4CAE000704 Relion Catalogue Web
4CAE000704 Relion Catalogue Web
Protection, control
and monitoring
For transmission lines, substations,
railways, power generation & renewables.
• Advanced protection,
control and monitoring solutions
• At the forefront of IEC 61850
technology
• Future proof applications meeting
digital substation requirements
2 D I G I TA L S U B S TAT I O N 3
— —
Power and automation technology Table of contents
solutions from ABB support the digital
transformation of your business from the
field to the boardroom and everywhere
in between. These solutions enable deep
insight into the power network, asset
004 – 009 Power infrastructure
performance management, energy Substation and Grid evolution.
efficiency and reduced operating costs. Main challenges and expectations.
—
Substation evolution.
From electro-mechanical
—
01 Classical Conventional ABB Ability Digital
Bay
level
Hard-wired Protection & Control Protection and control IEDs Protection and control IEDs
Process
level
Copper Cables and Fibre
Conventional AIS bay Conventional AIS bay DCB with FOCS and Motor Drive
6 R e l i o n ® p r ot e c t i o n a n d c o n t r o l P o w er i n fr a str u ct u re 7
—
Grid evolution.
Changes in the grid
topology and business model.
Trends in modern power grids.
— The trends that are having impact on The requirements and expectations on
02 Traditional and
modern day grid transmission grid technology: substation protection and control will
• Renewable penetration increase. Evolving grids have direct impact
• HVDC on protection and control systems.
• FACTS
• Phase-shifting transformers
• Micro-grids
• Nano-grids
• Electrical mobility
• Charging infrastructure for electric vehicles
• Digital transformation of transportation
• Digitalization of power grids
—
Evolving grid and substation.
Main challenges and expectations.
Requirements for a modern grid.
— —
Fundamental requirements Cyber
on protection and Security
control IEDs • User access control
• Secure communication
• High reliability
• Protocol hardening
• High availability
• Security logging
• High operational performance
• Patch management
• User friendliness and safety
• Cost effectiveness
• Interoperability
— —
Product related Life cycle
expectations requirements
• Scalability • Safeguard investment
• Flexibility and robustness over the entire life cycle
• Ability to facilitate conventional • Backward compatibility
to digital substation transition
10 R e l i o n ® p r ot e c t i o n a n d c o n t r o l P o w er i n fr a str u ct u re 11
— —
Relion® the power of one solution. Relion 670 and 650 series.
For protection, control and monitoring. The power of one.
To cope with any situation, a modern protection IED needs ABB’s high performing series of
to be configurable to fit within its intended application area. intelligent electronic devices (IEDs)
ABB’s solution to this requirement is the Relion® series of IEDs.
The Relion series offers a standardized library network. And in the smart grid, information is
—
—
of functionality on a high performance, common of vital importance, so advanced and accurate
hardware architecture, and provides the flexibility PMU (phasor measurement unit) functionality
03 Relion 670 Family
Relion 670 series
—
and configurability to suit any application area. will present you with the information you 04 Relion 650
• A flexible solution for every application
need to make your smart grid truly smart.
• Support for the most demanding requirements
The Relion series of devices cover the
of protection and control applications
complete protection, control and monitoring With its proven reliability, high accuracy and
• Ordering as pre-configured or customized
needs of your power infrastructure. high performance operation, the Relion family
- Three different hardware casings
devices can be used for the most demanding
(1/1, 3/4 and 1/2 19”)
Advanced control capabilities and system applications for your power system network.
- Advanced protection and control features
modeling, according to IEC 61850 will give you
- Multiple objects
new ways to design and dynamically operate your — - High level of functional integration
03
—
Relion® the power of one solution.
For line protection.
— —
Overhead lines and cables tie the electrical grid together. Cables Overhead lines
Overhead lines are exposed and particularly vulnerable to All encompassing application Applicable for all kinds of lines
everything from bad weather to flora and fauna. across short high-voltage including long, extremely high-voltage
underground cable link traversing series compensated overhead lines
a waterway to a combination deployed in rough challenging terrain.
of cable and overhead line.
—
Line protection solutions.
Relion® REL670, REL650, RED670 and RED650
Distance protection offers extensive protection
application opportunities for overhead lines and cables,
or combinations of overhead lines and cables.
—
05 Line protection
Differential protection is easier An alternative principle for line protection that
performance is quickly becoming the norm is differential
characteristics to integrate and delivers more protection. Differential protection is based on
consistent performance compared Kirchhoff’s laws, stating that all current into
a network node shall add up to zero in an
to distance protection, at the cost ideal system. What this practically means
of an increased hardware and for a line protection application is that the
current that is measured to flow into the line
communication dependency. should also be measured to come out.
Relion REL670 and REL650 offer line distance Series compensated lines X Not available X Not available
—
Line distance protection.
Relion® REL670 and REL650
Line distance protection offers extensive protection
application opportunities for overhead lines and cables,
or combinations of overhead lines and cables.
— The REL670 can offer more integrated • REL670-A42 offers everything included in
06 Line distance
protection options functionality compared to the REL650, REL670-A41, except the phase preference logic
such as full bay control functionality and • REL670-B42 is equal to the REL670-A42, but is
—
07 Ordering options synchrophasors (PMU) functionality. In order intended for 1 ½ or double breaker
for line distance to facilitate this additional functionality, there configurations.
protection
is a larger and more flexible choice in available • REL670-D42 is equal to REL670-A42, and in
hardware compared to the REL650 as well. addition includes synchrophasors (PMU)
functionality by default
REL670 and REL650 include features such as:
• Distance protection with 6 independent zones, REL650 comes in two different variants
for quadrilateral and mho characteristics • REL650-A11 offers a 6 zone distance protection
• Power swing detection and blocking, out-of- function with mho and quad characteristic, load
step and pole slip detection encroachment, power swing detection, out of
• Phase preference logic for the correct tripping step protection, overcurrent, frequency and
of multiple phase-to-earth faults in thermal overload protection. It also includes
compensated networks breaker failure protection, autoreclose and
• Back-up current, voltage and frequency synchrocheck functionality —
REL670 REL650
06
protection • REL650-A12 offers everything included in Distance protection X X
• Switchgear control functionality REL650-A11, and additionally phase preference
Speed < 1 cycle 1 1/2 cycle
logic. This functionality is required for a correct
Characteristic Mho, Quad Mho, Quad
REL670 comes in four different variants phase selection in high impedance or resonance
Zones 2 instances, 6 zones each 1 instance, 6 zones
• REL670-A41 offers a 6 zone distance protection earthed networks
Tripping 1ph/3ph 1ph/3ph
function with mho and quad characteristic, sub
Load encroachment X X
cycle tripping times, load encroachment, phase
Power swing blocking X X
preference logic, power swing detection.
Back-up protection Basic and additions as options Basic
Overcurrent, overvoltage, undervoltage,
Control of entire bay Optional Circuit breaker only
frequency and thermal overload protection are
available as backup protection functions and
included as basic or optional functionality. It
also includes breaker failure protection, —
REL670-A41 REL670-A42 REL670-B42 REL670-D42 REL650-A11 REL650-A12
07
autoreclose and synchrocheck functionality. High speed distance protection X X X X
This variant is used in isolated or high-
Distance protection X X
impedance earthed systems. All other variants
Phase preference logic X X
are intended for directly earthed systems.
Back-up protection Basic and additions as options Basic
Control of entire bay Optional Circuit breaker only
—
Line differential protection.
Relion® RED670 and RED650
Differential protection is easier to integrate and delivers
more consistent performance as distance protection, at the
cost of an increased communication dependency.
— Line differential protection offers an easy, RED670 and RED650 include such features as: RED670 comes in four variants RED650 comes in one variant
08 Line differential
protection options accurate and secure alternative to line distance • Differential protection from 3 to 5 line ends, • RED670-B33 offers 2 – 5 line ends differential • RED650-A11 offers a 3 ended line differential
protection in line protection applications, but with up to two in-zone transformers protection with the possibility for increased protection function, with an option for an in-
—
09 Ordering options requires communication between the line ends. • Dedicated IED communication, performance over a 2 Mbit data link, improving zone transformer. It also offers a 6 zone
for line differential or multiplexer support trip time performance. distance protection function with mho and
protection
Relion RED670 and RED650 offer line differential • Back-up current, voltage and • RED670-A42 offers a high speed differential quad characteristic, load encroachment, power
protection and the option for line and cable frequency protection protection with sub-cycle trip times, and swing detection, out of step protection,
distance protection in the same device. With includes overcurrent, voltage, frequency and overcurrent, frequency and thermal overload
its high performance, high bandwidth and In addition, RED670 can include all the thermal overload protection. These are included protection. It includes breaker failure
low latency communication channel, RED670 functionality available in REL670, resulting as basic or optional functionality. It also protection, autoreclose and synchrocheck
delivers subcycle trip times in both its in a single device capable of both line includes breaker failure protection, autoreclose functionality.
differential and distance protection functions. differential and line distance protection. and synchrocheck functionality.
• RED670-B42 is equal to the RED670-A42,
RED650 provides a predefined, preconfigured but is intended for 1 ½ or double breaker
variant with a small form factor and a configurations.
standardized application solution. • RED670-C42 is equal to RED670-A42, and
includes the high speed, sub cycle distance
RED670 and RED650 can either be outfitted protection as the backup functionality to the
with their own dedicated long/medium- existing high speed line differential protection.
range communication module, or use
a short-range communication channel
to a multiplexer so that an independent
communication network can be used.
— —
08 RED670 RED650 09 RED670-B33 RED670-A42 RED670-B42 RED670-C42 RED650-A11
Differential protection X X High speed differential protection X X X
Speed < 1 cycle 1 1/2 cycle Differential protection X X
Communication speed 64 kbit/s or 2 Mbit/s 64 kbit/s High speed distance protection Optional X
Line ends 2-5 2-3 Distance protection X
In-zone transformer X X Basic and Basic and Basic and Basic and
Tripping 1ph/3ph 1ph/3ph Back-up protection additions as additions as additions as additions as Basic
options options options options
Distance protection X X
Circuit breaker
Back-up protection Basic and additions as options Basic Control of entire bay Optional
only
Control of entire bay Optional Circuit breaker only
Single breaker, Single breaker, Double breaker, Single breaker,
Time synchronization PPS, IRIG-B, GPS, IEC/IEEE 61850-9-3 PPS, IRIG-B, IEC/IEEE 61850-9-3 Configuration
2-5 line ends 2-3 line ends 2-3 line ends 2-3 line ends
20 R e l i o n ® p r ot e c t i o n a n d c o n t r o l S u bstatio n s 21
—
Relion® the power of one solution.
For substations.
We deliver essential substation automation, high-voltage protection,
control and monitoring solutions for today’s power networks, — — —
ensuring they are ready for tomorrow’s challenges. Control applications Busbar protection Transformer protection
and voltage control
Advanced and ready made • Low impedance busbar protection
control solutions for interlocking for up to six bus bar zones
• Capability of protection transformer
and reservations
with differential protection and
As urban centers grow ever larger and the Substation solutions • Capability of using conventional
restricted earth fault
demand for electricity accelerates, power Substations are integral parts of a power hard wired measurements and
generation itself has entered a transitional phase. network, built to ensure grid infrastructure IEC61850-9-2 sampled values in
• Performing voltage regulation with
operates safely, reliably and efficiently. the same IED
the same IED
Traditional methods such as large-scale thermal Statistically, the number of faults in a substation
or hydro generation still dominate, but a new is substantially lower than in the more exposed
era of decentralized electricity generation overhead power lines, but the strategic
is developing. Decentralized generation is importance of a substation as a point where
characterized by small islands of balanced power everything in a power network comes together
supply and demand. But the intermittent nature makes the consequences of electrical failure
of this kind of generation, for example small wind even more severe. Reliability and capacity to
turbine or solar photovoltaic installations, makes minimize equipment damage is therefore vital.
a stable traditional electrical grid more important
than ever, and this is driving the development and ABB grid automation delivers an extensive
increased complexity of modern power networks. portfolio of protection, control and monitoring
solutions to keep substations safe and secure.
It is an accident of geography that many
power generation sites are situated far
from the centers of power consumption,
which means efficient ways of transporting
large amounts of electricity over longer and
longer distances is critically important.
—
Circuit breakers and disconnectors.
Relion® REC670, REC650 and REQ650
— Circuit breakers and disconnectors The REQ650 provides ideal breaker failure • The REC650-A02 offers a configured solution Breaker backup protection may also be included
10 Bay control
unit varieties Circuit breakers, disconnectors and earthing protection, enabling high-speed back-up tripping for a single circuit breaker, and up to 9 in ABB’s REC670 bay control unit. REC670 offers
switches typically comprise the bulk of the of surrounding breakers, and retripping of the disconnectors and earthing switches. It is an extensive back-up protection function
—
11 Ordering options components inside a substation. There are many target breaker. REQ650 breaker protection is the suitable for single or double busbars library, which it shares with all other protection
for apparatus control types of breakers and switches, and many ways ideal choice for refurbishment projects, where • The REC670-A30 is very similar to the products in the 670 and 650 series. REC670
of configuring the connections between them. old protection relays need to be replaced. REC650-A02, but offers the possibility for more delivers the same high-performance protection
binary inputs and outputs and can include functionality as a dedicated protection device.
Circuit breaker and disconnector control ABB’s REC650 and REC670 offer various back-up protection functionality
Driven and controlled by the substation pre-configured variants to cover the • The REC670-B30 and C30 extend upon the
automation system, IEDs reserve, interlock and different switchgear configurations that REC670-A30 offering by including control for
actuate the circuit breakers and disconnectors exist in substations around the world. more switchgear, namely 2 circuit breakers with
that enable the electrical grid to operate. 13 switches, and 6 circuit breakers with 24
Interlocking and reservations switches for the B30 and C30 configurations
Circuit breaker protection REC670 and REC650 have ready respectively
Circuit breakers typically combine failure made logic function blocks for bay • Phasor measurement (PMU) functionality is an
protection with autoreclose, synchro-check and station wide interlocking. option in all REC670 configurations, however
and system back-up protection of functions the REC670-D30 configuration includes this
related to current, voltage and frequency. In IEC 61850 based reservation philosophy function by default, readily configured to be
ABB Relion protection IEDs this functionality prevents multiple operations of more used. Functionality wise, the REC670-D30
is basic or optional, and also available in than one apparatus in the substation. configuration is equivalent to the REC670-A30.
a product specifically designed for this The REC670 may also be ordered as a
purpose – the REQ650 breaker protection customized device, where all functionality
Intelligent Electronic Device (IED). is optional
— —
10 REC670* REC650** 11 REC670-A30 REC670-B30 REC670-C30 REC670-D30 REC650-A02 REQ650-B11
Circuit breaker, disconnector and
Up to 6 circuit breakers and 24 switches Up to 1 circuit breaker and 9 switches
earthing switch control
1 circuit
Generic switch control Up to 150 double point objects Up to 30 double point objects 1 circuit 2 circuit 1 circuit 1 circuit
1 ½ circuit breaker,
breaker, breakers, breaker, breaker,
IEC 61850 Edition 1 and 2 Edition 1 and 2 breaker double busbar,
double busbar double busbar double busbar double busbar
with PMU
Reservation With or without confirmation
Interlocking Pre-defined or user defined Control (CB / SW) 1/9 2 / 13 6 / 24 1/9 1/9
Operation Direct or select-before-operate, with or without enhanced security Voltage regulation and
Optional
OLTC control
Protection Optional X
Control functionality can be optionally integrated in
*
all Relion 670 series products, except for RES670 Synchrocheck X X X X X X
** All Relion 650 series products include Autoreclose X X X X X
basic control for 1 circuit breaker
IEEE 1344 / C37.118 (PMU) Optional
IEC 61850-9-2 8 SV streams (Optional) 4 SV streams (Optional)
24 R e l i o n ® p r ot e c t i o n a n d c o n t r o l S u bstatio n s 25
—
Transformer protection, —
RET670 RET650
Voltage regulation
For single transformer or up to 8 parallel
For single transformer
transformers*
Tap changer control
—
Busbar protection.
Relion® REB670, REB650 and REB500
The heart of a substation is its busbar configuration. Although typically designed
in single or double busbar systems, there are many other designs, each with
specific advantages. ABB’s Relion family of IEDs provides the flexibility to adjust
to any busbar configuration, and delivers unrivaled reliability and performance.
Instead, low impedance differential In a distributed solution, a single, central IED Number of bays 60 24 Not applicable
protection is much easier to incorporate connects many satellites (bay units), which Number of zones 32 6 3
into modern protection systems, is are connected to the process. Typically, a
considerably safer and considered the best distributed solution scales much better, as the
solution by utilities all over the world. IO is not concentrated on a single IED, which also —
drastically reduces the wiring needed between 16 REB670
REB670-A20 REB670-A31 REB670-B20 REB670-B21 REB670-B31 REB500 REB650-A03
Customized
ABB grid automation provides products for different parts of the installation. Instead of
Low
two different approaches to low impedance many cables coming from every feeder to a Differential High
Low impedance, centralized impedance,
differential protection applications: central location, a single optical fiber cable principle impedance
distributed
REB670 for centralized and REB500 for between the bays and the central IED suffices. Measurement Three-phase Single-phase Three-phase
distributed busbar protection solutions. Zones 2 2 2 2 2 6 32 3
Although communication delays and the Bays 4 8 12 12 24 24 60 X
A centralized solution puts all process synchronization of many measurement points
Overcurrent /
inputs and outputs in a single place - the from different places reduces performance to end fault Optional X
busbar protection IED. This reduces IED some extent, it is still well within acceptable (and protection
hardware costs substantially, because it accepted) levels. While the additional hardware Voltage and
eliminates the need for additional hardware increases initial costs of a distributed installation current backup X X X
protection
in all bays, unlike a distributed solution. compared to a centralized solution, subsequent
installation costs can be reduced due to the Breaker failure
Optional X
protection
reduction of wiring throughout the installation.
Circuit breaker
REB500 delivers a high-performance solution, X X X X X Optional X
monitoring
with industry leading reliability and sub cycle
performance that scales up to very complex
system topologies and many connected feeders.
28 R e l i o n ® p r ot e c t i o n a n d c o n t r o l 29
—
Phasor measurement unit.
Relion® RES670
The Relion 670 series of protection and control intelligent
electronic devices (IEDs) can provide power system AC voltages
and currents as phasors.
— Enhanced monitoring enables power network Depending on the product, these devices
17 Available phasor
measurements operators to take fast remedial action and can transmit up to 32 analog phasors in two
per product type use existing power systems more efficiently. different data streams. The high accuracy of
— Better information supporting fast, reliable voltage and current measurements eliminates
18 Ordering options emergency actions reduces the need for relatively the need for any external measurement
for standalone phasor
measurement units high transmission margins made necessary transducers, which makes the 670 series ideal
by potential power system disturbances. for use in all types of Phasor Measurement
Unit (PMU)-based applications.
—
17 RES670 REL670, RED670, REC670 REG670 RET670
Phasors 32 8 16 24
Systems 2 1 2 1
Time synchronization GPS, IRIG-B, IEC/IEEE 61850-9-3
IEEE 1344-1995 and IEEE Std C37.118-2005 (Both measurements and data communication),
IEEE Std C37.118.1-2011 and IEEE Std C37.118.1a-2014 (Measurements),
Compliance IEEE Std C37.118.2-2011 (Data communication)
—
18 RES670-A20 RES670-B20 Customized
Configuration 3 bays, single busbar 6 bays, double busbar
C37.118 2011 and IEEE1344 reports 2 2 2
Phasor data 16 32 Up to 32
Analog data 8, up to 24 16, up to 24 Up to 24
Binary data 8, up to 24 16, up to 24 Up to 24
System protection Basic and optional Optional
30 R e l i o n ® p r ot e c t i o n a n d c o n t r o l R a ilw ay s 31
—
Relion® the power of one solution.
for railways.
ABB delivers a comprehensive range of rail and urban transport
infrastructure solutions for AC systems that ensure safe,
reliable power delivery to all essential rail assets.
Rapid urbanization plus the urgent need to Relion RER670 applications include protection, Line protection Catenary protection Transformer protection Control and monitoring
reduce carbon dioxide emissions are driving control and monitoring of AT and BT catenary • Line distance protection • Catenary distance • Transformer • Control for up
substantial new interest and investment in systems, single and double phase power • Scheme communication protection for 2 catenaries differential protection to 15 apparatuses
the transportation sector. Because of their transformers, single and double phase • Fault location • Scheme communication • Transformer under • Tap changer control
specialized nature, traction power protection transmission lines, and incorporate control • Back-up protection • Fault location impedance protection and supervision
and control systems can be challenging. and communication functionality based on IEC • Synchrocheck • Back-up protection • Restricted earth fault • Circuit breaker monitoring
61850 edition 2. The RER670 is designed to be and auto-reclose • Synchrocheck protection
With the Relion RER670, ABB offers a single used on 16.7 Hz, 50 Hz and 60 Hz networks. and auto-reclose • Transformer tank
solution encompassing the entire scope of railway overcurrent protection
power delivery; transmission, transformation With over 150000 Relion devices installed • Transformer energization
and delivery. In a single device it supports globally, RER670 has a robust family history control (16.7 Hz)
single and two phase systems in isolated, and is a testament of the trust that • Back-up protection
compensated or solidly earthed networks. has enabled numerous users to secure • Synchrocheck
their power infrastructure. • Monitoring of power
system harmonics
32 R e l i o n ® p r ot e c t i o n a n d c o n t r o l R a ilw ay s 33
— —
Railway solution. 19
Transformer Line Catenary Back-up Apparatus Auto- Synchro- Transformer Tap changer Harmonic I/U vector
protection protection protection protection control reclose check energization control control monitoring shift
A51 B60 B70 C61 H37/H38 H52 H51 H55 H53/H54 M27 supervision
Transformer
X X Optional Optional X Optional X
protection
Catenary
X X Optional X
protection
—
Relion® the power of one solution. Technology may change, but safety, quality and reliability remain the top
requirements of any power generation source. Whether the generation solution is
For power generation and renewables. large or small, centralized or distributed. In the end, every minute not spent
producing energy has tremendous financial and social consequences. ABB is at the
forefront of the digitalization that is sweeping over the power generation space.
We deliver secure power generation solutions by continuously adapting Our digital substation portfolio enables customers to build for the future - today,
to the active system situation, guaranteeing reliability and performance. while still enjoying the long-term ABB know-how and support of the existing market.
—
Generator protection,
control and monitoring.
Relion® REG670
Relion REG670 Intelligent Electronic Device (IED) is a protection and monitoring
solution for generators, prime movers and step-up transformers in hydro, pumped
storage, gas fired, combined cycle, steam, and cogeneration power plants.
— Supported by ABB’s extensive experience No changes are necessary in the primary circuit
21 Ordering options
for generator protection in generator protection solutions, REG670 or grounding resistor, so the design, installation
achieves a new level of performance with up and commissioning of the protection system
to 24 analog inputs, and the availability of is simple and fast. The third harmonic-based
IEC61850-9-2 process bus technology. Main 100 percent stator earth fault protection
and back-up protection can be integrated utilizes the differential principle, providing
into one IED, and additional components like high sensitivity and security to ensure proper
transformers can be included in the scope of operation even in low load conditions.
protection. This reduces the number of IEDs
needed to protect the generating station. It REG670 comes in 3 different
also increases availability, simplifies installation pre-configured variants, as well as a
and reduces lifecycle costs relating to completely customizable solution:
commissioning, maintenance and spare parts. • REG670-A20 offers a solution for a typical
generator protection application with
generator differential and back-up protection
Using an advanced and innovative including 12 analog inputs transformers in a half
filtering technique, REG670 can 19” case size
• REG670-B30 offers enhanced generator
provide integrated sub protection application with generator
synchronous resonance differential and back-up protection, including
24 analog inputs in a full 19” case size.
protection for turbo generators. Optionally, pole slip protection, 100% stator
earth fault protection and overall block
A REG670 generator protection scheme delivers
differential protection can be added —
REG670-A20 REG670-B30 REG670-C30
maximum dependability and availability, 21
• REG670-C30 offers complete unit protection,
featuring extremely fast detection criteria Generator differential,
including generator and generator transformer Generator differential and Generator and block
(typically 15 milliseconds) for generator transformer differential and
backup protection transformer protection
protection with 24 analog inputs in a full 19” backup protection
differential protection, while maintaining a high
case size. Optionally pole slip protection Generator differential protection x x x
level of security with DC offset functionality.
and 100% stator earth fault protection can Two winding transformer
Among the REG670’s many functions, is injection- Optional x
be added differential protection
based 100 percent stator and rotor earth fault
Three winding transformer/
protection, as well as third harmonic-based 100 Optional x
block differential protection
percent stator earth fault protection. These
solutions optimize the protection system’s Extensive function selection included,
Backup protection
and additional functionality available
cost-performance ratio in relation to the
Apparatus control Optional
importance or size of the generating station.
ABB’s innovative solution enables injection IEEE 1344/C37.118(PMU) Optional
via a neutral point VT, or even an open-delta IEC 61850-9-2 8 SV streams (Optional)
—
Protection and control manager for IEDs.
PCM600
—
22
Application configuration allows you to easily With the signal matrix, you can connect the
create, change or view an IED configuration. process termination with any I/O connection
The colors of the function blocks relate to point in the configuration in the same way as
the function status in the configuration: the traditional trip matrix.
Ethernet Switch
unconnected (gray), partially connected
PCM600 IED
In remote office (yellow) or fully connected (green).
Ethernet Switch
Gateway Gateway IED
With firewall With firewall
PCM600 IED PCM600 With the graphical display editor, you can easily The parameter setting tool allows you to change
On substation network Connected to the engineer the single line diagram according to or view all the parameters that an IED has,
IED front port
the switchgear arrangement for the IED HMI. for all the setting groups. When reading the
parameters from the IED, you can easily compare
the values in the PC with the ones in the IED.
The graphical representation of protection
characteristics supports you in visualizing, for
example, distance protection parameter setting.
— PCM600 provides versatile functionalities for the • Graphical representation of parameters
22 An overview
of PCM600's efficient entire life- cycle of Relion® protection and control simplifies setting of protection function
management of IED applications. This easy-to-handle tool helps you parameters
ABB's protection
and control IEDs manage your protection and control equipment • Configuration of IED hardware and IED display Tool suite for engineering, integration and testing.
all the way from application and communication • Communication management
— ABB‘s comprehensive suite of tools (PCM600, systems. With many advanced features, the
23 Tool suite configuration to disturbance handling, • Signal matrix for efficient and flexible
IET600 and ITT600) for engineering, integration tools allow you to manage your installation
for engineering, including automatic disturbance reporting. connection of CTs, VTs and binary input and
integration and testing and testing supports you throughout the efficiently in all situations from engineering and
output signals, as well as connection of the
complete lifecycle of protection and control IEDs commissioning to operation and maintenance.
PCM600 interacts with IEDs over the fast and GOOSE (Generic Object Oriented System-Wide
and IEC 61850-based substation automation
reliable TCP/IP protocol via a corporate LAN Events) signals between IEDs
or WAN, or alternatively directly through the • Comparison of configuration between IEDs
communication port at the front of the IED. It and PCM600, as well as SCL (substation —
23
is able to read and write all configuration configuration description language) files at SCD
and setting data of an IED with a single (substation configuration description) import
command. The user interface, workflow • Monitoring of IED signals and events System Engineering .scd Substation Automation System
and the IEC 61850-based data model in the • Integrated disturbance recording IET600
PCM600 are designed according to the same functionalities for scanning and analysis of
philosophy as the Relion protection and disturbance information
control IEDs, ensuring smooth and seamless • Copy/paste and export/import functions to
integration between the tool and the IEDs. allow efficient reuse of existing IEDs, bays
or substations
Top 10 features of the protection and control • Utilizes ABB’s unique Connectivity Package
IED manager PCM600: concept which contains a comprehensive System Testing Managing Relion
• Powerful application configuration for creating description of the IED, consisting of data ITT600 SA Explorer Protection and Control
and monitoring application configuration signals and parameters as well as the IED IEDs PCM600
documentation Process Interface Process Interface
40 R e l i o n ® p r ot e c t i o n a n d c o n t r o l S oft w a re E n gi n eeri n g Tools 41
—
Integrated engineering tool.
IET600
Integrated engineering tool IET600 is designed for configuring IET600 provides powerful graphic editors to design IET600’s communication editors allow fast
IEC 61850-based substation automation systems and applications and configure the substation topology according and easy configuration of the dataflow
to IEC 61850. System engineers can easily define between all IEC 61850-compliant IEDs in the
with IEC 61850 compliant IEDs from ABB and other vendors. the substation layout using the built-in Single Line substation. Built-in consistency checks and
palette of primary equipment, assign internal clear representation of information reduces
and customer-specific names to the devices, and errors during the engineering process.
print the configuration for documentation.
—
Integrated testing tool.
ITT600 SA Explorer
Integrated testing tool ITT600 SA Explorer is designed ITT600 SA Explorer makes GOOSE messages ITT600 SA Explorer allows you to connect to
for easy diagnosis and troubleshooting of IEC 61850-based visible, and presents the transmitted GOOSE any IEC 61850-compliant IED, browse the IED
values both on-line and off-line. The tool configuration, subscribe to IEC 61850 reports,
substation automation systems and applications. allows you to focus on the application behavior send Select-before-operate commands and
and verify the traffic instead of searching review the IED’s response in the built-in event list.
for specific values in GOOSE frames.
abb.com/protection-control