Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Power Systems POWER SYSTEMS TOPICS 111

Paralleling Switchgear:
Documenting the Sequence of Operation with Charts
The sequence of operation for a paralleling left) may not clearly illustrate the timing of events
switchgear project can be complex. Because or combine normal operation with how the system
no two power systems are exactly the same, responds to failure. Kohler’s unique chart-based
each should be custom-designed to meet the sequence of operation (below, right) offers a
requirements and challenges associated with the number of benefits, including step-by-step
project application. To reduce guesswork and explanation of sequence, timing and response
ambiguity during system design and operation, to failure. These multipurpose charts can also
Kohler Power Systems has developed sequence be used for submittal reviews, test procedures
charts that document how a system will respond to and operation and maintenance manuals.
both normal operations and system failures. This They provide a single point of reference when
intuitive approach helps ensure that the system will seeking to understand the operation of the
operate as designed with no surprises. paralleling switchgear.

A concise, detailed sequence of operation is This article describes the sequence chart
perhaps the single most important step when approach, how a chart is custom-created for an
designing paralleling switchgear (or any system individual system, and its benefits in the design,
capable of automatic operation). A traditional testing and training processes.
narrative-based sequence of operation (below,

Section 1 Modes of Operation SEQUENCE CHART (EXAMPLE)

UA Bus A GMA Gen Bus GMB Bus B UB


1.1 Emergency Mode
INITIAL
1.1.2 Return of utility STATE
X E O D O E X

The return to utility is controlled by the return to


1.1.1 Loss of utility utility control switch STEP EVENT RESPONSE IF FAIL
1 Utility A and utility B out of tolerance. Utility A Failure timer starts. A
The loss of starts engine start delay timer in the
PLC. If this timer expires, than the following Return to utility control switch
Utility B Failure timer starts. B
sequence occurs:

1. The closed utility breaker opens. Manual The system remains on generator
2 Both utility failure timers expire or
one timer expired while the other
Utility breaker UA opens. C
power until the operator depresses the is still timing. Utility breaker UB opens. D
2. The generators start. Return or Auto pushbutton. The Utility All available generators start.
stable timer does not time.
3. The first generator to reach 90% of rated Required GOL Bypass timer starts.
voltage and frequency closes onto the bus. 3 Utility breaker UA is open. Bus A Open Transfer timer starts.
First-on logic prevents both generators from When utility returns, the utility stable
closing onto the bus simultaneously. Auto
timer in the PLC starts. When the utility Startup Shed Option:
Based on the Load-Management settings,
stable timer expires the system loads on bus A are shed.
4. The other generator synchronizes to the automatically starts the return to utility
bus. When synchronized, its circuit breaker sequence. 4 Utility breaker UB is open. Bus B Open Transfer timer starts.
closes.
Startup Shed Option:
5. With both generators on-line, the tie breaker If the system is on generator
Based on the Load-Management settings,

closes. Return loads on bus B are shed.


power and utility power is available,
depressing the Return pushbutton 5 The first generator reaches rated
voltage and frequency.
The first generator breaker closes.
NOTE: Using the HMI, the operator can initiates the return to utility sequence.
preset the system to automatically signal a
load shed and then close the tie breaker if 6 The remaining generators independently The remaining generators independently synchronize to E, F
the second generator fails to go on-line. reach rated voltage and frequency. the bus and close their respective circuit breakers.
If open transfer mode is selected
6. If the generator management control is in
AUTO, the system will monitor the power 1. The tie breaker and the generator breakers 7 Required generators are online and the Generator main breaker GMA closes. G
demand of the load, if the load demand is open. bus A Open Transfer timer expired.

below the setpoints set by the operator, the


system will automatically take a generator 2. After the open transfer delay timer expires, 8 Generator main breaker GMA is closed. Bus A is on generator power.
off-line. If the load should increase, the the utility breaker closes.
system will automatically place the Required GOL Bypass timer stops.
generator back on-line. See section 5.7 for a 3. The generators shut down after completing
description of the generator management a cool down cycle. Generator Stabilization timer starts.

logic. 9 Generator Stabilization timer expires and Generator main breaker GMB closes. H
4. bus B Open Transfer timer expired.
7. If the system becomes overloaded or if a If closed transfer mode is selected
generator fails, the system will close a set of
normally open dry contacts signaling 1. The generators synchronize to the utility. 10 Generator main breaker GMB is closed. Bus B is on generator power.
downstream load to shed.
2. When synchronized, the utility breaker
closes. 11 Bus A and B on generator power. Startup Shed Option: I
Based on the Load-Management settings,
3. The generators soft (ramp) unloads. loads are added to the bus A and B.
Generator Management Option:
4. When the power flow across the tie breaker Becomes active if in Auto and all loads have been added.
reaches its unloaded trip point, the tie
breaker and the generator breakers open.
UA Bus A GMA Gen Bus GMB Bus B UB
FINAL
5. The generators shut down after completing STATE
a cool down cycle. O E X E X E O

TRADITIONAL Narrative-Based Chart KOHLER Chart-Based Sequence of Operation

KohlerPower.com ©2016 by Kohler Co.


POWER SYSTEMS TOPICS 111

DESIGNING A PARALLELING SWITCHGEAR PROJECT While progressing through each design A NEW APPROACH –
There are four distinct stages of designing a paralleling switchgear system.
stage, it is important to review decisions SEQUENCE CHARTS
made in the prior stages to be sure they
The unique charts developed by Kohler
1. Creating the single-line drawing 3. Selecting controls remain valid and make any necessary
Power Systems are a distinctive approach
The single-line drawing illustrates Controls enable a system to perform adjustments if changes are made. For
to documenting the sequence of operation.
how components of the electrical the specified sequences, allow for example, if the drawing is revised to add
These intuitive charts offer benefits for
system are connected and the operator interaction and provide all a bus tie breaker to the single line, it is
everyone involved in the design and
available routes through which required metering and protection. important that the sequence is updated to
operation of the project.
power may travel in the system. During the control selection phase, indicate the purpose of the tie breaker and
• They eliminate the ambiguity of knowing
consideration should be given to its role in the sequence of operation. how the system responds to both normal
2. Establishing the sequence operations and system failure.
of operation both the level and redundancy of
Each of the four stages used to design • They are easier to read than a typical
The sequence of operation describes the automatic controls, as well as
paralleling switchgear is vital to the creation flowchart.
the steps the system will take to to any manual controls required for
of a cohesive system. However, the most • They clearly show system response, timing
change from one state to another, operator intervention in the event of of response, and what the system and
challenging – and often the most important
an automatic control failure. operator can do if the system fails to
such as moving from “on utility for proper operation – is establishing the respond properly.
power” to “on generator power.” 4. Determining the switchgear structure sequence of operation. This is especially • They provide a checklist for testing and
A well-written sequence will describe The structure of the paralleling important for complex projects with commissioning the paralleling switchgear.
both normal operation and any switchgear lineup is the physical multiple utilities, where a detailed and
alternate sequences the system representation of the single line. Each sequence has two charts – the
precise sequence of operation provides the
takes if there is a failure during It contains the circuit breakers, sequence itself and the response to
foundation upon which the project is built.
normal operation. controls and meters. abnormal conditions.
Critical to the sequence of operation is an
• The sequence lists the steps the system
Each stage builds on the previous understanding of how the system works will take from the initial state to the final
one; following them in order is key normally and how it responds if there is a state as well as the expected system
failure in the normal sequence, such as a response to each step.
to a successful project.
breaker failing to open or close. • The response to abnormal conditions
describes the system response and the
action an operator can take if the system
does not respond as expected to an event.
Single-Line Diagram
The chart-based method describes
the operation that a typical paralleling
switchgear sequence takes in a series of
M2
steps that transition from an initial state,
such as “on utility power,” to a final state,
F6
GM2
F4
F5 such as “on generator power.” The number
M1 GM1 G2 of charts for an individual project will vary
G1
F3 depending on the number of normal states
F2
F1
and the different types of transitions, such
as open or closed, between the states.

www.KohlerPower.com
p. 2 Power Systems
POWER SYSTEMS TOPICS 111

THE FIVE STEPS IN CREATING A SEQUENCE CHART


Let’s look at the five steps we take in creating the chart, and how they illustrate – SEQUENCE CHART (EXAMPLE)
in sequence – the system’s loss of both utilities. The sequence to transfer from
UA Bus A GMA Gen Bus GMB Bus B UB
utility power is described in a series of steps. Within each step are an event and 1
INITIAL
STATE
X E O D O E X
a corresponding system response to the event. Simultaneous responses to the
same event are shown as separate response lines. 2 STEP EVENT RESPONSE IF FAIL
1 Utility A and utility B out of tolerance. Utility A Failure timer starts. A

THE FIVE STEPS IN CREATING A The power of the chart becomes evident in Utility B Failure timer starts. B
the next step of the sequence. When both
SEQUENCE CHART utility failure timers expire or one timer 3 2 5 Both utility failure timers expire or one Utility breaker UA opens. C
DETERMINE THE INITIAL STATE expires while the other is still timing, the timer expired while the other is still timing.
Utility breaker UB opens. D
1 following things happen simultaneously:
The initial state shows the status All available generators start.
of each breaker in the power transfer Required GOL Bypass timer starts.
• Utility breaker UA opens
sequence and the power status of each 3 Utility breaker UA is open. Bus A Open Transfer timer starts.
bus in the system. • Utility breaker UB opens
Startup Shed Option:
• All available generators start Based on the Load-Management settings,
In the initial state, the system is on utility loads on bus A are shed.
power, Utility Breaker A (UA) and Utility • Required GOL (Generator Online) 4 Utility breaker UB is open. Bus B Open Transfer timer starts.
Breaker B (UB) are closed and main Bypass timer starts
breakers Generator Main A (GMA) and Startup Shed Option:
Based on the Load-Management settings,
Generator Main B (GMB) are open. The The chart not only shows how a system loads on bus B are shed.
chart shows the status of each breaker responds to an event but also when
5 The first generator reaches rated The first generator breaker closes.
that is part of the power transfer sequence each response occurs. By showing each voltage and frequency.
and the power status of each of the three response on a separate line, the operator
buses in the system. can refer to the corresponding step on the 6 The remaining generators independently The remaining generators independently synchronize to E, F
“response to abnormal conditions” chart reach rated voltage and frequency. the bus and close their respective circuit breakers.
DEFINE THE TRIGGERING EVENT (below) to determine how to correct an
2
The triggering event starts the sequence. “if fail” scenario. 7 Required generators are online and the Generator main breaker GMA closes. G
Examples might be the receipt of a bus A Open Transfer timer expired.

remote start signal, the utility being out of 4 LIST THE FINAL STATE OF THE SYSTEM
tolerance or an operator pushing a button. The final state of the system is described 8 Generator main breaker GMA is closed. Bus A is on generator power.
For example, in Step 1, when UA and UB for each breaker within the power transfer
Required GOL Bypass timer stops.
are out of tolerance, both the UA Failure sequence and the power status of each
timer and the UB Failure timer start. bus in the system. Generator Stabilization timer starts.

9 Generator Stabilization timer expires and Generator main breaker GMB closes. H
The “if fail” column directs the operator to DETERMINE “IF FAIL” SCENARIOS bus B Open Transfer timer expired.
5
the corresponding letter on the “response Each system response is reviewed to
to abnormal conditions” chart, explaining determine if an “if fail” scenario is needed. 10 Generator main breaker GMB is closed. Bus B is on generator power.
how the system reacts if it does not In general, an “if fail” scenario is required
respond as expected. In this example, for any response that involves a breaker
the “if fail” describes the response that opening or closing or a timer starting. This 11 Bus A and B on generator power. Startup Shed Option: I
occurs if utility power returns before the step pre-plans how the system should Based on the Load-Management settings,
loads are added to the bus A and B.
failure timers expire. respond if a breaker fails to open or close
Generator Management Option:
or if something happens and a fail-safe Becomes active if in Auto and all loads have been added.
LIST EACH EVENT (STEP) AND timer expires. Responses that require an
3
CORRESPONDING RESPONSE “if fail” scenario include a generator failing
Each step required to transition from initial to start, a generator failing while running 4
FINAL
UA Bus A GMA Gen Bus GMB Bus B UB

state to desired final state is described. or generators becoming overloaded. In STATE


O E X E X E O
Each row in the sequence lists the an “if fail” scenario, the “if fail” column
required change in system state and the in the sequence chart references the
corresponding system response. For corresponding step in the “response to
example, if a system is performing an open abnormal conditions” chart, describing the
transfer back to the utility after a power system’s automatic response to that failure
outage, one of the events might be the and the actions an operator should take to
opening of the generator main breaker correct the system.
and the startup of the open transfer timer
(event/corresponding system response).
See chart on page 5.

www.KohlerPower.com
p. 4 Power Systems
POWER SYSTEMS TOPICS 111

THE PAYOFF OF KOHLER’S CHART-BASED APPROACH


RESPONSE TO ABNORMAL CONDITIONS CHART (EXAMPLE) Implementing a chart-based sequence Kohler’s chart-based approach to the
of operation instead of a narrative- sequence of operation provides a more
STEP FAIL EVENT SYSTEM RESPONSE OPERATOR ACTION based sequence provides a way to effective way to look at sequencing. It
A Utility A power returns Bus A remains on utility A. No operator action required.
comprehensively cover the “what ifs” ensures the stage is described without
before Utility A Failure
timer expires. while the project is still in the design stage. ambiguity and each step is clearly
B Utility B power returns Bus B remains on utility B. No operator action required. In addition, the sequence of operations explained. More importantly, if a system
before Utility B Failure
timer expires.
chart serves as a checklist during testing failure occurs, the system’s response
to provide better quality assurance. In is already known – often eliminating
C Utility breaker Utility A remains failed, Option #1: Reset the Fail to Open alarm. System attempts to open
UA fails to open. Utility B remains failed: utility breaker UA. When breaker opens, transfer automatically many cases, by simulating the sequence guesswork and minimizing system
Bus A is without power.
Generator main breaker
continues.
of operation and documenting it, the interruption. Making complex systems
GMA does not close. After Option #2: equipment performs at a higher level, simple – that’s the Kohler difference.
the required generators Manually open utility breaker UA. Transfer automatically continues if
are online, generator main system is in Auto. onsite start-up time decreases and
breaker GMB closes.
Option #3: 1. Place system in Manual. 3. If required, shed load.
reliability increases.
2. Manually open utility 4. Manually close generator
breaker UA. main breaker GMA.

Utility A remains failed, No operator action required.


Utility B returns: Bus A is
without power. The system
transfers bus B from generator
power to utility B power
following the expiration of
the Utility B Stable timer.

Utility A returns, Utility B Operator may manually transfer bus B from generator power to utility
remains failed: Bus A remains A power.
on utility A. Bus B remains on
generator power.

Utility A and Utility B return: No operator action required.


Bus A remains on utility A.
The system transfers bus B
from generator power to utility
B power following the expiration
of the Utility B Stable timer.

D Utility breaker UB Utility B remains failed, Utility A Option #1: Reset the Fail to Open alarm. System attempts to open
fails to open. remains failed: Bus B is without utility breaker UB. When breaker opens, transfer automatically
power. Generator main breaker continues.
GMB does not close.

Response to Abnormal Conditions Chart

www.KohlerPower.com
p. 6 Power Systems
POWER SYSTEMS TOPICS 111

Power Systems
Call toll-free in the U.S. and Canada
+1-920-565-3381, or visit
KohlerPower.com

KOHLER POWER SYSTEMS


Kohler, Wisconsin 53044
USA
Printed in U.S.A.
G26-22 5/16

©2016 Kohler Co.


All rights reserved. This white paper may not be reproduced or republished
in any form or in any media without prior written permission from Kohler Co.

You might also like