Professional Documents
Culture Documents
tEsT Performance Boiler PDF
tEsT Performance Boiler PDF
tEsT Performance Boiler PDF
.t
,,t
of
CONTENTS
Tests,Emissions
Tests,and NoiseTestsare coveredunder
Jl"""iJiiiJemonstration separate
GUIPINGPRINCIPLES
allowances
7. Degradation willnotbe applicable
to thistest,unlessunforseen
and substantial
delaysoccur.
..,.-t!*r;.-. - . -),
PAITON7 & 8 BOILERPERFORMANCE TESTINGWITHADAROCOAL
12 JUNE 1998 rev. OO
PERFORMANCE
TESTMATRIX
TEST#,f2 = 4 Hours)
(Duration
MEASUREMENT
METHODS
sH and RH spraytemperature
wiltbe measuredwith the stationtemperature
elements.
Terminaltube tempeSfurgsin the superheaterand
reheaterwill be recordedfrom surf;aceTC,s
locatedperABB-CEdrawings00494-1E-9931 and 00494_1E_9932.
GASANALYSTS
. t'
:
j l- '. . '.' -'.--'.-:.:
:{'!i:r.. . ' . - : .j , t t ! . - 1 , l -
r -iJ i:.tu. -':?!L l&1 j sldJ,
"t tf ii{t*t" drlnj|;sg,r rir-.4'&i{
PAITON7 & 8 BOILERPERFORMANCE
TESTINGWITHADAROCOAL
12JUNE1998rev.00
The 02 and gas temperatures will be measuredat each pointof the probegrid along with the
velocityhead measurement.The 02 and temperaturedata wilt be weightaveragedon the basis
of mass flow distributionin the associatedgas ducts. The mass flow distributiondeterminedin
thesetestswill also be usedto weightavemgethe O, and temperature datafromall gas inletand
all gas outletductsfor the efficiencyandAH leakagecalculations.
Duringgas duct probing,care must be takento; insertthe probesto the properdeptheach time,
orientthe probescorrecflywith regardto the directionof gas flow,seal the openingbetweenport
and probewith a rag or somethingto preventair in leakagethroughthe port,and inlure that there
is enoughtime at eachpointfor the gas sampleto travelfromprobeinletto analyzer(as indicated
whenthe 02 measurement reachessteadystateas judgedby the data-taker).
-AIR
TEMPERATURES
weuDryBulbambient
temperatures
willbemeasured
neartheFDfanintet.
Air temperaturesaround each airheaterwill be measuredwith type K or E unshielded
thermocoupleprobeswithinthe respectiveair ducts:
AH SecondaryAir Inlet 2-3 pointgrids AH PrimaryAir Inlet 1-3 pointgrid r
A H S e c o n d a r y A i r o u U e t 2 . 9 p o i n t g r i d s A H P r i m a r y A i r o 1 t l e t ! . 9 b o i n l 6r.r i d
The grid point measurements for each duct will be arithmeticalty 'i ''
averaged.The averageair inlet
temperaturesused for efficienrycalculationswill be weight averagedbised on total FD fan flow
vs. the sum of the individualmill air flows. The ratio will detarminethe split betweenSAH and
PAFIair llows. Eachof the SAH'swilt be assumedto have halfof the totaiSAH air flow and witl
be weightaveragedaccordingly.
Superheater
Outletat Boiler ReheaterOutletat Boiler
SteamDrum ReheaterInletat Boiler
Economizer lnlet at Stop/CheckValve
COAL SAMPLES
Coal samples for tests 1, 2' and 3 will be taken from each operatingfeeder.
These samples will be
taken every 112 hour and be at least 1 liter in volume. ihe samptes from
the feeders will be
combined on a clean sheet of plastic or tarpaulin. The samples will be protected
from drying and
foreign contamination.The samples will be mixed by rolling. The composite
sample will then be
PAITON7 & 8 BOILERPCNiONMANCETESTINGWITHADARO
COAL
1 2 J U N E1 9 9 8r e v . 0 0
ASH SAMPLES
TESTMETHODS
SH AND RH STEAMTEMPERATURE
TESTING
The sHo and RHo steamtemperatures
will be measuredin eachlink,at the boilerouflet.
FW TO SHO PRESSURE
DROPTESTING
REHEATERDIFFERENTIAL PRESSURE( RH ^P )
The RH aP will be calculatedfrom readings
of individualpressuretransmittersconnectedat the
boilerto the RHt and RHo lines. The measured
pressureswill be adjustedto take into account
the static pressuredue to water in the instrument
differentialwillbe adjustedto correctfortested lines. rf necessary,the calculatedpressure
pressuredropin pipingoutsideABB-cE,sscope
of
8
PAITON7 & 8 BOILERPERFORMANCE
TESTINGWITHADAROCOAL
12 JUNE 1998 rev.00
SUPERHEATER
AND REHEATER
SPRAYFLOW
The sprayflowcalculations
will be basedon the followingformulae;
o r , { \ M ' H i } + { W s ' H s} = { W o . H o }
a n d ,W o = ( V M + W s )
i.e. Wi { Hi - Ho }= Ws { Ho - Hs }
o r W s = W ( H i - H o) / ( H o - H s )
POWERCONSUMPTION
Kilowatthour meterswill be installedutilizingthe installedCTs and pTs for the 5 mills,Z pA & 2
FD fans, and 2 BWCPmotorsin service. Readingsare to be takenevery 15 minutes. For the
followingequipmentkilowattswill be determinedfrom motoramps & volts measuredevery 1/2
houn
lCoal Feeders gAir Heaters
1 each-Scanner
& SaalAirFan 1-SubmergedScraper Conveyor
These readingswill be taken at the motorswith a clamp on amp meter.The motor nameplate
powerfiactorwill be usedin thesepowerconsumption.calculations.
The readings for each crmponent will then be averaged and the averagesadded. This will be the measured
total power. A total of 152 Kw will be added to the measured total power to account for
the power
consumed by the followingunmeasuredmotors:
5_pulverizerLubeoilpumps
EFFICIENCY
TESTING
calculatedheatloss- dryfluegas;perASMEpTC4.1
calcutatedheattoss- H2Oin tuet;perASMEpTC4.1
heattoss- H2Ofromcomb.of H2;perASMEpTC
calcutated
4.1
heattoss- H2Oin ainperASMEpTC4.1
calculated
heatross- combustibre
carcurated in refuse.perASMEprc 4,1
heatloss- radiation;
calculated perASMEpic +.r tng.a AgMi standard
O.5Oo/o
heat loss - unac@unted radiation
losschart)
foq per contract
loss calcutation
wiltbe basedon an ash
ffi#T:;stible distribution
ot 9oo/oflyash
and 1oo/o
STEAMPURTTY
10
PAITON7 & 8 BOILERPERFORMANCE
TESTINGWITHADAROCOAL
12JUNE.t998 rev.00
AH LEAKAGE
AH leakagetestingand calculations
will followPTC4.3 as modifiedin this procedure.Gasflowwill
be basedon stoichiometry.
The test data will be basedon hand probingeach air heatergas inlet and oufletduct. Each of ) Hn*
these probeswill be equippedwith a thermocouplefor measuringthe gas temperature,a pitot
ahut
tubeto measureveloci$ head,and will be tubedup to gas samplingappiratus to evaluatethe O, [',1fr$
I
tt' Calnfh$
contentof the gas. To calculateairheaterleakage,measuredgas tempsand Or's will be weighi I
averagedbased on the velocityhead data. The GO2contentof the gas will be based oi a
)
stoichiometric
calculationusingthe testfuel analysesand theweightaverJgedOr's.
EFFICIENCY
CALCULATION
EXAMPLES
On eachof the nexttwo pagesis an efficienrycalculationsheet. The first sheetis the design
calculationwhereeverythingis basedon the exactdesignconditions.The only differencein the
two efficienciesshownat the bottomof this sheetis due to the manuf;actures marginbeing
includedin the rightcolumnwhichis the guaranteevalue. Thismarginis not inclu-ded irrthe ,as
tested'(left)columnwhich is the predictedefficiencyif everythingis pe.rfect.
r1
PAITON7 & 8 BOILERPERFORMANCE
TESTINGWITHADAROCOAL
DEsfGNEFfifiLll8l,,
tiL" uLAnoN
AoMErlu{.I
P.P.P.P. ph!!. i p.iron Z & I ag.t Dcatgn
Etf. TEST NO. VwGNp @tr. VAXIAT'LE
!!atcd to NAME
^l{yus oI ruet.... dc!ign
.r.uu - wL
Hydrog.n 3.35 % u/t 3.35 % urt H
Carton 53.84 % u/t 53.6.1 % wt. c
Sulfur 0.20 % urt 0.20 % u/t
Nitrogcn 0.67 96wt.
s
0.67 % u/t N
Orygcn 16.64 % wt 15.8.1 % u/t o
tufl 1.50 %u/t 1.50 % rn" A
Totrl 100.00 % s/L ,|00.00
% urL -r cl
9367 8TU /tb. 9387 BTU /tb.
; or
HHV
Enthetpyof rerrr.tcct tiquid at TeiJ csg.r rtw
I N/A 51.03 BTunb
_ Enthslpy d latJntod vrpor.t T!6d N/A HwEd
T.rt tcmpcraturu ot eir tor comOurUoi I 1097.7 ETUnb HVSd
E3.0 dcg.F
Enthalpyo( !€tuirt d llquirt at Tai I N/A T.6
s1.03BTUnb
Enthrtpy of uljretrd vrpor.t T.6 I N/A HwE
Mc.rund 0e3 tcmp cnfcdng eir hcebi |
10s7.7BTUnb N/ Hv8
722.0 dcg.F N/A
Mceeurrd grs tomp. lovinl eirhcetcr Tg1/t
275.0 dcg.F N/A
Moisfurain.ir Tg15
0.0163 lMb dry air 0.0163 lMb dry air
Arlr pit cvepor8tion Wma'
0.0000 lMb AF tucl N/A wmp
%-Ijd* innucsas(r.su.,,.,,,","01?If;'l3,i 0.fi)00 lMb AF tuct N/A
ill , 90.00 % 90.00 %
Wz
7.950 % u/t N/A Wc/
rs.ere ru qry vctl
3.580 % dry vol
'.
,'rtr
L2 lit n"'t,-i^.{iqf
/
PAITON7 & 8 BOILERPERFORMANCE
TESTINGWITHADAROCOAL
, EXAMpLE
oFA #l'iEl'''#it"
noME rrv{.r q{.J EF|:tLttsNUY lE5I ffi
"orcuLAnoN
P.P.P.P.phas. I Paiton7 e S 194 Tst pmc Exmpt TEST NO. Vll/O_Np @r vnntA0LE
tcstod to NAME
dosign
...-.......-...,...-MOtSrUrF
3.45 o/owt.
"tffil 52.80 % wt.
3.35 % tflt
53.6.1 % w{.
H
ExilGas
romp.
Adju'rod,",
r.#;:1T:t:l3lT.t:t1q:ffiraE) )=
) /( rs14-rao N/A 275.7 dcg.F Tg1sda
vaporcnrha,py
...... . .l:::'_:i:i".*_"*-11:1li: =
;l"ji,yi;',ll!trJl
N/A
NiA
289.8 dcg.F
1191.0BTUnb
Tglsnlda
Sp6cifichcat dry gas tvg.rir hoeter.........................-..........(avg.of H v1 5
Tgj5nt & TaE) = 0.2390 BTUnEdeg.F N/A
S p c i f i c h c a t d r y g a s t v g . a i r h € a t o r - . . . . . . . . . . . . - . . . - . . - . . . _ . . . . . . .o( af v g
Tg1s;tda s Taajy=
Cp
N/A 0.2391 BTUnHcg.F Cp
Ory gas...
4.40 9305 N/A N/A
N/A N/A 4.43 9387
2.68 9305 2.91 93E7
3.6't 9305 3.66 9387
o.12 9305 0.13 9387
ladiation: p€rfigurc 6,pag6 67 0.37 9305 0.37 9305
Jnmcesur6d lo3sca: pcr spccification o.17 0.17
0.50 0.50
o/.6J
13
PAITON7 & 8 BOILERPERFORMANCE TESTINGWITHADAROCOAL
12 JUNE 1998 rev. OO
PREPARATIONPRTORTO TESTING
T4
*.a-,1-,'--
r.-.-*),:-a,," -
PAITON7 & 8 BOILERPERFORMANCE
TESTINGWITHADAROCOAL
12 JUNE 1998 rev. OO
OPERATING
CONDTTIONS
No oilgunsin service.
All feedwaterheatersin service.
Allventsanddrainsclosed.
The unit must have been in continuousstableoperation,on designcoal, for a periodof time as
directedby the ABB-CECommissioning Engineerpriorto any Ml/O test to insurethat slagging
and foulingconditionsare stabilizedand representative
of normaloperation.
The boilershalloperateat the test loadconditionsfor a minimumof t hour priorto each test run.
This periodmaybe reducedif evidenceof stableoperationis acceptableto all parties
Use of sootblowersprior to and during the tests must be as directed by the ABB -
CE
CommissioningEngineer.
15
PAITON7 & 8 BOILERPERFORMANCE
TESTINGWITHADAROCOAL
i2 JUNE
1998 rev.00
15
t..
PAITON7 & 8 BOILERPERFORMANCE
TESTINGWITHADAROCOAL
iZ JUNE1998 rev.00
PaitonPrivatePower project
Phase1, Units7 & g
SUMMARYofGUARANTEES
GUARANTEES
Capacity- \ /UO-OP(Kg/S)/(tb/hr)
................ 634.9/ 5,039,859
S H OT e m p . ' ( " C t 6 ) / ( " F r 1 0 ) . . . . . . . . . . . . . 541/ 1006
RHOTemp.. ('Ct6)/(.Ft10).............. 541/ 1006
Max.(inclstatichead)dettap Econin/SHO(kpa)/(psi)...... 1,724I 250
Max.deltaP, RH|/RHO(kpa)/(psi).. 207| 30
Max.draftlossfurn.to AH gasoutduct (kpa)/(inw.g.)....... 3t12
Max.AH Leakage[prim.designcoatonty] (Kg/s)/(lb/hr)..... 56.2/ 446,000
Max.Carbonin Flyash-wlo€p (o/obywt).............. 15
Max.SHOleadtemp.differential
[40%toad- wlo€pl ("Cy("F) 14t25
Max.RHOleadtemp.differentiat toad- Vwo€pt ("Cy("F)
[40olo 14t25
(r(w.......... 9,015
Pulverizercapaci$ Guaranteeon one miil(boirerroad> Tsro)
HGI= 47,CoalHrO=24 (Kg/s)/(tb/hr)..............................
22 t 175,000
Footnotes:
' controtted
fromsH ffowof 380.9to 634.9Kg/s(3,023,315
to 5,038,859
o controiled rb/hr.)
fromRH flowof316to 527xgls(z,sii,rzs to+,r85,209
* With 15 ppm rb/hr.)
TDS in boilerwater.
L7
PAITON7 & 8 BOILERPERFORM4IT.CE
TESTTNG
12 JUNE 1998 rev. O0
WITHADAROCOAL
APPENDIX1
DATAREQUIREMENT
DETATLS
a
PAITON7 & 8 BOILERPERFORM.4JICE
TESTING
WITHADAROCOAL
12 JUNE1998 rev.00
--: -..-:-
r-j.-:-:- - - -f -:-.-T:-__=F4rp1*
:
@
PAITON7 A 8 BOILERPERFORJVIANCE
TESTINGWITHADAROCOAL
12 JUNE 1998 rev. OO
PI-ANTCOMPUTERDATA
The followingdatawill be collected
fromthe plantcomputerevery5
minutesduringall rests
GrossMW Load
MainSteamFlow SecondaryAH A'Air Out pressure
FW Flow SecondaryAH ,A,AirIn pressure
FW_Temperature SecondaryAH 'B'Air Out pressure
To Economizer
SHO Temperatures SecondaryAH ,B,AirIn pressure
Secondary AH 'A'GasIn pressure
!!]t_fgmneratures(before& afterdesh) Secondary AH ,A'GasOut pressure
RHOTemperatures
EconInletpressure Secondary AH 'B'Gasln pressure
TurbineThrotttepressure Secondary AH ,B'GasOut pressure
CRH Steampressure PrimaryAH Air Inletpressure
HRH Steampressure Primary AH Air Out pressure
Soot BlowerUsaqe Primary AH Gas In pressure
BumerTittpositiJn Primary AH Gas Out pressure
PA Fan 'A'
SOFATilt position Dischargepressure
RH SprayFlows PA Fan'B'Discharge pressure
1'.SH SprayFlows FD Fan'A,Discharge pressure
2* SH Spray FD Fan'B'Discharge pressure
'A Feeder Ffows All lD FanInletpreisures
'B' FeederSpeed& CoalFtow Fumacepressure
'C' FeederSpeed& CoalFlow Windboxto FumaceDiff.pressure
'D'Feeder Speed& CoalFlow EconomizerOuttetO,
'E'Feeder Speed& CoalFlow Stack Gas0,
Speed& CoalFlow
F'FeederSpeed& CoalFlow ChimneyFlueGas NO,
Pulverizer,A,AirFlow Drum Level
Pulverizer,B,Air PAH 'GasDamperposition
Ftow
Pulverizer,C,Air SAH Gas Damper,A'position
Flow
Pulverizer'D,AirFlow SAH Gas Damper,B,position
Pulverizer,E,AirFlow
Pulverizer,F'AirFlow
FD Fan'A,AirFlow
FD Fan'B'AirFtow
b
PAITON7 & 8 BOILERPERFORMANCE TESTINGWITHADAROCOAL
12JUNE1998
rev.00
APPENDTX
2
DRAWTNG
OF TEST
BOUNDRIES
a o
o
n
o
o
rE$ @
6
I
E;: o
!8E o
Etu o
:
E !;g iii I
E i s g $ ; - 18d I
-i
z
I !8.t
,
il
p 6
:!
i_
qc
IE
qH
EE
iE'tn
at E
F spF
\1 HgE
b3
T
?:
Lt
z 1r
a
I
PAITON7 & 8 BOILERPERFORMANCE TESTINGWITHADAROCOAL
12 JUNE1998
rev.00
APPENDIX3
PULVERIZERPOWERADJUSTMENTS
APPENDIX 3
PAITON7 &8 BOTLERPERFORMANCE TESTING
PulverizerPower Adjustment procedureand Guryes
ti.lurue1998rev.oo
This appendixprovidespulverizercorrectioncurves.Duringauxiliarypowertesting(Boiler
PerformanceTest#1), it may be necessaryto adjustthe mlasuredmill powerfor coalgrindabilig
(HGl)and higherheatingvatue(HHV).
BACKGROUND
MILL MA)(|MUMMECHANICALCAPACIry
(PA|TON7 & 8)
200000
190000
E
I
o 1800m
J
= 170000
o
J
IL
J 160000
o
C)
150000
140000
47
t-Gl
Curve#1
The Design coal HGI is 47. From Curve #1 it can be seen that
the design maximum mechanical
capacityof the Paiton7 & 8 millsis 175,000lb/hr per miil. At
the \Al/o-Np conditionof 4,7g4,162
lb/hr MSF' five millswlth the designcoalwilt each have grinJ
to 130,135lb/hr. The requiredmilt
through put of 130,135rb/hris 74.4%of the maximum
mill mechanicalcapacity.
1of3
- .
i
: : - : : - - -
APPENDIX3
PAITON7 & 8 BOILERPERFORMANCE TESTING
Pulverizerpower Adjustment procedure and curves
i2JUNE 1998 lgv. O0
REQUIRED
KW BASEDON % MILL LOADING& HGI (PAITON7
& E)
**!
F
-.* l-E
tY ro.mF
; I
g
F
Fr-.. F
El
g
E E
3
ct
U
u*- F
C
F
*rEt-
E
cco.o E
@*
2of3
APPENDIX3
PAITON7 &8 BOTLERPERFORMANCE TESTING
PulverizerPower Adjustment procedure and curves
12 JUNE1998rcv.00
lf the HGI of the testcoalsampleis between45 and 55 the effectof HGI on power
consumption
is
withinthe normalrangeof variationand thereis no needto adjustthe measured power.
mill
P 1.m
o
2 o.es
o
fi 0.s0
E
E
8 0.85
0.80
39 41 43 45 47 4St 51 53 s
tGl
MILL PO/VERCORRECITON
for GOALHEATIUGVALUE
1.@
o 1.040
o 1.BO
1.g,0
lt
z, 1.010
0 1.m
F
() 0.9s
lrJ 0.980
E
E 0.970
o
(t 0.m
0.950
m 91m am 95m 9700 9800
HGHFBT|IGVALIE- btunb
3of3
PAITON7 & 8 BOILERPERFORMANCE
TESTINGWITHADAROCOAL
1 2J U N E1 9 9 8r e v . 0 0
-J
APPENDIX4
PERFORMANCE
TESTINSTRUMENTATION
PAITON7&8 BOILER PERFORMANCETESTING
PERFORIT/IANCE
TEST INSTRUMENTATION
(i sIEAM/WATER TEMP.
MEASUREMENT:BoILER
nx RoarpondanttntetUni_ Re-T
Fi;-;-
BT rw+108 0019+1E851:l Thonnoweli rP
&c w-3114 lEE513 I nernowell
TP
RH Reaf PendantGrc[iiR
oo,{94-tEE513 Thermolell
)rwttta TP
RH OUUoILInk. L
P 1o1-51-70GBS- Thermoivetttn OFDIffi
0002 TP
RH Ouuoi Unk - R
P101-51-70c89 Th€nnofl€fi in DFD piprng
ooo2 TP
'0lT\ 1 SH Spray Water I
yyrclq
P101-51-70GBS-
?v{lw- z}4*
fvr/ fut D/rt :-.;',r,,u IE
D.A.5?
00()5
SH Spray Watei i
P101-51-70GBS_ r/
€ul-rr^l- 22Lc oo05 til IE
RH Sprsy Wat6t I V/ 2lFD ltFt,.t.;
,r r tr-.tz:r P10l-51-70cBs--
ld-Tw- 3zz 0005 Tvl L,rt Olfr ltFut j
TE
pageI
PAITON7&8 BOILERPERFORMANCE
pERFoRMANcE TESTTNG
TEsr rNsTRuMEruiaror.r
5ItsAM/WATER TEMP.
MEASUREMENT : HP HEATERS
lJ,la,t \fu,r,,t,'_,
C t - at- 70)-
tl& -Ty1-zz3g,g
-TDo-
HB-Iu-zt6A,a
?!t'rt-5t-
HD:T@-(ou,Afi
pRessunE
srEAM/WATER
MEASUREMEHT:
BoILER
Economt:or Inl€t Llnk
Fw-Pp-tz6
llu- P101-5t-7oGFIAA orain conne<son-
oo(X PT
Sle€mDrum
oote.-rEaSlZ- Nitogcn fill connection PT
SH OuU6t- L
Prol-5t-70GFW_ PnB$u.E tep In OFO ptdng.
0001 PT
SHOu0€t- R
Pl01-5t-70GFW- PresrurEtap in OTDpffi
oool PT
R H l n tl - L
usPP-137A
r,rulrurEtep tn DFDpiflng PT
(xxt2
xH InEl - R
ptor.sr-7oorW_ Pn}tsuna tap In OFO pifing
0002 PT
RH ouurt - L
P101-51-7(x)-Fw- Pr!!!Ur! tBp in DFD piFing
0002 PT
Ktr ouuet - R
P10t-5t-7(xlF\frL Pr€ssurotapin oFo ppin!-
0002 PT
STEAM/WATER
PRESSURE-
MEASUREMENT: HP HEATERS
'rJatcrEnronng
Xp nEiFE---
(Fimt Fwl
steam €ntcringTFffiE- futT-3ua LI L,1,'t d- PTS
StoemEntcri-9H_-ffiEE- aE-n-,*&.8
/tr)t:)t- /oo_ PTS
TB.PP.zaS
A,E UF: PTS
page2
PAITON7&8 BOILERPERFORMANCE
TESNNG
PERFORMANCETESTTNSTRUMENTATION
FLOW MEASUREMENT
2v RH SEraV r-w-FE.321
o(xt5
P101-5
0(x)5
1-7(x)-FW- FES
FES
-.l.tD < 0A bq'JDn l
Pulv€nzer Alr Flofl - PulvsrizeB A to F br--FE€664' b 00.c{- t E8528 FES
688F
-q
AIRTEMPERATURE
MEASUREMEMT -}
Arntient air dry bulb
Local instum€n( Mcssurod near FD -i,:.
tan Inlat
Ambacntair wrt bulb
Leal insfumant Mceruradncar FO
lan Inlct
Prirnary eir cntc,ing airheater B F - T P € s l a n O O S 2 , ooil94- E8526 i::
lnstru.ncntIn3artConncciiont2S AP
3 tapc per Ou,a
Prirnery air l€aving eirficltar BF-TP457 and 658 0049{-188528 InEtn flxtnl Insdt ConnGcliofl f2a
3 tspo paadrjd r------..
Socondary elr cntsfing airhestcf - L c(i. IP. oo.r94-1E8520 h!trurncnt ln!.rt Cd|ncction t10 AP
531i4.536A"537A 3 bpa pcr duct
Sccondary air ontering sirhcatff - R tt|.t I P- 00494-1EE520 lruEurndrtlru{xl Conncctircn
f.tO AP
5358.53€8.537S 3 bps p.r dud
SecDridery sir leaving eifiratr -L SC>TP. oo,r94-tEE5?0 Instun'|.flt trlscrt Conncanon *Zs AP
5,t2A'tt3A.544A 3 trp. pcr drrct
S6condary 6lr |€aving airhcatcr - R 8GTP. (XxTa-1E8520 h!tsun|cnt In!.rt Conncctton *23 AP
5a28,5.128,5...t8 3 bps pcr ducl
GASTEMPERATURE
MEASUREMENT
Ga3rntcring SA airhoabr - L 8GTAP.558A b 0(xc4-1E8520 lntm|lfEnt Insarl Corinrdion tn2 GP
570A 15 bF p.rduct
Gar cntering SA airhcetar - R BGTAP.ss€B b qxs+tE8520 lrufurncnt lns.rt Conn€don fZ-
5708 15 bp. pcr duct
Gs3 antsrlrB PA aifiasbt n(;tAP-595 b 6fit qxsa-1E8526 IniErirnent Intcrt Co.tn€cto.t ti 2 GP
0 tepo por dtn
Gas leaving SA Bifi€atrf - L tt(; tAP\5724 b os04-rE8520 lilfunEnt Inla.t ConnGciion *29 GP
6E5A 14 tep! por drJd
G8! blvtno SA sirhoetff - R BG.TAP.s72B b ff).rc4-tE8520 l]rttnlI|l. ll Inrart Connoctim l2g GP
5858 lit tep. pcr dud
Ga3 b8vino PA airfieata BG-TAP{I2 to S2t In!tn.,m6|ltIn&rfl conn€ctim f 11 GP
l0 tsps per dud
page 3
PA|TON7&8 BOILERPERFORTUANCE
TESTTNG
PERFORMANCE TESTINSTRUMENTATIO
N
GAS PRESSURE
MEASUREMENT
Gar cnlonng PA elrh€lrf 8ePP4(x (xx94-lE852E r.unnfitc rt In!€rt Conn€<iion 119 MAN
G8! lcrving SA airhcetrr - R BGPP.s71B qxc4-1E8520 lnrtun5nt Inccrl ConnGctio.t r2i II,IAN
{ _SAMFLF
FLYASH
COLLECTION
tslyash et PA airfieater out ot 8G-TAP-55€B to -
5708
hsfurn€nt Insert Conneciion #22 rso
Fryasnat sA etnoaterouuet_L 15 tapr psr dud
tt('-t-AP-5728 to r cuSzo lnsturnenttnrcrreonnG6i-Iia- tso
5858
Fryash rt sA airh€ator oulrot - R la laptpcrduct
EG-TAP412 to 621
hstumont Ins€rtConnocdon
ft 1 rso
I 0 tepc p€r duci
AUX. POWERMEASURETFi-
rD tan rnolor - L
Utilizc thc Station CT and pT \ /[{
FD fan nEtor - R
ffiffi;SffiTEnd=Fi Iffi
PA fan rnotor - L
Uuttzethc Station CT and Fi \4,i,
PA fan rnotor - R
uultzotho stationcT andPT \ a,t
Mi[ nptor - I tobt (s opeEtingt-
Utrlrzetho Slation CT and pT vvu
uoar tefitoft - 6 btal (S oporattng)
AM
B\ rcP rmbrs - A totat(2 opcraUng)
Utilize th€ Stabon CT and pT fM\l
AJrhaataf nx'tont - 3 total
ilt
Scann€f @ting hn rmtor
AT'|
S€al eir f,rn motor
AM
SSC rnoto.
AM
INSTRUMENT
WPE INDEX:
page5
PAITON7&8 BOILERPERFORMANCETESTING
PERFORMANCE TESTINSTRUMENTATION
page I
PATTON
7&8 BOILER
PERFORMANCE
pERFoRMANcE TESTING
TEsrrnrsrnumeruilnox
STFAM/WATER TEMP.
MEASUREMENT : HP HEATERS
235
slerm EntaringHp hoator6
p)B-Te
.6frr8
SleernEhte.ingHp hcatarT
-:229
t-16 TE
it*-T6-222rt,
B il6 -,t.1-i] tr
StcarnEntenngHF hEE;!
V*aterentertngHP HeaF6---
Hv-TE- mn,i] tltt\-;n''' I TE
rror-5,t_70GFw-
0{Yla TE
vYal6 Ento.ing Hp Hcator 7
FWTE€49A8
wat€r EnteringHp HeaterI ofit3 E
FWTE.356A.B-
0003 TE
wat€r LeavingHp HeatcrA
FlrV-TE-3ttiAiB
/uu-Fw-
0003 TE
.0:rE-,pZ)A,B H H - , , ' . . i ^A TE
DrainHP Heatar7
'lD
L€ - GtjA,B .',
u[1 z) TE
Drain HP Heater I
ttD-TE-b7A,a TE
1i,4-txi.^,1
sTEAM/WATERPRESSURE-
MEASUREMENT:BOILER
Econornrzor lnbt Link
,nnr-Fr
Sllam Drum
rrrt mo4
uretn conn6ction
PT
u{x8{-1EEst2
PT
sH ouuat- L
BS.PP-'OOA
r,r€$urBtap in OFDpiftng,
0001 PT
JH eutet - R
8$pp-iooE
l,nrllurE tap In OFD piping
@01 PT
R F I I n tt - L
agpp-razr-
Ptt!!u.! tap in OFD pipino
0002 PT
RH lnl€t-R
r,ro1-51-7o().FVl_ Pn}3surEtap h
OFDpiping PT
KH (JUdd. L
0002
t,rol-51-70GF1/\i rrutlurE utp in OFDpiping
0o02 PT
r{Houuet- R
Prot-51-70GFW EP In uru ptptng
0@2 PT
ITIEASUREMENT: Hp HEATERS
@
ilw-Pr-zzl- PTS
Wabr I osvingHPFffi-
(Finrl FvlA
Sr6rmF;Filr-6ffi--
frn/-Pr- ja,.- PTS
PTS
PTS
€ nr rtcat6r 6
PTS
page2
rlowuersunEIiEFF-
-Finat
FeeO{ater
P101r51-70GfW-
-.=......- 00(X FES
sHsprayl
ptot-st-zooFw-
(xX)5 FES
ffi plor-5r-7oorw-
-RH
Sprdy
0m5 ES
Ptot-51_7q)-F\AL
0005 FES
Prc epeeo*ararTffiTdffii-
l"r Turoine ncceFEffi ET
ro rannirFknr-Affi t t@dutE
FES
rurvetqer Air Ftow- putveEeEfGF
or-rtr-oocA b ool4tE8sZ-
666F FES
AIR TEMPERAATUR--
!|EASUREMENT
Arnbient
airdryEut6-
Local inctrurn€nt M-asifr;ea;FD--
Ambicntair wrt butb....- fan lnl6t
Locat irutrurnent Ueaiud'-neiiT O-
Prirnaryair anbrint ai.hoa---- fan Intet
652 oo.ls{-1EE526 nrEtr eertrt@qt rlJ AP
rrn.Ery ar t€tytng SitttaNtSr 3 bpr pcr du,a
ocd 0o{c4-1E6526 Inrttrncnt tnsartC&iffiEf-
-soco.xtary 3 tap! pcrduct
AP
air cnb*lg arneaiar - f_
oorc.rrEaieo- .rr.su.rgn lrur€rr uonmctm
53!!A.538A537A #10 AP
Dcconoaryair cnGdngainrffi 3 tetrr p€f Cuct
00.c1-1E85ra- 'rJuwrdr rns€fr L;onntction
5358.53AA 537R #10 AP
rocordary air baving airrrEF 3 tapr por Oua
q/1e
004e{-lE85to- tr,-usrrgt trlltr
5,12A.5{31 uonncciioat 123 AP
Do@ndaryairl€svinganeaheaffi--- 3 taps pcr dlrd
0049.-1ESE20- ..,_Yrr.Errr
5a28.5a28.5148 rrrq. wtroEuon FzJ AP
3 tapa pGr duct
v^g rsmrg|IAlUKE
IIEASUREMENT
tu ee . ffiro{tA tt oo.o4-iEas26- xEug..E.[
5t0A trrw( Lqnn€coon ,22 GP
# ns-rAP€s€g
15laa *ara
b 004e+1ES52o-
s70B [|ur wetrn@on lzz GP
Errqng rA e|trcaba 15bp. pcr duct
o03 rxxea-15tu2 __r_.rr,,r n.w. wt[rrgup|D IIZ GP
rqung sAaff|€abf - L I bps por Oua
ECTAP€72A_-E 00{9+1ES-'d- .rEr
5EsA u,,E'r ., rw r wr|€GIlOn UZE GP
qur|g DA atmaatrf - R 14 bp! p€r duct
D 00.*1E6520
5858 ,.|{r eunGcuoft,28 GP
t4 tap! p.f ducl
EGIAP{l2 b 621 oo{s1-TgBsE---
GP
10 tap! per duct
PAITON
7&8 BOTLERPERFORi/IANCE
pERFoRMA TESTING
NcErEsr rrusrCriiiirr.riino
ru
page4
PAITON7&8 BOTLERPERFORMANCE
TESTING
PERFORMANCE TEST TNSTRUMENTATION
FLYASH SlUpLe
COLLECTION
Flyashat PA airtteataroutt€t getlp-ss€B b 004e4-1E8520
5708
Inshrment trc€rt conn6cii{rn#22 rso
I 5 taps p€r ducl
FryB$ at sA eirhestefouuet- L tsG-TAP-5728 to o(xs+lEE520 Insl'Uolcd Insan conncdion *29 rso
5E5B
14 taps per duct
Frya8nat sA airhoetorouflot- R 6(j-IAP€l2 to 621 (Xx9.t-1E8528 hstrurnontInr€rt Conn€dion#i l rso
10 tapcp€rduci
F
INSTRUMENTTYPE
INDE(:
TE TemperafumElementStationInstrument
TP Tcst thomocouplc typc E
PT PrecisionprassuG transmitter
PTS Pressurotransmitterstationinstrument
I'AN Manometer
GP p.as-er.ooe- Gas eampringrrfrermocoupr.rlorocity
AP head probetype K unshierded
Air Probe- thermocouplepmbetype k unshieE&
WM Porer analyzer
AM Arnp M6ter
FES Flow ElemsntStationlnstrum6nt
FET FlowElemcntTest Instrurnont
tso lsokineticFlyashSampler
page 5
PULVERIZER
PERFORMANCE
TESTPROCEDURES
PULVERIZERPERFORMANCE
TESTING
The purverizerguaranteetesting
wit consistof purverizercapacity
testing.
This test will be perf.ormed
as described in sdr-'
prc 4.2 and as
modifiedherein. "' each ur
of the
tne foilowing
toto sections in accordance
ASME
The coal feeder will be calibrated
in accordancewith manufactures'
Raw coal and sampleswill be instructionsrrrior to testing.
t"r."n ir"tir the feederduring
the testing.
one pulverizerwill be mutually
selected - for
'v' testing-
rserr're-rts feeder
reeserspeedwill
the maxiumcapacityper the wiil be biasedup to achieve
iurve.
A mill is considereg-t:,.9:in
a steady state conditionif the
temperatureare in equilibrium: bowt dp, miil power and
Thi;;;; data wiil L" t"t""-r.m the mill ouflet
once the test begins'The attacheo Dcs every fifteen minutes
oata srreetwit be
once every hour duringthe
"o,r,pLt"o test.
Boiler Test Conditions:
Performance Guarantee:
usinsthecorrection
curves
asrequired
llrt:ji:Ln:flil.r:. tocompensate
forchanses
in HGI
Thesecorrectionscurvesare
shown in,Appendixl
6t15t9B
Page 1
P U L V E R IZ E RPERFORM ANCETEST PROCEDURES
PULVERIZERPERFORMANCE
TESTING
Performance Guarantee:
6/15t98
Page 1
P U L V E R IZ E RP E RFORMANGE
TEST PROCEDURES
F E E D E R , S P E E D( 8 )
COAL FLOW (Kq,/HR)
MOISTURE (B)
MOISTURE(?)
COMMENTS:
6/15/98
Page 2
APPENDIX 1
PAITON7 & 8 PULVERIZER PERFORMANCE TESTING
Pulverizercapacity Adjustmentprocedureand curves
12JUNE1998 rev.00
There are two kinds of adjustmentsthat will be made to the coal flow determined
during the
PulverizerCapacity Test.
The f rst adjustmentis for the test coal's HGl. This adjustmentaccounts
for the change in
mechanicalcapacity of the mill based on the grindabilityof the coal. For
this adjustmlnt curve #1
from Tab 1 Appendix 3 is used, and repeatedhere.
190000
e
I
o 180000
J
3 170000
o
J
ll.
J 160000
o
C)
150000
140000
4l_
HGI
Gurve#1
1of2
APPENDIX1
PAITON7 & 8 PULVERIZER PERFORMANCE TESTING
PulverizerCapacityAdjustment procedureand Curves
12 JUNE 1998 rev.00
Curve #3
lf the measured coal flow is "nea/ the mill's thermal limit the test will be passed. The term "nea/
is used loosely here because Curve #3 is not exact. Dependingon other variables such as
mill
outlet temperatureand how the moisturein the coal is bound, the predibtedmill capacity limits can
vary. For example,measuring178,OoO lb/hrof coalflow when the predictedthermallimit iss only
175,000lb/hrwould be considered.near..
Because these other variablesmake the moisturethermal limit curves less-than-perfect,it would
be best to use a test coal as close as possibleto the 24% design moistureto avoid having
to
account for this variable.
2 of 2
THE HOWDEN FAN COMPAI.,IY
rut,
Oivbbn ol
Howden Group Canada Umited
Cambridge Facility
ru
555 Conestoga Boulevard
Cambridge,Ontano N1R sxg
Tel: (519) 621-7111
fts
Fax (519) 621-O8Ol
FOR FIELDPERFORMANCE
PROCEDURE TESTSON
CENTRIFUGAL
FANSYSTEMS
IONTRACT: 63000494/63000594
HOWDENORDER: CF07-95020
LOCATION: INDONESI.A
M I TSU I : MOL -1 P B -0 01
FANS: 7478OOTVAF6A
DWD| A/3 cL.1soo 2950BAU
PREPARED
BY:
iil3l-lHli^?aT=?o*rMENr
HOW DENFAN CO.
DATE: N O V E M B E R1 7 , 1 9 9 2
INDEX
Page
1. lntroduction 2
2. AccessPorts.........: z
3. Test Methods.....
Performance
3.1 N u m b e ro f T e s t P o i n t s . . . . . . . . 2
,l
3.2 MeasurementLocations
3.3 V e l o c i t yP r o f i t eM e a s u r e m e n t s . . . . - . . . - . . - . .
3.4 StaticPressureMeasurements--....
3.5 P o w e rM e a s u r e m e n t s . . . . . . . . . . . . . 4
A
3.6 S p e e dM e a s u r e m a n t s . . . . . . . . . . . . .
3.7 TemperatureMeasurements.......-... 4
A
3.8 BarometncPressuM r ee a s u r e m e n t s . . . . - . . . . . . . . .
TestData...
5. Calculations
ql 4
VelocityProfile distortionLimits..,..........
5.2 lnletFlowProfileand FlowDistortion Calculations
q1 o
AmbientAir DensityCalculations................
5.4 AbsoluteViscosityfor Atmospheric Air..... o
5.5 FanInletDensity...... o
5.6 AverageVelocityPressureat TraverseP|ane..........
5.7 V e l o c i tayt P l a n e3 . . . . . . . . . . . . . . . . o
5.6 D e n s i tayt P l a n e3 . . . . . . . . . . . . . . . . o
5.9 FanFlowRateat TestConditions............ 7
5.10 FanVelocityPressureat TestCondition... 7
5.11 TotalPressuren at Fan lnlet.... 7
5.12 TotalPressureat Fan outlet.. I
6. Uncsrtainty
Analysis.....
7. AcceptanceCriteria
A Final Report I
Appendix
A - S y m b o l sa n d S u b s c r i p t s . . . . . . . . . . . . . 12-13
B - S a m p l e so f D a t aS h e e t . . . . . . . . . 14-16
l^ - ExampleIntetFlow DistortionCalculations 17-19
D - CompressibilityCoefficiencycalculations 20
E - Uncertainties and Per Unit Uncertainties................. 21-26
F - ExampleUincertainty Analysis.-... 27-35
PERFORMANCETESTSON
PROCEDUREFOR FIELDAERODYruNUIC
CENTRIFUGALFAN SYSTEMS
1. I N T R O D UC T ION
The two fan systemsthat will be tested in the field using this test procedureare PA Fans
"A" and "8" buittto Howden'sdrawingsnumbered2097F55and 2096F50,respectively.
The performanceof a fan when installedin a systemis dependentnot only on the fan,
but also on the systen:and on the interactionof one with the other. The inlet flow profile
has a significanteffecton the performanceof a fan. This standarddefinss an acceptable
intetflow profiteof whichthe system has insignificanteffecton fan performance.Any
instailationthat does not fall within the definedlimitationis regardedas unacceptablefor
the purposeof site testingto this standard. An unacceptableinstallationmust be
alteied'tobring it withinthe requirementsstatedin this standardfor the purposeof
judging fan performanc€acceptability.
2. ACCESSPORTS
To arcess the gas stream,access ports are providedas shown on the General
AssembtyDrawings. On each inlet box, there are nine (g) 4' NPT x 5" long pipesc/w
caps installedjusibelow the inlet of the inlet box, equallyspaced along the long side of
the inlet box. These portsare to be accessedwith a probe used to measurestatic
pressure(P,r)and velocitypressure(P6) atfan inlets. This velocitypressure
measurementwill be used to determinethe flow rate and for flow profileevaluation.
The four staticpressuretaps at fan outlet should be installedas shown on the G.A.
- one per side at 90 degreeapart at the end of the dischargecone. The
drar,rrings
aueragl value of these readingsdeterminesthe staticPressureat fan outlet(P.r).
Figure 1, which is a reducedportionof the G.A. drawing,shows the locationsof P"r, P,t
and P,zmeasur8rnent Planes.
TEST METHODS
PERFORMANCE
There wilt be a minimumof one (1) test pointor as many as three (3) test points
conductedon each system. lt will be left up to the customeror user as to how manytest
pointswill be tested.
ratlng point'
af the gfuaranteed
lf onfy a single point is tested, it shouldbe within 5o/o
To cover a short range of the fan curve,three test points are sufficient- The range of
thesethreetest poinisshouldcoverthe guaranteedpointand they shouldbe well
spaced. One pointshouldbe at the normalsysternresistance.A secondpoint shouldat
an increasedsystemresistanceand the third point should be taken at a reducedsystem
resistance.
3.2 Locations
Measurement
??, VelocityPrcfileMeasurements:
34 StaticPressureMeasurements:
'
,..i.
3.5 PowerMeasurements:
3.6 S p e e dM e a su re me n ts:
The fan speedmust be held constantduringa test. Speed shouldbe recordedat the
beginningof the test and at specifiedtime intervalsnot to exceed20 minutesfor the
o/o
durationof the test. Readingshouldnot vary by more than 1 for the total durationof
the test.
3.7 T e m o e r a t u re
Me a su re me n ts:
4. TEST DATA
Samplesof Site Test Data Sheetand Summaryof Test Resultsare shownin Appendix
B - F i g u r e s3 , 4 a n d 5 .
j=U i=T
I I V i . ;) / U T
j=t i=1
j=U
V=( t Vi.j )/u
j =1
i=T
Vi =( I Vi.l )/r
i=1
distortionparameter,
5.2.4 The transverse
i:T
V=[ I (V, - V )'/TIu xloo/ V
i=1
j'=U
V"= [ r(v - V )'/ulu X 1 0 0/ v
j =1
5. 3 A m b i e n ta i r d e n si tyca l cu l a ti o n :
p " = 7 0 7 3 ( p 5- . 3 7 8p o )/ R ( t o o+ 4 5 9 . 7)
t r = ( 1 1 . 0 0+ 0 . 0 1 8 t a ) x 1 0 €
V:=V,=1096(P"r/Pr)s
58 D e n s i t ya t p l a n e3
p : = p [ ( P , .+ 1 3 . 6 3p u) / ( P , ,+ 1 3 . 6 3p ' ] [ ( t t r+ 4 5 9 . 7 )/ ( t , . + a 5 9 7 ) ]
Qr=VrxAt
where Ar = cl'oSS-sectional
area of Plane 3.
O=Q1 =Q3x(prlp)
, r= P r - p a n d Q = Q 1 = Q 3
S i n c eP l a n el a n d P l a n e 3 a r e a t t h e s a m e p a l n e P
5 1 1 T o t a lp r e s su rea t fa n i n l e t.P rr
P,t=Prt#Put
where: Prr=IPrrr/n
P,r,= the static pressure at each traverse plane location
n= the numberof traversepoints
Pa=P"z+Prz
Pt=Pa-Ptr
P, = P,- Pu
5 . 1 5 F a n P o w e rIn p u ta t T e st C o n d i ti o ns,
H
H=Wtr/745.7
rtt=(QP,G)/(6362H)
where G = coefficiency.
the compressibility
See AppendixD for calculation.
5.17 Fan StaticEfficiency,11,
es=Tlt(Pr/Pr)
F a cto rR a ti o ,K e/ Ke"
5 18 C o m p r e s si b i l i ty
z l z . = [ ( P , , " + 1 3 . 6 3 p b c ) / ( P t+
1 1 3 . 6 3 p u ) ]( p i p " ) ( N / N " ) [ r " l ( r " - 1 ) ][ ( r - t ) / r ]
z"=zl(zl+)
xc=gln(l+xc)-1,and
conditions
of test resultsto specified
5.19 Conversion
Q"=Q(N"/N)(K"/l$")
P , "= P t ( N . / N )t ( p .i p ) i G/ K *)
P""=P" (N"/N)'(p"/p)
Pr.=Ps"-P""
7. ACCEPTANCECRITERIA
Tha test point is determinedto have rnet the quoted rating if the fan's guaranteedrating
pointfalls within the boundariesof the uncertaintyrectanglesdra.wnabout the test point
convertedto design conditions,or lies fully below the rectangle.,'
8. Final Report
When the results of the tesi on the units are deemed acceptable,a reportwill be written
and submittecj.This reportwill containall pertinentdata, observations,calculationsand
results.
5f ir. i o
z {
FF.:^
'- L { t
lrr'rr o ;
{ .E
; ";-{
i:iirr-si i
6 T
J
: I
II
li iilr;i'j i
ri
n..
rl tr,
t- l... ari
lls o :rf s
39
d i!
sie @
J6
U: |J
fl\l
Nlu
---
r:: -- I
t-'+-:]'
'{.
^9
:Y
I
c
| g
rr
I
It $f 99
sI
rl
rl E
:!
it rl
:t"'.,'t'.i rl
rl
t,,:
rl II
rl
-rJ. I
-T-
--,# I
I
ttrl
, rll I
, rll t-
, rl, ^5
I ttt
t'.;
= ':- rll
F F. [-- i
JI on
,;---:-
tt
I *o'
,l
? ta ' .
JJ.
EEI
tu
8 E,
t
8i F i
--t
s:: =
o
g ! -=[I oO.
o
n 4 t Qo. lt
U o
\J
( !
trt It
g3i
(J
|jl v it;
99.
F <t
U t
J t ryiiiEi ;l EI:
.:
;
cl
I 5:.i3!l Or
90
[E: 5i:l t
!i
_
) og
iiiiiii isH:
t hio o
o
d.
\r ? Erl{
q:l
!atE!itf
I
z
U I
0to
9F
!- o: ' - E
t--
ii ;d: .
.t Soi" J.
il4
i6
!l
t I5
t\
!isE: ( 9 t tr
LrJ
(L
c
!
( $Hq
zJJ
3 ; ; (r tr,
sd 3o
3:
'rllty
EG
r!
Gl
e'!
Fi'
ts@ 6[tt
(^
fr
<ci
5
rl
] Q
Ep
o
FHHF
E z
; I t;
-Jg
9o
:<
=<.
<s
3dd
- IFFz
J
o{
8n UO ..\<
:l s'
6o
g HE :: -' ,pP
\;d -9 I
o-
o
: iu
a\
rs h
(,
z
i3 s{
6 j
lo
I (r
d:'
:qii
8 .i;-["
4 V=
rgilr!
ry - . 1 E 6S
a
a r()s !$
! d'3s 3) ,I I
5t
)
iffil )l-5iilil1tJ - - < i
s ) | r t
/ tl U
10
,|: I
I
Increaseswith Increasingduct size. as defined
in Fig- where:
uts 74.
aspect of elemental area
The polnts aro to be located in the centroids of s aspect of duct crost-sEcttoi
equal
elemental areas with the elementatareas chosen
to
be similar in geometric shape to tn"- duct 2l The long dimensionof the elementalarea shall
cross_
ssctlon, such that: allgnwith the long dimensionof the ducr cross-
section.
1) Th9
ls.qect parameter S shail be between 2/3
and 4/3.
TAELEOF K VALUES
loo r.l
90
80
70
(n
z 60
. o 5o
q-
uJ
6 40
ul
F
30
l!
o 25
ut
20
f,
z
20 25 30 40 50 60 70 80 loo l 5 o z o o z s oc o o n '
D U C TC R O S S . S E C T I O N A
ALR E A
Figure7'4 Distribution
or Traverse
Pointsfor Rectangular
oucts (*rre 807-8
FIGURE2 11
A P P E NDIXA
4.2 SUBSCBIPTS
ADOITTONAL
r SubrcdPt
c
t
DatcrlPtlon
Conv€rted valua
Readlng
x Ptane0, 1, 2. -.- as aPproPrlats
0 Plane 0 (general test ar€a)
I
I Plans 1 (fan lnlet)
2 Plane 2 (tan outlet)
3 Ptan€ 3 (Pttot traverse stallon)
1 Ptine + ido*ntream'staticprossure)
12
Symbol Descriptlon l-P Unlt Sl Units
13
A P P E N D IB
X
vELocrwpRoFrLE
H.2INLET ouALrFrcArioru
resr DATAsHEET
Pvl Pvtc Pnt Pvtc Pvt Pvrc P"t Pvtc P"t Pvtc P"t Pvtc
1:15p il o.44 0.437 0.43 o.427 0.40 0.397 0.46 0.456 0.50 0.496 0.45 0.,146
i2 0.50 0.496 0.51 0.506 0.43 0.427 0.51 0.506 0.57 0.568 0.48 0.476
i3 0.54 0.537 0.57 0.568 0-44 0.€7 U.JJ 0.547 0.58 0.578 0.52 0.517
ia 0.62 0.619 0.57 0.568 0.50 0.496 0.61 0.608 0.64 0.639 0.57 0.558
i5 0.65 0.649 0.62 0.619 0,56 U.55i/ 0.67 0.570 0.69 0.590 0.59 0.588
i6 0.71 0.711 0.66 0.659 0.59 0.588 0.69 0.690 o.72 0.721 0.58 0.578
t7 0.68 0.680 0.66 0.659 0.57 0.568 0.69 0.690 0.68 0.680 0.59 0.588
i8 0.67 0.670 0.63 0.629 0.58 0.578 u.o/ 0.670 0.65 0.649 0.62 0.619
le 0.66 0.659 0.62 0.619 0.55 0.547 0.66 0.659 0.67 0.670 0.57 0.568
lro 0.62 0.519 0.59 0_588 0.52 0.517 0.61 0.608 0.61 0.608 0.54 0.537
i tr 0.56 0.557 0.54 n t2? 0.49 0.486 0.57 0.558 0.57 0.568 0.53 0.527
2:2Op itz 0.52 0.517 0.50 0.496 0.44 0.437 0.50 0.496 0.55 0.547 0.49 0.486
Av€rage 0.593 0.571 0.501 0.595 0.616 0.540
tt
in ft/min(V,.-) = 1os6(?)
AverageVelocity
wnere:
e v l c= ( tF *
A v e r a sP )'
\n/
P l a n t : C o m m u n i t yP o w e r U n l t N o . 2 A Test No. t D a t e :6 / 1 9 / 9 6
F a n T y p e & S i z e :8 6 i n c h D w D t C e n t r i f u q a lw i t h A i r t ; i t B l a d e ; -
Pressure Probe:AMCA Standard Pitot Tube
Data RecordedBy: Georqe Brown. Al Smith and Larrv Jones
Test SupervisonHarry Black
FIGURE3
14
-\i, --
.l
H.3 SITE TEST DATASHEET
TypicalF.D.UtilltyFan per AppendixJ
Plant: Community Power Co.
unttruo@re:6/19/86
FAN INSTALLATION
Slzs & ttp", SystemConligurationDrawingNo. C1g185
MrnufacturenXYZCompany (Ductingdimensions)
ldonlltlcstlonNo. AF 89.1902 Measurement PlaneLocallonsDrawingNo. 85
Tfmo:(Start)1:15PM (Finish)Z:20pM
P R E S S U R EP R O B E S
MOTOR Type:AMCA StandardPitot Tubes
Typc:Inductton ld€ntillcallonNo.S&3
HP; l@
MEASUREMENTUNITS
Voltc: 2300
Fan Pressure:ln. wg
Full LolIAmps:333
Temperature:DeO.F
ManufacturenBest ElectricCorp.
BarometeeIn.Hg.
ldcntlflcatlonNo. G1586870 Recordedby: T. Green.A. Smtth,L. Jones.G. Brown
GASTEMPERATURE
& BAROMETER MOTOR DATA
tor twt toz
Tlme Reading N F tw2
.F
tos tw3 pb KW R P M Torque
"F In.Hg.Volts Amps
OF
No. l. "F Input Angle N Ft Lbs
1:15p 99.6 116.0 99.3 9 4 . 7 29.00
I
11 7 6 894
1:45 2 99.8 117.5 99.5 9 4 . 8 29.01 11 6 0 690
220 3 99.8 r 18.0 99.7 a 4 ) 29.O2 11 6 8 '892
Av€rage 99.7 99.5 94.9 29.01 11 6 8 892
P R E S S U RR
EE A D I N G S
Prcraure Fluctu!tlon: t n l e rBox
Fan lnlet Disch.
Pst = * 0.02ln. wg Inboard Outboard Outlet Duct Duct
Ps2 = *0.05In. to 0.1in. wg Readino P r r Pst Ptr
Time P o s i t i o i .r n .w g .I n . w g I. n . w g I. n . w g r. nPse . Pro
Pst Ptr
.w g l n . w g I. n . w g
1:15p 1 €.64 -3.59 18.00
'.3 2 -3.59 -3.50 17.95
-3.57 -3.58 1E.00
4 .3.67 -3.63 18.10
5 €.57 €.66 17.80
o I
.3.62 I
-3.60 17.!X)
I 7 €.62 .3.62 r7.90
I -3.60 -3.62 17.80
'l:45p
1 .3.60 .3.62 17.70
2 -3.58 .3.60 17.90
? -3.56 -3.60 17.80
4 -3.63 -3.59 17.80
5 -3.53 -3.61 17.75
o -3.58 -3.56 17.80
7 -3.5s -3.64 17.60
8 -3.53 .3.62 17.75
2:2Op 1 -\t.c5 .3.63 17.75
2 -3.62 -3.62 17.85
d -.J.5 / -3.60 17.90
-J.O3 -3.58 18.00
-3.60
G F I G U R E4
7
-3.60
-3.58
.3.57
-3.65
17.90
17.80
17.80
6 -3.60 -3.63 17.70
Average -3.59 -3.61 17.85
15
FAN
with Airloil Blades
Slze & Typo: 89" dia..DWDI Centrifugal
DemPcr Posltioh: 1007o ooen
Inlct vancs: 607oopen
Outlot louvro3: None
& EAROMETER
INLETTEMPERATURE
Dry.bulbtemg,t63995'
Wet.bulbtemP,t*3 !!.9'
Brromotrlc pi"t",-P@ljn. Hg
DESIGNSPECIFICATIONS
Fan Inlet *ca 122.41llz
Fan outlet ersaJTiiS-f tz
Fan sas denrlty@g1ff
tn spced 89Orpm
lnboard Outboard
FAN INLET MEASUREMENTS
0.565in. wg 0.583in. wg
Inlct VelocltY Prcsaure.P't -3.59in. wg -3.61In. wg
Inlet Slstlc Prossurc, Pr1 -3.02ln. wg -3.03ln. wg
Inlct Total Prcraur!, P11 95'F
95'F
Fluo Gar TamPcraturc PttotTuba
Probc Typo
Pltot Tube
8 3
ProbeNumbcr 0.0674lbs/ft: 0.0674lbs/ft3
Grs DensltY,pr
FAN OUTLETMEASUREMENTS
DlechergcStallc Prcssurr, P 17.85ln. wg
Dlecharga Gas DensltY' P2 0.0684lbs/lt3
FAN MOTORMEASUREMENTS
1 1 6 0K w
PowerInput to Motor,W - 1555 hP
Motor HonePowcr Output' hP '
94.3s/o
Motor Etflcicncy,n
892
Fan Speed, N, in RPM
CORRECTEDPERFORMANCE
Total Volumelrlc Flow Rate' O3 390,969cfm
Dltterentlal Statlc Presaurc,APr. 2 0 . 3 0i n . w g
Fan Shatt HorsePower,H" 1 4 7 0h p
fFan
dll Total
lslEr Etllclencl,
L.r.v.e..ett'lt nr i 86.9%
Fen Statlc EfllctencY, r-84'9%
FIGURE5 '16
APPENDIXC
vELocrrYPRoFILEq
-r -t-
i = 1 , 2 , . . . ,(T1 2 )
iiiil D rr:l lfllltt
j = 1,2,...U( 3) ,ll
-!tuJ tr
r-:l/
--|
,/\ IN LET
1- - J--.2 BOX
/
l
I SHAFT I
t E
C ENTERLIN I
l^
\ ?-z \
IMPELLER INLETCONE
Flgure7-1A CentrifugalFan
-)
[ *uea 8o7-Bt
FIGURE6
17
D(AMPLE INLET FLOW DISTOHTION CALCUI.ATIONS
(For a typical utility Forced Draft (F. D.) fan see AppendicesJ and H)
POSITIONNUMBER
Traverse
Number h lz lg
Pvtc vr I
: Ylc
v1 fvrc v1
in. wg fpm In. wg fpm In. wg fpm
o l,
lro
Itt
0.659
0.608
0.568
3427,
3?9,2
3182
0.670
0.608
0.568
3456
3?9,2
3182
0.568
0.537
0.527
3182
3094
3065
l.rz 0-496 ?s73 0.547 3122 0.486 29(t
TNLETDUCT (P[-ANE 1)
18
A . 1 . . t E X A M P L E R E C T A N G U L A RF L O W O I S T O R T I O N C A L C U L A T I O N .
=lT
Velocity at Plane 1 (V1)in FPM
I
Traverse No. lr jz lg
iz 2819
;-i
l. 2851 2973
13-lu i2 3003 3182 2913
Plane 1 i3 3122 3210 w
l1 3?s,2 3ar75 3182
t.t) ,.1
/ t5 3456 3507 3237
,!'Y U,,
\ 'i' ':' ) 16 3507 3585 3210
(7.2-1)
V=
UT vl8 3507
3456
3481
3401
3237
gl21
(39068 + 3 9 7 6 6 + 372471/36
t, 3427 3456 .3182
3224 tpm lro 3?9,2 3?s,2 3091
I rr 3182 3182 3065
Ira 2973 3122 F43
N O T E : T h i s i n l e t f l o w p r o f i l e m e e t s t h e r e q u i r e m e n t so f t h i s t e s t s t a n d a r ds i n c e Q a n a Q a r e e a " n
u n d e r 1 0 % . T h i s e x a m p l e c o v e r s a t y p i c a l i n l e t v e l o c i t y p r o f i l e q u a l i f i c a t i o nt e s t a - n Oc a l i u l a t i o n o f
t h e i n l e t f l o w d i s t o r t i o n a t t h e e n t r a n c e o f o n e i n l e t b o x o f t h e d o u b l e - i n l e td o u b l e - w i d t h F . D . f a n
described in Appendix J. Since this fan has two inlet boxes each inlet box must rneet the tlow (
d i s t o n i o n r e q u i r e m e n t su s i n g t h i s p r o c e d u r e . I n a d d i t l o n ,t h e m e a n g a s v e l o c i t y a t t h e e n t r a n c et o
each Inlet box shall not differ by more than 5% (see Section 7.2.3).
19
APPENDTXD COMpHESSIBIUTv
COEFF|GIENT (Kp) CALCUT-ATION{2}
compressibilityis a term that definesthe volumelric change in a g.as
due to changes in pressure,temperature,
and composltlon. The compressibility_co:ffi.1"nl.^.(K/-ii-useo
'incompreisible ro marhematitaily express rhe difference
betweencompressible a.nd conditiorii. rnis c"eri;il
followingequationsor FigureB-1.' il be determinedusing the
o.21
o.22
o.20
0.rt
0 .r 6
o.ta
X 0 ,r 2
0.ro
.0.@
o.06
o.(x
o.02
o.o
0.0 o.(xl 0.0. 0.05 0.06 0 07 0.0E 0.09
z
/
F i sur eB- 1 ( AUCn
C
Bot_n )
20
l-P Unitr or
Symbol UncertalntYof Sl Unlta
X;AX Ai
lnstrumentation
Pressure Readings €p
The symbol e with the appropriate subscript will be
21
Fan Flow Rate eg IO.2 FORMUT-AE.
Gas Density ep In this section the necessaryformutae for the uncer-
Duct Area 81 tainty calculation are given without any values.
MeasuredVelocity 8P"t
Pressure Examples of values for most of the per unit uncer-
Pitot-StaticTube ern tainties are given in Appendix D, bui lt is imperative
Traversing(Location) that the test personnel involved use experienceand
Pitot-StaticTube eg common sense.
(Coefficient)
Speed €p 10.2.1 Density of Gas Handled by the Fan
Compressibillty BK"
Alr e, = (e62 + ed2 + gr2)o.s (10.2-l)
Oalculatcd Veleity Pressure 9p'
flue Gas ep = (euz * + em2)o.s (10.2-2)
Fan Flow Rate eg "ot
Duct Area €1 10.2.2 Flow (Mass Flow or Volume Flow)
Gas Density ep
In a section x:
Slatrc Pressrra €p.
€o, = [eAz * (er,/212 + (epn/2)2 + eTR2+ ea2]0.5
PressureLosses e6
Friction Loss Coefficient E1 (10.2-l
Instrumentation Ai
PressureReadings €p convertedto inlet volume flow
MeasuredVelocity ep,
Pressure Bo,=(eo,2+epf)o.s (10.2-4)
Speed 8p
Gas Denslty eP convertedto another rpm (N)
Compressibillty oKo
6ONK,= (eqrz + eNz * exr2)o.S (10.2-5)
Iotal Pressr.ne ept
10.2.3 Velocity Pressure
Statlc Pressure 9p.
Velocity Pressure ep" €po = (4eO,2 + ep + 4eAz)0-5 (r0.2€)
Pressure Losses e6
Frlction Loss Coefficient q 10.2-4 Fan Total pressure. The followingcal-
Compressibillty €Ke culationwill be followedin the site test to estiblish
Speed Bp per unit uncertaintyfor the fan total pressurewhere
Gas Density ?p the planeof traversemeasurement a;td the planeof
static pressuremeasurementare the same.
Fan Slnlt Po*v B6
APt2 = (APrg2 + AP"32 + AKz)o.s (10.2-zt
Elearical Power Input eW
Speed e11 Othen'.rise:
Power Losses eg
Torquemeter +f AP'' = (APrrz .' Ap"r2 a 66210.s (10.2-g)
Compressibility €K"
Gas Density ep AP,r = (APrrz * aprr2)o.s (10.2-9)
Fan Efiiciency Ert AP, - (AP,r2 + apt2z)o.s (10.2-to)
Fan Flow Rate eq ep, = AP,/P, (10.2_11)
Static Pressure. €P'
or Converted to another rpm and density:
Total Pressure €pr
Compressibility €Kp , = (ep,2+ 4 epz + ep + e*"a10's (0.2-12)
eP,NpKo
Fan Shaft Power Eg
22
A
10.2.5 Fen Sletlc Prsnure' The lollowlngg.al- tainty woutd occur from e4i to (ea1+^19 ery):':'
similar increasewould ociiir for tiib static efliciency
tul,ationwffl be iollowed In the site test to establlsh
'.n-epJ
ttte
static
unii r.rncettatnty
-ptane
of traverse
pressure are the
for fan static pressurewhere
rheasurement
same.
and lhe plane of
uncertalnty
The followingderivationillustratesthat the uncertain-
G
iV of n, wilt iot be alteredby a changeof N (applles
LPt2=(aP.s2+aKz)o's ( 1 0 . 2 - 1 3 ) to 4s also):
Ou PtN Kox
Othenrlse: nr=T
H)','(ffi)
aP.2 = (aP.t2 + AKlo's (10.2-14)
7O.2.7 EtliciencY
23
APPENDX D. PER UNIT UNCEHTAINTIES The normal content of llue ash can be considered
negligibleor includedin e..
Ust of per unit uncertalntles.
O.4. DUCT AREA
D.1 BAROMETFICPHESSURE
D.4.1 Area if Well Definede4 = 0.005. An areais
P.1.t Barometric pressure measured on mercury well defined if:
barometer
a) Round Ducts. Actualmeasurements at fourdl_
Po = Hg T 0.05 ln. Hg ameters equallyspacedcan be made with an
uncertaintyof 0.002,and the differencebetween
eu = 0.0018 the biggest and the smallestdo not exceed
0.005x D.
lf Pp ls to be establlshedin a duct, p* has to be
added,whlch may result in eo = O.O0?. b) RectangularDucts. Actualmeaasurements at
four equallyspacedstationsat each side can be
D.1.2 Barometricpressuremeasuredwith anerold made with an uncertalnryof 0.002, and the dif_
barometereu = 0.003. ferencebetweenthe blggestand the smallestat
each side do not excaed0.003of the mbasured
D.2. TEMPERATURE values.
I
24
pressibility correction. calibration, gradient velocitY. For low voltage motors bigger lhan 500 kW.
Etocfage effect. and Pitot-statictube inclination' lf €s cdn be 0-015
D.5. RPM
For high voltage motors smaller than 500 kW'
Bs C?n be 0-015
Motor losses are ditflcult to measure,but a rough 0.04O In. wg (10 Pa)
estimategives: €L ' 0-1. Becauseof these motor U-rube rnanometer
on the motor efficiency. Indined rnilnometer:
losses,eL is Oepeindent slope ratio 2:1 0.020 ln. wg (5 Pa)
slope ratio 5:1 0.ff)8 in- wg (2 Pa)
D-7.3 For a calibratedrnotores will be dependent slope ratio 10:l 0-0(X ln. wg (1 Pa)
upon the calibration. lt ls necessaryto maintain slope ratio 20:1 0.002 in. wg (0.5 Pa)
voltageand frequencyin accordancewith calibration
valuel and the motor run a periodof time so that its Micromanometer 0.001 in. wg (0.25 Pa)
temperaturecan be consideredconstant- Under
thesecircumstancesand by using0.2%of full range Pressuretransducer (0.003 to 0.01) x Range
uncenaintyinstruments:
For low voltagemotors smallerthan 500 kW',
€s Can be 0.020
25
.D.9.2 Uncertainty on the Measured Pressure ep- [ai2 + (ep x p3r)2lo,s/ptr (o.s4)
(usefulfor judging the qualityof the measurement).
0.9.2.3 Static Pressure in a buct (Using a pitot-
D.9.2.1 Velocity PressureUsed for Pitot Trav- Static Tube)- tf the flow rate in the duct inj a mean
€rJA, 9p, velocity V, and a mean velocity pressure p.,. there
-Oetocity
will be an additionat error of 10% of the
Steady readings enr - 0.01 pressurs.
Minor fluctuations ep"r - 0.02 APr, = [al2 + ep x P"r)z + (0.1 x pvJlto.s (D.g-S]
Fluctuations ep"r - 0.03 epo= [Al2 + (ep x P"r)z + (0.1 x P,J2los/ps
(D€-6)
a(APv) = [ai2 + (en x pv)2]o.s (D.s-1)
D.10 Uncertainty on Losses Between Fan and
MeasuredPlanes.
(D.e-2)
P, Per unit uncertalntyon the frictlon loss coetficlent
_ D.9.2.2 StaticPressure(lnsidea PlenumUsing inctudinguncertaintyon duct tenEh er = 0.04.
Taps)
Per unit uncertainty on losses benreen tan and
Steady readlngs ep, - 0.005 measuringplanes
inor fluctuatlons ep. - 0.010 8K =.(etz + 4egz)o.s (D.10-l)
It the fluctuatlonsappearto be large,this locationwill
not be suitablefor measurement:
26
APPEND|XFEXAMPLEUNGERTA|NwANALYSISTYPICALUTILITYF.D.FAN
and
Data are a combinationof specifiedfan duty
Thls exampleis a typical pretest calculation.
requiredafter the actual test'
customerdrawings."Anotheranalysis is
J.3 GENERALDESCRTPTION
pressure traverses are to be taken at the
J.3.1 Fen FlOw Rate. For this example velocity to intet conditions using density
common intake duct. Flow rate is calculated and corrected
changes.
to be conducted at the entry to the
J.3.2 Fan StitiC Preerure. static pressure traversesare
static pressure rise' Fan statlc
lnlet box and at the discharge of thJ evase to determinethe the inlet from the statlc
prassure is then calculated by subtracting tne velocity pressure at
pressure rise.
are to be recorded at each of the
J.3.3 Fan Gar Density. Wet-anddry-bulb temperatures
Fan gas density is calculateduSing
above planestogetherwith barom",ri"'p,".rure readings'
these and the static pressure readings above'
27
PLANE3
FLOWMEASURING SECTION
CIRCULAROUCT
3 TRAVERSEPLANESAT 60" PLANE 2 (OR4)
(PRO8EINSERTEDFROM STATIC PRESSURE
BOTHSIOES) M€ASUREMENT
PLANEAT OISCHARGE
OF THE OIFFUSER
PI-ANEI
STATICPHESSURE
MEASUREMENT PLANEAT
ENTRYTO INLETBOX.
NUMBEFOF PORTSFOR
PITOTTRAVEFSESDEPENOENT
UPONSIZEOF DUCT
Figure J-l
J.4 PRETESTUNCEFTAINWCALCULATIONS
o o .= 0 . 0 0 3 ou = 0.003
From Apprndlx o.l.l brrom.tric p,.3rur. rt
rlt. to bo mc.tu'.d with dlgltrl jnrtrum.nts
urlng thc remc prlnclplc .t rnorold
Then.
6a = 0.02 = 0.02
€1
28
from clrawlngs
From Appcndir D.4'l Dlmcnsions
b'
u".a to talculatc rrca' Uncrrtatnty could
: vcry mucn in cxccrs ol 0'02' but minimum
I valucr uscd lor this 'xrmplc'
L'
Qp " = 0 . 0 0 6 0 2
8-. = 0.00649
fioh ePPcndix J'4.1
where:
Ai=1Pa
Al = 0.004 in. wg
-om Appcndk 0.9'l inctincd manomrtcr rt lo:l
9P' = 0.02
oP' = o'02
lluctuallons
fiJm epp"ndix D-9.2.1assuming m'not
P"t = 1 4 8 P a
Prt = Pv3 = 0.593 ln' wg
Sii eppcirEixJ.2.1' Addlttonal
valuct
Then.
€6 = o'ol
On - 0.01
Fiom Appcndir 0.5 ncglcctlng cllccts of Pltot
A
tubf co.tflcl.nt
$
Then,
6 Y'
n. =[0.022 + (0.00602/2)2
8a. =tO.O22
-+ + (0.00649/2)2
(0.0211/212 + (0.0211/212
+ d.012 .u g.g12lo.s (10.2-3)
+ 6.012 .u g.g121o's
= 0.0268
- 0-0269 -
J.4.2-1 Converted 1o Inlet Volume Flow Rate' Bot
From Scction 10.2.2
Same as l-P (10.2-4)
eo,=(eor2*ep,2)o'5
A r r u m l n gr p 1 . r p l
Semc inrtru'mcntrtion,tamc uncrrtalnty
Then.
s
Bo, = (0.02692 + 0.006492)0' eO, = (0.02682 * g.96692z)o's
= Q.0277 = O-O275
29
where:
9Q, = O'O277
F r o m A p p e n d i tJ . 4 . Z . t
eQl = 0'0275
(
eu - 0-005 eN = 0.005
From Appondir D.6 mcasurlmrnl ol spccd
Then.
€ONK'=(0.02772 + 0.0052 e o N K o= ( Q . 0 2 7 5 2 + O . O O 5 2
1 9.962210.5 .,u 9.992210.s
= 0.0282 = 0.0280
op. = LP./Pr
By dctlnltlon Inctuding cfloctt ol vcloclty
Same as l-P ( 10f- 17) I
wh€re:
(ofr.2+"rrl)'r
=
APr {tfuFrr]a5 Same as l-P (10.2-16)
:
J.4.4.1 Abrotute Uncertlinty in Total -
Prceaurc tt Inlet, Ap6
Al = 0.04 ln. wg
From Apprndk 0.9.1 normally U-tubc manomltrr
Al=l0Pa
is
ur.d tor mceruring rtetic pratturo.
ep = o-01
From Appcndir 0.9.2.2 minor ftucturtions
9P = o-01
t
30
Pst = '896 -Pa
P.r = -3.6 ln. wg
fr6h epprndlx J.2.r rddltlonal valur
Then,
A P r r = [ 0 . 0 4 2+ ( 0 . 0 1 ^ 1 9 . 6 ) 2 A P s t = 1 1 9 : - * ( 0 ' 0 1x 8 9 6 ) 2
+(0.1 x 146)210's (D'9-5)
+ (0.1 x 0.59)2lo.s
- o.og rn. wg ' = 19'8 Pa
Also,
APvt=€P'rXPy1 AP"r=€p,.,XPr1
= 0.0683 x 146
- 0.0686 x 0.59
- 0.04 ln. wg =10Pa
Therefore.
APrr = (0.082 'u g.g4{0'5 AP6 = (19.82.r 192)o's
= 22Pa
0-09 ln. wg
eP = o'01 6p = o'01
From Append|r D.9.2.2 minor llucturtionr
Then,
..I
31
'
. :. . .'
. :.i i : . : . . . r) . , .- . . . : . . - : : : r - . , . . : . -. - : j : i . ; - j . :
".,
J.4.4.3 Abrolute Uncertainty in Fan Static
Pr€ssure,AP"
8p, = AP'/P"
= 0.21/20.41 Same as l-P (10.2-17)
= 52/5082
- 0.0103 = 0.0102
J.4.4.4 Converted to Specilied Conditions, ap,xpK,
(P, N2, p and Kp)
gP,NpKp = (ep.2 + 4eN2 * epr2 * exr2)0.5 Same as l-P (10.2-1
8)
where:
oP'=o'o1og
'
From Apgcndir J.4.4 ep.=o'0102
ox = 0.005
From Appcndir O.6 oN = 0'005
or, = 0.006
{tdrnepp.nlix J.1.2-r QP, = o'00602
Therefore.
e p r N p K=e [ 0 . 0 1 0 3 2+ ( 4 x O . O O S 2 )
+ 0.006492.r 9.992210.5
e p . N p K=
, [ 0 . 0 1 0 2 2t ( a x 0 . O O 5 2 l
+ 0.006022+ 0.002210.5
I
- 0.0159
- 0.0156
J.4.5 Frn Sheft power, e6
From Scstlon tO.2.lt
ex = [(erxW)2 + (eLxL)e]o.s7g
Same as l-P (10.2-1e)
where:
ew = 0.02
Fiim rppondlx 0.7-r i 0.5 ot fu1 ^ngc ew = 0'02
unc.rtrintyInltrumrnt! urcd.
et = 0-l
FLm ApprnctirD.7.1 €L = 0'1
H = 1467
ero,nipp'.octirJ.2 t8n scrcction H = 1094 kw
W = 1467/0.95 = 1544 HP
A r r u m . d9 5 a m o r o rc f f i c t c n c y W = 1094/0.95 = 1151.6kW
L=W-H=TTHp
L=57.6kW
32
Then'
where:
ex = 0.0217 ex = 0.02]7
FromAppcndirJ.4.5
eu = 0.005 eN = 0.005
From Appcndix 0.6.1
eHNpKe =
EHNpKe ti
rr??.ir:It ir3rti:? f |t"T;;-. I.;;?3i,iI
: *. = 0.0271
. where:
€_p.=0.0103 : €p,=0.0102
From Appcndir J.4.4
e _ X= 0 . 0 2 1 7 OX = 0.02t7
From Appcndix J.t.S
Then,
t
\
33
J.5 ABSOLUTE UNCEHTATNTIESUSED FOR PLOTTING UNCEFTAINW BOUNDARIES
By deflnitlon. Also eqpxD used since plottlng boundaries on quoted characterlstlc curva.
A?.=i4.X€ry. A4r=i4.x04.
- i 85.6x0.0367 .i85.6x0.0365
: ; 3.14% = T 3.12%
q
;U? r
o
=
I
IT
5zo
o
tt,
U
G
I -.--" -' caLcut-aTEo
UNCEFTAIIiTY
Fte REGTANGLE
]D
z
E
too.6
Figure J-2 Erample l-P Flow Rate vq Static Pressure Uncertainty Chert
34
- uNGEFfATNTY (APPRoxrMATEot
RECTANGLE
ffi
s .F
: ouorEDEFFtclENctcunvE l
I (HYPOTHmC^Q
: T-:l
!lrl r
o
tr
L
g
IF
360
o
z
r !i3(Xl
G
I
H szm
aD
!,
H
L
sro
a.9
l < 3(Xl,
v6
z
f,rm
O SPECTFIEOGUAR^NTEE FOI}IT AT T8
f,
I
()
265
U
o
c\
U
I UNCEFTAINTY
F
RECT^NGLE
So
6
(APPFOXIMATED): UNGERTAINTY:: OUOTEOEFRCTENCYCUFVE
--- RECTANGLE |HYP(ITHET|CALI
z (CALCUIjTEOI:-
L
GUABANTEEPCIINTAT TB:
OSPECTFIED
?<
Submerged
Scraper
Conveyor
Test Procedure
I
l- The procedure as written by John Thompson an be modified to use a crane dynamometer
and a
suitable containerfor collectingthe ash.
2 . Grab samples,taken during the collection of the ash sample, of a known volume wiil be mixed
and
weighed. The samplewill then be dried and re-weighed.
conEs TO. F. yl.rtoo.n: 6. Harrlr; XUTEEN Clf PAOES INCLUOIIiG THIS PAGE:
MESSAGE
Pritou 7 &8 -Indoncsia
submergeut"if;:,?:""",x1$"f
lr"'movalsvstem
Craig,
Further to your request in the referenced fax, please find anached a copy of the test procedure for proving
.the perlbrmance criteria for the Submerged Scraper Conveyor as required in the spccificarion of the above
mcntioned projcct-
Kind regalds,
frfu*Arr'tu
R. Bombardiere
MATERhIIS HANDLING DEPANTM ENT
l'reamble
Storage capacities have also bcen determined during the design phase and are
confirrned in the compliance of the cquipment, as built, with the approved drawings.
1hc jet pumps, which provide the motive power for pyrites removal, havc been rype
tr:sted to verify water consumption and evacuation capacity beforc the equipmenr was
shipped. No other testing of the pyrites system is recommended or prescribed as part
ol'this procedure.
l'- A maxirnum peak dry ash rate of 20 MTPH and a norrnal rate of 5 MTPH:
2- The moisture in the ash as it discharges from lhe submerged scraper conveyor
shall be at a level to permit conveying with thc bett conveyor.
'l'he
following procedure is a proposed method for determining that the plant mccts
these criteria.
BsAcEpuBE
()rrvimctric Cepncity
F.quipmcnt Required
. water-tight receiving bin of at lcast 3 m] which will fit beneath the emergency
chute.
. Weighbridge
. Stopwatch
ROLT S-ROYCE INE LIS'TFTI.AL P(OVT'EFT (PACTFIC) LT3
\
--j
Note: The accurar:y of tlris rnethod improves as the size of the receiving bin
increases. If a small rcceiving hin is u-sed,care tnust bc taken to cnsure that timc
me&surcment does skew thc rcsult and that thc time measured is an accuratc reflection
rrf tfie true rate of scrapcr blades pa-ssingover the conveyor head. Ltkewise, the level
gf ash should be rhc full hcighr of the scraper blades throughout the test. Any mal-
ctistribution of ash cturing the collection period, which leaves some of the scraPer
hlades only partially covered, will reduce the determined grnvimeric capacity
runnecessarily.
l)e-wrtering Capability
2- Whcn thcre is confidencc that thc scraper is fully covered (maxirnum ol" Slrrs
rvith plant at nourirral loadirrg) tlre bottom ash Uansfer belts ancl the scraper conveyor
should be re-snned.
3- As ash is drawn our of thc scraper conveyor it should be observed tlrat the
height of the ash is equat to the height of thc scrapcr blades; this condition
corresponds to the maximum discharge ratc from the conveyor-
4. Obscrve the condirion of the ash as it is carried away by thc bclt convcyor- If
the moisture contelt is satisfactory, lhe ash will not run-back toward the loading point
and no ash or water will flow off the tail-end of thc convcyor. These observations will
vcrify performance compliance on the required dc-watering capability of the scraper
convcyor.
FTCDLI..S-FTOYCE INDTJSTRTA,L POUUE'. (PACIFIC)
LTD
rhetruckandre_weigh.Determinethe
1,", *nln"i,onl..#fft::,,,,:"tl.nto quantiryof
PERFORMANCE CALCULATIONS
SYSTEMS DESCRIPTION
infornration in this document is subject to change eithout notice. This document contains
infonmationto the Bail.ey ControtsCompany and is not to be disctosed to any third Party or
o u t l . , r i t t e n c o n s e n to f t h e B a i l . e yc o n t r o t s c o m p a n yU, i c k t i f f e , o h i o .
PERFORMANCE MONTTORTNG
TIt" syst'em will interface with and uses the Network 9o/rnfL 90
Distributed Cont'rol System to accumulate the data. A ten minute
running average on aff variables is used for filter ing and
smoothing the input data.
The system is configured to have 100 inputs and L2s results per
boiler-turbine-generator unit .
The f u n c t i o n to manually substitute or insert data is available
from t h e o p e r a t o r s c o n s o l e .
Boiler Efficiency
Loss due to dry flue gas is the sensible heat in dry flue gas
calculated on a molal basis. The flue constituents are identified
based on fuel analysis and excess air calculations. The mean molal
specific heat and the change in temperature is used to calculate
the Ioss.
T h e i np u t p a ra me te rs a re:
1. Unit load
2 . M a xi mu mco n ti n u o u s r ating of the unit.
Loss due t,o moisture in the fuel and loss due to hydrogen in the
fuel are calculated in two parts. The first is tfe t5ss due to
la t e n t h e at a n d th e se co n d- loss is due to sensible heat. T he
amount of moisture in the flue gas is based on the amount of water
and the amount of hydrogen in ttre fuel. The 1atent heat is
calculated as the factor io reduce t,he high heat of cornbustion to
the low heat of combust,ion. Like the se-nsible heat in dry f lue
gdsr ttte moisture sensible heat is calculated using the nearf molal
specific heat and the temperature change.
The input parameters are:
1. Moisture in the fuel
2. H yd ro g e n i n th e fu el
3. T e n p e ra tu re o f th e flue gas enter ing the air heater
4. Ambient air t,emperature
5. Hi g h e r h e a ti n g va l ue of the fuel
T h e L o s s d u e to co mb u sti b L e s in r efuse is based of the am ount of
BTU rost to the ash. T1pically, this is based on input,s by the
operator.
Condenser performance
Heat Rates
Turbine Cycle Net Heat Rate is defined ad the ratio of total heat
charged to the turbine cycle to the Net unit ceneration.
Gross Turbine Cycle Heat Rate is defined as the ratio of total heat
charged to the turbine cycle to the Gross unit Generation.
Turbine Cycle Reference Heat Rate is calcul-ated from the turbine-
generator manufacturer's theoreticar heat barances.
Net Unit Heat Rate is defined as the Turbine Cycle Net Heat Rate
adjusted for Boiler Efficiency.
Reference Gross Unit Heat Rate is defined as Gross Unit Heat Rate
as calculated from the turbine generator manufacturerrs theoretical
heat balances adjusted for Boiler Efficiency as calculated from the
boiler manufacturer,s data.
COMBINEDCYCLEPLANTPERFORMANCE
CALCULATIONS
Thisis a description Cycleplantperformance
of typicalCombined calculations that can be
performed in a BaileyMFPmodule.Alsoreferto similardescriptionsfor Utilityplantsand
lndustrialSteamplantsfor othermiscellaneous that mightbe appropriate.
calculations As
always,the appropriate are requiredin orderto perform
sensorsor manualinputconstants
the calculation.
A. Fuel PropertyCalculations
where
FUEL_LHV- lower heatingvalueof fuel
(Bru/tb)
FUEL_LHV"- perfectgas lower heatingvalue
(Bru/rb)
Reference:60 deg F, 14.73psia
-
Z compressibility factor
F - correctionfactor for temperatureand
pressure
where
X, - mole fractionof gas constituent
HCX'- lowerheatingvalueof gas constituent
Thecompressibility
factor,Z, is calculated
as
Z = 1.00369- (.0101r SGFUEL)+ (.007 -
IXrl
where
Z - compressibilityfactor
SGFUEL- gas fuel specificgravity
-
\ mole fractionof contained
nonhydrocarbon gases
where
FUEL_LHV- fuel lowerheatingvalue(BTU/lb)
F U E L _ H H V- fu e t h i g h erheatingvalue( BTU/lb)
%_WI_H - weight percenthydrogenin fuel (%)
2
B. Gas TurbinePerformanceCalculations
Performance
Calculation
PowerOutput
ThermalEfficiency
HeatRate
SpecificFuel
PowerOutput(MW)
The gas turbinepoweroutputshall be measuredby the determination of
electricgeneratoroutputor by the determination
of force or torqueand
speed.
ThermalEfficiency(%)
The gas turbinethermalefficiencyis definedas the ratioof the net energy
outputto the energysuppliedto the gas turbine,expressed as a percent.
The gasturbinethermalefficiencycalculation is definedas:
*
THERMAL EFF _ POWER_OUTPUT CONSTANT
HEAT INPUT
where
THERMAL_EFF- thermalefficiency(%)
POWER_OUTPUT- poweroutput(MW)
HEAT_INPUT - heat input(BTU/hr)
CONSTANT - conversionconstant
(3412142BTUthr/MW)
The heat input is the mass flow rate of fuel(s)multipliedby the high or low
heatvalueof the fuel(s).The performancecalculationpackagewill use the
fuel lowerheatingvalue as a basis.
3
The heat input is definedas follows:
HEAT_INPUT = FUEL_FLOW + FUEL LHV
where
HEAT_INPUT- heatinput(BTU/hr)
FUEL_FLOW- fuelflow(lb/hr)
FUEL_LHV- lowerheatingvalue(BTU/lb)
HeatRate(BTU/KW-hr)
The gas turbineheat rate is definedas the heat inputper unit of power
output.The gas turbineheatratecalculation is definedas:
CONSIA/VI HEAT_INP\JT* coNSTANT|
HEAT RATE =
THERMAL EFF POWER_OUTPUT
where
HEAT_RATE - heat rate (BTU/KW-hr)
THERMAL_EFF - thermalefficiency(%)
HEAT_INPUT- heatinput(BTU/tb)
POWER_OUTPUT - poweroutput(MW)
CONSTANTI - conversionconstant
coNSTANT2 - converston
constant
SpecificFuel Consumption(lb/KW-hr)
The gas turbinespecificfuel consumptionis definedas the fuel consumption
rate per unit of power output. The gas turbine specificfuel consumption
calculationis definedas:
where
SP_FUEL_CONS- specificfuel consumption(lb/KW_hr)
HEAT_RATE - heat rate (BTU/KW-hr)
FU E L _ L H V - fu e l l o w erheatingvalue( BTU/lb)
FUEL_FLOW - fuetftow(tb/hr)
POWER_OUTPUT - poweroutput(MW)
CONSTANT - conversion
constant(1000KWperMW)
4
inlettemperature
andatmosphericpressure.The correctedpoweroutputand heat
input(or thermalefficiency)
canthenbe compared withthe guarantee
values.
c. HeatRecoverySteamGeneratorCalculations
The primaryperformance measuresfor the heatrecoverysteamgenerator
as definedby the ASMEPTC4.4 - 1981are efficiencyor effectivenessat
specifiedoperationconditionsand capacityat specifiedoperatingcondi-
tions. Additionalperformance
measuresincludethe heatrecoverysteam
generatorpinchpoint.
PerformanceCalculation
Capacity
Efficiency- l/O Method
Efficiency- LossesMethod
EfFectiveness
P i n chP o i n t
Capacity
Capacity of the HRSG is definedas eitheractual evaporationin termsof
massflow of steamper unit time or heat absorbedby the workingfluidsper
u n i tt i me .
lnput-OutputMethodEfficiency
lnput-output Method Efficiencyis a direct way of calculatingthe HRSG
efficiency. The Input-OutputMethod Efficiency requires the accurate
measurementof those factorsnecessaryfor calculatingthe total heat input
to the HRSG and the heat absorbedby the workingfluid or fluids.
E F F,V, ^ - O U T P U T* 1 O o
INPUT
5
where
EFFro- input-outputefficiency (%)
OUTPUT- thermaloutput(btu/hr)
INPUT-thermatinput(btu/hr)
where
j - heatrecoverysteamgeneratorsection
k - numberof heatrecoverysteamgenerator
sections
Qofi)- heatabsorbedby workingfluidin
sectionj (btu/hr)
where
j - sectionnumber
n - numberof parallelfeedwaterstreams
Fr*,, - feedwaterflowstreami (lb/hr)
h*o,, - feedwaterouiletenthalpystreami (btu/lb)
h*,,, - feedwaterinletenthalpystreami (btu/lb)
6
Whenthe heatrecovery steamgeneratorsectionis an evaporator,
the heat
absorbedin thatsectionj is calculated
as
QAO)= Fsr*hsr * Faoo*haoo- F rw*hr* - Fao,*hao,
where
j - sectionnumber
F", - steamflow(lb/hr)
h", - saturatedsteamenthalpyat drumpressure
(btu/lb)
Froo- blowdownflowout (lb/hr)
hroo- saturatedwaterenthalpyat drumpressure
(btu/lb)
FFw- feedwaterflow (lb/hr)
hFw- feedwaterenthalpy(btu/lb)
Fro,- blowdownflow in (lb/hr)
hro,- enthalpyof blowdownflow into the drum(btu/lb)
where
F., - desuperheater oufletsteamflow (lb/hr)
h." - enthalpyof ouiletsteam(btu/lb)
F", - superheater inletsteamflow(lb/hr)
h", - superheater inletsteamenthatpy(btu/lb)
Fo"- desuperheater inletwaterflow(lb/hr)
ho"- desuperheater inletwaterenthalpy(btu/lb)
ln ASME Test Code PTC 4.4, the thermalinput is definedas the sensible
heat in the exhaustgas suppliedto the HRSG plus the chemicalheat in the
supplementalfuel, if applicable,plus the heat creditsaddedto the working
fluid, air, gas and other fluid circuitswhich cross the envelopeboundary.
Such creditsincludethe following:
Therefore,
thermarinputcan be carcurated
as foilows
=
INPUT Fe*hn,* + HEAT_CREDIT + feE2_FLOWsupp*FIJEL_LHVsupp
where
TNPUT- thermatinput(BTU/hr)
Fo- exhaustgasflowthroughthe HRSG(lb/hr)
ho,"- exhaustgas enthalpyabovethe reference
temperature (BTU/Ib)
HEAT-CREDrr- totarof heatcreditsotherthan
the supplementaryfuelchemical
heat(BTU/hr)
FUE!_FLOW",""_supplementary fuetflow(lb/hr)
FUEL_LHVrrr, _ lowerheatingvalue
supplementaryfuel(BTU/Ib)
The thermal input, INPUT'is a functio.n of the gas turbineexhaustgas ftow and
temperature.Theseparameters aredifficult
to measuL becauseof the unusualgeometry
of gasturbineexhaustsystemsandassociated ductsystemsconnecting
an alternative, to the HRSG. As
the thermalinputcan be calculated usingthe gas turbineheatbalance
method.
Thegasturbineheatbalancemethodenablesdetermination
of the sensible
heatin the gas turbineexhaustgaswithoutthe requirement
for determina-
tionof exhaustgasflowandexhaustgastemperature by measurement.
majorparameters The
usedin thismethodaregasturbinehLatconsumption and
poweroutput.Secondary parameters,whichcomplete the heatbalance,are
steam or water injectionand the miscetlaneous losseswhich- include
auxiliaries,
radiation,
lubricating
oil cootingand turbinecooting.
The gas turbineheatbaranceequationis as foilows
F UEL_FLOW * F lJEL_LHV* q,
T= +FU EL_FLOW* CP,
100- urr*(Trurr- T*\- pG * C
oFw-rN.,* *-, r, - H
fl ^*_rN) * Fr_,r,* (H"_,r,-H^._,rr)-1oso * F*, u,- Loss
where
FUEL_FLOW- fuet ftow (lb/hr)
FUEL_LHV- lowerheatingvalue (BTU/lb)
11"- burnerefficiency(%)
CPrre.-- fuel heat capacity(BTU/lbdeg F)
Trr.. - fuel temperature(degF)
T* - referencetemperature (deg F)
PG - poweroutput(MW)
CNST- constantto convertMW to BTU/hr
F*_,r,- waterinjectionflow(lb/hr)
H*_,n.,- waterinjectionenthalpy(BTU/Ib)
H**_,",- referencewaterinjectionenthalpy
(BTU/tb)
-
F"_,*, steaminjectionflow(lb/hr)
H"_,nr, - steaminjectionenthalpy(BTU/lb)
H*"_,",- referencesteaminjeclionenthalpy
(Bru/tb)
LOSS - miscellaneous
gas turbinelosses
(BTU/hr)
The ASME Test code PTC 4.4 definesthe heat lossesas follows:
- Heat loss in moistexhaustgas
- Heat loss due to surfaceradiationand convection
- Heat loss in the circulatingpump cooling
water and seal water leavingthe envelope
- H e a t l o ssi n mi sce l l a neous
coolant
9
The heat recoverysteam generatorradiationand convection
losses are
small comparedto.theexhaustgas losses. However,such
losseshave to
be evaluatedin orderto determiiethe overallefficiency,
as definedby the
lossesmethod.Also,accuratecalculationof the intermediate
gas temfera-
turesrequiresthe magnitudeof radiationand convectionlossesas an input.
where
Qn= 0174- E - 4 *460c
f[ 1 0 0 ) (
Tu*460q
100 )J.^"
Qp- radiationheatlosses(btu/hr)
-
E surfaceemissivity (btu/hr/ft2)
T" - surfacetemperature (degF)
T" - ambientair temperature(degF)
\ - areaof surfacethroughwhichheatloss oc-
CUTS
(ft')
The convectionloss shallbe determinedfrom
Qc=0.296-(f"-T"\t.zs .(
W+68. 9
6 8 . 9 ).o.
where
Q" - convectionheat losses(btu/hr)
W - averagesurfaceair velocity(fpm)
T. - surfacetemperature(deg F)
Tu - ambientair temperature(deg F)
,\ - area of surfacethroughwhich heat rossoccurs
(ft2)
QRc=Qn*Q"
where
Q*" - radiationand convectionheat loss (btu/lb)
10
fi""'[:":'f::fi3:s"g,5::,T;:iJ5:.",'cooranuossesdonotappryhere
LOSS = Fa * Hcour *
en"
where
LOSS - heat recovery
steamgeneratorheat loss (btu/lb)
Fo- exhaust gasnowtfOlnii
hoor,- t*:g-"1<]raust'gas
enthafpy
e*" - radiation (btu/tb)
andconirection
heatloss(btu/lb)
@ffectiveness
Effectiveness quantiti"rtn"T"at
device and is ihe ratio tn" transferperformance of a heatrecovery
entharpy "i
dropof the gas wniln d.p ;; tn" g", to the maximum
i"".,tharpy
in"oi"ti*rri porrior" The
methodrequires.the-accurate Effectiveness
measurement of HRsG gas temperature
appropriaterocations.The at
gas andwatertemperatures maximumentharpydropwourd
occurwhenthe
woutdcoincide on" o?,or" points. prc
prefersthe effectiveness 4.4
as tnl rJndamental "i p"rrorrr,"nce
reffectsthe meritof the ooirer, measuresince it
wniln is not;;d;;xpressed
by efficiency.
The actuareffectiveness
of eachheattransfersection
fromworkingffuid_andgas t"rp"r"trres. The is computeddirecry
to the expectedperfor-man"".-in" u"tuesare compared
usingthe heatrecovery expected""tr"-r
effecrrveness is catculated
steamgenerator conductance moder.
The maximumheattransfer
ratein an individualsectionwoutdoccurwhen
the gas outfettemperature
reaches, the
whentheworkingffuidouteti"rp"r"trr" *o.r.ingJr-;dinrettemperatureor
reacr,"Jtn"'L", inrettemperature.
11
For each sectionj, the actual effectivenessis calculatedas follows
thenEA =
if DTWA> DTGA, * looo/o
ffi
where
j- se cti o nn u mb e r
Efi) - sectionaleffectiveness(%)
DTGfi) - (To,-Tor)- gas temperaturedrop (degF)
DTW(J)- (T*r-T*') - working fluid temperatureincrease(deg F)
DTMAX(J)- (To,-T*,,)- maximumtemperaturedifference(deg F)
Overall Effectiveness
Overall effectivenessof the HRSG is definedas the ratio of the enthalpy
drop of the gas to the maximumenthalpydrop of the gas which is theoreti-
cally possible.The maximumenthalpydrop would occurwhen the gas and
water temperatures would coincideat one or more points(pinchpoints).
12
The maximumtheoreticalfypossibfe
assumingthatthe working j":p:,111r9 grop,is computed by
fluiOintetor sectionj is the pinch point. This
calculationfollows
-T*,ral
DTrrD -- l l i
Tn(R)
* Qa,ror
IE;;l
where
j - sectionnumber
k - numberof sections
DT""(i)- maximumpossible
temperature
drop_
sectioni(deoF)
r"(k) - tT:,Q-o;;i"19itemperature
T*,*0)- working (desF)
fluid inletiemperaturefor
section.j(degF) For evaporators,
this is the saturationtemperature.
Qo(q)- heat,absorbed b/ wort<ing
q (btu/fb) fluidsection
Q4ro,- tola]heatabsorbedby
workingffuid
(btu/tb)
The smalrestmaximumpossibre
callymaximumpossibter"d;;;;e temperattledrop,DTr"u),is the theoreti_
dropDT""r.
Theactualheatre,coverysteamgenerator
as forows overa,effectiveness
is carcurated
Tn(k) - I.(0)
EFT = * 100%
DT,,,
where
EFT _ actualoveralleffectiveness
(%)
To(k)- HRlg gas intettemp-erature
To(0) (deg F)
t*lgga_s ouflett",ip"r",ure(des
DT"",_smalleitmaximum F)
ilssibret"rpJ."irre drop(degF)
1s
Pi n c hP o i n t
Fincfrpoint is definedas the minimumtemperaturedifferencebetweenthe
HRSGgas and water/steam cycles. The actualpinchpoint is calculatedas
follows
DTP=TG(m-1)-TwtN(m)
where
DTP - PinchPoint(deg F)
m - PinchPointlocation
To(m-1)- gas temperaturewherethe pinchoccurs(deg F)
T*^(m) - workingfluid inlet temperaturewhere pinch occurs
(d e g F )
Calculation
Performance
Heat Rate
CorrectedHeat Rate
lsentropicEfficien
Heat Rate
The steam turbineperformanceis evaluatedby comparingthe corrected
calculatedsteamturbineheat rate with the designsteamturbineheat rate.
The corrected steam turbine heat rate is obtained by correctingthe
14
steamturbine
heatrateforoperating
ffi!:;f"t conditions
thatdeviatefrom
HR = Heat_Supptied
_ Heat_Returned
pW
HR=
where
HR _ steamturbineheat
pG _ generatoroutput rate (Btu/kwh)
(MW)
w,, - feedwaterfrowto the steam
generator(rb/hr)
ht - enthalpyof steamentering
tne-mainllrnin"(Btu/tb)
htr - entharpyof feedwaterrea-ving
r""J*Jo system(Btu,b)
Group1 corrections:
- Condenser condensate
subcoofingdeviation
correction.
- condensermakeup
frowdeviation
correction.
Group2 corrections:
- Throtflepressure
deviationcorrection.
- Throtiletemperature
deviation.orr""iion.
- Turbineexhaustpressure
deviationcorrection.
The Group1 correctioncurves prc
in
MW, 2400 psr, 1000t1000],'*iin g 1_ygr"deveroped froma typicar320
pressurerhese curvesare 7 FW h;;;;"nd a 2.5"HGback_
appric":|" ; ;;;;;;;e
]o -roof pfants(up to 600
}[H,lTl j3 lffi, | ;"*#r.-lr, "" deveIopeJ r thespecifiedcyc
Ie
"T "
asthose
I?:?:l3"i","Jlffitf['.il?J::.."ile usedinthecomprehensive
15
Thesecorrectionsaccountfor operatingconditionsthat deviatefrom design.
The calculatedheat rate is valid or the presentoperatingconditions.The
correctionsONLY allowfor comparisonwith the designheat rate.
lsentropicEfficiency
The steamturbineisentropicefficiencyis definedas the ratio of the sum of
the isentropicpoweracrosseach steamturbinesectiondivided by the actual
poweroutput. The steamturbineisentropicpoweroutput is a functionof the
steam turbine configuration,i.e. numberof steam turbine parts and the
numberof sectionsin each turbinepart. In the mostgeneralcase, the steam
turbine isentropicefficiencyis calculatedas
where
lE - isentroPicefficiencYo/o
i - numberof steam turbine Parts
j - numberof steamturbinesectionsper part
6Hi,i- isentropicenthalpydrop part i section
j(btu/lb)
F,,- Parti net flow sectionj
(F.*ri - Foor,)(lb/hr)
PG - generatoroutPut(MW)
E. Condenser PerformanceCalculations
16
If-lnfly performancemeasures
for the
ASME PTC12.2_ 1eB3areGiil berow.condenseras definedby the
Performance
Calculation
ExpectedCondenser pressure
OverallThermalTransmittance
Condensatesubcoofi
FfpectegCondenser pressure
The condenserpressureis thE
most.importantperformance measure,as it
ts closelyrelatedto the usefutexpansion'or
condenser stearfi
in tn" turbine.The actuat
vacuum,a condenseiinput,is comfar"o-io
evaluatethe potentiarincrear" expected vacuumto
in 3t"ar powergeneration.
p'"'.r,"'iJtn","t*"tion
""p"nrion
prJr.rr"
"no orthe
expected
]ff."#:J?3ff:l:,T"'
where
PC. - condenser
"rp"^:!"9condenserpressure(psia)
T",u- expected saturation'i"r]"r"ture (degF)
The expectedcondenser saturation
ove aItransmittance rhet;,[?:'l1Hf#i*ffiiffi:""t,
ra|| therm
determinea rerationshipfor tne cooiing*"Grl;p"rltrr" :'J::J?:
thermaltransmittance rise.The overa'
i, catcutateJ as foflows
g = F" * co* - In
A [-r":rt j
Lr"-rrl
where
U - overallthermaltransmittance
(BTU/hrYt2"F)
F" - coolingwater flow (lb/hr)
Co, - specific_heatof cooling
water (BTU/fb/F)
A - surfacearea (sq ft
)
T, - coolingwater inletiemperature
(deg F)
T, - cooling_waterouilet temperature
(deg
T, - saturationtemperaturectrrespondingF)
condenserpressure. This temperatui to
is
17
o
calculatedfrom saturationtemperature
atgorirhm
(degF)
The relationship
for the coolingwatertemperature
riseis as foflows
where
7= UxA
F" * Co,
and
Tr,e- expectedcondensersaturation
temperature
(degF)
Z _ expectedconductance
18
-z
F rx (Hr+ Co*32)+F r"* Crx Tr"+ Fru* Cr* Tru +F C rrxTt * (1- e )
I,,, "* -z)
Co* (Fs +Fru+ F r") nC or*F r*11- e
where
T".. - expectedcondensersaturation temperature(degF)
F" - coolingwaterflow (lb/hr)
F" - condensersteamflow(lb/hr)
H. - steamenthalpyat inlet(btu/lb)
Co- specificheatof water(btu/lb/deg F)
-
T"oruohotwell temperature (degF)
F"" - returncondensate flow(lb/hr)
-
Tr" returncondensatetemperature (degF)
-
Fr, make-upwaterflow (lb/hr)
T", - make-uP temPerature (degF)
Co'"- specificheatof coolingwater(btu/lb/deg
F)
-
T' coolingwaterinlet temperature (deg F)
T, - coolingwateroutlettemperature (degF)
OverallThermalTransmittance
OverallThermalTransmittance theamountof heattransferredper
describes
unitof time,unitof surfacearea,anddegreeof temperature difference.The
actualthermaltransmittance is obtaineddirectlyfromthe currentoperating
parameters.
tt-
f*n f"f* ft*n for* ff
where
r* - water side film resistancereferredto the
OD of the tube
r",- steamside film resistance
r* - thermalresistanceof the oxidefilm on
the insideand outsideof tubes
-
ro* thermalresistanceof the oxidefile on
the insideand outsideof tubes
-
r, Increasein thermalresistancedue to an
accumulationof dirt, scale,slime,etc.
on used condensertubes. Determinebased
factorat design
o n a .8 5 cl e a n l i n ess
condenserload.
-
Uo Overallthermaltransmittance with clean
used tubes
19
The aboveheattransferresistances
tube materialand oimensionr-"no arecomplexfunctionsof the condenser
operatingconditions.(Referto pic the characteiisticsof water at the
12.2Ap;;;ix z tordetairs)
@
condensate subcoolinilsthe difference
betweenthesaturation
temperature
ff:"'f:jf'ffil:;:,"","T"oenservacuum
andthetemperatur"
oi tn"
ft is important
to minimizecondensatesubcoofing,
returnedto the feedwater. as this heatthat
conJ"nsers are normarydesignedmustbe
subcooring cannottakeprace.in"ir".", tne so that
is zero' Any deviation'from expeci"o u"rr" for subcoofing
tn"i i. an indicationoimechanicar
suchas air leakageor vacuumpump probtems,
capacitylimitations.
Drs=rs,qr-T"oro
where
DTS- condensate subcooling(degF)
T.^, - saturationtemperature-@
cJndenser
pressure(degF)
lcoruo.- temperatureof condensatein hotwell
(des F)
The performancemeasuresfor
the cooring
-coie
tower as defined
crr ncleli;;;" rest by the ASME
5rl.."ftlrrr"?#. roiw"t"r_coolins
rowers
PerformanceCafculation
ThermalCapability
Cold Water Temperature
PredictedCold Water Temperature
Range
PredictedRange
Approach
20
ThermalCapability
Th" thermalcapabilityof the coolingtower is definedas the ratio of the
adjustedtest circulatingwater rate to the predictedtest circulating water rate
at ine test thermalconditions.The thermalcapabilityor tower capabilityis
definedbelow
=
TowER-cAPABtLtrY x 1oo.o
ffi
where
TOWER-CAPABILITY- coolingtowercapability
(%)
. WATER-RATEADJ - adjustedtest circulatingwater
rate (gPm)
WATER-RATE' - predictedtest circulatingwater
rate (gPm)
FAN-POWERD
WATER-RATEADJ= WAIER-RAIE .(
t\ FAN_POWERADJ
)'"
where
WATER-RATEADJ - adjustedtest circulatingwater
rate (gPm)
WATER-RATE - measuredcirculatingwater rate
(g p m)
FAN-POWER' - designfan Power(HP)
FAN-POWER^', - correctedtest fan power (HP)
The fan power is correctedfor any variationof the fan air densityfrom the
designfan air density.This correctionfor air densityis necessarybecause
the manufacturer'sperformancecurves are based on constant fan blade
pitchangle. As atmospheric air conditionsand/orheat load conditionsvary
from design,the mass air rate will vary, causinga direct variationin air
pressureloss and air horsepower.Referto ASMEPTC 23-1986and the CTI
AcceptanceTest Code for CoolingTowersfor the detailedequations.
21
eojd WaterTemperature
uotdwatertemperature is the mostimportant
closelyrelatedto_l!" cono"n.li'pr"rrrr" performance measure,as it is
Thecordwatertemperature and turbine power generation.
is definedag the averagetemperature
as it leavesthe towerfirf and "witnout of water
makeupwater,th_e_,cofd the basin. browdown and
"ni"o
watertemperature is the
basinor in the discharge " mixed temperature
in the
"onOuii.
when blowdown andmakeupwaterexist,thecoldwater
temperatureat
toweroutfetis estimate!.from a oynamicenergyoriun"" of the coofing the cooling
towerwater
-nliiiln, inth""il;;1"]"in,th"rolrowins
:fi':i,*'#f[5,::J-jj""o dirrerential
where
V, - water basin vofume (ft3) i
p _ water density (lb/ft3)
T" - water.basintemperature(deg
F) '
L - circutating
wateritow ltOlniy "
T*, - cofdwatertemperature cooring
F", _ make_up - toweroutet (degF)
waterflow(lb/hr)
Tr, - make-upwatertemperature (degF)
Fro- blowdownflow (lb/hr)
-( \ /- \
Twz= r" - 1 * :!pl tuu * Fuul *
* u" o *dr"
I\ L/ It '
L ) t-'dt
The predictedcordwatertemperature
is obtainedfroma protof circurating
waterrateversuscooringwatertemperature
inletwetbulbtemperatuie. at the coolingtowerrange
rnis proiis determin;Jfr", manufacturer,sand
data.
Approach
Approachis the differencebetween
ambientwet-burb the cordwatertemperature and the
temperature at thetestconditions.
towercannotcoorwater iheoreticary, a cooring
to a temfeiaturerowertnanine prevairing
temperature'The actualapproach wet_bulb
is obtaineooiiecilyfrom the current
22
operatingparameters,while the predictedapproachis computedfrom the
predictedcold watertemperature.
APPROACH=Trr-To*,
APPROACHT=T*r,r-To*"
where
APPROACH- coolingtowerapproach(deg F)
APPROACH"- predictedcoolingtowerapproach
(d e s F )
-
T*, cold water temperaturecoolingtower
outlet(deg F)
T*r,, - predictedcold water temperaturecooling
tower outlet(degF)
To*, - ambientair wet bulb temperature(deg F)
Range
Range is the differencebetweenhot and cold water temperatures.As the
circulatingwater flow is often constant,range is a direct measure of the
cooling duty. The predictedrange is obtaineddirectlyfrom the predicted
cold water temperature.
RANGE=Twr-Twz
RANGE.=Twr-T*r.,
where
RANGE- coolingtowerrange (deg F)
RANGE' - predictedcoolingtowerrange(deg F)
T*, - cold water temperaturecoolingtower
i n l e t(d e g F )
T*, - cold water temperaturecoolingtower
o u tl e t(d e g F )
T*r." - predictedcold watertemperaturecooling
tower outlet(degF)
23
rti..?i.:i.:. .; ',1:,::..,..j,t.::.
'"t'::;-.,j. . :,:,a.i
. , j i J , . . - . . + r : : ?.:.,.' . r : , ,- ::.. .:.' -rt .
PerformanceCalculation
PURPAEfficiency
ThermalUse
GrossPlantEfficiency
GrossPlantHeatRate
Net PlantEfficiency
Net PlantHeatRate
PURPAEfficiency
PublicUtilityRegulatorypoliciesAct (PURPA)Efficiencyis
definedas
follows
PGrn + .5 x THERM_ OUT\
EFFru^ro =[ -) * 1O0o/o
Q,,,,
where
EFFpuRpA - pURpA efficiency(%)
. PG*r, - plantnet poweroutput(MW)
THERM_OUT - ptantthermaloutput(MW)
Qrrr. - totalfuel heatinputfromgas turbines
and duct burners(MW)
ThermalUse
ThermalUse is definedas follows
where
- plantthermaluse(%)
THERM_USE
GrossPlantOutput
The plant'sgrosspoweroutputis the sumof the gas
turbineand steam
turbinegenerator
outputinputs.
24
Gross Plant Efficiency
The gross plant efficiencyis definedas follows
PGn' + PG" + Qoo^ )
^=f ff).1oo%
E F F :^ =(
wnere
EFFGR - gross plant efficiency(%)
PGor - total gas turbinepower output (MW)
PG"r - total steamturbinepoweroutput(MW)
Q"*" - processheat consumption(MW)
Qrr.'- - total fuel heat inputfrom gas turbines
and duct burners(MW)
where
QMWA,ror - total heat absorbedby workingfluid
in heat recoverysteamgenerator(MW)
-
Q", heat used in the steamturbine(MW)
The heat used in the steam turbine,Q"r, is the sum of the heat used to
generatebackpressurepower and the heat used to generate condensing
oower.
HRATE**=
#;#
where
HRATE.R- gross plantheat rate (btu/kwh)
k - constantto convertmw to btu/kwh
25
Net PlantOutput
Theplant'snet poweroutputis the differencebetween
the gas turbineand
steamturbinegenerator outputsand theptanrspaiasitic
poweroutputis usuallyan inputto the performance roading.The net
assessment routine.
Net PlantEfficiency
The net plantefficiencyis definedas follows
EFFNE'=(#)*1oo%o
where
EFFNET - net plantefficiency
(%)
PG*., - plantnet poweroutput(MW)
Qrre.- totalfuelheatinputfromgas'turbines
and ductburners(MW)
NetPlantHeatRate
The net plantheatrate is definedas follows
HRATETTT=
w
where
HRATENE,- net plant heat rate (btu/kwh)
k - constantto convertmw to btu/kwh
26
CALCULATIONS
STEAMPLANTPERFORMANCE
TNDUSTRIAL
of typicalIndustrialSteamplantperformance
Thisis a description calculations
that
can be performedin a BaileyMFP module.Also referto similardescriptions for
Utilityplantsand CombinedCycle plants for othermiscellaneous
calculations
that
mightbe appropriate. As always,the appropriate sensors
or manual
inputconstants
arerequiredin orderto performthe calculation.
A. CombustionCalculations
PercentExcessAir
On line boileretficiencycombustion calculations deviatesignificantly
fromthe procedures givenin PTC4.1. The PTC procedureusesOrsat
datato establishthe# of air per# of as firedfuel. The Orsatprovides
percentby volumeof COr, q, Nl,and CO in the dry flue gas. The
Orsat operatesat ambienttemperature thereforethe moisturein the
fluegasis condensed outof thesampleandsampleis considered dry.
where
Molesof th-eoretical
O, _the mofesof O,
necessaryfor compretecombustionor tbo #s of
the fuel.
Combining
Ee 1 & Ee 2:
(o/oOri
n theFlue G as)(Totat Molesof
%Excess Air = 6 6 3)
uor@'
C H 2 S-W
+ Nz.,H-ca
_+
-3874(;-;-*-a
- 12 2 Tt'f-.;
" (EO5)
-r_i___
_r
12 4 3232
2
C *H, *S *14l *Nz
12 2 . 32 18 28 +3.874
s c- - =
"K ( E O6 )
C *H, *S o,
-
1243232
C*6H.*9S
' 9 3 7 1 *?W *9N-
K.^
JU
= +3.874
Q+3H2*9s-2o,
B8
Percentoz=ffi
where
C, H2,S, \ry,Or, N, are the #s of carbon,hydrogen,sulfur,
water & nitrogenper 100 #s of as firedfuel.
3.874is the molesof Nr, CO2,W & inertsin standardcombustionair per mole
of o, in standardcombustionair. ie Molesof otherthan O, per mole of O, in
standardcombustionair.
standardcombustionair has 0.013#s
of moistureper # of dry air. This
amountof moisturecorespondsto ambient
humidity. F andoo p"i"Lnt relative
"ii.iio
The constants4.g74,3.g74 and 20.51g
must be modifiedbased on the
measuredmoisturein the combustion
air.
Note:whole numbermofecutar
weightsare shownfor simpricity
Typicalvaluesof l(*. are as follows:
Naturalgas- 5.375
B u n k eC
r oil 5.145
Bituminous coal 5.125
Sub-bituminous coal_ S.2Ss
Lignite S.T1S
Pinewoodbark,40%moisture6.175
Hardwoodbark,4Oo/o moisture_ 6.345
Bagasse 6.905
CokeOvenGas- 5.540
Blastfurnacegas- 10.895
4
CALCULATIONS
UTILITYPLANTPERFORMANCE
This is a descriptionof the more typical Utilityplant performancecalculationsthat can be
performedin a BaileyMFP module. As always,the appropriatesensorsor manualinput
constantsare requiredin orderto performthe calculation.Practicallyany performance
calculationcan be performedin an MFP.
A. Bo i l e r Ga l cu l a ti o n s
Calculations
Performance
BoilerFuel Efficiency
CorrectedBoilerFuel Efficienc
BoilerFuel Efficiency
The boilerfuel efficiencyis a directway of evaluatingthe boiler performance.
The boiler fuel efficiencyis obtainedby dividingthe thermaloutputby the
thermalinput.The boilerfuel efficiencyis definedbelow
^- - )UTPUT * 1oo
EFFDT
INPUT
where
EFFBF- boiler fuel efficiency (%)
OUTPUT- thermaloutput(btu/hr)
INPUT-thermalinput(btu/hr)
fn ASME Test code PTc 4'1, the thermal
output is definedas
the chemical
fuerprusthecredits
minustherosses.rhis quantityi.
::?:li:il: "omprt"o
OUT?UT=Hr*H"*_H,
where
OUTPUT- thermatoutput(BTU/hr)
H"n- sumof heatcredits(BTU/hr)'
H,_- sumof heatlosses(fifUlnr) '
H,- chemicalheatin the fuel (efU/fO)
Therefore,thermalinputcan be calculated
as follows
INPUT = H,
where
INPUT-thermalinput(BTU/hr)
H,- chemicalheatin the fuet
1'AfUnn)
Thusthe boilerfuelefficiency
calculation
becomes
Hr *Hcn -H
EFF BF = 1OO *
Hf
or
EFFBF=100+CR-L
where
CR - the sum of the credits (%)
L - the sum of the losses (%)
2
Percentheat Credits(CR)
CRe= Heat in enteringair
CRz= Heat in atomizingsteam
CR, = Sensibleheat in fuel
CR* = Pulverizeror crusherPower
CR* - Boilercirculatingpump power
CRr - Primaryfan Power
CR, - Recirculatinggas fan Power
CR,a = Heat suppliedby moisturein enteringair
CR* = Heat in the coolingwater
Percentheat Losses(L)
Luc= Unburnedcarbon in refuse
Lc = Heat in dry gas
L', = Moisturein fuel
Ln = Moisturefrom burninghydrogen
L.n = Moisturein air
Lz = Heat in atomizingsteam
L"o = Carbonmonoxide
LuH= UnburnedhYdrogen
Lusc= UnburnedhYdrocarbons
La = Radiationand convection
Lo= Radiationto ash pit, sensibleheat in slag & latentheat
of fusionof slag
Lo= Sensibleheat in flue dust
L, = Heat in pulverizerrejects
Lw = Heat in coolingwater
Lx = Soot blowing
L, = Estimatedand Unaccountedfor heat losses
The feedwaterflow, main & reheat steam flows and their enthalpiesas
determinedin the turbine heat rate calculationsare used by the boiler
to determinecreditsand lossesthat are a functionof
efficiencycalculations
boilerheat productionratherthan a functionof 10,000BTUs of as fired fuel.
3
The forfowinocoTe,ctions are _appfiedto correctthe carcuratedoper.ating
boiferefficiencyto designcondit'i-Jns.
- combustion air temperature
- or rerative
humidity
."-i deviations
llomizing steam usage deviation
- Air heaterleakagedeviation
- Moisturein the fuefdeviations
- Fuelcomposition (Hr) deviation
Note: The carcuratedboiterefficiency
is varidfor the presentoperating
'o"ections
ot{LY r* ;";;"ri"on witntrJoJsisn
;:ilSJt:"#:,"rI|1 "no'
B.
The steamturbineperformancecalcufations
plants that do not have the are a simplifiedofferingfor
instrumentation n"ilrr-rv for a comprete
ANSI/ASMEPTc 6 turbine performance
requirescompfeteinstrumentation
"y;i; of the tesi. ANSI/ASMEprc 6
water heaters- The unit performance turbine exractionsand all feed
parametersare cafcutatedfrom
minimum of instrumentation a
in additionto the normalplantinstrumentation.
Theperformance packagecalculatesthe current
cafculatedvafuefor operating heatrate and correctsthe
co'ectedperformance tnat Jeuiate from design. The
"onoitions
can.beiompared.with
be trendedto uncoverequipment designperformance and can
degradation.
Turbineefficiencies
are carcufated
whereinstrumentation
is avaifabre.
PerformanceCalculations
Heat Rate
CorrectedHeat Rate
HeatRate
ASMEPTC6'', ':,:l""it:aty
designeda.sa simpfified
towcostmethodof
monitoring
theturbinecycfep"rro*"nce. rt
measurements requires
a minimumof accurate
and providesgenericcorrection-;"to^
measured heatrateto designof,erating to correctthe
conditions.
4
the heat input to the turbinecycle
Turbinecycte Heat Rate_
generatoroutput
where
W,r = Feedwaterflow
hr = Enthalpyof throttlesteam
Ws = Hot reheat flow
hz = Cold reheatenthalpy
P,"rp= BTUs added by motor drivenfeed pump
W."uh= Steam flow to steam coil air heater
h" = Enthalpyof condensate
Pn = Generatorpower output
The main, and reheat steam flows are determinedfrom the measured
feedwater flow by adding attemperatorflows, and subtractingboiler
blowdown,design turbine leakagesand the extractionflow to the top HP
heater. The extractionflow is determinedby solvinga mass and energy
balancearoundthe top HP heater. This ANSI/ASMEPTC 6.1 methodonly
requireshigh accuracyinstrumentation for unit generation,the HP and lP
turbine,the top HP heaterand the condenser. This methodwas developed
by the ASME primarilyto monitorchanges in the overall turbine cycle
performance.
5
i
: _ ; : . : -
, '
:t .:-;:!
Group1 corrections
Group2 corrections:
-
- Jhrotflepressuredeviationcorrection.
Throtfletemperature
deviationcorrection.
- Reheattemperaturedeviationcorrection.
- Reheaterpressuredropdeviationcorrection.
- Turbineexhaustpressuredeviationcorrection.
Group2 corrections
arethesameas thoseusedin the comprehensive
6 steamturbinetest procedure. prc
Thesecorrections
accountfor operating
conditions
that deviatefromdesign.
6
C. Feedwater Heater:Calculations
Performance
Calculation
TerminalTemperature (T.fD)
Difference
TemperatureRise
DrainCooler DCA
TerminalTemperatureDifference(TTD)
where
TTD_HTR - feedwaterheaterterminal
temperaturedifference(deg F)
TSAT_HTR- feedwaterheatersaturatesteam
temperature,a functionof the
steam inletpressure(deg F)
THTR_OUT- feedwaterheateroutlet temperature
(d e s F )
FeedwaterTemperatureRise
where
TR_HTR - feedwaterheatertemperaturerise
(d e g F )
T_HTR_OUT- feedwaterheaterouflet
temperature(deg F)
T_HTR_IN- feedwaterheaterinlettemperature(deg F)
Solvingfor h15NL G:
ntsrvto- AHte-ak(h1sA
-h_8A)+hlsG
100
t15NLcan be determined fromhISNL G.
where
AHleak- the percentair heaterfeakage
(%)
h_8A_ the enthalpyof the combustioi
aii ai
the air heater'sair inlettemp
(BTU/tb)
h15A_ the enthafpy of the combustion air at
the a.irheater'sgas ouilettemp
(BTU/lb)
hl SG _ the enthalpyof thefluegas at
the air
heater'sfluegas exittemp
h1SNLG_ the enthalpyof theflue iefU/lO)
g", tn"
air heater,sflueias exittemp_ no "t
teakage(BTU/|b)
tl SNL_ the.airfluegasouflettemperature _
no leakage(degF)
Note:The enthafpyof combustion air is dependent
speciflchumidity.Theentharpy on its temperatureand
of fruegas is dependenton its temperature,
moisturecontentandconstiiuentg".r9,
and dry frue gas can be determinEd The entharpyof dry air,moisture
coefficients fgm_simpre quadraticcurvefits. The
are givenin B&w steam,40th Ed,
arerelativeto 77 F- The coefficients.for i"g"'giz. Theseentharpies
g"n"ii;-Jt fruegas may be used.
Theenthalpyof dry frueg"" oo"= not
varysignificanfly basedon composi_
tion' lf the entharpyof the gas is
known,thelemperaturecan be found
solvingfor the positiveroot'orthe quadratic by
equation.
E.
performance
measures
are unit net heatrateand
lffd[T,:",*'#
Performance
Calculations
UnitNet HeatRate
ControllableLosses
10
DrainCoolerApproach(DCA)
where
DCA - drain cooleraPProach(deg F)
T-DRAIN-OUT - outgoingdrain temperature
(desF)
- feedwater
T_HTR_IN heaterinlettemperature
(d e g F )
D. Ai r H e a te rC a l cu l a ti o n s
Calculation
Performance
Gas side efficiency
Air
The air:heaterr
gas sideeffieiencyis:
_tl'NL)(1OO)
AH_EFF_ (t14
t14 _t_8
where
AH_EFF _ the percentair heater gas
side
efficiency (%)
t14 - the air heaterflue gas inlet
temperature(deg F
tl SNL _ the cafculateO air heaterflue gas
exit temp - no leakage (deg F) e-.-
t_8 _ the air heater combJstiona]r
intet
temperature (deg F)
Air HeaterLeakage
-h_BA)= _hlsc)
1(hlsNLG
ffirrruo
9
Unit Net Heat Rate
where
W,t = Feedwaterflow
h1 = EnthalpYof throttlesteam
Ws = Hot reheatflow
hz = Cold reheatenthalpy
Buu,= Heatof auxiliarysteamfrom boiler
Pn = GeneratorPoweroutPut
P" = Auxiliarypowerused bY unit
AFBE = Adjustedfractionalboilerefficiency
L i mi ta ti o n s:
The net unit heat rate will not be calculatedat low loads,duringhotwellor
deaeratorlevelupsetsor duringsignificantloadchanges.
11
F.
Controlfableparametersshould be monitored
by high accuracy measure_
ments.
12
F. ControllableParameterCalculations
Throttlepressure
Throttletemperature
Mainsteamattemperator flow
Reheattemperature
Reheatsteamattemperator flow
Condenser pressure
Condenser condensate
temperature
Condensermakeupflow
Finalfeedwatertemperature
Auxiliarypower
FluegasexcessO,
Fluegascombustibles
Fluegastemperature
12