 15880 15880 13760 13760 13760 ‡
75 15880 15880 13760 13760 13760 ‡
100 19360 19360 15880 13760 13760 ‡
125 25200 25200 15880 15880 15880 ‡
150 25200 25200 15880 15880 15880 ‡
200 25200 * ‡ 25200 25200 15880 15880 ‡
250 28680 * ‡ 28680 * ‡ 25200 25200 25200 ‡
300 31200 * ‡ 25200 25200 25200 ‡
350 28680 * ‡ 25200 30920 ‡
400 30,920 30920 ‡
500 35760 * ‡
600 40200 * ‡
700

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL
575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL
Effective August 1, 2010 / Cat v10 200-480VAC STD
Prices subject to change without notice [C] 100,000 AMPS RMS SYMMETRICAL
‡ Available with “B” Breaker only 200-480VAC STD
* Oversized Enclosure

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP450 AUTOTRANSFORMER
FULL SERVICE FIRE PUMP CONTROLLER

STANDARD FEATURE SELECTION [ ] PUMP ROOM TEMPERATURE


Price of controller includes the following local visual THERMOSTAT MOUNTED ON
LED indications: Power On, Phase Reversal, EXTERIOR OF ENCLOSURE
System Fault, and Test Operation. [ ] NEMA 2 RATED $42
Standard Default Volt Free (Dry) Contacts include: [ ] NEMA 4 RATED $160
Power Available, Phase Reversal, Pump Running, [ ] LOW SUCTION CUT OFF PRESSURE
and Controller not in Auto. SWITCH (externally mounted) $500
In addition to the above LED indications a [ ] MODBUS COMMUNICATION via RS485
maximum of twelve (12) user specified alarm STANDARD
conditions can be displayed on the Liquid Crystal
ENCLOSURES
Display (LCD) display of the Operator Interface
[ ] NEMA 2 STANDARD
Display (OID). A maximum of nine (9) additional
[ ] NEMA 3R $375
volt free (dry) contacts can be added. Below is a
[ ] NEMA 3R (Oversized Enclosure, denoted
list of possible alarm conditions. Consult factory for
by asterisk (*) on page 1) $640
alarm conditions not listed.
Quantity
[ ] NEMA 4 $1200
Alarm Dry of [ ] NEMA 4 (Oversized Enclosure, denoted
Displayed Cont Contacts by asterisk (*) on page 1) $2200
Description on OID acts Required
LOW PUMP ROOM TEMP [Ŷ] [Ŷ] [ ] NEMA 4X PAINTED STEEL $1600
RESERVOIR LOW [Ŷ] [Ŷ] [ ] NEMA 4X PAINTED STEEL (Oversized
RESERVOIR EMPTY [Ŷ] [Ŷ] Enclosure, denoted by asterisk (*) on
RESERVOIR HIGH [Ŷ] [Ŷ] page 1) $2600
FLOW METER ON [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 304
RELIEF VALVE OPEN [Ŷ] [Ŷ] STAINLESS STEEL) $2667
GAS DETECTION [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 304 STAINLESS
LOW SUCTION PRESSURE [Ŷ] [Ŷ] STEEL) (Oversized Enclosure, denoted
LOW FIREWATER PRESSURE [Ŷ] [Ŷ] by asterisk (*) on page 1) $4000
LOW PURGE PRESSURE [Ŷ] [Ŷ] [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
HIGH GEAR OIL TEMP [Ŷ] [Ŷ] CONSULT FACTORY
LOW GEAR OIL PRESSURE [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
HIGH VIBRATION [Ŷ] [Ŷ] STEEL) $4800
EMERGENCY POWER ON [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
PUMP ROOM DOOR OPEN [Ŷ] [Ŷ] STEEL) (Oversized Enclosure, denoted by
Maximum number of additional Alarms is 12 asterisk (*) on page 1) $7333
Maximum Number of contacts, including [ ] NEMA 4X (316 PAINTED STAINLESS STEEL)
default contacts, can not exceed 9. Each
Alarm Condition can have a maximum 3
contacts. CONSULT FACTORY
[ ] NEMA 12 $25
OPTIONS [ ] REMOVABLE GLAND PLATE $250
[ ]H SPACE HEATER [ ] PURGE SYSTEM, Type Z System, per
[ ] WITH THERMOSTAT $320 NFPA 496 suitable for Class I, Division 2,
[ ] WITH HUMIDISTAT $320 Group C/D CONSULT FACTORY
[ ]W OMIT LEGS, WITH 3" (76.2 mm)
CHANNELS N/C PLUMBING
[ ] EXPORT CRATING – SUITABLE FOR [ ] 300 PSI FOR FRESH WATER STANDARD
BELOW DECK STORAGE $997 [ ] 600 PSI FOR FRESH WATER $120
[ ] 300 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $670
[ ] 600 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $790

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Fire Pump Controller
For Electric Motor Driven Fire Pumps

5QNKF5VCVG
4GFWEGF8QNVCIG6[RGU


5GTKGU/2
5QHV5VCTV5QHV5VQR

Metron Fire Pump Controllers conform to the
latest requirements of Chapter 10, National Fire
Protection Association Pamphlet 20, Standard
for Centrifugal Fire Pumps as adopted by
Underwriters Laboratories and Factory Mutual.

Sizes range from 15 to 600 horsepower, 200 to


600 volts, 60 Hz. These controllers are used on
reduced voltage type installations using a solid
state starter for “Soft” starting and “Soft” stopping
of electric motors.

Only the highest quality components, all UL listed


or UL recognized, are used throughout to assure
the best possible reliability. The cabinet is
fabricated of heavy gauge reinforced steel with
drip-proof hood. All field wiring and service
connections may be made from the front, allowing
the controller to be mounted flush against a wall.

The controller is completely wired, assembled, and


tested at the factory before shipment, and ready
for immediate installation.

MP700 Fire Pump Controller


MSC0212 v11
Nine (9) of the following auxiliary alarms can be HIGH DISCHARGE PRESSURE
programmed and recorded in the event/alarm logs and NO LOAD CONDITION
annunciated on the OID display screen and/or output
relay contact(s). These alarm conditions include: Options
LOW PUMP ROOM TEMP
RESERVOIR LOW Option H: Space Heater
RESERVOIR EMPTY If the ambient atmosphere is especially damp, a space
RESERVOIR HIGH heater rated at 100 watts may be supplied to reduce
FLOW METER ON moisture in the cabinet. A thermostat is supplied as
RELIEF VALVE OPEN standard with this option. A humidistat may be
LOW SUCTION PRESSURE substituted if specified.
HIGH PUMP ROOM TEMPERATURE Option W: Omit Legs
LOW FIREWATER PRESSURE For systems where the controller is mounted on a
LOW PURGE PRESSURE common skid with the pump and motor, the legs of the
LOW GEAR OIL PRESSURE controller may be omitted, 3” (76.2mm) channels or wall
HIGH GEAR OIL TEMPERATURE mounting brackets can be supplied. If specified, lifting
GAS DETECTION eyes may also be supplied.
HIGH VIBRATION
EMERGENCY POWER ON Enclosure
PUMP ROOM DOOR OPEN The following NEMA type enclosures are also available:
3R, 4, 4X (Painted Cold Rolled Steel), 4X (304 or 316
Data logging: The controller includes two (2) separate Stainless Steel), and 12
data logs for storing system data that is readable through
the OID or copied to a computer equipped with an SD
card reader. The 2 data logs are as follows:
Pressure Log: The pressure log provides a continuous
pressure record for 30 days. The pressure log samples
shall be time and date stamped and stored in permanent
non-volatile SD memory card. The pressure log can be
searched by each sample, by minute, or by hour through
the OID.
Event Log: The event log will store up to 300 of the most
current events. These events can include, but is not
limited to, any of the following events/alarms:
PUMP RUNNING
POWER AVAILABLE
PHASE REVERSAL
MOTOR OVERLOAD
REMOTE START
LOCAL START
PUMP ON DEMAND
SYSTEM FAULT
PRESSURE TRANSDUCER FAULT
PUMP FAILED TO START
LOW INTAKE SHUTDOWN ALARM
SUPERVISORY POWER FAILURE
LOW PRESSURE
AUTO WEEKLY TEST START
UNDER FREQUENCY
OVER FREQUENCY
LOW ZONE / HIGH ZONE CONTACTS

MSC0212 v11
Standard and Optional Features

Detection; Shorted SCR Detection; Phase Loss


Standard Features Monitor; Heatsink Over Temperature Switch
x NEMA Type 2 drip proof metal freestanding enclosure
Function - The MP700 series Soft Start electric fire x Operator Interface Device (OID) with 4 lines by 20
pump controllers utilizes a state of the art solid state character display with large character backlit Liquid
motor controller. The motor voltage is raised to an initial Crystal Display (LCD) capable of being read in both
torque value. This is an adjustable value of locked rotor direct sunlight or dark lighting conditions
torque. The motor voltage is gradually increased during x 10 pushbuttons for easy screen navigation, LED lamp
the acceleration ramp time. The acceleration ramp time test, alarm reset, controller test and horn silencing
is set to 10 seconds as required by NFPA 20, but it is x Removable labels to allow for easy field language
adjustable from approximately 3 to 30 seconds. changes
After a minimum run period and all starting causes have x All controller settings are programmable through the
returned to normal, the solid state controller will initiate a OID. All features are enabled or disabled through the
stop sequence. This function will reduce surges in the OID, no jumpers or external wires are needed allowing
pumping system during stopping of a centrifugal pump by easy field modification
smoothly decelerating the motor at a selectable rate. x The system status data is displayed on the OID. The
This will reduce the possibility of surges occurring in the displayed items include: System pressure, Phase to
system. Phase (AB, BC, AC) voltage, Phase current (A, B, C),
Current time and date, System Events and Notifications
such as Remote Start, Local Start etc., Number of
starts, Total motor run hours, Time remaining on
sequential motor start and motor stop timers, Status of
automatic stop setting.
x Auxiliary alarm functions displayed on the OID LCD
screen
x Audible horn with silence feature for silencable alarms
Operator Interface Device (OID) with LED x Lamp test feature
Annunciator and Digital Display x Foreign languages selectable through the OID
x Microprocessor based logic with real time/date clock
capable of running a minimum of 14 days without AC
power connected to controller
x SD Memory card used to record pressure log, event
and log, and auxiliary user programs. Pressure log is
stored in separate comma delimited ASCII text files
with each file containing data for one day. The SD card
is removable and can be read by any PC equipped with
an SD card reader.
x Input and output status LED's provide visual indication
of each discrete input's or output's on/off status
x RS485 Communications Port
x MODBUS Communication Protocol via RS485 port
x Service Entrance Rated
Standard Auxiliary alarms:
The controller includes as standard six (6) discrete
auxiliary inputs, nine (9) form 'C' auxiliary relay outputs.
These auxiliary inputs and outputs are in addition to
those mandated by NFPA 20. All auxiliary inputs,
outputs, and OID Display can be field programmed
x The solid state unit is supplied with the following through the OID.
protection features: Instantaneous Overcurrent

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Fire Pump Controller
For Electric Motor Driven Fire Pumps
Model MP700 Soft Start/Soft Stop Microprocessor Electric Motor Fire Pump Controller
Audible horn with silence feature for Data logging
Specifications silencable alarms
Lamp test feature
The controller shall have separate data logs for
storing system data that is readable through the
Foreign languages selectable through the OID OID.
The Fire Pump Controller shall be factory
assembled, wired and tested as a unit and shall Microprocessor based logic with real Pressure Log: The controller shall have a
conform to all requirements of the latest edition time/date clock capable of running a Pressure log with continuous pressure recording
of NFPA 20, NFPA 70 and be Third Party minimum of 14 days without AC power of 30 days of data. The pressure log samples
Listed by Underwriters Laboratories (UL) and connected to controller and non-volatile flash shall be time and date stamped and stored on a
Approved by Factory Mutual (FM). The memory to permanently store the continuous removable SD card memory. The pressure log
controller shall be available for 208, 230, 380- pressure log, event log, alarm log and all user shall be searchable by each sample, by minute,
415, or 480 volt three phase power. changeable set points and system data. or by hour. Each days entries shall be stored in a
Battery backup of any kind not allowed separate file on the SD card. SD memory shall
Controller Equipment Features Input and output status LED's to provide be readable by any PC equipped with an SD
The controller shall include the following visual indication of each discrete input's or memory card reader.
standard features: output's on/off status
RS485 Communications Port Event Log: The event log shall be capable of
NEMA Type 2 drip proof metal freestanding MODBUS Communication Protocol via storing no less than 3000 events. These events
enclosure RS485 port shall include, but is not limited to, any of the
The controller shall be designed for Soft Start All wiring terminals on PCB's shall be following events/alarms:
starting and shall incorporate a special Pump removable type PUMP RUNNING
Control feature which eliminates excessive POWER AVAILABLE
Service Entrance Rated
acceleration torque problems (water hammer) PHASE REVERSAL
and related effects. The controller shall stop Auxiliary alarms MOTOR OVERLOAD
the motor by reducing the speed in a manner As standard the controller shall include 6 REMOTE START
that prevents any sudden changes in torque discrete auxiliary inputs, 9 form 'C' auxiliary LOCAL START
and minimizes surges in the system resulting relay outputs. These auxiliary inputs and PUMP ON DEMAND
in a smooth deceleration to the pump outputs are in addition to those mandated by SYSTEM FAULT
Operator Interface Device (OID) with 4 lines NFPA 20. All auxiliary inputs, outputs, and PRESSURE TRANSDUCER FAULT
by 20 character display with large character OID screens shall be field programmable PUMP FAILED TO START
backlit LCD capable of being read in both through the OID. This permits a multitude of LOW INTAKE SHUTDOWN ALARM
direct sunlight or dark lighting conditions customizable controller configurations to meet SUPERVISORY POWER FAILURE
10 pushbuttons for easy screen navigation, each installations unique needs without adding LOW PRESSURE
system test, lamp test, alarm reset, and horn cost to the controller. The use of jumpers, AUTO WEEKLY TEST START
silencing soldering, or other external components are not UNDER FREQUENCY
Multicolored LED's for alarm and mode allowed. OVER FREQUENCY
annunciation LOW ZONE / HIGH ZONE CONTACTS
The user can select any 9 of the following
LEDs shall be labeled with removable labels HIGH DISCHARGE PRESSURE
auxiliary alarms that can be programmed and
to allow for easy field modification of NO LOAD CONDITION
recorded in the event log and annunciated with
language changes an OID screen and output relay contact for Each event or alarm recorded in the event log
All controller settings shall be programmable conditions such as but not limited to: shall have the following data recorded with the
through the OID and shall be protected by LOW PUMP ROOM TEMP event/alarm:
two password levels RESERVOIR LOW Time and Date of Event or Alarm
All features shall be enabled or disabled RESERVOIR EMPTY System Pressure
through the OID, no jumpers or external wires RESERVOIR HIGH Descriptive Text Message of the Event/Alarm
shall be needed or allowed to activate or de- FLOW METER ON Motor Running Status
activate a feature RELIEF VALVE OPEN Phase to Phase Volts
The system status data shall be displayed LOW SUCTION PRESSURE
on the OID. The displayed items shall Phase Amps
HIGH PUMP ROOM TEMPERATURE
include: System pressure, Phase to Phase LOW FIREWATER PRESSURE The internal logic of the controller shall be
(AB, BC, AC) voltage, Phase current (A, LOW PURGE PRESSURE capable of operation in a temperature range of
B, C), System Events and Notifications, LOW GEAR OIL PRESSURE 4.4ºC to 40ºC and high, non-condensing,
Current time and date, Number of starts, HIGH GEAR OIL TEMPERATURE humidity levels.
Total motor run hours, Displayed GAS DETECTION
countdown timers for: Sequential motor The controller shall be manufactured by Metron.
HIGH VIBRATION
start and motor stop, Status of Automatic EMERGENCY POWER ON
Stop Setting PUMP ROOM DOOR OPEN

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP700 SOLID STATE REDUCED VOLTAGE
FULL SERVICE FIRE PUMP CONTROLLER

Model Options Hp Volts Withstand


MP700

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 11240 11240 11240 11240 11240 ‡
20 11240 11240 11240 11240 11240 ‡
25 12340 12340 11240 11240 11240 ‡
30 12340 12340 11240 11240 11240 ‡
40 13440 13440 11240 11240 11240 ‡
50 13590 13590 13590 11240 11240 ‡
60 14340 14340 13440 13440 13440 ‡
75 15640 15640 13440 13440 13440 ‡
100 18740 18740 13760 13760 13760 ‡
125 24740 24740 15440 15440 15440 ‡
150 24440 24440 15440 15440 15440 ‡
200 24940 * ‡ 24940 24940 16040 16040 ‡
250 28440 * ‡ 28440 * ‡ 24940 24940 24940 ‡
300 30740 * ‡ 25200 25200 25200 ‡
350 30740 * ‡ 29640 29640 ‡
400 29640 29640 ‡
500 32860 * ‡
600 36740 * ‡
700

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL
575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL
Effective August 1, 2010 / Cat v10 200-480VAC STD
Prices subject to change without notice [C] 100,000 AMPS RMS SYMMETRICAL
‡ Available with “B” Breaker only 200-480VAC STD
* Oversized Enclosure
Effective: January 1, 2011. Replaces all previous prices.
Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP700 SOLID STATE REDUCED VOLTAGE
FULL SERVICE FIRE PUMP CONTROLLER

STANDARD FEATURE SELECTION [ ] PUMP ROOM TEMPERATURE


Price of controller includes the following local visual THERMOSTAT MOUNTED ON
LED indications: Power On, Phase Reversal, EXTERIOR OF ENCLOSURE
System Fault, and Test Operation. [ ] NEMA 2 RATED $42
Standard Default Volt Free (Dry) Contacts include: [ ] NEMA 4 RATED $160
Power Available, Phase Reversal, Pump Running, [ ] LOW SUCTION CUT OFF PRESSURE
and Controller not in Auto. SWITCH (externally mounted) $500
In addition to the above LED indications a [ ] MODBUS COMMUNICATION via RS485
maximum of twelve (12) user specified alarm STANDARD
conditions can be displayed on the Liquid Crystal
ENCLOSURES
Display (LCD) display of the Operator Interface
[ ] NEMA 2 STANDARD
Display (OID). A maximum of nine (9) additional
[ ] NEMA 3R $375
volt free (dry) contacts can be added. Below is a
[ ] NEMA 3R (Oversized Enclosure, denoted
list of possible alarm conditions. Consult factory for
by asterisk (*) on page 1) $640
alarm conditions not listed.
Quantity
[ ] NEMA 4 $1200
Alarm Dry of [ ] NEMA 4 (Oversized Enclosure, denoted
Displayed Cont Contacts by asterisk (*) on page 1) $2200
Description on OID acts Required
LOW PUMP ROOM TEMP [Ŷ] [Ŷ] [ ] NEMA 4X PAINTED STEEL $1600
RESERVOIR LOW [Ŷ] [Ŷ] [ ] NEMA 4X PAINTED STEEL (Oversized
RESERVOIR EMPTY [Ŷ] [Ŷ] Enclosure, denoted by asterisk (*) on
RESERVOIR HIGH [Ŷ] [Ŷ] page 1) $2600
FLOW METER ON [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 304
RELIEF VALVE OPEN [Ŷ] [Ŷ] STAINLESS STEEL) $2667
GAS DETECTION [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 304 STAINLESS
LOW SUCTION PRESSURE [Ŷ] [Ŷ] STEEL) (Oversized Enclosure, denoted
LOW FIREWATER PRESSURE [Ŷ] [Ŷ] by asterisk (*) on page 1) $4000
LOW PURGE PRESSURE [Ŷ] [Ŷ] [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
HIGH GEAR OIL TEMP [Ŷ] [Ŷ] CONSULT FACTORY
LOW GEAR OIL PRESSURE [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
HIGH VIBRATION [Ŷ] [Ŷ] STEEL) $4800
EMERGENCY POWER ON [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
PUMP ROOM DOOR OPEN [Ŷ] [Ŷ] STEEL) (Oversized Enclosure, denoted
Maximum number of additional Alarms is 12 by asterisk (*) on page 1) $7333
Maximum Number of contacts, including [ ] NEMA 4X (316 PAINTED STAINLESS STEEL)
default contacts, can not exceed 9. Each
Alarm Condition can have a maximum 3
contacts. CONSULT FACTORY
[ ] NEMA 12 $25
OPTIONS [ ] REMOVABLE GLAND PLATE $250
[ ]H SPACE HEATER [ ] PURGE SYSTEM, Type Z System, per
[ ] WITH THERMOSTAT $320 NFPA 496 suitable for Class I, Division 2,
[ ] WITH HUMIDISTAT $320 Group C/D CONSULT FACTORY
[ ]W OMIT LEGS, WITH 3" (76.2 mm)
CHANNELS N/C PLUMBING
[ ] EXPORT CRATING – SUITABLE FOR [ ] 300 PSI FOR FRESH WATER STANDARD
BELOW DECK STORAGE $997 [ ] 600 PSI FOR FRESH WATER $120
[ ] 300 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $670
[ ] 600 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $790

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Fire Pump Controller
For Electric Motor Driven Fire Pumps

8CTKCDNG(TGSWGPE[&TKXG
8(& 
4GFWEGF8QNVCIG6[RGU


5GTKGU/2
8CTKCDNG(TGSWGPE[&TKXG
8(& 

Metron Fire Pump Controllers conform to the latest
requirements of Chapter 10, National Fire
Protection Association Pamphlet 20, Standard for
Centrifugal Fire Pumps as adopted by
Underwriters Laboratories and Factory Mutual.

Sizes range from 50 to 350 horsepower, 200 to


480 volts, 60 Hz. These controllers are used on
reduced voltage installations using a variable
frequency drive to adjust the speed of the pump to
compensate for variations in suction pressure and
system demand to maintain a constant output
pressure from shutoff to full flow of the pump.

Only the highest quality components, all UL listed or


UL recognized, are used throughout to assure the
best possible reliability. The NEMA 12 standard
cabinet is fabricated of heavy gauge reinforced steel
with drip-proof hood. All field wiring and service
connections may be made from the front, allowing
the controller to be mounted flush against a wall.

The controller is completely wired, assembled, and


tested at the factory before shipment, and ready for
immediate installation.

MP800-700 with Transfer Switch


in NEMA 12 Enclosure Fire Pump Controller
MSC0212 v11
Standard and Optional Features

Function - The MP800 series Variable Frequency Drive Current time and date, System Events and Notifications
(VFD) electric motor fire pump controllers utilizes a state such as Remote Start, Local Start etc., Number of
of the art VFD with Swinging Choke Filter that is suitable starts, Total motor run hours, Time remaining on
for operation of a motor rated for VFD operation. The sequential motor start and motor stop timers, Status of
controller is designed for operation of motors that operate automatic stop setting.
with a 1.0 service factor. The controller compensates for x Auxiliary alarm functions displayed on the OID LCD
the effects of changing suction pressures that result in a screen
higher pump discharge pressure. The VFD provides soft x Audible horn with silence feature for silenceable alarms
start (ramp up) and soft stop (ramp down) to minimize x Lamp test feature
water hammer. Due to the operation characteristics of x Foreign languages selectable through the OID
the VFD the inrush current is greatly reduced. The x Microprocessor based logic with real time/date clock
current limit is factory default at 125% of full load current capable of running a minimum of 14 days without AC
but is field adjustable. power connected to controller
x SD Memory card used to record pressure log, event
Standard Features and log, and auxiliary user programs. Pressure log is
Operator Interface Device (OID) with LED Annunciator stored in separate comma delimited ASCII text files with
and Digital Display each file containing data for one day. The SD card is
removable and can be read by any PC equipped with
an SD card reader.
x Input and output status LED's provide visual indication
of each discrete input's or output's on/off status
x One RS485 Serial Port
x MODBUS Communication Protocol via RS485 port
x Service Entrance Rated
Auxiliary alarms:
The controller includes as standard five (5) discrete
auxiliary inputs, seven (7) form 'C' auxiliary relay outputs.
These auxiliary inputs and outputs are in addition to those
mandated by NFPA 20. All auxiliary inputs, outputs, and
OID Display can be field programmed through the OID.
Five (5) of the following auxiliary alarms can be
programmed and recorded in the event/alarm logs and
annunciated on the OID display screen and/or output
relay contact(s). These alarm conditions include:
x NEMA Type 2 drip proof metal freestanding enclosure LOW PUMP ROOM TEMP
x Operator Interface Device (OID) with 4 lines by 20 RESERVOIR LOW
character display with large character backlit Liquid RESERVOIR EMPTY
Crystal Display (LCD) capable of being read in both RESERVOIR HIGH
direct sunlight or dark lighting conditions FLOW METER ON
x 10 pushbuttons for easy screen navigation, LED lamp RELIEF VALVE OPEN
test, alarm reset, controller test and horn silencing LOW SUCTION PRESSURE
x Removable labels to allow for easy field language HIGH PUMP ROOM TEMPERATURE
changes LOW FIREWATER PRESSURE
x All controller settings are programmable through the LOW PURGE PRESSURE
OID. All features are enabled or disabled through the LOW GEAR OIL PRESSURE
OID, no jumpers or external wires are needed allowing HIGH GEAR OIL TEMPERATURE
easy field modification GAS DETECTION
x The system status data is displayed on the OID. The HIGH VIBRATION
displayed items include: System pressure, Phase to EMERGENCY POWER ON
Phase (AB, BC, AC) voltage, Phase current (A, B, C), PUMP ROOM DOOR OPEN

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Data logging:
The controller includes two (2) separate data logs for Options
storing system data that is readable through the OID or
copied to a computer equipped with an SD card reader. Option H: Space Heater
The 2 data logs are as follows: If the ambient atmosphere is especially damp, a space
heater rated at 100 watts may be supplied to reduce
Pressure Log: The pressure log provides a continuous moisture in the cabinet. A thermostat is supplied as
pressure record for up to 31 days. The pressure log standard with this option. A humidistat may be
samples are time and date stamped and stored in substituted if specified.
permanent non-volatile SD memory card. The pressure
log can be searched by each sample, by minute, or by Option W: Omit Legs
hour through the OID. For systems where the controller is mounted on a
common skid with the pump and motor, the legs of the
Event Log: The event log will store up to 3000 of the controller may be omitted, 3” (76.2mm) channels or wall
most current events. These events can include, but is not mounting brackets can be supplied. If specified, lifting
limited to, any of the following events/alarms: eyes may also be supplied.
PUMP RUNNING
POWER AVAILABLE Additional Options
PHASE REVERSAL Reduced voltage bypass starting: Autotransformer Start
MOTOR OVERLOAD or Solid State Soft Start/Stop.
REMOTE START Enclosure
LOCAL START The following NEMA 12 standard.
PUMP ON DEMAND
SYSTEM FAULT
PRESSURE TRANSDUCER FAULT
PUMP FAILED TO START
LOW INTAKE SHUTDOWN ALARM
SUPERVISORY POWER FAILURE
LOW PRESSURE
AUTO WEEKLY TEST START
UNDER FREQUENCY
OVER FREQUENCY
LOW ZONE / HIGH ZONE CONTACTS
HIGH DISCHARGE PRESSURE
NO LOAD CONDITION

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Fire Pump Controller
For Electric Motor Driven Fire Pumps
Model MP800 Variable Frequency Drive (VFD) Electric Motor Fire Pump Controller
Audible horn with silence feature for Data logging
Specifications silenceable alarms
Lamp test feature
The controller shall have separate data logs for
storing system data that is readable through the
The Fire Pump Controller shall be factory Foreign languages selectable through the OID OID.
assembled, wired and tested as a unit and shall Microprocessor based logic with real time/date
conform to all requirements of the latest edition of clock capable of running a minimum of 14 days Pressure Log: The controller shall have a pressure
NFPA 20, NFPA 70 and be Third Party Listed by without AC power connected to controller and log with continuous pressure recording for up to
Underwriters Laboratories (UL). The controller non-volatile flash memory to permanently store 31 days of data. The pressure log samples shall be
shall be available for 208, 230, 380-415, or 480 the continuous pressure log, event log, alarm time and date stamped and stored on a removable
volt three phase power. log and all user changeable set points and SD card memory. The pressure log shall be
system data. Battery backup of any kind not searchable by each sample, by minute, or by hour.
Controller Equipment Features
allowed. Each days entries shall be stored in a separate file
The controller shall include the following standard Input and output status LED's to provide visual on the SD card. SD memory shall be readable by
features: indication of each discrete input's or output's any PC equipped with an SD memory card reader.
NEMA Type 12 drip proof metal freestanding on/off status
Event Log: The event log shall be capable of
enclosure One RS485 Serial Port
storing no less than 3000 events. These events
Variable Frequency Drive (VFD) electric motor MODBUS Communication Protocol via RS485 shall include, but is not limited to, any of the
fire pump controllers utilizes a state of the art port following events/alarms:
VFD with Swinging Choke Filter that is suitable All wiring terminals on PCB's shall be PUMP RUNNING
for operation of a motor rated for VFD removable type POWER AVAILABLE
operation. The controller is designed for Service Entrance Rated PHASE REVERSAL
operation of motors that operate with a 1.0 Auxiliary alarms MOTOR OVERLOAD
service factor only. The controller compensates REMOTE START
for the effects of changing suction pressures that As standard the controller shall include 5 discrete LOCAL START
result in a higher pump discharge pressure. The auxiliary inputs, 7 form 'C' auxiliary relay outputs. PUMP ON DEMAND
VFD provides soft start (ramp up) and soft stop These auxiliary inputs and outputs are in addition SYSTEM FAULT
(ramp down) to minimize water hammer. Due to those mandated by NFPA 20. All auxiliary PRESSURE TRANSDUCER FAULT
to the operation characteristics of the VFD the inputs, outputs, and OID screens shall be field PUMP FAILED TO START
inrush current is greatly reduced. The current programmable through the OID. This permits a LOW INTAKE SHUTDOWN ALARM
limit is factory default at 125% of full load multitude of customizable controller SUPERVISORY POWER FAILURE
current but is field adjustable. configurations to meet each installations unique LOW PRESSURE
Operator Interface Device (OID) with 4 lines by needs without adding cost to the controller. The AUTO WEEKLY TEST START
20 character display with large character backlit use of jumpers, soldering, or other external UNDER FREQUENCY
LCD capable of being read in both direct components are not allowed. OVER FREQUENCY
sunlight or dark lighting conditions LOW ZONE / HIGH ZONE CONTACTS
The user can select any 5 of the following
10 pushbuttons for easy screen navigation, HIGH DISCHARGE PRESSURE
auxiliary alarms that can be programmed and
system test, lamp test, alarm reset, and horn NO LOAD CONDITION
recorded in the event log and annunciated with an
silencing
OID screen and output relay contact for conditions Each event or alarm recorded in the event log shall
Multicolored LED's for alarm and mode such as but not limited to: have the following data recorded with the
annunciation
LOW PUMP ROOM TEMP event/alarm:
LEDs shall be labeled with removable labels to RESERVOIR LOW Time and Date of Event or Alarm
allow for easy field modification of language RESERVOIR EMPTY System Pressure
changes RESERVOIR HIGH Descriptive Text Message of the Event/Alarm
All controller settings shall be programmable FLOW METER ON
through the OID and shall be protected by two Motor Running Status
RELIEF VALVE OPEN Phase to Phase Volts
password levels LOW SUCTION PRESSURE
All features shall be enabled or disabled through Phase Amps
HIGH PUMP ROOM TEMPERATURE
the OID, no jumpers or external wires shall be LOW FIREWATER PRESSURE The internal logic of the controller shall be capable
needed or allowed to activate or de-activate a LOW PURGE PRESSURE of operation in a temperature range of 4.4ºC to
feature LOW GEAR OIL PRESSURE 40ºC and high, non-condensing, humidity levels.
The system status data shall be displayed on the HIGH GEAR OIL TEMPERATURE
OID. The displayed items shall include: System GAS DETECTION The controller shall be manufactured by Metron.
pressure, Phase to Phase (AB, BC, AC) voltage, HIGH VIBRATION
Phase current (A, B, C), System Events and EMERGENCY POWER ON
Notifications, Current time and date, Number of PUMP ROOM DOOR OPEN
starts, Total motor run hours, Displayed
countdown timers for: Sequential motor start
and motor stop, Status of Automatic Stop
Setting.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP800 VARIABLE FREQUENCY DRIVE
FULL SERVICE FIRE PUMP CONTROLLER

Model Bypass Hp Volts Withstand


MP800

Across The Line Start

Horsepower Voltage
200/208 220/240 380/415 440/480
15 † † † †
20 † † † †
25 † † † †
30 † † † †
40 46,850 44,840 44,730 43,350
50 52,160 49,770 48,150 46,680
60 54,300 53,700 52,790 50,100
75 64,540 59,630 58,190 53,200
100 76,560 67,190 64,960 62,470
125 98,430 77,920 75,160 67,890
150 † † 79,750 74,080
200 † † 86,010 80,080
250 † † 101,200 86,250
300 † † 108,120
350 † 113,300
400 † †
500 †
600
700

WITHSTAND RATING
[C]
100,000 AMPS RMS SYMMETRICAL 200-480VAC
Effective January 1, 2011 / Cat v11
† Consult factory for price

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP800 VARIABLE FREQUENCY DRIVE DUAL UTILITY TRANSFER
FULL SERVICE FIRE PUMP CONTROLLER

Model Bypass Hp Volts Withstand


MP800 450

Autotransformer Closed
Transition Start W/ Dual
Utility Transfer Switch

Horsepower Voltage
200/208 220/240 380/415 440/480
15 † † † †
20 † † † †
25 † † † †
30 † † † †
40 67,240 65,270 64,590 63,210
50 73,850 70,730 68,060 66,540
60 76,160 75,560 73,180 70,220
75 88,840 83,150 78,580 73,590
100 102,710 93,340 87,380 85,310
125 131,590 105,750 97,600 91,410
150 † † 105,960 97,600
200 † † 114,900 105,560
250 † † 135,420 143,090
300 † † 147,950
350 † 151,310
400 † †
500 †
600
700

WITHSTAND RATING
[C]
100,000 AMPS RMS SYMMETRICAL 200-480VAC
Effective January 1, 2011 / Cat v11
† Consult factory for price

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP800 VARIABLE FREQUENCY DRIVE
FULL SERVICE FIRE PUMP CONTROLLER

Model Bypass Hp Volts Withstand


MP800

Solid State Soft Start Bypass

Horsepower Voltage
200/208 220/240 380/415 440/480
15 † † † †
20 † † † †
25 † † † †
30 † † † †
40 53,490 51,520 50,120 48,740
50 58,980 56,590 55,920 52,070
60 60,770 60,170 59,430 56,740
75 72,410 67,500 64,830 59,840
100 85,920 76,550 70,800 69,460
125 111,130 90,620 81,740 75,550
150 † † 87,410 81,740
200 † † 98,920 86,520
250 † † 114,110 99,160
300 † † 121,310
350 † 127,930
400 † †
500 †
600
700

WITHSTAND RATING
[C]
100,000 AMPS RMS SYMMETRICAL 200-480VAC
Effective January 1, 2011 / Cat v11
† Consult factory for price

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP800 VARIABLE FREQUENCY DRIVE
FULL SERVICE FIRE PUMP CONTROLLER

[ ] PURGE SYSTEM, Type Z System, per


NFPA 496 suitable for Class I, Division 2,
BYPASS METHODS: Group C/D
[ ] 300 – ACROSS THE LINE PLUMBING
[ ] 450 – AUTO-TRANSFORMER [ ] 300 PSI FOR FRESH WATER STANDARD
[ ] 700 – SOFT START/STOP [ ] 600 PSI FOR FRESH WATER
[ ] 300 PSI STAINLESS STEEL FOR
OPTIONS SALTWATER/FOAM
[ ]H SPACE HEATER [ ] 600 PSI STAINLESS STEEL FOR
[ ] WITH THERMOSTAT SALTWATER/FOAM
[ ] WITH HUMIDISTAT
[ ]W OMIT LEGS, WITH 3" (76.2 mm)
CHANNELS
[ ] EXPORT CRATING – SUITABLE FOR
BELOW DECK STORAGE
[ ] PUMP ROOM TEMPERATURE
THERMOSTAT MOUNTED ON
EXTERIOR OF ENCLOSURE
[ ] NEMA 2 RATED
[ ] NEMA 4 RATED
[ ] LOW SUCTION CUT OFF PRESSURE
SWITCH (externally mounted)
[ ] MODBUS COMMUNICATION via RS485
ENCLOSURES

[ ] NEMA 3R
[ ] NEMA 3R (Oversized Enclosure,
denoted by asterisk (*) on page 1)
[ ] NEMA 4
[ ] NEMA 4 (Oversized Enclosure, denoted
by asterisk (*) on page 1)
[ ] NEMA 4X PAINTED STEEL
[ ] NEMA 4X PAINTED STEEL (Oversized
Enclosure, denoted by asterisk (*) on
page 1)
[ ] NEMA 4X (PAINTED 304 STAINLESS
STEEL)
[ ] NEMA 4X (PAINTED 304 STAINLESS
STEEL) (Oversized Enclosure, denoted
by asterisk (*) on page 1)
[ ] NEMA 4X (304 STAINLESS STEEL)
[ ] NEMA 4X (PAINTED 316 STAINLESS
STEEL)
[ ] NEMA 4X (PAINTED 316 STAINLESS
STEEL) (Oversized Enclosure, denoted
by asterisk (*) on page 1)
[ ] NEMA 4X (316 STAINLESS STEEL)
[ ] NEMA 12 STANDARD
[ ] REMOVABLE GLAND PLATE

Effective: January 1, 2011. Consult factory for current pricing.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
TRANSFER
SWITCHES
SECTION CONTENTS:
Full Service Power Transfer Switch Bulletin
Transfer Switch Schematic
Model MP300 with Transfer Switch Price Sheet
Model MP300 with Transfer Switch Drawings
Model MP400 with Transfer Switch Price Sheet Switch
Model MP400 with Transfer Switch Drawings
Model MP420 with Transfer Switch Price Sheet
Model MP420 with Transfer Switch Drawings
Model MP430 with Transfer Switch Price Sheet
Model MP430 with Transfer Switch Drawings
Model MP435 with Transfer Switch Price Sheet
Model MP435 with Transfer Switch Drawings
Model MP450 with Transfer Switch Price Sheet
Model MP450 with Transfer Switch Drawings
Model MP700 with Transfer Switch Price Sheet
Model MP700 with Transfer Switch Drawings
Model MP800 with Transfer Switch Price Sheet
Limited Service Model M30 with Transfer Switch Bulletin
Model M30 with Transfer Switch Price Sheets
Model M30 with Transfer Switch Drawings

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Power Transfer Switches
For Electric Motor Driven Fire Pumps

5GTKGU/65
#WVQOCVKE6TCPUHGT5YKVEJ
Metron MTS Automatic Transfer Switch provide operation of electric fire
pump motors from a alternate source of power when the normal source
fails. They may be used with any Metron electric fire pump controller—
Across the Line, Primary Resistance, Part Winding, Wye-Delta, Auto
Transformer or Solid State Reduced Voltage Types. These transfer
switches are an integral part of the fire pump controller. They are factory
assembled, shipped and installed as a part of the controller.
The combination fire pump controller/transfer switch is listed by
Underwriters’ Laboratories’, Factory Mutual, and meets all the latest
requirements of Chapter 10 of NFPA 20 Standard for Installation of
Centrifugal Fire Pumps.
The MTS Automatic Transfer Switch is a mechanically held double throw
switch with a fast acting drive mechanism. Operating coils are
momentarily energized from the source to which the load is being
transferred. The switch is interlocked electrically and mechanically to
prevent both services form feeding the load at the same time. The
transfer switch is capable of manual (non-electrical) operation.
Under voltage sensing devices are supplied which monitor each phase of
normal service. When the voltage of any phase falls below the pre-set
level the transfer switch automatically transfers to the alternate source.
Voltage and frequency sensing devices are provided to monitor one
phase of the alternate source and will inhibit transfer to the alternate
source until adequate voltage and frequency are available.
The transfer switch provides a special circuit that de-energizes the motor
control circuit five (5) second prior to transfer in either direction to prevent
high current transients due to an out-of-phase condition between the
motor and the source to which it is being connected.
A contact is provided to actuate the engine starting circuit when normal
source fails. To prevent false starts, a time delay (factory set at 1/2 to 3
seconds) is provided between normal source failure and actuation of the
engine start contact.
An isolation switch ahead of the alternate source input terminals of the
transfer switch is provided. When the switch is opened, auxiliary contacts
in the generator start circuit prevent starting if commanded to by the
transfer switch. An additional auxiliary contact on the isolation switch is
provided for remote annunciation of isolation switch position.
An adjustable time delay (0-30 min.) prevents restoration to normal
service for a pre-set period of time to assure normal line stabilization.
An auxiliary N.O. contact is provided for remote annunciation of transfer
to emergency. This contact is operated by the transfer mechanism as a
direct indication of switch position.
Pilot lights for indication of Switch in Normal position, Switch in
Emergency position, and Emergency Isolation Switch in Off. Audible
indication of Emergency Isolation Switch in Off is also included.
A test switch is also provided which simulates loss of normal power so
that the transfer switch operation can be checked without interrupting
normal service to the fire pump controller.

MP435 Fire Pump Controller with Automatic Transfer Switch


All photographs and/or images are typical and may not represent actual product supplied

MSC0212 v11
Power Transfer Switches
For Electric Motor Driven Fire Pumps
Electric Motor Fire Pump Controller with Automatic Transfer Switch
MODBUS Communication Protocol via RS485 Data logging:
Specifications port The controller shall have separate data logs for
storing system data that is readable through the OID.
The controller shall include the following standard All wiring terminals on PCB's shall be removable
type Pressure Log: The controller shall have a Pressure
features:
log with continuous pressure recording of 30 days of
NEMA Type 2 drip proof metal freestanding Automatic Transfer Switch: UL Listed for Fire data. The pressure log samples shall be time and
enclosure Pump Service, sized at least 115% of motor full date stamped and stored on a removable SD card
load current and shall conform to all requirements memory. The pressure log shall be searchable by
AUTO, MANUAL, TEST, and OFF mode
of NFPA 20 Chapter 10. It shall be installed in a each sample, by minute, or by hour. Each days
buttons illuminated with colored LED's for
controller mode operation barriered compartment of the fire pump entries shall be stored in a separate file on the SD
controller. The complete assembly, controller and card. SD memory shall be readable by any PC
Operator Interface Device (OID) with 4 lines by transfer switch, shall be shipped as a single unit. equipped with an SD memory card reader.
20 character display with large character backlit
The Transfer Switch shall be supplied with a Event Log: The event log shall be capable of storing
LCD capable of being read in both direct sunlight
special circuit to prevent higher than normal no less than 3000 events. These events shall
or dark lighting conditions
starting currents when transferring from one include, but is not limited to, any of the following
10 pushbuttons for easy screen navigation, system source to the other. This circuit shall deactivate events/alarms:
test, lamp test, alarm reset, and horn silencing the fire pump motor five (5) seconds prior to MOTOR QUIT FAULT
transfer in either direction. MOTOR OVERLOAD
Multicolored LED's for alarm and mode PHASE REVERSAL
annunciation Alternate Source Isolation Switch: Externally PUMP FAILED TO START
operable, quick break type sized at least 115% of LOW VOLTAGE
LEDs shall be labeled with removable labels to motor full load current. Auxiliary contacts on the
allow for easy field modification if additional HIGH VOLTAGE
isolation switch shall be interwired with the PRESSURE TRANSDUCER FAULT
alarms and/or language changes engine start contacts to prevent starting of the PUMP ON DEMAND
All controller settings shall be programmable engine should the isolation switch be in the open LOW DISCHARGE PRESSURE
through the OID and shall be protected by two position. Shall be front mounted and wired for HIGH DISCHARGE PRESSURE
password levels ease of maintenance and allowing the unit to be REMOTE START SIGNAL
mounted flush against a wall. DELUGE VALVE START
All features shall be enabled or disabled through LOW PUMP ROOM TEMPERATURE
Auxiliary alarms:
the OID, no jumpers or external wires shall be RESERVOIR LOW
As standard the controller shall include 6 discrete
needed or allowed to activate or de-activate a RESERVOIR EMPTY
auxiliary inputs, 9 form 'C' auxiliary relay outputs.
feature RESERVOIR HIGH
These auxiliary inputs and outputs are in addition to
The system status data shall be displayed on the those mandated by NFPA 20. All auxiliary inputs, FLOW METER ON
OID. The displayed items shall include: System outputs, and OID LED's shall be field programmable RELIEF VALVE OPEN
pressure, Phase to Phase (AB, BC, AC) voltage, through the OID. This permits a multitude of GAS DETECTION
Phase current (A, B, C), Current time and date, customizable controller configurations to meet each LOW SUCTION PRESSURE
Number of starts, Total motor run hours, installations unique needs without adding cost to the LOW FIREWATER PRESSURE
Displayed countdown timers for: Sequential controller. The use of jumpers, soldering, or other LOW PURGE PRESSURE
motor start and motor stop, Status of Automatic external components are not allowed. HIGH GEAR OIL TEMPERATURE
Stop Setting. LOW GEAR OIL PRESSURE
The user can select any 9 of the following auxiliary HIGH VIBRATION
Audible horn with silence feature for silencable alarms that can be programmed and recorded in the PUMP ROOM DOOR OPEN
alarms event/alarm logs and annunciated with an LED and
output relay contact for conditions such as: Alarm Log: The Alarm Log shall be a separate
Lamp test feature LOW PUMP ROOM TEMP subset of the event log and shall display the last 10
RESERVOIR LOW alarms recorded in the system.
English or Spanish languages selectable through RESERVOIR EMPTY
the OID Each event or alarm recorded in the either event log
RESERVOIR HIGH or alarm logs shall have the following data recorded
Microprocessor based logic with real time/date FLOW METER ON with the event/alarm:
clock capable of running a minimum of 14 days RELIEF VALVE OPEN
Time and Date of Event or Alarm
without AC power connected to controller and GAS DETECTION
System Pressure
non-volatile flash memory to permanently store LOW SUCTION PRESSURE
LOW HYDRAULIC PRESSURE Descriptive Text Message of the Event/Alarm
the continuous pressure log, event log, alarm log Motor Running Status
and all user changeable set points and system LOW FIREWATER PRESSURE
LOW PURGE PRESSURE Phase to Phase Volts
data. Battery backup of any kind not allowed.
LOW GEAR OIL PRESSURE Phase Amps
Input and output status LED's to provide visual HIGH VIBRATION The internal logic of the controller shall be capable
indication of each discrete input's or output's EMERGENCY POWER ON of operation in a temperature range of 4.4ºC to 40ºC
on/off status PUMP ROOM DOOR OPEN and high, non-condensing, humidity levels.
One RS485 Serial Port The controller shall be manufactured by Metron.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP300 ACROSS THE LINE
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH
Model Options Hp Volts Withstand Transfer Switch Size
MP300 MTS-

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 22,030 22,030 22,030 22,030 22,030 ‡
20 22,030 22,030 22,030 22,030 22,030 ‡
25 22,030 22,030 22,030 22,030 22,030 ‡
30 22,250 22,030 22,030 22,030 22,030 ‡
40 23,290 23,290 22,030 22,030 22,030 ‡
50 23,970 23,290 22,030 22,030 22,030 ‡
60 25,030 25,030 23,290 23,070 23,070 ‡
75 25,410 25,030 23,290 23,290 23,070 ‡
100 28,200 28,200 25,030 23,290 23,290 ‡
125 37,810 31,120 25,030 25,030 24,350 ‡
150 37,810 37,810 26,460 25,030 25,030 ‡
200 46,410 * ‡ 37,810 31,120 28,200 25,410 ‡
250 49,750 * ‡ 49,750 * ‡ 37,810 31,120 31,120 ‡
300 65,415 * ‡ 37,810 37,810 31,120 ‡
350 49,270 * ‡ 40,670 33,980 ‡
400 40,670 40,670 ‡
500 52,690 * ‡
600 66,755 * ‡
700

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL 575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL 200-480VAC STD
[C] 100,000 AMPS RMS SYMMETRICAL 200-480VAC STD

Normal Power Source and Alternate Power Source Withstand Rating


Value is the same as value indicated above.

Horsepower Voltage
200 208 220/240 380/415 440/480 550/600
15 100A 100A 100A 100A 100A 100A
20 100A 100A 100A 100A 100A 100A
25 100A 100A 100A 100A 100A 100A
30 150A 150A 100A 100A 100A 100A
40 150A 150A 150A 100A 100A 100A
50 225A 225A 150A 100A 100A 100A
60 225A 225A 225A 150A 100A 100A
75 260A 260A 225A 150A 150A 100A
100 400A 400A 400A 225A 150A 150A
125 600A 600A 400A 225A 225A 150A
150 600A 600A 600A 400A 225A 225A
200 800A 800A 600A 400A 400A 260A
250 800A 800A 800A 600A 400A 400A
300 1000A 600A 600A 400A
350 800A 600A 400A
Effective January 1, 2011 / Cat v11 400 600A 600A
Prices subject to change without notice 500 800A
‡ Available with “B” Breaker only 600 1000A
* Oversized Enclosure 700

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP300 ACROSS THE LINE
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH

STANDARD FEATURE SELECTION [ ] LOW SUCTION CUT OFF PRESSURE


Price of controller includes the following local visual SWITCH (externally mounted) $500
LED indications: Power On, Phase Reversal, System [ ] MODBUS COMMUNICATION via RS485
Fault, Transfer Switch in Normal, Transfer Switch in STANDARD
Emergency, Emergency Isolation Switch Open, and ENCLOSURES
Test Operation. [ ] NEMA 2 STANDARD
Standard Default Volt Free (Dry) Contacts include: [ ] NEMA 3R $750
Power Available, Phase Reversal, Pump Running, [ ] NEMA 3R (Oversized Enclosure, denoted
and Controller not in Auto. by asterisk (*) on page 1) $1280
In addition to the above LED indications a maximum [ ] NEMA 4 $2400
of twelve (12) user specified alarm conditions can be [ ] NEMA 4 (Oversized Enclosure, denoted by
displayed on the Liquid Crystal Display (LCD) display asterisk (*) on page 1) $4400
of the Operator Interface Display (OID). A maximum [ ] NEMA 4X PAINTED STEEL $3200
of nine (9) additional volt free (dry) contacts can be [ ] NEMA 4X PAINTED STEEL (Oversized
added. Below is a list of possible alarm conditions. Enclosure, denoted by asterisk (*) on
Consult factory for alarm conditions not listed. page 1) $5200
Quantity [ ] NEMA 4X (UNPAINTED 304
Alarm Dry of
Displayed Cont Contacts STAINLESS STEEL) $5334
Description on OID acts Required [ ] NEMA 4X (UNPAINTED 304
LOW PUMP ROOM TEMP [■] [■] STAINLESS STEEL) (Oversized
RESERVOIR LOW [■] [■] Enclosure, denoted by asterisk (*) on
RESERVOIR EMPTY [■] [■] page 1) $8000
RESERVOIR HIGH [■] [■] [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
FLOW METER ON [■] [■] CONSULT FACTORY
RELIEF VALVE OPEN [■] [■]
[ ] NEMA 4X (UNPAINTED 316 STAINLESS
GAS DETECTION [■] [■]
LOW SUCTION PRESSURE
STEEL) $9600
[■] [■]
LOW FIREWATER PRESSURE [■] [■]
[ ] NEMA 4X (UNPAINTED 316
LOW PURGE PRESSURE [■] [■] STAINLESS STEEL) (Oversized
HIGH GEAR OIL TEMP [■] [■] Enclosure, denoted by asterisk (*) on
LOW GEAR OIL PRESSURE [■] [■] page 1) $14666
HIGH VIBRATION [■] [■] [ ] NEMA 4X (316 PAINTED STAINLESS STEEL)
EMERGENCY POWER ON [■] [■] CONSULT FACTORY
PUMP ROOM DOOR OPEN [■] [■] [ ] NEMA 12 $50
Maximum number of additional Alarms is 12
[ ] REMOVABLE GLAND PLATE (one plate
for controller section and one plate for
Maximum Number of contacts, including
default contacts, can not exceed 9. Each transfer switch section) $500
Alarm Condition can have a maximum 3 [ ] PURGE SYSTEM, Type Z System, per
contacts. NFPA 496 suitable for Class I, Division 2,
Group C/D CONSULT FACTORY
OPTIONS
[ ]H SPACE HEATER
[ ] WITH THERMOSTAT $320 PLUMBING
[ ] WITH HUMIDISTAT $320 [ ] 300 PSI FOR FRESH WATER STANDARD
[ ]W OMIT LEGS, WITH 3" (76.2 mm) [ ] 600 PSI FOR FRESH WATER $120
CHANNELS N/C [ ] 300 PSI STAINLESS STEEL FOR
[ ] EXPORT CRATING – SUITABLE FOR SALTWATER/FOAM $670
BELOW DECK STORAGE $1659 [ ] 600 PSI STAINLESS STEEL FOR
[ ] PUMP ROOM TEMPERATURE SALTWATER/FOAM $790
THERMOSTAT MOUNTED ON
EXTERIOR OF ENCLOSURE
[ ] NEMA 2 RATED $42
[ ] NEMA 4 RATED $160

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP400 PRIMARY RESISTANCE
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH
Model Options Hp Volts Withstand Transfer Switch Size
MP400 MTS-

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 23,210 23,210 23,210 23,210 23,210 ‡
20 23,210 23,210 23,210 23,210 23,210 ‡
25 23,210 23,210 23,210 23,210 23,210 ‡
30 23,430 23,210 23,210 23,210 23,210 ‡
40 25,270 25,270 23,290 23,290 23,290 ‡
50 25,990 25,310 23,330 23,330 23,330 ‡
60 27,290 27,290 25,330 25,110 25,110 ‡
75 27,690 27,310 25,350 25,350 25,130‡
100 31,500 31,500 29,230 26,370 26,370 ‡
125 44,410 37,720 25,600 29,230 28,550 ‡
150 45,330 45,330 33,920 30,150 30,150 ‡
200 54,530 * ‡ 45,930 39,980 33,920 31,130‡
250 56,730 * ‡ 56,730 * ‡ 46,670 39,980 39,980 ‡
300 70,955 * ‡ 47,370 47,370 40,680‡
350 59,250 * ‡ 50,190 43,500‡
400 50,190 50,190 ‡
500 62,150 * ‡
600 78,975 * ‡
700

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL 575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL 200-480VAC STD
[C] 100,000 AMPS RMS SYMMETRICAL 200-480VAC STD

Normal Power Source and Alternate Power Source Withstand Rating


Value is the same as value indicated above

Horsepower Voltage
200 208 220/240 380/415 440/480 550/600
15 100A 100A 100A 100A 100A 100A
20 100A 100A 100A 100A 100A 100A
25 100A 100A 100A 100A 100A 100A
30 150A 150A 100A 100A 100A 100A
40 150A 150A 150A 100A 100A 100A
50 225A 225A 150A 100A 100A 100A
60 225A 225A 225A 150A 100A 100A
75 260A 260A 225A 150A 150A 100A
100 400A 400A 400A 225A 150A 150A
125 600A 600A 400A 225A 225A 150A
150 600A 600A 600A 400A 225A 225A
200 800A 800A 600A 400A 400A 260A
250 800A 800A 800A 600A 400A 400A
300 1000A 1000A 1000A 600A 600A 400A
350 800A 600A 400A
Effective January 1, 2011 / Cat v11 400 600A 600A
Prices subject to change without notice 500 800A
‡ Available with “B” Breaker only 600 1000A
* Oversized Enclosure 700

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP400 PRIMARY RESISTANCE
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH

STANDARD FEATURE SELECTION [ ] LOW SUCTION CUT OFF PRESSURE


Price of controller includes the following local visual SWITCH (externally mounted) $500
LED indications: Power On, Phase Reversal, [ ] MODBUS COMMUNICATION via RS485
System Fault, Transfer Switch in Normal, Transfer STANDARD
Switch in Emergency, Emergency Isolation Switch
ENCLOSURES
Open, and Test Operation.
[ ] NEMA 2 STANDARD
Standard Default Volt Free (Dry) Contacts include:
[ ] NEMA 3R $750
Power Available, Phase Reversal, Pump Running,
[ ] NEMA 3R (Oversized Enclosure, denoted
and Controller not in Auto.
by asterisk (*) on page 1) $1280
In addition to the above LED indications a
[ ] NEMA 4 $2400
maximum of twelve (12) user specified alarm
[ ] NEMA 4 (Oversized Enclosure, denoted
conditions can be displayed on the Liquid Crystal
by asterisk (*) on page 1) $4400
Display (LCD) display of the Operator Interface
[ ] NEMA 4X PAINTED STEEL $3200
Display (OID). A maximum of nine (9) additional
[ ] NEMA 4X PAINTED STEEL (Oversized
volt free (dry) contacts can be added. Below is a
Enclosure, denoted by asterisk (*) on
list of possible alarm conditions. Consult factory for
page 1) $5200
alarm conditions not listed.
Quantity
[ ] NEMA 4X (UNPAINTED 304
Alarm Dry of STAINLESS STEEL) $5334
Displayed Cont Contacts [ ] NEMA 4X (UNPAINTED 304
Description on OID acts Required
LOW PUMP ROOM TEMP [Ŷ] [Ŷ] STAINLESS STEEL) (Oversized
RESERVOIR LOW [Ŷ] [Ŷ] Enclosure, denoted by asterisk (*) on
RESERVOIR EMPTY [Ŷ] [Ŷ] page 1) $8000
RESERVOIR HIGH [Ŷ] [Ŷ] [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
FLOW METER ON [Ŷ] [Ŷ] CONSULT FACTORY
RELIEF VALVE OPEN [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
GAS DETECTION [Ŷ] [Ŷ] STEEL) $9600
LOW SUCTION PRESSURE [Ŷ] [Ŷ] [ ] NEMA 4X (UNPAINTED 316
LOW FIREWATER PRESSURE [Ŷ] [Ŷ] STAINLESS STEEL) (Oversized
LOW PURGE PRESSURE [Ŷ] [Ŷ] Enclosure, denoted by asterisk (*) on
HIGH GEAR OIL TEMP [Ŷ] [Ŷ] page 1) $14666
LOW GEAR OIL PRESSURE [Ŷ] [Ŷ] [ ] NEMA 4X (316 PAINTED STAINLESS
HIGH VIBRATION [Ŷ] [Ŷ] STEEL)
EMERGENCY POWER ON [Ŷ] [Ŷ] CONSULT FACTORY
PUMP ROOM DOOR OPEN [Ŷ] [Ŷ] [ ] NEMA 12 $50
Note: Resistor Bank Enclosure Maximum Rating is NEMA 3R when NEMA 4, 4X or 12 Enclosure is supplied
Maximum number of additional Alarms is 12
[ ] REMOVABLE GLAND PLATE (one plate
Maximum Number of contacts, including
default contacts, can not exceed 9. Each
for controller section and one plate for
Alarm Condition can have a maximum 3 transfer switch section) $500
contacts. [ ] PURGE SYSTEM, Type Z System, per
NFPA 496 suitable for Class I, Division
OPTIONS
2, Group C/D CONSULT FACTORY
[ ] H SPACE HEATER
[ ] WITH THERMOSTAT $320
PLUMBING
[ ] WITH HUMIDISTAT $320
[ ] 300 PSI FOR FRESH WATER STANDARD
[ ] W OMIT LEGS, WITH 3" CHANNELS N/C
[ ] 600 PSI FOR FRESH WATER $120
[ ] EXPORT CRATING – SUITABLE FOR
[ ] 300 PSI STAINLESS STEEL FOR
BELOW DECK STORAGE $1659
SALTWATER/FOAM $670
[ ] PUMP ROOM TEMPERATURE
[ ] 600 PSI STAINLESS STEEL FOR
THERMOSTAT MOUNTED ON
SALTWATER/FOAM $790
EXTERIOR OF ENCLOSURE
[ ] NEMA 2 RATED $42
[ ] NEMA 4 RATED $160

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP420 PART WINDING
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH
Model Options Hp Volts Withstand Transfer Switch Size
MP420 MTS-

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 22,630 22,630 22,630 22,630 22,630 ‡
20 22,630 22,630 22,630 22,630 22,630 ‡
25 22,630 22,630 22,630 22,630 22,630 ‡
30 22,850 22,630 22,630 22,630 22,630 ‡
40 24,270 24,270 22,930 22,630 22,630 ‡
50 24,950 24,270 22,930 22,930 22,930 ‡
60 26,290 26,290 24,270 24,050 24,050 ‡
75 26,670 26,290 24,270 24,270 24,050 ‡
100 30,700 30,700 26,290 25,610 25,610 ‡
125 41,410 34,720 26,290 26,290 25,610 ‡
150 41,410 41,410 31,400 26,290 26,290 ‡
200 52,510 * ‡ 43,910 31,400 31,400 28,610 ‡
250 54,670 * ‡ 54,670 * ‡ 41,410 34,720 34,720 ‡
300 69,555* ‡ 69,555 * ‡ 41,410 41,410 34,720 ‡
350 50,010 * ‡ 41,410 34,720 ‡
400 53,010 * ‡ 43,910 43,910 ‡
500 67,955 * ‡ 55,950 * ‡
600 76,215 * ‡ 70,995 * ‡
700 74,515 * ‡

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL 575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL 200-480VAC STD
[C] 100,000 AMPS RMS SYMMETRICAL 200-480VAC STD

Normal Power Source and Alternate Power Source Withstand Rating


Value is the same as value indicated above

Horsepower Voltage
200 208 220/240 380/415 440/480 550/600
15 100A 100A 100A 100A 100A 100A
20 100A 100A 100A 100A 100A 100A
25 100A 100A 100A 100A 100A 100A
30 150A 150A 100A 100A 100A 100A
40 150A 150A 150A 100A 100A 100A
50 225A 225A 150A 100A 100A 100A
60 225A 225A 225A 150A 100A 100A
75 260A 260A 225A 150A 150A 100A
100 400A 400A 400A 225A 150A 150A
125 600A 600A 400A 225A 225A 150A
150 600A 600A 600A 400A 225A 225A
200 800A 800A 600A 400A 400A 260A
250 800A 800A 800A 600A 400A 400A
300 1000A 1000A 1000A 600A 600A 400A
350 800A 600A 400A
Effective January 1, 2011 / Cat v11 400 800A 600A 600A
Prices subject to change without notice 500 1000A 800A
‡ Available with “B” Breaker only 600 1200A 1000A
* Oversized Enclosure 700 1000A

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP420 PART WINDING
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH

STANDARD FEATURE SELECTION [ ] LOW SUCTION CUT OFF PRESSURE


Price of controller includes the following local visual SWITCH (externally mounted) $500
LED indications: Power On, Phase Reversal, [ ] MODBUS COMMUNICATION via RS485
System Fault, Transfer Switch in Normal, Transfer STANDARD
Switch in Emergency, Emergency Isolation Switch
ENCLOSURES
Open, and Test Operation.
[ ] NEMA 2 STANDARD
Standard Default Volt Free (Dry) Contacts include:
[ ] NEMA 3R $750
Power Available, Phase Reversal, Pump Running,
[ ] NEMA 3R (Oversized Enclosure, denoted
and Controller not in Auto.
by asterisk (*) on page 1) $1280
In addition to the above LED indications a
[ ] NEMA 4 $2400
maximum of twelve (12) user specified alarm
[ ] NEMA 4 (Oversized Enclosure, denoted
conditions can be displayed on the Liquid Crystal
by asterisk (*) on page 1) $4400
Display (LCD) display of the Operator Interface
[ ] NEMA 4X PAINTED $3200
Display (OID). A maximum of nine (9) additional
[ ] NEMA 4X PAINTED STEEL $3200
volt free (dry) contacts can be added. Below is a
[ ] NEMA 4X PAINTED STEEL (Oversized
list of possible alarm conditions. Consult factory for
Enclosure, denoted by asterisk (*) on
alarm conditions not listed.
Quantity page 1) $5200
Alarm Dry of [ ] NEMA 4X (UNPAINTED 304
Displayed Cont Contacts STAINLESS STEEL) $5334
Description on OID acts Required
LOW PUMP ROOM TEMP [■] [■] [ ] NEMA 4X (UNPAINTED 304
RESERVOIR LOW [■] [■] STAINLESS STEEL) (Oversized
RESERVOIR EMPTY [■] [■] Enclosure, denoted by asterisk (*) on
RESERVOIR HIGH [■] [■] page 1) $8000
FLOW METER ON [■] [■] [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
RELIEF VALVE OPEN [■] [■] CONSULT FACTORY
GAS DETECTION [■] [■] [ ] NEMA 4X (UNPANTED 316 STAINLESS
LOW SUCTION PRESSURE [■] [■] STEEL) $9600
LOW FIREWATER PRESSURE [■] [■] [ ] NEMA 4X (UNPAINTED 316
LOW PURGE PRESSURE [■] [■] STAINLESS STEEL) (Oversized
HIGH GEAR OIL TEMP [■] [■] Enclosure, denoted by asterisk (*) on
LOW GEAR OIL PRESSURE [■] [■] page 1) $14666
HIGH VIBRATION [■] [■] [ ] NEMA 4X (316 PAINTED STAINLESS
EMERGENCY POWER ON [■] [■] STEEL)
PUMP ROOM DOOR OPEN [■] [■] CONSULT FACTORY
Maximum number of additional Alarms is 12 [ ] NEMA 12 $50
Maximum Number of contacts, including [ ] REMOVABLE GLAND PLATE (one plate
default contacts, can not exceed 9. Each for controller section and one plate for
Alarm Condition can have a maximum 3
contacts. transfer switch section) $500
[ ] PURGE SYSTEM, Type Z System, per
OPTIONS NFPA 496 suitable for Class I, Division 2,
[ ]H SPACE HEATER Group C/D CONSULT FACTORY
[ ] WITH THERMOSTAT $320
[ ] WITH HUMIDISTAT $320 PLUMBING
[ ]W OMIT LEGS, WITH 3" (76.2 mm) [ ] 300 PSI FOR FRESH WATER STANDARD
CHANNELS N/C [ ] 600 PSI FOR FRESH WATER $120
[ ] EXPORT CRATING – SUITABLE FOR [ ] 300 PSI STAINLESS STEEL FOR
BELOW DECK STORAGE $1659 SALTWATER/FOAM $670
[ ] PUMP ROOM TEMPERATURE [ ] 600 PSI STAINLESS STEEL FOR
THERMOSTAT MOUNTED ON SALTWATER/FOAM $79
EXTERIOR OF ENCLOSURE
[ ] NEMA 2 RATED $42
[ ] NEMA 4 RATED $160

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP430 WYE-DELTA OPEN TRANSITION
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH
Model Options Hp Volts Withstand Transfer Switch Size
MP430 MTS-

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 22,890 22,890 22,890 22,890 22,890 ‡
20 22,890 22,890 22,890 22,890 22,890 ‡
25 22,890 22,890 22,890 22,890 22,890 ‡
30 23,110 22,890 22,890 22,890 22,890 ‡
40 24,660 24,660 23,130 23,130 23,130‡
50 25,810 25,130 23,130 23,130 23,130 ‡
60 27,150 27,150 24,660 24,440 24,440 ‡
75 27,530 27,150 24,660 24,660 24,440 ‡
100 31,440 31,440 26,850 26,170 26,170 ‡
125 42,430 35,740 27,930 27,930 27,250 ‡
150 42,430 42,430 31,740 27,930 27,930‡
200 53,890 * ‡ 44,930 32,340 32,340 31,290 ‡
250 53,890 * ‡ 56,060 * ‡ 42,430 35,740 35,740 ‡
300 69,755 * ‡ 69,755 * ‡ 45,530 43,030 36,340 ‡
350 54,180 * ‡ 45,530 38,840 ‡
400 56,060 * ‡ 45,530 45,530 ‡
500 70,065 * ‡ 58,060* ‡
600 77,535 * ‡ 72,615* ‡
700 76,635 * ‡

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL 575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL 200-480VAC STD
[C] 100,000 AMPS RMS SYMMETRICAL 200-480VAC STD

Normal Power Source and Alternate Power Source Withstand Rating


Value is the same as value indicated above

Horsepower Voltage
200 208 220/240 380/415 440/480 550/600
15 100A 100A 100A 100A 100A 100A
20 100A 100A 100A 100A 100A 100A
25 100A 100A 100A 100A 100A 100A
30 150A 150A 100A 100A 100A 100A
40 150A 150A 150A 100A 100A 100A
50 225A 225A 150A 100A 100A 100A
60 225A 225A 225A 150A 100A 100A
75 260A 260A 225A 150A 150A 100A
100 400A 400A 400A 225A 150A 150A
125 600A 600A 400A 225A 225A 150A
150 600A 600A 600A 400A 225A 225A
200 800A 800A 600A 400A 400A 260A
250 800A 800A 800A 600A 400A 400A
300 1000A 1000A 1000A 600A 600A 400A
350 800A 600A 400A
Effective January 1, 2011 / Cat v11 400 800A 600A 600A
Prices subject to change without notice 500 1000A 800A
‡ Available with “B” Breaker only 600 1200A 1000A
* Oversized Enclosure 700 1000A

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP430 WYE-DELTA OPEN TRANSITION
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH

STANDARD FEATURE SELECTION [ ] PUMP ROOM TEMPERATURE


Price of controller includes the following local visual THERMOSTAT MOUNTED ON
LED indications: Power On, Phase Reversal, EXTERIOR OF ENCLOSURE
System Fault, Transfer Switch in Normal, Transfer [ ] NEMA 2 RATED $42
Switch in Emergency, Emergency Isolation Switch [ ] NEMA 4 RATED $160
Open, and Test Operation. [ ] LOW SUCTION CUT OFF PRESSURE
Standard Default Volt Free (Dry) Contacts include: SWITCH (externally mounted) $500
Power Available, Phase Reversal, Pump Running, [ ] MODBUS COMMUNICATION via RS485
and Controller not in Auto. STANDARD
In addition to the above LED indications a ENCLOSURES
maximum of twelve (12) user specified alarm [ ] NEMA 2 STANDARD
conditions can be displayed on the Liquid Crystal [ ] NEMA 3R $750
Display (LCD) display of the Operator Interface [ ] NEMA 3R (Oversized Enclosure, denoted
Display (OID). A maximum of nine (9) additional by asterisk (*) on page 1) $1280
volt free (dry) contacts can be added. Below is a [ ] NEMA 4 $2400
list of possible alarm conditions. Consult factory for [ ] NEMA 4 (Oversized Enclosure, denoted
alarm conditions not listed. by asterisk (*) on page 1) $4400
Quantity [ ] NEMA 4X PAINTED STEEL $3200
Alarm Dry of
Displayed Cont Contacts [ ] NEMA 4X PAINTED STEEL (Oversized
Description on OID acts Required Enclosure, denoted by asterisk (*) on
LOW PUMP ROOM TEMP [■] [■] page 1) $5200
RESERVOIR LOW [■] [■] [ ] NEMA 4X (UNPAINTED 304
RESERVOIR EMPTY [■] [■] STAINLESS STEEL) $5334
RESERVOIR HIGH [■] [■] [ ] NEMA 4X (UNPAINTED 304
FLOW METER ON [■] [■] STAINLESS STEEL) (Oversized
RELIEF VALVE OPEN [■] [■]
Enclosure, denoted by asterisk (*) on
GAS DETECTION [■] [■]
LOW SUCTION PRESSURE
page 1) $8000
[■] [■]
LOW FIREWATER PRESSURE [■] [■]
[ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
LOW PURGE PRESSURE [■] [■] CONSULT FACTORY
HIGH GEAR OIL TEMP [■] [■] [ ] NEMA 4X (UNPANTED 316 STAINLESS
LOW GEAR OIL PRESSURE [■] [■] STEEL) $9600
HIGH VIBRATION [■] [■] [ ] NEMA 4X (UNPAINTED 316
EMERGENCY POWER ON [■] [■] STAINLESS STEEL) (Oversized
PUMP ROOM DOOR OPEN [■] [■] Enclosure, denoted by asterisk (*) on
Maximum number of additional Alarms is 12
page 1) $14666
[ ] NEMA 4X (316 PAINTED STAINLESS
Maximum Number of contacts, including
default contacts, can not exceed 9. Each STEEL) CONSULT FACTORY
Alarm Condition can have a maximum 3 [ ] NEMA 12 $50
contacts. [ ] REMOVABLE GLAND PLATE (one plate
for controller section and one plate for
OPTIONS
[ ]H SPACE HEATER transfer switch section) $500
[ ] WITH THERMOSTAT $320 [ ] PURGE SYSTEM, Type Z System, per
[ ] WITH HUMIDISTAT $320 NFPA 496 suitable for Class I, Division 2,
[ ]W OMIT LEGS, WITH 3" (76.2 mm) Group C/D CONSULT FACTORY
CHANNELS N/C
[ ] EXPORT CRATING – SUITABLE FOR PLUMBING
BELOW DECK STORAGE $1659 [ ] 300 PSI FOR FRESH WATER STANDARD
[ ] 600 PSI FOR FRESH WATER $120
[ ] 300 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $670
[ ] 600 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $790

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP435 WYE-DELTA CLOSED TRANSITION
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH
Model Options Hp Volts Withstand Transfer Switch Size
MP435 MTS-

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 24,990 24,990 25,290 25,290 25,290 ‡
20 24,990 24,990 25,290 25,290 25,290 ‡
25 24,990 24,990 25,290 25,290 25,290 ‡
30 25,610 25,390 25,290 25,290 25,290 ‡
40 27,160 27,160 25,530 25,290 25,290 ‡
50 28,390 27,710 25,530 25,530 25,530 ‡
60 29,650 29,650 27,060 26,840 26,840 ‡
75 31,730 31,350 27,060 27,060 26,840 ‡
100 35,640 35,640 30,250 29,570 29,570 ‡
125 46,630 39,940 31,330 31,330 30,650 ‡
150 46,630 46,630 35,140 31,330 31,330 ‡
200 57,730 * ‡ 49,130 35,740 35,740 34,690 ‡
250 60,150 * ‡ 60,150 * ‡ 47,030 40,340 40,340 ‡
300 74,255 * ‡ 74,075 * ‡ 49,530 47,630 40,940 ‡
350 58,730 * ‡ 50,130 43,440 ‡
400 62,150 * ‡ 50,130 50,130 ‡
500 77,255 * ‡ 62,150 * ‡
600 85,895 * ‡ 77,255 * ‡
700 81,465 * ‡

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL 575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL 200-480VAC STD
[C] 100,000 AMPS RMS SYMMETRICAL 200-480VAC STD

Normal Power Source and Alternate Power Source Withstand Rating


Value is the same as value indicated above

Horsepower Voltage
200 208 220/240 380/415 440/480 550/600
15 100A 100A 100A 100A 100A 100A
20 100A 100A 100A 100A 100A 100A
25 100A 100A 100A 100A 100A 100A
30 150A 150A 100A 100A 100A 100A
40 150A 150A 150A 100A 100A 100A
50 225A 225A 150A 100A 100A 100A
60 225A 225A 225A 150A 100A 100A
75 260A 260A 225A 150A 150A 100A
100 400A 400A 400A 225A 150A 150A
125 600A 600A 400A 225A 225A 150A
150 600A 600A 600A 400A 225A 225A
200 800A 800A 600A 400A 400A 260A
250 800A 800A 800A 600A 400A 400A
300 1000A 1000A 1000A 600A 600A 400A
350 800A 600A 400A
Effective January 1, 2011 / Cat v11 400 800A 600A 600A
Prices subject to change without notice 500 1000A 800A
‡ Available with “B” Breaker only 600 1200A 1000A
* Oversized Enclosure 700 1000A

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP435 WYE-DELTA CLOSED TRANSITION
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH

STANDARD FEATURE SELECTION [ ] PUMP ROOM TEMPERATURE


Price of controller includes the following local visual THERMOSTAT MOUNTED ON
LED indications: Power On, Phase Reversal, EXTERIOR OF ENCLOSURE
System Fault, Transfer Switch in Normal, Transfer [ ] NEMA 2 RATED $42
Switch in Emergency, Emergency Isolation Switch [ ] NEMA 4 RATED $160
Open, and Test Operation. [ ] LOW SUCTION CUT OFF PRESSURE
Standard Default Volt Free (Dry) Contacts include: SWITCH (externally mounted) $500
Power Available, Phase Reversal, Pump Running, [ ] MODBUS COMMUNICATION via RS485
and Controller not in Auto. STANDARD
In addition to the above LED indications a ENCLOSURES
maximum of twelve (12) user specified alarm [ ] NEMA 2 STANDARD
conditions can be displayed on the Liquid Crystal [ ] NEMA 3R $750
Display (LCD) display of the Operator Interface [ ] NEMA 3R (Oversized Enclosure, denoted
Display (OID). A maximum of nine (9) additional by asterisk (*) on page 1) $1280
volt free (dry) contacts can be added. Below is a [ ] NEMA 4 $2400
list of possible alarm conditions. Consult factory for [ ] NEMA 4 (Oversized Enclosure, denoted
alarm conditions not listed. by asterisk (*) on page 1) $4400
Quantity [ ] NEMA 4X PAINTED STEEL $3200
Alarm Dry of
Displayed Cont Contacts [ ] NEMA 4X PAINTED STEEL (Oversized
Description on OID acts Required Enclosure, denoted by asterisk (*) on
LOW PUMP ROOM TEMP [■] [■] page 1) $5200
RESERVOIR LOW [■] [■] [ ] NEMA 4X (UNPAINTED 304
RESERVOIR EMPTY [■] [■] STAINLESS STEEL) $5334
RESERVOIR HIGH [■] [■] [ ] NEMA 4X (UNPAINTED 304
FLOW METER ON [■] [■] STAINLESS STEEL) (Oversized
RELIEF VALVE OPEN [■] [■]
Enclosure, denoted by asterisk (*) on
GAS DETECTION [■] [■]
LOW SUCTION PRESSURE
page 1) $8000
[■] [■]
LOW FIREWATER PRESSURE [■] [■]
[ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
LOW PURGE PRESSURE [■] [■] CONSULT FACTORY
HIGH GEAR OIL TEMP [■] [■] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
LOW GEAR OIL PRESSURE [■] [■] STEEL) $9600
HIGH VIBRATION [■] [■] [ ] NEMA 4X (UNPAINTED 316
EMERGENCY POWER ON [■] [■] STAINLESS STEEL) (Oversized
PUMP ROOM DOOR OPEN [■] [■] Enclosure, denoted by asterisk (*) on
Maximum number of additional Alarms is 12
page 1) $14666
[ ] NEMA 4X (316 PAINTED STAINLESS
Maximum Number of contacts, including
default contacts, can not exceed 9. Each STEEL) CONSULT FACTORY
Alarm Condition can have a maximum 3 [ ] NEMA 12 $50
contacts. Note: Resistor Bank Enclosure Maximum Rating is NEMA 3R when NEMA 4, 4X or 12 Enclosure is supplied

[ ] REMOVABLE GLAND PLATE (one plate


OPTIONS for controller section and one plate for
[ ]H SPACE HEATER transfer switch section) $500
[ ] WITH THERMOSTAT $320 [ ] PURGE SYSTEM, Type Z System, per
[ ] WITH HUMIDISTAT $320 NFPA 496 suitable for Class I, Division 2,
[ ]W OMIT LEGS, WITH 3" (76.2 mm) Group C/D CONSULT FACTORY
CHANNELS N/C PLUMBING
[ ] EXPORT CRATING – SUITABLE FOR [ ] 300 PSI FOR FRESH WATER STANDARD
BELOW DECK STORAGE $1659 [ ] 600 PSI FOR FRESH WATER $120
[ ] 300 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $670
[ ] 600 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $790

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP450 AUTOTRANSFORMER
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH
Model Options Hp Volts Withstand Transfer Switch Size
MP450 MTS-

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 27,450 27,450 27,450 27,450 27,450 ‡
20 27,450 27,450 27,450 27,450 27,450 ‡
25 27,450 27,450 27,450 27,450 27,450 ‡
30 27,670 27,450 27,450 27,450 27,450 ‡
40 29,750 29,750 27,450 27,450 27,450 ‡
50 30,430 29,750 27,450 27,450 27,450 ‡
60 32,550 32,550 29,750 29,530 29,530 ‡
75 32,930 32,550 29,750 29,750 29,530 ‡
100 37,460 37,460 32,550 29,750 29,750 ‡
125 49,990 43,300 32,550 32,550 31,870 ‡
150 49,990 49,990 33,980 32,550 32,550 ‡
200 58,590 * ‡ 49,990 43,300 33,980 32,930 ‡
250 62,070 * ‡ 62,070 * ‡ 49,990 43,300 43,300 ‡
300 76,595 * ‡ 49,990 49,990 43,300 ‡
350 62,070 * ‡ 55,710 49,020 ‡
400 55,710 55,710 ‡
500 69,150 * ‡
600 85,595 * ‡
700

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL 575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL 200-480VAC STD
[C] 100,000 AMPS RMS SYMMETRICAL 200-480VAC STD

Normal Power Source and Alternate Power Source Withstand Rating


Value is the same as value indicated above.

Horsepower Voltage
200 208 220/240 380/415 440/480 550/600
15 100A 100A 100A 100A 100A 100A
20 100A 100A 100A 100A 100A 100A
25 100A 100A 100A 100A 100A 100A
30 150A 150A 100A 100A 100A 100A
40 150A 150A 150A 100A 100A 100A
50 225A 225A 150A 100A 100A 100A
60 225A 225A 225A 150A 100A 100A
75 260A 260A 225A 150A 150A 100A
100 400A 400A 400A 225A 150A 150A
125 600A 600A 400A 225A 225A 150A
150 600A 600A 600A 400A 225A 225A
200 800A 800A 600A 400A 400A 260A
250 800A 800A 800A 600A 400A 400A
300 1000A 600A 600A 400A
350 800A 600A 400A
Effective January 1, 2011 / Cat v11 400 600A 600A
Prices subject to change without notice 500 800A
‡ Available with “B” Breaker only 600 1000A
* Oversized Enclosure 700

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP450 AUTOTRANSFORMER
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH

STANDARD FEATURE SELECTION [ ] PUMP ROOM TEMPERATURE


Price of controller includes the following local visual THERMOSTAT MOUNTED ON
LED indications: Power On, Phase Reversal, EXTERIOR OF ENCLOSURE
System Fault, Transfer Switch in Normal, Transfer [ ] NEMA 2 RATED $42
Switch in Emergency, Emergency Isolation Switch [ ] NEMA 4 RATED $160
Open, and Test Operation. [ ] LOW SUCTION CUT OFF PRESSURE
Standard Default Volt Free (Dry) Contacts include: SWITCH (externally mounted) $500
Power Available, Phase Reversal, Pump Running, [ ] MODBUS COMMUNICATION via RS485
and Controller not in Auto. STANDARD
In addition to the above LED indications a ENCLOSURES
maximum of twelve (12) user specified alarm [ ] NEMA 2 STANDARD
conditions can be displayed on the Liquid Crystal [ ] NEMA 3R $750
Display (LCD) display of the Operator Interface [ ] NEMA 3R (Oversized Enclosure, denoted
Display (OID). A maximum of nine (9) additional by asterisk (*) on page 1) $1280
volt free (dry) contacts can be added. Below is a [ ] NEMA 4 $2400
list of possible alarm conditions. Consult factory for [ ] NEMA 4 (Oversized Enclosure, denoted
alarm conditions not listed. by asterisk (*) on page 1) $4400
Quantity [ ] NEMA 4X PAINTED STEEL $3200
Alarm Dry of
Displayed Cont Contacts [ ] NEMA 4X PAINTED STEEL (Oversized
Description on OID acts Required Enclosure, denoted by asterisk (*) on
LOW PUMP ROOM TEMP [■] [■] page 1) $5200
RESERVOIR LOW [■] [■] [ ] NEMA 4X (UNPAINTED 304
RESERVOIR EMPTY [■] [■] STAINLESS STEEL) $5334
RESERVOIR HIGH [■] [■] [ ] NEMA 4X (UNPAINTED 304
FLOW METER ON [■] [■] STAINLESS STEEL) (Oversized
RELIEF VALVE OPEN [■] [■]
Enclosure, denoted by asterisk (*) on
GAS DETECTION [■] [■]
LOW SUCTION PRESSURE
page 1) $8000
[■] [■]
LOW FIREWATER PRESSURE [■] [■]
[ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
LOW PURGE PRESSURE [■] [■] CONSULT FACTORY
HIGH GEAR OIL TEMP [■] [■] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
LOW GEAR OIL PRESSURE [■] [■] STEEL) $9600
HIGH VIBRATION [■] [■] [ ] NEMA 4X (UNPAINTED 316
EMERGENCY POWER ON [■] [■] STAINLESS STEEL) (Oversized
PUMP ROOM DOOR OPEN [■] [■] Enclosure, denoted by asterisk (*) on
Maximum number of additional Alarms is 12
page 1) $14666
[ ] NEMA 4X (316 PAINTED STAINLESS
Maximum Number of contacts, including
default contacts, can not exceed 9. Each STEEL) CONSULT FACTORY
Alarm Condition can have a maximum 3 [ ] NEMA 12 $50
contacts. [ ] REMOVABLE GLAND PLATE (one plate
for controller section and one plate for
OPTIONS
[ ]H SPACE HEATER transfer switch section) $500
[ ] WITH THERMOSTAT $320 [ ] PURGE SYSTEM, Type Z System, per
[ ] WITH HUMIDISTAT $320 NFPA 496 suitable for Class I, Division 2,
[ ]W OMIT LEGS, WITH 3" (76.2 mm) Group C/D CONSULT FACTORY
CHANNELS N/C
[ ] EXPORT CRATING – SUITABLE FOR PLUMBING
BELOW DECK STORAGE $1659 [ ] 300 PSI FOR FRESH WATER STANDARD
[ ] 600 PSI FOR FRESH WATER $120
[ ] 300 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $670
[ ] 600 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $790

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP700 SOLID STATE REDUCED VOLTAGE
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH

Model Options Hp Volts Withstand Transfer Switch Size


MP700 MTS-

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 27,010 27,010 27,010 27,010 27,010 ‡
20 27,010 27,010 27,010 27,010 27,010 ‡
25 28,110 28,110 27,010 27,010 27,010 ‡
30 28,330 28,110 27,010 27,010 27,010 ‡
40 29,430 29,430 27,010 27,010 27,010 ‡
50 30,260 29,580 29,360 27,010 27,010 ‡
60 31,010 31,010 29,430 29,210 29,210 ‡
75 32,690 32,310 29,430 29,430 29,210 ‡
100 36,840 36,840 30,430 29,750 29,750 ‡
125 49,530 42,840 32,110 32,110 31,430 ‡
150 49,230 49,230 33,540 32,110 32,110 ‡
200 58,330 * ‡ 49,730 43,040 34,140 33,090 ‡
250 61,830 * ‡ 61,830 * ‡ 49,730 43,040 43,040 ‡
300 76,135 * ‡ 49,990 49,990 43,300 ‡
350 64,130 * ‡ 54,430 47,740 ‡
400 54,430 54,430 ‡
500 66,250 * ‡
600 82,135 * ‡
700

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL 575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL 200-480VAC STD
[C] 100,000 AMPS RMS SYMMETRICAL 200-480VAC STD

Normal Power Source and Alternate Power Source Withstand Rating


Value is the same as value indicated above

Horsepower Voltage
200 208 220/240 380/415 440/480 550/600
15 100A 100A 100A 100A 100A 100A
20 100A 100A 100A 100A 100A 100A
25 100A 100A 100A 100A 100A 100A
30 150A 150A 100A 100A 100A 100A
40 150A 150A 150A 100A 100A 100A
50 225A 225A 150A 100A 100A 100A
60 225A 225A 225A 150A 100A 100A
75 260A 260A 225A 150A 150A 100A
100 400A 400A 400A 225A 150A 150A
125 600A 600A 400A 225A 225A 150A
150 600A 600A 600A 400A 225A 225A
200 800A 800A 600A 400A 400A 260A
250 800A 800A 800A 600A 400A 400A
300 1000A 600A 600A 400A
350 800A 600A 400A
Effective January 1, 2011 / Cat v11 400 600A 600A
Prices subject to change without notice 500 800A
‡ Available with “B” Breaker only 600 1000A
* Oversized Enclosure 700

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP700 SOLID STATE REDUCED VOLTAGE
FULL SERVICE FIRE PUMP CONTROLLER WITH TRANSFER SWITCH

STANDARD FEATURE SELECTION [ ] PUMP ROOM TEMPERATURE


Price of controller includes the following local visual THERMOSTAT MOUNTED ON
LED indications: Power On, Phase Reversal, EXTERIOR OF ENCLOSURE
System Fault, Transfer Switch in Normal, Transfer [ ] NEMA 2 RATED $42
Switch in Emergency, Emergency Isolation Switch [ ] NEMA 4 RATED $160
Open, and Test Operation. [ ] LOW SUCTION CUT OFF PRESSURE
Standard Default Volt Free (Dry) Contacts include: SWITCH (externally mounted) $500
Power Available, Phase Reversal, Pump Running, [ ] MODBUS COMMUNICATION via RS485
and Controller not in Auto. STANDARD
In addition to the above LED indications a
ENCLOSURES
maximum of twelve (12) user specified alarm
[ ] NEMA 3R $750
conditions can be displayed on the Liquid Crystal
[ ] NEMA 3R (Oversized Enclosure, denoted
Display (LCD) display of the Operator Interface
by asterisk (*) on page 1) $1280
Display (OID). A maximum of nine (9) additional
[ ] NEMA 4 $2400
volt free (dry) contacts can be added. Below is a
[ ] NEMA 4 (Oversized Enclosure, denoted
list of possible alarm conditions. Consult factory for
by asterisk (*) on page 1) $4400
alarm conditions not listed.
Quantity
[ ] NEMA 4X PAINTED STEEL $3200
Alarm Dry of [ ] NEMA 4X PAINTED STEEL (Oversized
Displayed Cont Contacts Enclosure, denoted by asterisk (*) on
Description on OID acts Required
LOW PUMP ROOM TEMP [■] [■] page 1) $5200
RESERVOIR LOW [■] [■] [ ] NEMA 4X (UNPAINTED 304
RESERVOIR EMPTY [■] [■] STAINLESS STEEL) $5334
RESERVOIR HIGH [■] [■] [ ] NEMA 4X (UNPAINTED 304
FLOW METER ON [■] [■] STAINLESS STEEL) (Oversized
RELIEF VALVE OPEN [■] [■] Enclosure, denoted by asterisk (*) on
GAS DETECTION [■] [■] page 1) $8000
LOW SUCTION PRESSURE [■] [■] [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
LOW FIREWATER PRESSURE [■] [■] CONSULT FACTORY
LOW PURGE PRESSURE [■] [■] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
HIGH GEAR OIL TEMP [■] [■] STEEL) $9600
LOW GEAR OIL PRESSURE [■] [■] [ ] NEMA 4X (UNPAINTED 316
HIGH VIBRATION [■] [■] STAINLESS STEEL) (Oversized
EMERGENCY POWER ON [■] [■] Enclosure, denoted by asterisk (*) on
PUMP ROOM DOOR OPEN [■] [■] page 1) $14666
Maximum number of additional Alarms is 12 [ ] NEMA 4X (316 PAINTED STAINLESS
Maximum Number of contacts, including STEEL)
default contacts, can not exceed 9. Each CONSULT FACTORY
Alarm Condition can have a maximum 3
contacts. [ ] NEMA 12 $50
[ ] REMOVABLE GLAND PLATE (one plate
OPTIONS for controller section and one plate for
[ ]H SPACE HEATER transfer switch section) $500
[ ] WITH THERMOSTAT $320 [ ] PURGE SYSTEM, Type Z System, per
[ ] WITH HUMIDISTAT $320 NFPA 496 suitable for Class I, Division 2,
[ ]W OMIT LEGS, WITH 3" (76.2 mm) Group C/D CONSULT FACTORY
CHANNELS N/C PLUMBING
[ ] EXPORT CRATING – SUITABLE FOR [ ] 300 PSI FOR FRESH WATER STANDARD
BELOW DECK STORAGE $1659 [ ] 600 PSI FOR FRESH WATER $120
[ ] 300 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $670
[ ] 600 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $790

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP800 VARIABLE FREQUENCY DRIVE DUAL UTILITY TRANSFER
FULL SERVICE FIRE PUMP CONTROLLER

Model Bypass Hp Volts Withstand


MP800 300

Across The Line Start W/ Dual


Utility Transfer Switch

Horsepower Voltage
200/208 220/240 380/415 440/480
15 † † † †
20 † † † †
25 † † † †
30 † † † †
40 63,840 61,870 61,400 60,020
50 69,880 66,760 64,870 63,350
60 72,020 71,420 69,780 66,820
75 82,680 77,350 75,180 70,190
100 95,840 86,470 82,680 79,460
125 123,040 97,200 91,800 85,610
150 † † 97,890 91,800
200 † † 105,290 99,360
250 † † 125,810 105,530
300 † † 132,730
350 † 137,630
400 † †
500 †
600
700

WITHSTAND RATING
[C]
100,000 AMPS RMS SYMMETRICAL 200-480VAC
Effective January 1, 2011 / Cat v11
† Consult factory for price

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP800 VARIABLE FREQUENCY DRIVE DUAL UTILITY TRANSFER
FULL SERVICE FIRE PUMP CONTROLLER

Model Bypass Hp Volts Withstand


MP800 450

Autotransformer Closed
Transition Start W/ Dual
Utility Transfer Switch

Horsepower Voltage
200/208 220/240 380/415 440/480
15 † † † †
20 † † † †
25 † † † †
30 † † † †
40 67,240 65,270 64,590 63,210
50 73,850 70,730 68,060 66,540
60 76,160 75,560 73,180 70,220
75 88,840 83,150 78,580 73,590
100 102,710 93,340 87,380 85,310
125 131,590 105,750 97,600 91,410
150 † † 105,960 97,600
200 † † 114,900 105,560
250 † † 135,420 143,090
300 † † 147,950
350 † 151,310
400 † †
500 †
600
700

WITHSTAND RATING
[C]
100,000 AMPS RMS SYMMETRICAL 200-480VAC
Effective January 1, 2011 / Cat v11
† Consult factory for price

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP800 VARIABLE FREQUENCY DRIVE DUAL UTILITY TRANSFER
FULL SERVICE FIRE PUMP CONTROLLER

Model Bypass Hp Volts Withstand


MP800 700

Solid State Soft Start Bypass


W/ Dual
Utility Transfer Switch

Horsepower Voltage
200/208 220/240 380/415 440/480
15 † † † †
20 † † † †
25 † † † †
30 † † † †
40 70,480 68,510 66,790 65,410
50 76,700 73,580 72,640 68,740
60 78,490 77,890 76,420 73,460
75 90,550 85,220 81,820 76,830
100 105,200 95,830 88,520 86,450
125 135,740 109,900 99,460 93,270
150 † † 105,550 99,460
200 † † 118,200 105,800
250 † † 138,720 118,440
300 † † 145,920
350 † 152,540
400 † †
500 †
600
700

WITHSTAND RATING
[C]
100,000 AMPS RMS SYMMETRICAL 200-480VAC
Effective January 1, 2011 / Cat v11
† Consult factory for price

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP800 VARIABLE FREQUENCY DRIVE
FULL SERVICE FIRE PUMP CONTROLLER

[ ] PURGE SYSTEM, Type Z System, per


NFPA 496 suitable for Class I, Division 2,
BYPASS METHODS: Group C/D
[ ] 300 – ACROSS THE LINE PLUMBING
[ ] 450 – AUTO-TRANSFORMER [ ] 300 PSI FOR FRESH WATER STANDARD
[ ] 700 – SOFT START/STOP [ ] 600 PSI FOR FRESH WATER
[ ] 300 PSI STAINLESS STEEL FOR
OPTIONS SALTWATER/FOAM
[ ]H SPACE HEATER [ ] 600 PSI STAINLESS STEEL FOR
[ ] WITH THERMOSTAT SALTWATER/FOAM
[ ] WITH HUMIDISTAT
[ ]W OMIT LEGS, WITH 3" (76.2 mm)
CHANNELS
[ ] EXPORT CRATING – SUITABLE FOR
BELOW DECK STORAGE
[ ] PUMP ROOM TEMPERATURE
THERMOSTAT MOUNTED ON
EXTERIOR OF ENCLOSURE
[ ] NEMA 2 RATED
[ ] NEMA 4 RATED
[ ] LOW SUCTION CUT OFF PRESSURE
SWITCH (externally mounted)
[ ] MODBUS COMMUNICATION via RS485
ENCLOSURES

[ ] NEMA 3R
[ ] NEMA 3R (Oversized Enclosure,
denoted by asterisk (*) on page 1)
[ ] NEMA 4
[ ] NEMA 4 (Oversized Enclosure, denoted
by asterisk (*) on page 1)
[ ] NEMA 4X PAINTED STEEL
[ ] NEMA 4X PAINTED STEEL (Oversized
Enclosure, denoted by asterisk (*) on
page 1)
[ ] NEMA 4X (PAINTED 304 STAINLESS
STEEL)
[ ] NEMA 4X (PAINTED 304 STAINLESS
STEEL) (Oversized Enclosure, denoted
by asterisk (*) on page 1)
[ ] NEMA 4X (304 STAINLESS STEEL)
[ ] NEMA 4X (PAINTED 316 STAINLESS
STEEL)
[ ] NEMA 4X (PAINTED 316 STAINLESS
STEEL) (Oversized Enclosure, denoted
by asterisk (*) on page 1)
[ ] NEMA 4X (316 STAINLESS STEEL)
[ ] NEMA 12 STANDARD
[ ] REMOVABLE GLAND PLATE

Effective: January 1, 2011. Consult factory for current pricing.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Limited Service Controller
For Electric Motor Driven Pumps










Metron MTS Automatic Transfer Switches provide
operation of Limited Service Pump motors from an
alternate source of power when the normal source
fails. These transfer switches are a part of the
Limited Service pump controller; although mounted
in a separate compartment, they are factory
assembled, shipped and installed as a part of the
controller.
The combination Limited Service controller/ transfer
switch is listed by Underwriters Laboratories and
meets all the latest requirements of NFPA 20
Standard for Installation of Centrifugal Fire Pumps.
Use of this controller must be acceptable to the
authority having jurisdiction.
The MTS Automatic Transfer Switch is a
mechanically held double throw switch with a fast
acting drive mechanism. Operating coils are
momentarily energized from the source to which the
load is being transferred. The switch is interlocked
electrically and mechanically to prevent both
services from feeding the load at the same time.
The transfer switch is capable of manual (non-
electrical) operation.


Hubbell Industrial Controls, Inc.


Metron Fire Pump Control Division

MSC0212 v11
Standard and Optional Features

Auxiliary alarm functions displayed on the OID LCD


Standard Features screen
Operator Interface Device (OID) with LED Audible horn with silence feature for silencable
Annunciator and Digital Display alarms
Lamp test feature
Foreign languages selectable through the OID
Microprocessor based logic with real time/date clock
capable of running a minimum of 14 days without
AC power connected to controller
SD Memory card used to record pressure log, event
log, and auxiliary user programs. Pressure log is
stored in separate comma delimited ASCII text files
with each file containing data for one day. The SD
card is removable and can be read by any PC
equipped with an SD card reader.
Input and output status LED's provide visual
indication of each discrete input's or output's on/off
status
One RS485 Serial Port
MODBUS Communication Protocol via RS485 port
Service Entrance Rated
Automatic Transfer Switch: UL Listed for Fire Pump
NEMA Type 2 drip proof metal freestanding Service, sized at least 115% of motor full load
enclosure current and shall conform to all requirements of
Operator Interface Device (OID) with 4 lines by 20 NFPA 20 Chapter 10. It shall be installed in a
character display with large character backlit Liquid barriered compartment of the fire pump controller.
Crystal Display (LCD) capable of being read in both The complete assembly, controller and transfer
direct sunlight or dark lighting conditions switch, shall be shipped as a single unit.
10 pushbuttons for easy screen navigation, LED The Transfer Switch shall be supplied with a special
lamp test, alarm reset, controller test and horn circuit to prevent higher than normal starting
silencing currents when transferring from one source to the
Removable labels to allow for easy field language other. This circuit shall deactivate the fire pump
changes motor five (5) seconds prior to transfer in either
All controller settings are programmable through the direction.
OID. All features are enabled or disabled through Alternate Source Isolation Switch: Externally
the OID, no jumpers or external wires are needed operable, quick break type sized at least 115% of
which allows easy field modification motor full load current. Auxiliary contacts on the
The system status data is displayed on the OID. isolation switch shall be inter-wired with the engine
The displayed items include: System Pressure, start contacts to prevent starting of the engine
Phase to Phase (AB, BC, AC) Voltage, Phase should the isolation switch be in the open position.
Current (A, B, C), Current Time and Date, System Shall be front mounted and wired for ease of
Events and Notifications such as Remote Start, maintenance and allowing the unit to be mounted
Local Start etc., Number of Starts, Total Motor Run flush against a wall.
Hours, Time Remaining on Sequential Motor Start
and Motor Stop Timers, Status of Automatic Stop
Setting

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
HIGH VIBRATION
GAS DETECTION Options
EMERGENCY POWER ON Option H: Space Heater
PUMP ROOM DOOR AJAR If the ambient atmosphere is especially damp, a space
LOW INTAKE heater rated at 100 watts may be supplied to reduce
Data logging: moisture in the cabinet. A thermostat is supplied as standard
The controller includes two (2) separate data logs for storing with this option. A humidistat may be substituted if specified.
system data that is readable through the OID or copied to a Option T: Weekly Test Start Solenoid
computer equipped with an SD card reader. The 2 data logs In some cases it may be desirable to have the electric motor
are as follows: run at a preset time each week for approximately 30 minutes.
Pressure Log: The pressure log provides a continuous The controller includes a built in weekly test function. This
pressure record for 30 days. The pressure log samples shall option complements the standard function by simulating a
be time and date stamped and stored in a permanent non- loss of pressure. Simulation of pressure loss is
volatile SD memory card. The pressure log can be searched accomplished by opening a solenoid valve, which reduces
by each sample, by minute, or by hour through the OID. the system pressure below the starting pressure of the
controller.
Event Log: The event log will store up to 300 of the most
current events. These events can include, but are not limited Option W: Omit Legs
to, any of the following events/alarms: For systems where the controller is mounted on a common
PUMP RUNNING skid with the pump and motor, the legs of the controller may
POWER AVAILABLE be omitted, 3” (76.2mm) channels or wall mounting brackets
PHASE REVERSAL can be supplied. If specified, lifting eyes may also be
MOTOR OVERLOAD supplied.
REMOTE START Enclosure
LOCAL START The following NEMA type enclosures are also available: 3R,
PUMP ON DEMAND / FIRE CONDITION 4, 4X (Painted Cold Rolled Steel), 4X (304 or 316 Stainless
SYSTEM FAULT Steel), and 12
AUTO MODE
MANUAL MODE
OFF MODE MTS100A Power Transfer Switches
PRESSURE TRANSDUCER FAULT Motor HP Line Voltage Catalog Number
FAILED TO START 7.5-30 208-575 VAC / 3 Phase MTS100
LOW INTAKE SHUTDOWN 5-15 115-230 VAC / 1 Phase MTS100
SUPERVISORY POWER FAILURE
LOW PRESSURE
AUTO WEEKLY TEST START
UNDER FREQUENCY
OVER FREQUENCY
LOW ZONE / HIGH ZONE CONTACT
HIGH DISCHARGE PRESSURE
NO LOAD CONDITION
HIGH VOLTS
LOW VOLTS

MSC0212 v11
Limited Service Controller
For Electric Motor Driven Pumps
Model MP30 Limited Service Across-the-line Start Electric Motor Controller with Dual Utility Transfer Switch
load current and shall conform to all Pressure Log: The controller shall have a Pressure
Specifications requirements of NFPA 20 Chapter 10. It shall
be installed in a barriered compartment of the
log with continuous pressure recording of 30 days
of data. The pressure log samples shall be time and
The Limited Service Controller shall include the fire pump controller. The complete assembly, date stamped and stored on a removable SD card
following standard features: controller and transfer switch, shall be shipped memory. The pressure log shall be searchable by
NEMA Type 2 drip proof metal freestanding as a single unit. each sample, by minute, or by hour. Each days
enclosure The Transfer Switch shall be supplied with a entries shall be stored in a separate file on the SD
AUTO, MANUAL, TEST, and OFF mode special circuit to prevent higher than normal card. SD memory shall be readable by any PC
buttons illuminated with colored LED's for starting currents when transferring from one equipped with an SD memory card reader.
controller mode operation source to the other. This circuit shall deactivate
Event Log: The event log shall be capable of
Operator Interface Device (OID) with 4 lines by the fire pump motor five (5) seconds prior to
storing no less than 3000 events. These events
20 character display with large character backlit transfer in either direction.
shall include, but is not limited to, any of the
LCD capable of being read in both direct Alternate Source Isolation Switch: Externally
following events/alarms:
sunlight or dark lighting conditions operable, quick break type sized at least 115% of
PUMP RUNNING
10 pushbuttons for easy screen navigation, motor full load current. Auxiliary contacts on
POWER AVAILABLE
system test, lamp test, alarm reset, and horn the isolation switch shall be inter-wired with the
PHASE REVERSAL
silencing engine start contacts to prevent starting of the
MOTOR OVERLOAD
Multicolored LED's for alarm and mode engine should the isolation switch be in the open
REMOTE START
annunciation position. Shall be front mounted and wired for
LOCAL START
LEDs shall be labeled with removable labels to ease of maintenance and allowing the unit to be
PUMP ON DEMAND / FIRE CONDITION
allow for easy field modification if additional mounted flush against a wall.
SYSTEM FAULT
alarms and/or language changes Auxiliary alarms: AUTO MODE
All controller settings shall be programmable As standard the controller shall include 6 discrete MANUAL MODE
through the OID and shall be protected by two auxiliary inputs, 9 form 'C' auxiliary relay outputs. OFF MODE
password levels These auxiliary inputs and outputs are in addition PRESSURE TRANSDUCER FAULT
All features shall be enabled or disabled through to those mandated by NFPA 20. All auxiliary FAILED TO START
the OID, no jumpers or external wires shall be inputs, outputs, and OID LED's shall be field LOW INTAKE SHUTDOWN
needed or allowed to activate or de-activate a programmable through the OID. This permits a SUPERVISORY POWER FAILURE
feature multitude of customizable controller configurations LOW PRESSURE
The system status data shall be displayed on the to meet each installations unique needs without AUTO WEEKLY TEST START
OID. The displayed items shall include: System adding cost to the controller. The use of jumpers, UNDER FREQUENCY
pressure, Phase to Phase (AB, BC, AC) voltage, soldering, or other external components are not OVER FREQUENCY
Phase current (A, B, C), Current time and date, allowed. LOW ZONE / HIGH ZONE CONTACT
Number of starts, Total motor run hours, HIGH DISCHARGE PRESSURE
Displayed countdown timers for: Sequential The user can select any 9 of the following auxiliary NO LOAD CONDITION
motor start and motor stop, Status of Automatic alarms that can be programmed and recorded in the HIGH VOLTS
Stop Setting. event/alarm logs and annunciated with an LED and LOW VOLTS
output relay contact for conditions such as: Alarm Log: The Alarm Log shall be a separate
Audible horn with silence feature for silencable
LOW PUMP ROOM TEMPERATURE subset of the event log and shall display the last 10
alarms
RESERVOIR LOW alarms recorded in the system.
Lamp test feature
RESERVOIR EMPTY
English or Spanish languages selectable through RESERVOIR HIGH Each event or alarm recorded in the either event log
the OID FLOW METER ON or alarm logs shall have the following data
Microprocessor based logic with real time/date RELIEF VALVE OPEN recorded with the event/alarm:
clock capable of running a minimum of 14 days LOW SUCTION PRESSURE Time and Date of Event or Alarm
without AC power connected to controller and HIGH PUMP ROOM TEMPERATURE System Pressure
non-volatile flash memory to permanently store LOW FIREWATER PRESSURE Descriptive Text Message of the Event/Alarm
the continuous pressure log, event log, alarm log LOW PURGE PRESSURE Motor Running Status
and all user changeable set points and system LOW GEAR OIL PRESSURE Phase to Phase Volts
data. Battery backup of any kind not allowed. HIGH GEAR OIL TEMPERATURE Phase Amps
Input and output status LED's to provide visual HIGH VIBRATION
indication of each discrete input's or output's GAS DETECTION The internal logic of the controller shall be capable
on/off status EMERGENCY POWER ON of operation in a temperature range of 4.4ºC to
One RS485 Serial Port PUMP ROOM DOOR AJAR 40ºC and high, non-condensing, humidity levels.
MODBUS Communication Protocol via RS485 LOW INTAKE
port The controller shall be manufactured by Metron.
All wiring terminals on PCB's shall be Data logging:
removable type The controller shall have separate data logs for
Automatic Transfer Switch: UL Listed for Fire storing system data that is readable through the
Pump Service, sized at least 115% of motor full OID.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
LIMITED SERVICE PUMP CONTROLLER
WITH TRANSFER SWITCH

Model Options Hp Volts Withstand


MP30

SEE SEPARATE OPTION


PAGE FOR LIMITED
SERVICE FIRE PUMP
CONTROLLERS

3 Phase Single Phase


HP
200/208 220/240 380/415 440/480 550/600 110/120 200/208 220/240
5 12079 12079 12079
7.5 12079 12079 11959 11959 11959 12329 12329
10 12329 12329 11959 11959 11959 12409 12409
15 12329 12329 12209 12209 12209 12409
20 12409 12409 12209 12209 12209
25 12409 12409 12249 12249 12249
30 12409 12409 12289 12289 12289

B 18,000 AMPS RMS SYM. 208/240 STD


B 14,000 AMPS RMS SYM. 460/600 STD
C 65,000 AMPS RMS SYM. 208/240 300
C 25,000 AMPS RMS SYM. 480 300
C 18,000 AMPS RMS SYM. 600 300

Normal Power Source and Alternate Power Source Withstand


Rating Value is the same as value indicated above.

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP30 ACROSS THE LINE
LIMITED SERVICE PUMP CONTROLLER WITH TRANSFER SWITCH
[ ] EXPORT CRATING – SUITABLE FOR
STANDARD FEATURE SELECTION BELOW DECK STORAGE $997
Price of controller includes the following local visual [ ] PUMP ROOM TEMPERATURE
LED indications: Power On, Phase Reversal, THERMOSTAT MOUNTED ON
System Fault, Transfer Switch in Normal, Transfer EXTERIOR OF ENCLOSURE
Switch in Emergency, Emergency Isolation Switch [ ] NEMA 2 RATED $42
Open, and Test Operation. [ ] NEMA 4 RATED $160
Standard Default Volt Free (Dry) Contacts include: [ ] LOW SUCTION CUT OFF PRESSURE
Power Available, Phase Reversal, Pump Running, SWITCH (externally mounted) $500
and Controller not in Auto. [ ] MODBUS COMMUNICATION via RS485
In addition to the above LED indications a maximum STANDARD
of twelve (12) user specified alarm conditions can ENCLOSURES
be displayed on the Liquid Crystal Display (LCD) [ ] NEMA 2 STANDARD
display of the Operator Interface Display (OID). A [ ] NEMA 3R $780
maximum of nine (9) additional volt free (dry) [ ] NEMA 4 $1400
contacts can be added. Below is a list of possible [ ] NEMA 4X PAINTED STEEL $1400
alarm conditions. Consult factory for alarm [ ] NEMA 4X (UNPAINTED 304
conditions not listed.
Quantity STAINLESS STEEL) $3200
Alarm Dry of [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
Displaye Cont Contacts CONSULT FACTORY
Description d on OID acts Required
LOW PUMP ROOM TEMP [■] [■] [ ] NEMA 4X (UNPAINTED 316
RESERVOIR LOW [■] [■] STAINLESS STEEL) $4800
RESERVOIR EMPTY [■] [■] [ ] NEMA 4X (316 PAINTED STAINLESS STEEL) .....................
RESERVOIR HIGH [■] [■] CONSULT FACTORY
FLOW METER ON [■] [■] [ ] NEMA 12 $390
RELIEF VALVE OPEN [■] [■] [ ] REMOVABLE GLAND PLATE $500
GAS DETECTION [■] [■] [ ] PURGE SYSTEM, Type Z System, per
LOW SUCTION PRESSURE [■] [■] NFPA 496 suitable for Class I, Division 2,
LOW FIREWATER PRESSURE [■] [■]
LOW PURGE PRESSURE
Group C/D CONSULT FACTORY
[■] [■]
HIGH GEAR OIL TEMP [■] [■]
LOW GEAR OIL PRESSURE [■] [■] PLUMBING
HIGH VIBRATION [■] [■] [ ] 300 PSI FOR FRESH WATER STANDARD
EMERGENCY POWER ON [■] [■] [ ] 600 PSI FOR FRESH WATER $120
PUMP ROOM DOOR OPEN [■] [■] [ ] 300 PSI STAINLESS STEEL FOR
Maximum number of additional SALTWATER/FOAM $175
Alarms is 12 [ ] 600 PSI STAINLESS STEEL FOR
Maximum Number of contacts,
including default contacts, can not SALTWATER/FOAM $295
exceed 9. Each Alarm Condition can
have a maximum 3 contacts.

OPTIONS
[ ]H SPACE HEATER
[ ] WITH THERMOSTAT $320
[ ] WITH HUMIDISTAT $320
[ ]T WEEKLY TEST SOLENOID
[ ] BRASS $840
[ ] STAINLESS STEEL $1335
[ ]W OMIT LEGS, WITH 3" (76.2 mm)
CHANNELS N/C

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
LIMITED
SERVICE
CONTROLLERS
SECTION CONTENTS:
M30 Limited Service Bulletin
Model M30 Price Sheets
Model M30 Drawings

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Limited Service Controller
For Electric Motor Driven Pumps







These controllers are for use with squirrel
cage motors, 30 horsepower or less, 575
volts or less, across-the-line type starting
and must be acceptable to the authority
having jurisdiction. Limited Service
controllers are withstand rated and listed
by Underwriters Laboratories.
Construction of these controllers differs
from the Electric Fire Pump controllers in
that the manually operated isolation
switch is not supplied and the circuit
breaker is of the thermal-magnetic type.

The controller is completely wired,


assembled, and tested at the factory
before shipment, and ready for immediate
installation.

Hubbell Industrial Controls, Inc.


Metron Fire Pump Control Division

MSC0212 v11
Standard and Optional Features

Auxiliary alarm functions displayed on the OID LCD


Standard Features screen
Operator Interface Device (OID) with LED Audible horn with silence feature for silencable
Annunciator and Digital Display alarms
Lamp test feature
Foreign languages selectable through the OID
Microprocessor based logic with real time/date
clock capable of running a minimum of 14 days
without AC power connected to controller
SD Memory card used to record pressure log,
event log, and auxiliary user programs. Pressure
log is stored in separate comma delimited ASCII
text files with each file containing data for one day.
The SD card is removable and can be read by any
PC equipped with an SD card reader.
Input and output status LED's provide visual
indication of each discrete input's or output's on/off
status
One RS485 Serial Port
MODBUS Communication Protocol via RS485 port
Service Entrance Rated
NEMA Type 2 drip proof metal freestanding Standard Auxiliary alarms:
enclosure The controller includes, as standard, six (6) discrete
Operator Interface Device (OID) with 4 lines by 20 auxiliary inputs, and nine (9) form 'C' auxiliary relay
character display with large character backlit Liquid outputs. These auxiliary inputs and outputs are in
Crystal Display (LCD) capable of being read in addition to those mandated by NFPA 20. All
both direct sunlight or dark lighting conditions auxiliary inputs, outputs, and OID screens can be
10 pushbuttons for easy screen navigation, LED field programmed through the OID.
lamp test, alarm reset, controller test and horn Nine (9) of the following auxiliary alarms can be
silencing programmed and recorded in the event/alarm logs
Removable labels to allow for easy field language and annunciated on the OID display screen and/or
changes output relay contact(s). These alarm conditions
All controller settings are programmable through include:
the OID. All features are enabled or disabled LOW PUMP ROOM TEMPERATURE
through the OID, no jumpers or external wires are RESERVOIR LOW
needed which allows easy field modification RESERVOIR EMPTY
The system status data is displayed on the OID. RESERVOIR HIGH
The displayed items include: System Pressure, FLOW METER ON
Phase to Phase (AB, BC, AC) Voltage, Phase RELIEF VALVE OPEN
Current (A, B, C), Current Time and Date, System LOW SUCTION PRESSURE
Events and Notifications such as Remote Start, HIGH PUMP ROOM TEMPERATURE
Local Start etc., Number of Starts, Total Motor Run LOW FIREWATER PRESSURE
Hours, Time Remaining on Sequential Motor Start LOW PURGE PRESSURE
and Motor Stop Timers, Status of Automatic Stop LOW GEAR OIL PRESSURE
Setting HIGH GEAR OIL TEMPERATURE

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
HIGH VIBRATION
GAS DETECTION Options
EMERGENCY POWER ON Option H: Space Heater
PUMP ROOM DOOR AJAR If the ambient atmosphere is especially damp, a space
LOW INTAKE heater rated at 100 watts may be supplied to reduce
Data logging: moisture in the cabinet. A thermostat is supplied as
The controller includes two (2) separate data logs for standard with this option. A humidistat may be
storing system data that is readable through the OID substituted if specified.
or copied to a computer equipped with an SD card Option T: Weekly Test Start Solenoid
reader. The 2 data logs are as follows: In some cases it may be desirable to have the electric
motor run at a preset time each week for
Pressure Log: The pressure log provides a
approximately 30 minutes. The controller includes a
continuous pressure record for 30 days. The pressure
built in weekly test function. This option complements
log samples shall be time and date stamped and
the standard function by simulating a loss of pressure.
stored in a permanent non-volatile SD memory card.
Simulation of pressure loss is accomplished by
The pressure log can be searched by each sample, by
opening a solenoid valve, which reduces the system
minute, or by hour through the OID.
pressure below the starting pressure of the controller.
Event Log: The event log will store up to 300 of the Option W: Omit Legs
most current events. These events can include, but For systems where the controller is mounted on a
are not limited to, any of the following events/alarms: common skid with the pump and motor, the legs of the
PUMP RUNNING controller may be omitted, 3” (76.2mm) channels or
POWER AVAILABLE wall mounting brackets can be supplied. If specified,
PHASE REVERSAL lifting eyes may also be supplied.
MOTOR OVERLOAD
REMOTE START Enclosure
LOCAL START The following NEMA type enclosures are also
PUMP ON DEMAND / FIRE CONDITION available: 3R, 4, 4X (Painted Cold Rolled Steel), 4X
SYSTEM FAULT (304 or 316 Stainless Steel), and 12
AUTO MODE
MANUAL MODE
OFF MODE
PRESSURE TRANSDUCER FAULT
FAILED TO START
LOW INTAKE SHUTDOWN
SUPERVISORY POWER FAILURE
LOW PRESSURE
AUTO WEEKLY TEST START
UNDER FREQUENCY
OVER FREQUENCY
LOW ZONE / HIGH ZONE
CONTACTS
HIGH DISCHARGE PRESSURE
NO LOAD CONDITION
HIGH VOLTS
LOW VOLTS

MSC0212 v11
Limited Service Controller
For Electric Motor Driven Pumps
Model MP30 Limited Service Across-the-line Start Electric Motor Pump Controller
changeable set points and system data. removable SD card memory. The pressure log
Specifications Battery backup of any kind not allowed.
Input and output status LED's to provide
shall be searchable by each sample, by minute,
or by hour. Each days entries shall be stored in a
visual indication of each discrete input's or separate file on the SD card. SD memory shall
General Controller Description output's on/off status be readable by any PC equipped with an SD
The Limited Service Controller shall be factory One RS485 Serial Port memory card reader.
assembled, wired and tested as a unit and shall MODBUS Communication Protocol via Event Log: The event log shall be capable of
conform to all requirements of the latest edition RS485 port storing no less than 3000 events. These events
of NFPA 20, NFPA 70 and be Third Party All wiring terminals on PCB's shall be shall include, but are not limited to, any of the
Listed by Underwriters Laboratories (UL). The removable type following events/alarms:
controller shall be available for 208, 230, 380- Service Entrance Rated PUMP RUNNING
415, 480 or 575 volt three phase power. POWER AVAILABLE
Auxiliary alarms
Controller Equipment Features PHASE REVERSAL
As standard the controller shall include 6 MOTOR OVERLOAD
The controller shall include the following discrete auxiliary inputs, 9 form 'C' auxiliary REMOTE START
standard features: relay outputs. These auxiliary inputs and LOCAL START
NEMA Type 2 drip proof metal freestanding outputs are in addition to those mandated by PUMP ON DEMAND / FIRE CONDITION
enclosure NFPA 20. All auxiliary inputs, outputs, and SYSTEM FAULT
Operator Interface Device (OID) with 4 lines OID screens shall be field programmable AUTO MODE
by 20 character display with large character through the OID. This permits a multitude of MANUAL MODE
backlit LCD capable of being read in both customizable controller configurations to meet OFF MODE
direct sunlight or dark lighting conditions each installations unique needs without adding PRESSURE TRANSDUCER FAULT
10 pushbuttons for easy screen navigation, cost to the controller. The use of jumpers, PUMP FAILED TO START
system test, lamp test, alarm reset, and horn soldering, or other external components are not LOW INTAKE SHUTDOWN
silencing allowed. SUPERVISORY POWER FAILURE
Multicolored LED's for alarm and mode LOW PRESSURE
The user can select any 9 of the following
annunciation AUTO WEEKLY TEST START
auxiliary alarms that can be programmed and
LEDs shall be labeled with removable labels UNDER FREQUENCY
recorded in the event log and annunciated with
to allow for easy field modification of an OID screen and output relay contact for OVER FREQUENCY
language changes LOW ZONE / HIGH ZONE CONTACTS
conditions such as but not limited to:
All controller settings shall be programmable HIGH DISCHARGE PRESSURE
LOW PUMP ROOM TEMP
through the OID and shall be protected by NO LOAD CONDITION
RESERVOIR LOW
two password levels HIGH VOLTS
RESERVOIR EMPTY
All features shall be enabled or disabled LOW VOLTS
RESERVOIR HIGH
through the OID, no jumpers or external wires FLOW METER ON Each event or alarm recorded in the event log
shall be needed or allowed to activate or de- RELIEF VALVE OPEN shall have the following data recorded with the
activate a feature LOW SUCTION PRESSURE event/alarm:
The system status data shall be displayed on HIGH PUMP ROOM TEMPERATURE Time and Date of Event or Alarm
the OID. The displayed items shall include: LOW FIREWATER PRESSURE System Pressure
System pressure, Phase to Phase (AB, BC, LOW PURGE PRESSURE Descriptive Text Message of the Event/Alarm
AC) voltage, Phase current (A, B, C), System LOW GEAR OIL PRESSURE Motor Running Status
Events and Notifications, Current time and HIGH GEAR OIL TEMPERATURE Phase to Phase Volts
date, Number of starts, Total motor run hours, GAS DETECTION
Phase Amps
Displayed countdown timers for: Sequential HIGH VIBRATION
motor start and motor stop, Status of EMERGENCY POWER ON The internal logic of the controller shall be
Automatic Stop Setting. PUMP ROOM DOOR AJAR capable of operation in a temperature range of
Audible horn with silence feature for LOW INTAKE 4.4ºC to 40ºC and high, non-condensing,
silencable alarms humidity levels.
Data logging
Lamp test feature
The controller shall be manufactured by Metron.
Foreign languages selectable through the OID The controller shall have separate data logs for
Microprocessor based logic with real storing system data that is readable through the
time/date clock capable of running a OID.
minimum of 14 days without AC power
Pressure Log: The controller shall have a
connected to controller and non-volatile flash
Pressure log with continuous pressure recording
memory to permanently store the continuous
of 30 days of data. The pressure log samples
pressure log, event log, alarm log and all user
shall be time and date stamped and stored on a

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
LIMITED SERVICE PUMP CONTROLLER
Model Options Hp Volts Withstand
MP30

SEE BACK PAGE FOR


OPTIONS

3 Phase Single Phase


HP
200/208 220/240 380/415 440/480 550/600 110/120 200/208 220/240
5.0 3810 3810 3810
7.5 3810 3810 3690 3690 3690 4060 4060
10 4060 4060 3690 3690 3690 4140 4140
15 4060 4060 3940 3940 3940 4140
20 4140 4140 3940 3940 3940
25 4140 4140 3980 3980 3980
30 4140 4140 4020 4020 4020

B 18,000 AMPS RMS SYM. 208/240 STD


B 14,000 AMPS RMS SYM. 460/600 STD
C 65,000 AMPS RMS SYM. 208/240 300
C 25,000 AMPS RMS SYM. 480 300
C 18,000 AMPS RMS SYM. 600 300

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP30 ACROSS THE LINE
LIMITED SERVICE PUMP CONTROLLER
[ ] PUMP ROOM TEMPERATURE
STANDARD FEATURE SELECTION THERMOSTAT MOUNTED ON
Price of controller includes the following local visual EXTERIOR OF ENCLOSURE
LED indications: Power On, Phase Reversal, System [ ] NEMA 2 RATED $42
Fault, and Test Operation. [ ] NEMA 4 RATED $160
Standard Default Volt Free (Dry) Contacts include: [ ] LOW SUCTION CUT OFF PRESSURE
Power Available, Phase Reversal, Pump Running, SWITCH (externally mounted) $500
and Controller not in Auto. [ ] MODBUS COMMUNICATION via RS485
In addition to the above LED indications a maximum STANDARD
of twelve (12) user specified alarm conditions can be ENCLOSURES
displayed on the Liquid Crystal Display (LCD) display [ ] NEMA 2 STANDARD
of the Operator Interface Display (OID). A maximum [ ] NEMA 3R $390
of nine (9) additional volt free (dry) contacts can be [ ] NEMA 4 $700
added. Below is a list of possible alarm conditions. [ ] NEMA 4X PAINTED STEEL $700
Consult factory for alarm conditions not listed. [ ] NEMA 4X (PAINTED 304 STAINLESS
Quantity
Alarm Dry of STEEL) $1600
Displaye Cont Contacts [ ] NEMA 4X (304 STAINLESS STEEL)
Description d on OID acts Required
LOW PUMP ROOM TEMP
CONSULT FACTORY
[■] [■]
RESERVOIR LOW [■] [■]
[ ] NEMA 4X (PAINTED 316 STAINLESS
RESERVOIR EMPTY [■] [■] STEEL) $2400
RESERVOIR HIGH [■] [■] [ ] NEMA 4X (316 STAINLESS STEEL)
FLOW METER ON [■] [■] CONSULT FACTORY
RELIEF VALVE OPEN [■] [■] [ ] NEMA 12 $195
GAS DETECTION [■] [■] [ ] REMOVABLE GLAND PLATE $250
LOW SUCTION PRESSURE [■] [■] [ ] PURGE SYSTEM, Type Z System, per NFPA
LOW FIREWATER PRESSURE [■] [■] 496 suitable for Class I, Division 2, Group C/DCONSULT
LOW PURGE PRESSURE [■] [■]
HIGH GEAR OIL TEMP [■] [■] PLUMBING
LOW GEAR OIL PRESSURE [■] [■] [ ] 300 PSI FOR FRESH WATER STANDARD
HIGH VIBRATION [■] [■] [ ] 600 PSI FOR FRESH WATER $120
EMERGENCY POWER ON [■] [■] [ ] 300 PSI STAINLESS STEEL FOR
PUMP ROOM DOOR OPEN [■] [■]
SALTWATER/FOAM $175
Maximum number of additional
Alarms is 12 [ ] 600 PSI STAINLESS STEEL FOR
Maximum Number of contacts, SALTWATER/FOAM $295
including default contacts, can not
exceed 9. Each Alarm Condition can
have a maximum 3 contacts.

OPTIONS
[ ]H SPACE HEATER
[ ] WITH THERMOSTAT $320
[ ] WITH HUMIDISTAT $320
[ ]T WEEKLY TEST SOLENOID
[ ] BRASS $840
[ ] STAINLESS STEEL $1335
[ ]W OMIT LEGS, WITH 3" (76.2 mm)
CHANNELS N/C
[ ] EXPORT CRATING – SUITABLE FOR
BELOW DECK STORAGE $997

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
JOCKEY PUMP
ƒ
ƒ ALARM PANELS
ƒ RESIDENTIAL
FIRE PUMP
CONTROLLER
SECTION CONTENTS:
M15 Bulletin
M15 Price Sheets
Model M15 Drawings
MS3 Bulletin
MS3 Price Sheets
Remote Alarm Panel Bulletin
Electric Remote Alarm Panel Price Sheet
Diesel Engine Remote Alarm Panel Price Sheet
Model 1701C Drawings
Model 1802B Drawings
Residential Fire Pump Controller
RFP Price Sheet
RFP Drawings

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
M15 Series Jockey
Pump Controllers

/5GTKGU
,QEMG[2WOR%QPVTQNNGTU 


The M15 Jockey (or make-up) Pump Controllers
are in the same system as the main fire pump
controller(s). Their purpose is to maintain normal
water pressure and to help prevent unnecessary
cycling of the main fire pump(s).
The M15 series jockey Pump Controllers are
listed to UL 508 Standard for Industrial Controls.
Each controller contains an externally operable
fused disconnect switch with fuses which are
horsepower rated, a motor contactor with
protective overload relay, and a door mounted
hand-off-auto switch all housed in a NEMA 2 drip
proof enclosure. As an option, a circuit breaker is
available in lieu of the fused disconnect
The M15A and M15B Jockey Pump Controllers
include a pressure switch with independent high
and low set points for automatic starting and
stopping. The pressure switch is piped to an
external 1/4 inch NPT connector.
The M15A incorporates a control power
transformer and run period timer.
The M15B omits the run period timer and the
control power transformer (transformer is
available as an optional adder)
Standard features of the M15A
x Externally operable disconnect
x Horsepower rated fuses
x Hand-Off-Auto selector switch
x Pressure switch (4.5 - 232 PSI)
x Control power transformer
x Minimum run period timer
x NEMA 2 enclosure


MSC0212 v11
M15 JOCKEY PUMP CONTROLLER
(Example M15AL-1.5-480)

Model Options Hp Volts


M15 *
See back pg.

3 PHASE 1 PHASE
HP 208 220 240 380 415 440 480 575 600 115 208 220 240

.25 790 790 790 820 855 790 790 930 930 790 790 790 790
.33 790 790 790 820 855 790 790 930 930 790 790 790 790
.50 790 790 790 820 855 790 790 930 930 790 790 790 790
.75 790 790 790 820 855 790 790 930 930 790 790 790 790
1.0 790 790 790 820 855 790 790 930 930 800 790 790 790
1.5 790 790 790 820 855 790 790 930 930 810 790 790 790
2.0 790 790 790 820 855 790 790 930 930 820 800 800 800
3.0 800 800 800 820 855 790 790 930 930 870 810 800 800
4.0 810 810 810 820 855 790 790 930 930 870 820 820 820
5.0 810 810 810 820 855 790 790 930 930 945 850 850 820
7.5 830 820 810 830 865 800 800 930 930 N/A 870 870 870
10 830 830 830 830 865 800 800 940 940 N/A 915 915 880
15 890 890 890 855 885 810 810 950 950 N/A N/A N/A N/A
20 1015 1015 920 855 855 855 820 950 950 N/A N/A N/A N/A
25 1140 1140 1140 920 855 885 885 950 950 N/A N/A N/A N/A
30 N/A N/A N/A 950 950 885 885 950 950 N/A N/A N/A N/A
40 N/A N/A N/A 1070 1070 950 950 1010 1010 N/A N/A N/A N/A
50 N/A N/A N/A 1205 1205 1145 1145 1050 1050 N/A N/A N/A N/A

* Model type:
M15A – with Run Period Timer and Control Transformer .................................. STD
M15B – without Run Period Timer and Control Transformer ............................. -125

NOTE: Options utilizing 120VAC components i.e. space heater, hour meter, etc. must be
supplied with control power transformer for proper operation. M15B without
Control Transformer is not available @ 550-600 VAC

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
ADDITIONAL MODIFICATIONS
MODEL M15

OPTIONS:
[ ] C Pump failed to start .......................................................................................................400
[ ] H Space Heater with Thermostat or Humidistat ...............................................................320
[ ] J Loss of Control Power dry contacts ................................................................................90
[ ] L Local Pump Running light ............................................................................................120
[ ] M Motor Lockout circuit .....................................................................................................90
[ ] S Sequential start circuit ..................................................................................................245
[ ] U Local Motor Stopped light ............................................................................................120
[ ] V Power Available dry contact .........................................................................................180
[ ] X Remote Start circuit ........................................................................................................90
[ ] Total Hour meter ...........................................................................................................125

PLUMBING:
[ ] Potter Pressure Switch in lieu of Standard Alco ...........................................................140
[ ] 600 PSI for freshwater ..................................................................................................200
[ ] 300 PSI stainless steel (saltwater/foam) .......................................................................280
[ ] 600 PSI stainless steel (saltwater/foam) .......................................................................480

ENCLOSURES:
[ ] NEMA 2 ...................................................................................................................... STD
[ ] NEMA 3R .....................................................................................................................150
[ ] NEMA 4 ........................................................................................................................695
[ ] NEMA 4X (PAINTED STEEL) ...........................................................................................695
[ ] NEMA 4X (304 UNPAINTED STAINLESS STEEL) ...............................................................1060
[ ] NEMA 4X (304 PAINTED STAINLESS STEEL) .................................... CONSULT FACTORY
[ ] NEMA 4X (316 UNPAINTED STAINLESS STEEL) ...............................................................1593
[ ] NEMA 4X (316 PAINTED STAINLESS STEEL) .................................... CONSULT FACTORY
[ ] NEMA 12 ......................................................................................................................195
[ ] 18” (457.2 mm) steel mounting legs .............................................................................100
[ ] 18” (457.2 mm) stainless steel mounting legs ..............................................................200
[ ] Export crating ...............................................................................................................277
[ ] Tropicalization ................................................................................................................75

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MS3 Series Jockey
Pump Controllers

/55GTKGU
,QEMG[2WOR%QPVTQNNGTU 


The MS3 Jockey (or make-up) Pump Controllers
are in the same system as the main fire pump
controller(s). Their purpose is to maintain normal
water pressure and to help prevent unnecessary
cycling of the main fire pump(s).
The MS3 series Jockey Pump Controllers are
listed to UL 508 Standard for Industrial Controls.
Each controller contains an externally operable
fused disconnect switch with fuses which are
horsepower rated, motor contactors with
protective overload relay, and a door mounted
hand-off-auto switch all housed in a NEMA 2 drip
proof enclosure. As an option, a circuit breaker is
available in lieu of the fused disconnect
The MS3 Jockey Pump Controllers include a
pressure switch with independent high and low
set points for automatic starting and stopping.
The pressure switch is piped to an external 1/4
inch NPT connector.
Standard features of the MS3
x Externally operable disconnect
x Horsepower rated fuses
x Hand-Off-Auto selector switch
x Pressure switch
x Control power transformer
x Minimum run period timer
x NEMA 2 enclosure
x Wye-Delta Open Transition Starting


MSC0212 v11
MS3 JOCKEY WYE-DELTA START PUMP CONTROLLER

Model Options Hp Volts


MS3
See back pg.

3 PHASE
HP 208 220 240 380 415 440 480 575 600

0.25 2,428.00 2,397.00 2,397.00 2,482.00 2,482.00 2,386.00 2,386.00 † †

0.33 2,428.00 2,397.00 2,397.00 2,482.00 2,482.00 2,386.00 2,386.00 † †

0.50 2,428.00 2,397.00 2,397.00 2,482.00 2,482.00 2,386.00 2,386.00 † †

0.75 2,428.00 2,397.00 2,397.00 2,482.00 2,482.00 2,386.00 2,386.00 † †


1.0 2,428.00 2,397.00 2,397.00 2,482.00 2,482.00 2,386.00 2,386.00 † †

1.5 2,428.00 2,397.00 2,397.00 2,482.00 2,482.00 2,386.00 2,386.00 † †

2.0 2,428.00 2,397.00 2,397.00 2,482.00 2,482.00 2,386.00 2,386.00 † †

3.0 2,437.00 2,395.00 2,392.00 2,482.00 2,482.00 2,386.00 2,386.00 † †


4.0 2,479.00 2,395.00 2,464.00 2,482.00 2,482.00 2,386.00 2,386.00 † †
5.0 2,479.00 2,464.00 2,464.00 2,482.00 2,482.00 2,386.00 2,386.00 † †

7.5 2,608.00 2,464.00 2,464.00 2,532.00 2,532.00 2,395.00 2,395.00 † †


10 2,608.00 2,529.00 2,529.00 2,532.00 2,532.00 2,395.00 2,395.00 † †

15 2,789.00 2,584.00 2,584.00 2,664.00 2,664.00 2,458.00 2,458.00 † †

20 2,958.00 2,810.00 2,810.00 2,664.00 2,664.00 2,523.00 2,523.00 † †

25 3,551.00 2,965.00 2,965.00 2,716.00 2,716.00 2,570.00 2,570.00 † †

† Consult factory for price

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
ADDITIONAL MODIFICATIONS
MODEL MS3

OPTIONS:
[ ] C Pump failed to start .......................................................................................................400
[ ] H Space Heater with Thermostat or Humidistat ...............................................................320
[ ] J Loss of Control Power dry contacts ................................................................................90
[ ] L Local Pump Running light ............................................................................................120
[ ] M Motor Lockout circuit .....................................................................................................90
[ ] S Sequential start circuit...................................................................................................245
[ ] U Local Motor Stopped light ............................................................................................120
[ ] V Power Available dry contact .........................................................................................180
[ ] X Remote Start circuit ........................................................................................................90
[ ] Total Hour meter ...........................................................................................................125

PLUMBING:
[ ] Potter Pressure Switch in lieu of Standard Alco ...........................................................140
[ ] 600 PSI for freshwater ..................................................................................................200
[ ] 300 PSI stainless steel (saltwater/foam)........................................................................280
[ ] 600 PSI stainless steel (saltwater/foam)........................................................................480

ENCLOSURES:
[ ] NEMA 2 ...................................................................................................................... STD
[ ] NEMA 3R .....................................................................................................................170
[ ] NEMA 4 ........................................................................................................................715
[ ] NEMA 4X (PAINTED STEEL) ...........................................................................................715
[ ] NEMA 4X (PAINTED 304 STAINLESS STEEL)....................................................................1060
[ ] NEMA 4X (304 STAINLESS STEEL) ...................................................CONSULT FACTORY
[ ] NEMA 4X (PAINTED 316 STAINLESS STEEL)....................................................................1613
[ ] NEMA 4X (316 STAINLESS STEEL) ...................................................CONSULT FACTORY
[ ] NEMA 12 ......................................................................................................................195
[ ] 18” (457.2 mm) steel mounting legs .............................................................................100
[ ] 18” (457.2 mm) stainless steel mounting legs ..............................................................200
[ ] Export crating................................................................................................................297
[ ] Tropicalization ................................................................................................................83

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Rem
mote Alarm Pa
anels
For Fire Pu
ump Co
ontrolle
ers
Featu ures
This microprocessor baased remote
moniitor from Meetron is the latest versioon

NFPA / LPC / EN
of a whole linee of successsful productts.
This unit feaatures statte-of-the art a
microocontroller devices,
d dessigned arounnd
the laatest UL staandards. Thee unit offers a
comppact, robustt and reliaable producct,
offeriing a great deal
d more fllexibility thaan
its prredecessors.
It features
f 6 channel monitoring,
16
desiggned primarrily for use with thhe
Metroon range of fire puump control
systemms, providinng remote supervision
s o
of
compplete installaations from any manneed
pointt. (for exam mple; gate houses annd
This will
w be the case for inttermittent, or o
recepption points)
infreqquent alarm states, or faults whicch
The features in this modell include DIP have been
b clearedd. Channels that
t remain in i
switcches which enables
e bankks of inputs to the alaarm state, hoowever, willl return to thhe
be coonfigured on n site for acctive high/loow activee flashing sttate, soundinng the alarm m
operaation, smalleer footprint, and attractivve once more.
m
packaaging in a style
s that will
w blend innto
A Laamp test faacility is inncluded. Thiis
most environmments witthout beinng
versioon also now has a more cost effectivve
intrussive, yet imp
possible to iggnore when an
integral battery baack up and charger optioon
alarm
m state is trig
ggered.
along with a new w low cost repeat alarm m
The indicators are identiffied by tw wo outputt-card.
removable chann nel allocationn labels. Theese
labelss may be pre-printed to order by b
Metroon, or you maym decide to legend thhe
panell yourself on site. One O label is
intended for chaannel allocaation and thhe
otherr for zone infformation.
Whenn in an alarmm state, the unit
u will sounnd
the alarm,
a and flash the correspondinng
indicator on the front panel, in order to
alert the operatorr. Depressingg the ‘MUTE E’
button will silennce the alarrm and activve
channnel indicatoors will ceease to flassh,
holdiing steady in
n the ‘ON’ state.
s Pressinng
the ‘R
RESET’ buttton will retuurn all inactivve
fault channels to the ‘STAND DBY’ state,
clear the correspoonding indiccators.

e o M m v e h 6
Hubbell Industrial Controls,
·
Inc. - Metron
2
Fire Pump
l
Control nDivision | 4301
.
Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com e
 MSC0212 v11
Remote Alarm Panels
For Fire Pump Controllers
Maximum power <300mA
rating
Power supply 12v D.C./240v A.C.
(selectable 110v)
Dimensions 10.3 in wide x 8 in high
x 4.5 in deep
Enclosure Mild steel, wall
mounting
Inputs 16, 12v digital

Outputs 1 volt-free, single pole,


c/o relay o/p, 5A rated.
(For remote common
fault)

High output audible


alarm.

16 l.e.d. indicators,
plus A.C. status
indicator.
Weight 6.5lbs approx.

Voltage Supply Options

120v/110V 240v/230V

When ordering please specify:

No. of active channels.


Normally open / normally closed standby state.
Channel legend.
Supply voltage.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
 MSC0212 v11
REMOTE ALARM PANEL
UL LISTED

MODEL RAP-E – ELECTRIC MOTOR REMOTE ALARM PANEL


For use with Electric Motor Fire Pump Controllers; default alarms are: PUMP
RUNNING, POWER FAILURE, PHASE REVERSAL, and CONTROLLER NOT
IN AUTO, up to twelve (12) additional user specified alarms are available

MODEL RAP-D – DIESEL ENGINE REMOTE ALARM PANEL

For use with Diesel Engine Fire Pump Controllers; default alarms are: SYSTEM
FAILURE, CONTROLLER NOT IN AUTO, ENGINE RUNNING, and BATTERY
FAILURE, up to twelve (12) additional user specified alarms are available

Model RAP-E or RAP-D Remote Alarm Panel $896.00

NOTE: Maximum of sixteen (16) lights are available.

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Residential Fire Pump
Controller

4(25GTKGU
4GUKFGPVKCN(KTG2WOR
%QPVTQNNGTU 


The Metron Residential Fire Pump
Controllers are designed to provide control
of an electric motor driven fire pump for one
and two family dwellings. Simplex and
Duplex pump control systems are available.
The controller provides for both automatic
and manual start functions. A pressure
switch is provided to monitor the system
pressure. When pressure drops below a
predetermined point, the motor contactor(s)
is energized to start the pump motor. On a
Duplex pump system, there is a short time
delay, field adjustable, that delays starting of
the second motor contactor. The delay
permits motor starting without overloading
the electric supply. A timer is also provided
to allow automatic stopping of the pump
motor(s) once the timer has timed out and
the system pressure has risen above a
predetermined point. The automatic stop
feature is field convertible to manual stop if
so desired. Audible and visual signals are
provided to indicate pump running.
Additional visual signals are provided to
indicate power is available and the motor is
stopped.

Standard Short Circuit Rating of 10,000


Amps RMS Symmetrical and is suitable for
Service Entrance.

RFP Residential Fire Pump Controller Bulletin RFP 04/09


MSC0212 v11
RESIDENTIAL FIRE PUMP CONTROLLER
UL LISTED

MODEL RFP

Simplex Controller 0.5 – 7.5 Horsepower, 230VAC/1 Phase/ 60 Hz


List Price Consult Factory

Duplex Controller 0.5 – 7.5 Horsepower, 230VAC/1 Phase/ 60 Hz


List Price Consult Factory

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Additive Pump Controller
Diesel Engine Additive “Foam” Pump Controller



The Metron Model FD4F-J controller is designed to


specifically meet the latest NFPA 20 and UL 218 standards
for Diesel Engine Additive Pump Controllers.
This controller implements the latest component and
microprocessor logic technology available. It incorporates
years of experience in the design and manufacture of fire
pump control systems.
The components are installed in a NEMA 2 dust and drip
proof enclosure with optional NEMA 3R, 4, 4X, or 12 ratings
available. The Operator Interface Device (OlD), manual start
pushbuttons, stop push button and Auto-Off-Manual selector
switch are located on the exterior door for easy access. The
battery disconnect switches are located on the main
mounting panel inside the enclosure. An internal variable has
been added to control the pressure relieving dump valve.
The dump valve contact must be supplied with an external
power source for operation of the valve. The dump valve
contact will close upon the controller receiving a start
command such as a pressure drop or deluge valve signal.
The dump valve will remain open after the engine starts for
approximately 10 seconds.
The controller’s logic is based on discrete components using
the latest technology with high quality, highly reliable printed
circuit boards (PCBs) and PCB mounted relays. The
controller uses a microprocessor to control automatic engine
and alternation between batteries during cranking. It also
monitors and records system alarms and pressure, battery
voltage and engine functions. This controller is suitable for
all engine types with either ‘energized to run’ or ‘energize to
stop’ fuel solenoids.
Inside the controller are two independent fully automatic
microprocessor controlled battery chargers rated at 10 Amps
each. The battery chargers operate in such a manner as to
ensure that the engine batteries are fully charged within 24
hours. PCB mounted LED’s are provided for indication of
AC Power On, and Battery Power On.
The controller is supplied with wall mounting brackets as
standard. It may be supplied with optional 24” (609.6 mm)
legs for free standing floor or skid mounting. Stainless steel
plumbing is provided as standard.

Hubbell Industrial Controls, Inc.


Metron Fire Pump Control Division

MSC0212 v11
Standard and Optional Features

Spanish languages are standard and selectable through the


Standard Features OlD. Additional languages available upon request.
Operator Interface Device (OID) with LED Annunciator and • The OlD includes 12 pushbuttons for easy screen navigation,
Digital Display: system mode changes, alarm reset, horn silencing, and lamp
General Controller Description test.
The Additive Pump Controller conforms to all requirements of the • The built in annunciator includes multicolored LED’s for alarm
latest edition of NFPA 20, NFPA 70 and is Listed by and mode indications. The annunciation LED’s have
removable labels that allow the user to easily make changes, if
additional alarms and/or language changes are needed.
• All controller settings are programmable through the OlD.
Programming changes are protected by two levels of
passwords to prevent unauthorized modification.
• The OlD displays System Pressure, Start Pressure, Battery 1
Voltage, Battery 2 Voltage, Battery 1 Charger Amps, and
Battery 2 Charger Amps providing the operator instant system
status, Status of Automatic Stop Setting. LED indication of
Loss of DC Power. A detailed Battery Voltage and Charging
Current screen is also supplied. Current time and date,
Number of starts, Total engine run hours, Displayed
countdown timers for: Sequential engine start and engine stop,
and Time until AC Power fail start.
• The state of the art microprocessor based logic includes a real
time/date clock that can operate for a minimum of 14 days
without DC power connected to controller.
• An SD Memory card is used to record pressure log (feature
can be turned on/off), event log, and auxiliary user programs.
The pressure log is stored in separate comma delimited ASCII
text files with each file containing data for one day. The SD
card is removable and can be read by any PC equipped with
an SD card reader.
• One RS485 data port is included as standard.
• MODBUS Communication Protocol via RS485 port
• If there is ever a need to change the internal components all
Underwriters Laboratories (UL) and Approved by Factory Mutual wiring to the internal board is removable without the use of any
(FM). special tools or soldering.
The controller is available for either 12VDC or 24VDC operation. Auxiliary alarms and contacts
Included as standard, the controller is suitable for 120VAC or As standard the controller includes 6 discrete auxiliary inputs, 8
208/240VAC input power at no additional cost. form ‘C’ auxiliary relay outputs. These auxiliary inputs and
outputs are in addition to those mandated by NFPA 20. All
Controller Standard Features auxiliary inputs, outputs, and OlD LED’s are field programmable
• The controller includes two 10 Amp battery chargers that are making it very easy to make changes to the controller in the field.
temperature compensated and includes integral LED’s for Through the OlD the operator can select any 8 of the following
indication of charge AC Failure, and Battery Power On. auxiliary alarms which will be recorded in the event/alarm logs
• Two outer door mounted manual crank pushbuttons and two and annunciated with an LED and/or output relay contact:
battery on/off switches located on the interior back panel. ENGINE QUIT FAULT HIGH ENGINE OIL TEMP
• Includes stainless steel plumbing as well as a standard dry PRESSURE TRANSDUCER FAULT LOW JACKET WATER FLOW
contact to operate a dump valve with time delay setting. PUMP ON DEMAND LOW JACKET WATER LEVEL
• Outer door mounted AUTO, OFF, MANUAL selector switch LOW DISCHARGE PRESSURE LOW HYDRAULIC PRESSURE
with mode condition illuminated on OID with colored LED's HIGH DISCHARGE PRESSURE GAS DETECTION
REMOTE START SIGNAL LOW FIREWATER PRESSURE
• Operator Interface Device (OlD) with 4 lines by 20 character DELUGE VALVE START AIR DAMPER CLOSED
display with large character backlit LCD capable of being read HIGH FUEL LEVEL AIR DAMPER OPEN
in both direct sunlight or dark lighting conditions. English or

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Diesel Engine Additive Pump Controller

FUEL SPILL LOW PURGE PRESSURE Controller Operation


FUEL TANK RUPTURE LOW GEAR OIL PRESSURE Automatic Mode:
LOW PUMP ROOM TEMP LOW COOLANT LEVEL Starting conditions such as pressure drop, and deluge valve start,
RESERVOIR LOW HIGH GEAR OIL TEMP will cause the user adjustable sequential start delay timer to begin
RESERVOIR EMPTY HIGH VIBRATION operation. After start delay is completed the engine will start and
RESERVOIR HIGH LOW FUEL PRESSURE the operation will be recorded in the event log. In addition to the
FLOW METER ON HIGH EXHAUST TEMP sequential start timer the Automatic Weekly Test Start, AC Power
RELIEF VALVE OPEN HIGH FUEL TEMP Fail Start are programmable by the user through the OlD. All
LOW SUCTION PRESSURE PUMP ON DEMAND system statistics are continuously monitored and changes are
logged into the internal logs. System statistics include, but are not
Data logging: limited to, battery charger volts/amps, battery voltage, and system
Pressure Log: The Pressure log provides a continuous pressure pressures are continuously monitored and changes are logged.
recording for one month of data. Each time the pressure log
records a pressure it includes the time and date of the reading and Stopping conditions: Auto engine stop delay, engine lockout, low
is stored on the SD memory card. If the controller is set for non- suction shutdown, automatic stop during automatic weekly test for
pressure actuation there will not be any pressure logs provided. low oil pressure and high water temperature are all OlD user
programmable features.
The data recorded in the pressure log can be searched by each
sample, by minute, or by hour allowing for easy access to specific Manual Mode:
data. If a control logic failure occurs, two crank pushbuttons are provided
that will bypass all internal logic and allow manual operation of the
Event Log: The event log is also stored on the SD memory card. It engine.
will hold a maximum of 3000 events. These events include any of
the following events/alarms:
BATTERY 1 FAULT SYSTEM AUTO MODE
Options
BATTERY 2 FAULT ENGINE LOCKOUT SIGNAL Option H: Space Heater
BATTERY 1 LOW VOLTAGE SYSTEM AUTO MODE If the ambient atmosphere is especially damp or humid, a space
BATTERY 2 LOW VOLTAGE SYSTEM MANUAL MODE heater rated at 100 watts may be supplied to reduce moisture in the
CHARGER 1 FAULT SYSTEM OFF MODE cabinet. A thermostat is supplied as standard with this option. A
CHARGER 2 FAULT SYSTEM TEST RUN humidistat may be substituted at no additional charge.
AC POWER FAIL ALARM RESET
ENGINE OVERSPEED LOW PRESSURE CONDITION Option N: Step-down Transformer
ENGINE FAILED TO START LOW PRESSURE START When AC voltage exceeds 240 VAC single phase, an integral
ENGINE QUIT DELUGE START transformer may be provided for operation from 380 to 600 VAC
ENGINE LOW OIL PRESSURE REMOTE START 50/60 Hz input. Exact voltage and frequency must be specified
ENGINE HIGH WATER TEMP AC POWER FAIL START when ordering.
PRESSURE DROP HORN SILENCED Option W: 24 Inch (609.6 mm) Legs
STOP PUSHBUTTON PRESSURE TRANSDUCER Provided for free standing installations when wall mounting is not
PRESSED FAULT practical. If specified, lifting eyes may also be supplied.
CONTACTOR COIL FAILURE
Plus any of the 8 programmable auxiliary alarms listed above Enclosure
The following NEMA type enclosures are also available: 3R, 4, 4X
Every event or alarm that is recorded includes the following data (Painted Cold Rolled Steel), 4X (304 or 316 Stainless Steel), and
with the recorded event or alarm: 12.
• Time and Date of Event or Alarm
• System Pressure
• Descriptive Text Message of the Event/Alarm
• System Auto Mode Status
• Engine Running Status
• Charger 1 Status
• Charger 2 Status
• Battery 1 Status
• Battery 2 Status

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Additive Pump Controller
Diesel Engine Additive “Foam”Pump Controller

• Microprocessor based logic with real time/date PRESSURE

Specifications clock capable of running a minimum of 14 days


without DC power connected to controller and
Data logging:
The controller shall have separate data logs for
General Controller Description non-volatile flash memory to permanently store storing system event and pressure data that is
the continuous pressure log, event log, alarm readable through the OlD or printable on the
The Additive Pump Controller shall be factory log and all user changeable set points and internal printer. The data logs shall be stored on
assembled, wired and tested as a unit and shall system data. Battery backup of any kind not a removable SD memory card. The file format
conform to all requirements of the latest edition of allowed. shall be standard ASCII text. These logs shall be
NFPA 20, NFPA 70 and be Third Party Listed by • Input and output status LED’s to provide visual as follows:
Underwriters Laboratories (UL) and Approved by indication of each discrete input’s or output’s Pressure Log - if provided: The controller shall
Factory Mutual (FM). The controller shall be on/off status have a Pressure log with continuous pressure
available for either 12VDC or 24VDC systems. • Internal variable to control dump valve. recording one month of data. Each day’s data
• Ability to turn on/off pressure display. shall be in a separate file. The pressure log
Controller Equipment Features • One RS485 Serial Port samples shall be time and date stamped and
The controller shall include the following standard • MODBUS Communication Protocol via RS485 stored in permanent non-volatile flash memory.
features: port The pressure log shall be searchable by each
• NEMA Type 2 drip proof metal wall mount • All wiring terminals on PCB’s shall be sample, by minute, or by hour.
enclosure removable type
Event Log: The event log shall be capable of
• Stainless steel plumbing. Auxiliary alarms: storing no less than 3000 events. These events
• Dual Battery chargers, 10 amp microprocessor As standard the controller shall include 6 discrete shall include any of the following events/alarms:
temperature compensated with integral auxiliary inputs, 8 form ‘C’ auxiliary relay outputs. BATTERY 1 FAULT SYSTEM AUTO MODE
volt/amp digital display and integral LEDs for These auxiliary inputs and outputs are in addition ENGINE LOCKOUT
indication of AC Power On and Battery Power BATTERY 2 FAULT SIGNAL
to those mandated by NFPA 20. All auxiliary
On BATTERY 1 LOW
inputs, outputs, and OlD LED’s shall be field SYSTEM AUTO MODE
• Two outer door mounted crank pushbuttons VOLTAGE
programmable through the OlD. This permits a BATTERY 2 LOW SYSTEM MANUAL
and two inner panel mounted battery on/off multitude of customizable controller configurations VOLTAGE MODE
switches to meet each installations unique needs without CHARGER 1 FAULT SYSTEM OFF MODE
• Outer door mounted key operated AUTO, OFF, adding cost to the controller. The use of jumpers, CHARGER 2 FAULT SYSTEM TEST RUN
MANUAL, mode selector switch soldering, or other external components is not AC POWER FAIL ALARM RESET
• Operator Interface Device (OID) with 4 lines by allowed. LOW PRESSURE
ENGINE OVERSPEED
20 character display with large character CONDITION
backlit LCD capable of being read in both The user can select any 8 of the following ENGINE FAILED TO LOW PRESSURE
direct sunlight or dark lighting conditions auxiliary alarms that can be programmed and START START
recorded in the event/alarm logs and annunciated ENGINE QUIT DELUGE START
• 12 pushbuttons for easy screen navigation,
with an LED and output relay contact: ENGINE LOW OIL
alarm reset, and horn silencing PRESSURE REMOTE START
• Multicolored LED’s for alarm and mode HIGH ENGINE OIL
ENGINE QUIT FAULT ENGINE HIGH WATER AC POWER FAIL
annunciation TEMPERATURE
TEMP START
PRESSURE
• LEDs shall be labeled with removable labels to LOW JACKET WATER PRESSURE
TRANSDUCER
allow for easy field modification if additional FLOW TRANSDUCER HORN SILENCED
FAULT FAULT
alarms and/or language changes LOW JACKET WATER
• All controller settings shall be programmable PUMP ON DEMAND STOP PUSHBUTTON
LEVEL PRESSURE DROP
through the OlD and shall be protected by two PRESSED
LOW DISCHARGE LOW HYDRAULIC CONTACTOR COIL
password levels PRESSURE PRESSURE FAILURE
• All features shall be enabled or disabled HIGH DISCHARGE (PLUS ANY OF THE 8 PROGRAMMABLE
GAS DETECTION
through the OlD, no jumpers or external wires PRESSURE AUXILIARY ALARMS LISTED ABOVE)
shall be needed or allowed to activate or de- REMOTE START LOW FIREWATER Each event or alarm recorded in the either event
activate a feature SIGNAL PRESSURE log or alarm logs shall have the following data
• The system status data shall be displayed on AIR DAMPER
DELUGE VALVE START recorded with the event/alarm:
the OlD. The displayed items shall include: CLOSED
Pump On Demand, Contactor Coil Failure, HIGH FUEL LEVEL AIR DAMPER OPEN • Time and Date of Event or Alarm
System pressure, Battery 1 Voltage, Battery 2 LOW PURGE • System Pressure
FUEL SPILL
Voltage, Battery 1 Charger Amps, Battery 2 PRESSURE • Descriptive Text Message of the Event/Alarm
LOW GEAR OIL • System Auto Mode Status
Charger Amps, Current time and date, Number FUEL TANK RUPTURE
PRESSURE • Engine Running Status
of starts, Total engine run hours, Displayed LOW PUMP ROOM LOW COOLANT
countdown timers for: • Charger 1 Status
TEMPERATURE LEVEL
Sequential engine start and engine stop, and • Charger 2 Status
HIGH GEAR OIL
Time until AC Power fail start, Status of RESERVOIR LOW • Battery 1 Status
TEMPERATURE
Automatic Stop Setting. LED indication of Loss RESERVOIR EMPTY HIGH VIBRATION • Battery 2 Status
of DC Power. LOW FUEL The internal logic of the controller shall be
RESERVOIR HIGH
• Audible horn with horn silence feature for PRESSURE capable of operation in a temperature range of
silenceable alarms HIGH EXHAUST 4.4°C to 40°C and high, non-condensing,
FLOW METER ON
• Lamp test feature TEMPERATURE humidity levels.
• English or Spanish languages selectable HIGH FUEL
RELIEF VALVE OPEN
through the OlD TEMPERATURE
LOW SUCTION PUMP ON DEMAND

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
DIESEL ENGINE FIRE PUMP CONTROLLER
SELECTION CHART MODEL FDF4

BASE PRICE includes built-in 12 or 24 Quantity


VDC, Negative Ground Battery chargers $6,889 Form C of
VOLTAGE (PLEASE SPECIFY) Dry Contacts
Description LED Contacts Required
[ ] 12 VDC NEGATIVE GROUND ENGINE QUIT FAULT [■] [■]
[ ] 24 VDC NEGATIVE GROUND PRESSURE TRANSDUCER FAULT [■] [■]
PUMP ON DEMAND [■] [■]
[ ] 60 HZ OPERATION (DEFAULT) LOW DISCHARGE PRESSURE [■] [■]
[ ] 50 HZ OPERATION HIGH DISCHARGE PRESSURE [■] [■]
(All items below require a N.O. or N.C. contact provided by the customer)
[ ] 120 VAC / 1 PHASE OPERATION ENGINE LOCKED OUT [■] [■]
[ ] 240 VAC / 1 PHASE OPERATION REMOTE START SIGNAL [■] [■]
[ ] ALL OTHER VOLTAGES (OPTION N DELUGE VALVE START [■] [■]
REQUIRED) (A maximum of six of the following can be chosen below)
HIGH FUEL LEVEL [■] [■]
DIESEL ENGINE TYPE FUEL SPILL [■] [■]
FUEL TANK RUPTURE [■] [■]
[ ] UL/FM LISTED ENGINE LOW FUEL PRESSURE [■] [■]
[ ] NON-UL/NON-FM LISTED ENGINE HIGH FUEL TEMPERATURE [■] [■]
Specify __________________________ RESERVOIR LOW [■] [■]
RESERVOIR HIGH [■] [■]
STANDARD FEATURE SELECTION RESERVOIR EMPTY [■] [■]
Price of controller includes the following local visual LOW PUMP ROOM TEMPERATURE [■] [■]
LED indications: System Fault, Battery #1 Healthy, FLOW METER ON [■] [■]
Battery #2 Healthy, Charger #1 Failure, Charger #2 RELIEF VALVE OPEN [■] [■]
Failure, AC Power Loss, Engine Running, Engine LOW SUCTION PRESSURE [■] [■]
Failed to Start, Engine Low Oil Pressure, Engine High HIGH ENGINE OIL TEMPERATURE [■] [■]
Water Temp., Engine Overspeed, Low Fuel, Speed LOW JACKET WATER FLOW [■] [■]
Switch Failure, Contactor Coil Failure, Loss of DC LOW JACKET WATER LEVEL [■] [■]
LOW HYDRAULIC PRESSURE [■] [■]
Power, Switch in Auto, Switch in Manual, and Test
LOW FIREWATER PRESSURE [■] [■]
Operation
AIR DAMPER CLOSED [■] [■]
Standard Default Volt Free (Dry) Contacts include: AIR DAMPER OPEN [■] [■]
Controller not in Auto, System Fault, Engine Running LOW PURGE PRESSURE [■] [■]
(two (2) sets), and Battery Fault LOW GEAR OIL PRESSURE [■] [■]
In addition to the above LED indications a maximum of LOW COOLANT LEVEL [■] [■]
ten (10) user specified alarm conditions can be HIGH GEAR OIL TEMPERATURE [■] [■]
displayed. A maximum of six (6) additional volt free HIGH VIBRATION [■] [■]
(dry) contacts can be added. In the next column is a HIGH EXHAUST TEMPERATURE [■] [■]
list of suggested alarm conditions. Consult factory for Maximum number of additional LEDs is 10
alarm conditions not listed.
Maximum Number of contacts, including default
contacts, can not exceed 9. Each Alarm Condition
can have a maximum 3 contacts.

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
DIESEL ENGINE FIRE PUMP CONTROLLER
SELECTION CHART MODEL FDF4

OPTIONS [ ] MODBUS COMMUNICATION via RS485 Standard

[ ] H SPACE HEATER (100 WATT) PLUMBING


[ ] THERMOSTAT $250
[ ] HUMIDISTAT $250
[ ] J INTEGRAL BATTERY [ ] 300 PSI SALTWATER / FOAM Standard
CHARGERS
(Included in base price) [ ] 600 PSI SALTWATER / FOAM $150
[ ] JJ INTEGRAL BATTERY
CHARGERS CONSULT FACTORY ENCLOSURE
This option required for engines with
high capacity starting batteries that [ ] NEMA 2 Standard
exceed 220 Ampere Hours
[ ] NEMA 3R $ 350
[ ] N STEP DOWN TRANSFORMER
All voltages above 240 VAC [ ] NEMA 4 (PAINTED STEEL) $ 600
Specify Voltage_____________ $492 [ ] NEMA 4X (PAINTED STEEL) $ 600
[ ] W 24” (609.6mm) LEGS FOR FREE [ ] NEMA 4X (UNPAINTED 304
STANDING (FLOOR) STAINLESS STEEL) $3447
INSTALLATION $220
[ ] NEMA 4X 304 PAINTED STAINLESS
[ ] W 24” (609.6mm) STAINLESS STEEL STEEL
LEGS FOR FREE STANDING
CONSULT FACTORY
(FLOOR) INSTALLATION $880
[ ] NEMA 4X (UNPAINTED 316
[ ] REMOVABLE GLAND PLATE $250
STAINLESS STEEL) $3500
[ ] FUEL LEVEL SWITCH WITH ONE
[ ] NEMA 4X 316 PAINTED STAINLESS
ALARM POINT † $290
STEEL
[ ] FUEL LEVEL SWITCH WITH TWO CONSULT FACTORY
ALARM POINTS † $1248
[ ] NEMA 12 (SPECIFY) N/C
[ ] PUMP ROOM TEMPERATURE
THERMOSTAT MOUNTED ON [ ] LIFTING EYES N/C
EXTERIOR OF ENCLOSURE
[ ] NEMA 2 RATED $42 † Device shipped loose for Customer Installation
[ ] NEMA 4 RATED $160
[ ] LOW SUCTION CUT OFF PRESSURE
SWITCH (externally mounted) $500
[ ] EXPORT CRATING (Suitable for below
deck or airfreight) $600
[ ] PURGE SYSTEM, Type Z System, per
NFPA 496 suitable for Class I, Division 2,
Group C/D CONSULT FACTORY
Prices subject to change without notice.

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Limited Service Controller
Electric Additive “Foam” Pump Controller








These controllers are for use with squirrel cage
motors, 30 horsepower or less, 575 volts or less,
across-the-line type starting and must be
acceptable to the authority having jurisdiction.
Limited Service controllers are withstand rated
and listed by Underwriters Laboratories.
Construction of these controllers differs from the
Electric Additive Pump controllers in that the
manually operated isolation switch is not
supplied and the circuit breaker is of the thermal-
magnetic type.
An internal variable has been added to
control the pressure relieving dump valve.
The dump valve contact must be supplied
with an external power source for
operation of the valve. The dump valve
contact will close upon the controller
receiving a start command such as a
pressure drop or deluge valve signal. The
dump valve will remain open after the
engine starts for approximately 10
seconds.
The controller is completely wired, assembled,
and tested at the factory before shipment, and
ready for immediate installation.

MPF30 Limited Service Controller


MSC0212 v11
Standard and Optional Features

and Motor Stop Timers, Status of Automatic Stop


Standard Features Setting
Operator Interface Device (OID) with LED Audible horn with silence feature for silencable
Annunciator and Digital Display alarms
Lamp test feature
Foreign languages selectable through the OID
Microprocessor based logic with real time/date
clock capable of running a minimum of 14 days
without AC power connected to controller
SD Memory card used to record pressure log,
event log, and auxiliary user programs. Pressure
log is stored in separate comma delimited ASCII
text files with each file containing data for one day.
The SD card is removable and can be read by any
PC equipped with an SD card reader.
Input and output status LED's provide visual
indication of each discrete input's or output's on/off
status
One RS485 Serial Port
MODBUS Communication Protocol via RS485 port
Service Entrance Rated
NEMA Type 2 drip proof metal freestanding Standard Auxiliary alarms:
enclosure The controller includes, as standard, six (6) discrete
Operator Interface Device (OID) with 4 lines by 20 auxiliary inputs, and nine (9) form 'C' auxiliary relay
character display with large character backlit Liquid outputs. These auxiliary inputs and outputs are in
Crystal Display (LCD) capable of being read in addition to those mandated by NFPA 20. All
both direct sunlight or dark lighting conditions auxiliary inputs, outputs, and OID screens can be
10 pushbuttons for easy screen navigation, LED field programmed through the OID.
lamp test, alarm reset, controller test and horn Nine (9) of the following auxiliary alarms can be
silencing programmed and recorded in the event/alarm logs
Includes stainless steel plumbing as well as a and annunciated on the OID display screen and/or
standard dry contact to operate a dump valve with output relay contact(s). These alarm conditions
time delay setting include:
All controller settings are programmable through LOW PUMP ROOM TEMPERATURE
the OID. All features are enabled or disabled RESERVOIR LOW
through the OID, no jumpers or external wires are RESERVOIR EMPTY
needed which allows easy field modification RESERVOIR HIGH
The system status data is displayed on the OID. FLOW METER ON
The displayed items include: System Pressure, RELIEF VALVE OPEN
Phase to Phase (AB, BC, AC) Voltage, Phase LOW SUCTION PRESSURE
Current (A, B, C), Current Time and Date, System HIGH PUMP ROOM TEMPERATURE
Events and Notifications such as Remote Start, LOW FIREWATER PRESSURE
Local Start etc., Number of Starts, Total Motor Run LOW PURGE PRESSURE
Hours, Time Remaining on Sequential Motor Start LOW GEAR OIL PRESSURE
HIGH GEAR OIL TEMPERATURE

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Electric Additive “Foam” Pump Controller

HIGH VIBRATION
GAS DETECTION Options
EMERGENCY POWER ON Option H: Space Heater
PUMP ROOM DOOR AJAR If the ambient atmosphere is especially damp, a space
LOW INTAKE heater rated at 100 watts may be supplied to reduce
Data logging: moisture in the cabinet. A thermostat is supplied as
The controller includes two (2) separate data logs for standard with this option. A humidistat may be
storing system data that is readable through the OID substituted if specified.
or copied to a computer equipped with an SD card Option T: Weekly Test Start Solenoid
reader. If the controller is set for non pressure In some cases it may be desirable to have the electric
actuation there will not be any pressure logs provided. motor run at a preset time each week for
The 2 data logs are as follows: approximately 30 minutes. The controller includes a
built in weekly test function. This option complements
Pressure Log: The pressure log provides a
the standard function by simulating a loss of pressure.
continuous pressure record for 30 days. The pressure
Simulation of pressure loss is accomplished by
log samples shall be time and date stamped and
opening a solenoid valve, which reduces the system
stored in a permanent non-volatile SD memory card.
pressure below the starting pressure of the controller.
The pressure log can be searched by each sample, by
minute, or by hour through the OID. This feature can Option W: Omit Legs
be toggled on/off. For systems where the controller is mounted on a
common skid with the pump and motor, the legs of the
Event Log: The event log will store up to 300 of the controller may be omitted, 3” (76.2mm) channels or
most current events. These events can include, but wall mounting brackets can be supplied. If specified,
are not limited to, any of the following events/alarms: lifting eyes may also be supplied.
PUMP RUNNING
POWER AVAILABLE Enclosure
PHASE REVERSAL The following NEMA type enclosures are also
MOTOR OVERLOAD available: 3R, 4, 4X (Painted Cold Rolled Steel), 4X
REMOTE START (304 or 316 Stainless Steel), and 12
LOCAL START
PUMP ON DEMAND / FIRE CONDITION
SYSTEM FAULT
AUTO MODE
MANUAL MODE
OFF MODE
PRESSURE TRANSDUCER FAULT
FAILED TO START
LOW INTAKE SHUTDOWN
SUPERVISORY POWER FAILURE
LOW PRESSURE
AUTO WEEKLY TEST START
UNDER FREQUENCY
OVER FREQUENCY
LOW ZONE / HIGH ZONE CONTACTS
HIGH DISCHARGE PRESSURE
NO LOAD CONDITION
HIGH VOLTS
LOW VOLTS

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
LIMITED SERVICE ADDITIVE PUMP CONTROLLER
Model Options Hp Volts Withstand
MP30

SEE BACK PAGE FOR


OPTIONS

3 Phase Single Phase


HP
200/208 220/240 380/415 440/480 550/600 110/120 200/208 220/240
5.0 3985 3985 3985
7.5 3985 3985 4135 4135 4135 4235 4235
10 4235 4235 4135 4135 4135 4315 4315
15 4235 4235 4115 4115 4115 4315
20 4315 4315 4115 4115 4115
25 4315 4315 4115 4115 4115
30 4315 4315 4195 4195 4195

B 18,000 AMPS RMS SYM. 208/240 STD


B 14,000 AMPS RMS SYM. 460/600 STD
C 65,000 AMPS RMS SYM. 208/240 300
C 25,000 AMPS RMS SYM. 480 300
C 18,000 AMPS RMS SYM. 600 300

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP30 ACROSS THE LINE
LIMITED SERVICE ADDITIVE PUMP CONTROLLER
[ ] PUMP ROOM TEMPERATURE
STANDARD FEATURE SELECTION THERMOSTAT MOUNTED ON
Price of controller includes the following local visual EXTERIOR OF ENCLOSURE
LED indications: Power On, Phase Reversal, System [ ] NEMA 2 RATED $42
Fault, and Test Operation. [ ] NEMA 4 RATED $160
Standard Default Volt Free (Dry) Contacts include: [ ] LOW SUCTION CUT OFF
Power Available, Phase Reversal, Pump Running, PRESSURE SWITCH (externally
and Controller not in Auto. mounted) $500
In addition to the above LED indications a maximum [ ] MODBUS COMMUNICATION via RS485
of twelve (12) user specified alarm conditions can be STANDARD
displayed on the Liquid Crystal Display (LCD) display ENCLOSURES
of the Operator Interface Display (OID). A maximum [ ] NEMA 2 STANDARD
of nine (9) additional volt free (dry) contacts can be [ ] NEMA 3R $390
added. Below is a list of possible alarm conditions. [ ] NEMA 4 $700
Consult factory for alarm conditions not listed. [ ] NEMA 4X PAINTED STEEL $700
Quantity
Alarm Dry of [ ] NEMA 4X (UNPAINTED 304 STAINLESS
Displaye Cont Contacts STEEL) $1600
Description d on OID acts Required
LOW PUMP ROOM TEMP [■] [■] [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
RESERVOIR LOW [■] [■] CONSULT FACTORY
RESERVOIR EMPTY [■] [■] [ ] NEMA 4X (UNPAINTED 316 STAINLESS
RESERVOIR HIGH [■] [■] STEEL) $2400
FLOW METER ON [■] [■] [ ] NEMA 4X (316 PAINTED STAINLESS STEEL) ......................
RELIEF VALVE OPEN [■] [■] CONSULT FACTORY
GAS DETECTION [■] [■] [ ] NEMA 12 $195
LOW SUCTION PRESSURE [■] [■] [ ] REMOVABLE GLAND PLATE $250
LOW FIREWATER PRESSURE [■] [■]
[ ] PURGE SYSTEM, Type Z System, per NFPA
LOW PURGE PRESSURE [■] [■]
HIGH GEAR OIL TEMP
496 suitable for Class I, Division 2, Group
[■] [■]
LOW GEAR OIL PRESSURE [■] [■]
C/D CONSULT FACTORY
HIGH VIBRATION [■] [■]
EMERGENCY POWER ON [■] [■] PLUMBING
PUMP ROOM DOOR OPEN [■] [■] [ ] 300 PSI STAINLESS STEEL FOR
Maximum number of additional SALTWATER/FOAM Standard
Alarms is 12 [ ] 600 PSI STAINLESS STEEL FOR
Maximum Number of contacts,
including default contacts, can not SALTWATER/FOAM $120
exceed 9. Each Alarm Condition can
have a maximum 3 contacts.

OPTIONS
[ ]H SPACE HEATER
[ ] WITH THERMOSTAT $320
[ ] WITH HUMIDISTAT $320
[ ]T WEEKLY TEST SOLENOID
[ ] BRASS $840
[ ] STAINLESS STEEL $1335
[ ]W OMIT LEGS, WITH 3" (76.2 mm)
CHANNELS N/C
[ ] EXPORT CRATING – SUITABLE FOR
BELOW DECK STORAGE $997

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Additive Pump Controller
Electric Additive “Foam” Pump Controller






Metron Additive Pump Controllers conform to the latest
requirements of Chapter 10, National Fire Protection
Association Pamphlet 20, Standard for Centrifugal Fire
Pumps as adopted by Underwriters Laboratories and
Factory Mutual. They are withstand rated and listed by
Underwriters’ Laboratories and approved by Factory Mutual
Research Corporation.

Sizes range from 15 to 50 horsepower, 200 to 600 volts, 60


Hz. These controllers are for use on Across-the-Line type
installations.

Only the highest quality components, all UL listed or UL


recognized, are used throughout to assure the best possible
reliability. The cabinet is fabricated of heavy gauge
reinforced steel with drip-proof hood. All field wiring and
service connections may be made from the front, allowing
the controller to be mounted flush against a wall. An internal
variable has been added to control the pressure relieving
dump valve. The dump valve contact must be supplied with
an external power source for operation of the valve. The
dump valve contact will close upon the controller receiving a
start command such as a pressure drop or deluge valve
signal. The dump valve will remain open after the engine
starts for approximately 10 seconds.

The controller is completely wired, assembled, and tested at


the factory before shipment, and ready for immediate
installation.

MPF300 Additive Pump Controller


MSC0212 v11
Standard and Optional Features

hours, Time remaining on sequential motor start


Standard Features and motor stop timers, Status of automatic stop
Operator Interface Device (OID) with LED setting.
Annunciator and Digital Display Auxiliary alarm functions displayed on the OID LCD
screen
Audible horn with silence feature for silencable
alarms
Lamp test feature
Foreign languages selectable through the OID
Microprocessor based logic with real time/date
clock capable of running a minimum of 14 days
without AC power connected to controller
SD Memory card used to record pressure log, event
and log, and auxiliary user programs ASCII text files
with each file containing data for one day. The SD
card is removable and can be read by any PC
equipped with an SD card reader.
Input and output status LED's provide visual
indication of each discrete input's or output's on/off
status
One RS485 Serial Port
MODBUS Communication Protocol via RS485 port
NEMA Type 2 drip proof metal freestanding Service Entrance Rated
enclosure
Operator Interface Device (OID) with 4 lines by 20 Standard Auxiliary alarms:
character display with large character backlit Liquid The controller includes as standard six (6) discrete
Crystal Display (LCD) capable of being read in both auxiliary inputs, nine (9) form 'C' auxiliary relay
direct sunlight or dark lighting conditions outputs. These auxiliary inputs and outputs are in
10 pushbuttons for easy screen navigation, LED addition to those mandated by NFPA 20. All auxiliary
lamp test, alarm reset, controller test and horn inputs, outputs, and OID Display can be field
silencing programmed through the OID.
Removable labels to allow for easy field language These alarm conditions include:
changes LOW PUMP ROOM TEMP
Includes stainless steel plumbing as well as a RESERVOIR LOW
standard dry contact to operate a dump valve with RESERVOIR EMPTY
time delay setting. RESERVOIR HIGH
All controller settings are programmable through the FLOW METER ON
OID. All features are enabled or disabled through RELIEF VALVE OPEN
the OID, no jumpers or external wires are needed LOW SUCTION PRESSURE
allowing easy field modification HIGH PUMP ROOM TEMPERATURE
The system status data is displayed on the OID. LOW FIREWATER PRESSURE
The displayed items include: System pressure, LOW PURGE PRESSURE
Phase to Phase (AB, BC, AC) voltage, Phase LOW GEAR OIL PRESSURE
current (A, B, C), Current time and date, System HIGH GEAR OIL TEMPERATURE
Events and Notifications such as Remote Start,
Local Start etc., Number of starts, Total motor run

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Electric Additive “Foam” Pump Controller

GAS DETECTION
HIGH VIBRATION Options
EMERGENCY POWER ON
PUMP ROOM DOOR OPEN Option H: Space Heater
If the ambient atmosphere is especially damp, a
Data logging: space heater rated at 100 watts may be supplied to
The controller includes separate data logs for storing reduce moisture in the cabinet. A thermostat is
system data that is readable through the OID or supplied as standard with this option. A humidistat
copied to a computer equipped with an SD card may be substituted if specified.
reader. If the controller is set for non pressure
Option W: Omit Legs
actuation there will not be any pressure logs provided.
For systems where the controller is mounted on a
The data logs are as follows:
common skid with the pump and motor, the legs of
Pressure Log: The pressure log provides a the controller may be omitted, 3” (76.2mm) channels
continuous pressure record for 30 days. The or wall mounting brackets can be supplied. If
pressure log samples shall be time and date stamped specified, lifting eyes may also be supplied.
and stored in permanent non-volatile SD memory
Enclosure
card. The pressure log can be searched by each
The following NEMA type enclosures are also
sample, by minute, or by hour through the OID.(Not
available: 3R, 4, 4X (Painted Cold Rolled Steel), 4X
used on remote applications).
(304 or 316 Stainless Steel), and 12
Event Log: The event log will store up to 300 of the
most current events. These events can include, but is
not limited to, any of the following events/alarms:
PUMP RUNNING
POWER AVAILABLE
PHASE REVERSAL
MOTOR OVERLOAD
REMOTE START
LOCAL START
PUMP ON DEMAND
SYSTEM FAULT
PRESSURE TRANSDUCER FAULT
PUMP FAILED TO START
LOW INTAKE SHUTDOWN ALARM
SUPERVISORY POWER FAILURE
LOW PRESSURE
AUTO WEEKLY TEST START
UNDER FREQUENCY
OVER FREQUENCY
LOW ZONE / HIGH ZONE CONTACTS
HIGH DISCHARGE PRESSURE
NO LOAD CONDITION

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
Additive Pump Controller
Electric Additive “Foam” Pump Controller
Model MPF300 Across-the-line Start Microprocessor Electric Motor Additive “Foam” Pump Controller
permanently store the continuous pressure log, Pressure Log: The controller shall have a
Specifications event log, alarm log and all user changeable
set points and system data. Battery backup of
Pressure log with continuous pressure recording
of 30 days of data. The pressure log samples
any kind not allowed. shall be time and date stamped and stored on a
General Controller Description Input and output status LED's to provide visual removable SD card memory. The pressure log
The Additive Pump Controller shall be factory indication of each discrete input's or output's shall be searchable by each sample, by minute, or
assembled, wired and tested as a unit and shall on/off status by hour. Each days entries shall be stored in a
conform to all requirements of the latest edition Internal variable to control dump valve. separate file on the SD card. SD memory shall be
of NFPA 20, NFPA 70 and be Third Party Listed • Ability to turn on/off pressure display. readable by any PC equipped with an SD
by Underwriters Laboratories (UL) and One RS485 Serial Port memory card reader.
Approved by Factory Mutual (FM). The MODBUS Communication Protocol via Event Log: The event log shall be capable of
controller shall be available for 208, 230, 380- RS485 port storing no less than 3000 events. These events
415, or 480 volt three phase power. Internal variable to controle dump valve. shall include, but is not limited to, any of the
Service Entrance Rated following events/alarms:
Controller Equipment Features
PUMP RUNNING
Ability to turn on/off pressure display and
The controller shall include the following POWER AVAILABLE
logging.
standard features: PHASE REVERSAL
NEMA Type 2 drip proof metal freestanding Auxiliary alarms MOTOR OVERLOAD
enclosure REMOTE START
As standard the controller shall include 6 discrete LOCAL START
Stainless steel plumbing.
auxiliary inputs, 9 form 'C' auxiliary relay PUMP ON DEMAND
Operator Interface Device (OID) with 4 lines
outputs. These auxiliary inputs and outputs are SYSTEM FAULT
by 20 character display with large character
in addition to those mandated by NFPA 20. All PRESSURE TRANSDUCER FAULT
backlit LCD capable of being read in both
auxiliary inputs, outputs, and OID screens shall PUMP FAILED TO START
direct sunlight or dark lighting conditions
be field programmable through the OID. This LOW INTAKE SHUTDOWN ALARM
10 pushbuttons for easy screen navigation, permits a multitude of customizable controller
system test, lamp test, alarm reset, and horn SUPERVISORY POWER FAILURE
configurations to meet each installations unique LOW PRESSURE
silencing needs without adding cost to the controller. The
Multicolored LED's for alarm and mode AUTO WEEKLY TEST START
use of jumpers, soldering, or other external UNDER FREQUENCY
annunciation components are not allowed.
LEDs shall be labeled with removable labels OVER FREQUENCY
to allow for easy field modification of The user can select any 9 of the following LOW ZONE / HIGH ZONE CONTACTS
language changes auxiliary alarms that can be programmed and HIGH DISCHARGE PRESSURE
All controller settings shall be programmable recorded in the event log and annunciated with NO LOAD CONDITION
through the OID and shall be protected by two an OID screen and output relay contact for Each event or alarm recorded in the event log
password levels conditions such as but not limited to: shall have the following data recorded with the
All features shall be enabled or disabled LOW PUMP ROOM TEMP event/alarm:
through the OID, no jumpers or external wires RESERVOIR LOW Time and Date of Event or Alarm
shall be needed or allowed to activate or de- RESERVOIR EMPTY
System Pressure
activate a feature RESERVOIR HIGH
Descriptive Text Message of the Event/Alarm
The system status data shall be displayed on FLOW METER ON
RELIEF VALVE OPEN Motor Running Status
the OID. The displayed items shall include: Phase to Phase Volts
System pressure, Phase to Phase (AB, BC, LOW SUCTION PRESSURE
HIGH PUMP ROOM TEMPERATURE Phase Amps
AC) voltage, Phase current (A, B, C), System
Events and Notifications, Current time and LOW FIREWATER PRESSURE The internal logic of the controller shall be
date, Number of starts, Total motor run hours, LOW PURGE PRESSURE capable of operation in a temperature range of
Displayed countdown timers for: Sequential LOW GEAR OIL PRESSURE 4.4ºC to 40ºC and high, non-condensing,
motor start and motor stop, Status of HIGH GEAR OIL TEMPERATURE humidity levels.
Automatic Stop Setting. GAS DETECTION
HIGH VIBRATION The controller shall be manufactured by Metron.
Audible horn with silence feature for
silencable alarms EMERGENCY POWER ON
Lamp test feature PUMP ROOM DOOR OPEN
Foreign languages selectable through the OID Data logging
Microprocessor based logic with real time/date
clock capable of running a minimum of 14 The controller shall have separate data logs for
days without AC power connected to storing system data that is readable through the
controller and non-volatile flash memory to OID.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP300 ACROSS THE LINE
FULL SERVICE ADDITIVE PUMP CONTROLLER
Model Options Hp Volts Withstand
MP300

SEE SEPARATE OPTION PAGE FOR


ELECTRIC FIRE PUMP
CONTROLLERS

Horsepower Voltage
200/208 220/240 380/415 440/480 550/600
15 6930 6930 6930 6930 6930
20 6930 6930 6930 6930 6930
25 6930 6930 6930 6930 6930
30 6930 6930 6930 6930 6930
40 7970 7970 6930 6930 6930
50 7970 7970 6930 6930 6930
60 9030 9030 7970 7970 7970
75 9030 9030 7970 7970 7970
100 10770 10770 9030 7970 7970
125 13020 13020 9030 9030 9030
150 13020 13020 9030 9030 9030
200 13690* ‡ 13690 13690 10770 9030
250 17030* ‡ 17030*‡ 13690 13690 13690
300 20690* ‡ 13690 13690 13690
350 16550* ‡ 16550 16550
400 16550 16550
500 19970* ‡
600 22030* ‡
700

WITHSTAND RATING
[B] 22,000 AMPS RMS SYMMETRICAL
575 VAC STD
[B] 50,000 AMPS RMS SYMMETRICAL
Effective January 1, 2011 / Cat v11 200-480VAC STD
Prices subject to change without notice [C] 100,000 AMPS RMS SYMMETRICAL
‡ Available with “B” Breaker only 200-480VAC STD
* Oversized Enclosure

Effective: January 1, 2011. Replaces all previous prices.


Prices subject to change without notice.

Hubbell Industrial Controls, Inc. - Metron Fire Pump Control Division | 4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800 · Fax: 336-434-2801 | Email: salesmail@metroninc.com · www.metroninc.com
MSC0212 v11
MP300 ACROSS THE LINE
FULL SERVICE ADDITIVE PUMP CONTROLLER

STANDARD FEATURE SELECTION [ ] PUMP ROOM TEMPERATURE


Price of controller includes the following local visual THERMOSTAT MOUNTED ON
LED indications: Power On, Phase Reversal, EXTERIOR OF ENCLOSURE
System Fault, and Test Operation. [ ] NEMA 2 RATED $42
Standard Default Volt Free (Dry) Contacts include: [ ] NEMA 4 RATED $160
Power Available, Phase Reversal, Pump Running, [ ] LOW SUCTION CUT OFF PRESSURE
and Controller not in Auto. SWITCH (externally mounted) $500
In addition to the above LED indications a [ ] MODBUS COMMUNICATION via RS485
maximum of twelve (12) user specified alarm STANDARD
conditions can be displayed on the Liquid Crystal
ENCLOSURES
Display (LCD) display of the Operator Interface
[ ] NEMA 2 STANDARD
Display (OID). A maximum of nine (9) additional
[ ] NEMA 3R $375
volt free (dry) contacts can be added. Below is a
[ ] NEMA 3R (Oversized Enclosure, denoted
list of possible alarm conditions. Consult factory for
by asterisk (*) on page 1) $640
alarm conditions not listed.
Quantity
[ ] NEMA 4 $1200
Alarm Dry of [ ] NEMA 4 (Oversized Enclosure, denoted
Displayed Cont Contacts by asterisk (*) on page 1) $2200
Description on OID acts Required
LOW PUMP ROOM TEMP [■] [■] [ ] NEMA 4X PAINTED STEEL $1600
RESERVOIR LOW [■] [■] [ ] NEMA 4X PAINTED STEEL (Oversized
RESERVOIR EMPTY [■] [■] Enclosure, denoted by asterisk (*) on
RESERVOIR HIGH [■] [■] page 1) $2600
FLOW METER ON [■] [■] [ ] NEMA 4X (UNPAINTED 304
RELIEF VALVE OPEN [■] [■] STAINLESS STEEL) $2500
GAS DETECTION [■] [■] [ ] NEMA 4X (UNPAINTED 304
LOW SUCTION PRESSURE [■] [■] STAINLESS STEEL) (Oversized
LOW FIREWATER PRESSURE [■] [■] Enclosure, denoted by asterisk (*) on
LOW PURGE PRESSURE [■] [■] page 1) $3750
HIGH GEAR OIL TEMP [■] [■] [ ] NEMA 4X (304 PAINTED STAINLESS STEEL)
LOW GEAR OIL PRESSURE [■] [■] CONSULT FACTORY
HIGH VIBRATION [■] [■] [ ] NEMA 4X (UNPAINTED 316
EMERGENCY POWER ON [■] [■] STAINLESS STEEL) $4500
PUMP ROOM DOOR OPEN [■] [■] [ ] NEMA 4X (UNPAINTED 316
Maximum number of additional Alarms is 12 STAINLESS STEEL) (Oversized
Maximum Number of contacts, including Enclosure, denoted by asterisk (*) on
default contacts, can not exceed 9. Each page 1) $6875
Alarm Condition can have a maximum 3
contacts. [ ] NEMA 4X (316 PAINTED STAINLESS STEEL)

OPTIONS CONSULT FACTORY


[ ]H SPACE HEATER [ ] NEMA 12 $25
[ ] WITH THERMOSTAT $320 [ ] REMOVABLE GLAND PLATE $250
[ ] WITH HUMIDISTAT $320 [ ] PURGE SYSTEM, Type Z System, per
[ ]W OMIT LEGS, WITH 3" (76.2 mm) NFPA 496 suitable for Class I, Division 2,
CHANNELS N/C Group C/D CONSULT FACTORY
[ ] EXPORT CRATING – SUITABLE FOR
BELOW DECK STORAGE $997 PLUMBING
[ ] 300 PSI STAINLESS STEEL FOR
SALTWATER/FOAM Standard
[ ] 600 PSI STAINLESS STEEL FOR
SALTWATER/FOAM $120