Professional Documents
Culture Documents
Syed Musadiq Isolation Room Design Final
Syed Musadiq Isolation Room Design Final
Organised by
2
HVAC Systems in Hospitals
An Effective HVAC System Controls Risk from Hospital-
Acquired Infections
Hospital, clinics and other medical
facilities pose several unique challenges that
aren't present in traditional HVAC situations.
As such, it's important for designers,
engineers, installers, maintenance personnel
and other HVAC professionals to be familiar
with installing HVAC systems for medical
PLACE IMAGE HERE
purposes.
1.Contact, both direct and indirect, is the most common mode of transmission in health care
facilities and other indoor environments. HVAC has little impact on this mode of transmission.
2.Droplet transmission is characterized by dispersion of microorganisms from an infected
person over short ranges (3–6 feet). The aerodynamics of this results in microbes contained in fluids
that fall out of the air in rapid fashion.
3.Airborne transmission involves dissemination of microbes via droplet nuclei beyond short
ranges, such as via an HVAC system.
HVAC design for health care facilities is all about providing a safer environment for patients
and staff. The basic difference between air conditioning for healthcare facility and that of other
building types stem from:
CODES/STANDARDS
TYPES OF ISOLATION REFERANCES
ROOMS
GUIDELINES
DESIGN
DESIGN CRITERIA
CONSIDERATION
EXAMPLE
3
Codes/ Standards/ References
Codes:
Standard:
NFPA 101
Guidelines:
Facility Guidelines Institute (FGI) Guidelines (2014) – for ventilation refers to ASHRAE Standard 170 - 2017
“Guidelinesfor Environmental Infection Control in Health-Care Facilities”, Recommendations of CDC (centers for Disease
Control & Prevention )and the Healthcare Infection Control Practices Advisory Committee (HICPAC), 2014
3
TYPES OF ISOLATION ROOMS
Combined AII/PE
Contact isolation
3
TYPES OF ISOLATION ROOMS
• AIR TERMINALS
• FILTERATION SYSTEM
• EXHAUST SYSTEM
• MOINTERING DEVICE
• ANTE ROOM REQUIREMENTS
AIR TERMINAL TYPE TO BE USED IN AII ROOM
FILTERATION
SYTEM WITHIN
AHU
• FOR AN AII ROOM
ASHRAE STANDARD
REQUIRES THE AHU TO
BE INSTALLED WITH TWO
FILTER BANKS, ONE
MERV 7 UP STEAM AND
THE OTHER MERV 14 IN
THE DOWN STREAM.
• AIR SHOULD BE
DISCHARGED AT A HEIGHT
OF 3MTS ABOVE ROOF
LEVEL @ ≥ 2500 FPM.
ANTEROOM : ANTE ROOMS ARE RECOMMENDED FOR AII ROOM AND
PE ROOM BUT NOT MANDATORY.
---------------------------------------------------------------------------------------------------
Calculate ACH based on exhaust flow
If not occupied pressure relationship is maintained and min ACH 6
Switching controls for reversible airflow (pressure relationship) shall
not be permitted(note t)
TOTAL
AII ROOM WITHOUT ANTE ROOM EXHAUST
250 CFM
Considering a room with dimensions :
Length : 10 ft
Width : 10 ft
And height : 10 ft
Volume of the room will become :10*10*10 = 1000ft3
ACH = (60*CFM)/VOLUME
CFM = (12*1000)/60
=200 CFM
AII ROOM WITH ANTE ROOM
TOTAL
Volume of the room will become :10*10*10 = 1000ft3 EXHAUST
350 CFM
300
FORMULA FOR ROOM AIR CHANGES PER HOUR (ACH) CFM
50
ACH = (60*CFM)/VOLUME CFM
CFM = (ACH * VOLUME)/60
50
AIR CHANGES IN ANTE ROOM . CFM
CONSIDERING TOILET AND ANTE ROOM
VOLUME TO BE 240 FT3
MIN ACH FOR ANTE ROOM : 10 ACH
CFM = (10*240)/60
= 40 CFM
3
TYPES OF ISOLATION ROOMS
These rooms are meant for patients with weakened immune system
In this case it is the patient who must be protected from infectious microbials
Also protection from opportunistic organisms that are not a threat to healthy individuals
DESIGN CONSIDERATIONS FOR AN
PE ROOM
HVAC COMPONENTS
• AIR TERMINALS
• FILTERATION SYSTEM
• MOINTERING DEVICE
• ANTE ROOM REQUIREMENTS
AIR TERMINAL TYPE TO BE USED IN PE ROOM
• FOR AN PE ROOM
ASHRAE STANDARD
REQUIRES THE AHU TO
BE INSTALLED WITH
FILTER BANK, ONE MERV
7 UP STEAM AND THE
OTHER HEPA AT THE
TERMINAL
Transfer air from PE room to ante room and ante room to corridor
•Assume mid range in tightness – use 300 cfm transfer air (TA)
Return/Exhaust system:
•Air from ante room and PE room may be returned to AHU / RA from Ante Room: 250 cfm
•Toilet exhaust must be exhausted to outside / TE: 100 cfm
•PE room RA = PE room SA – TA to ante room – TA to toilet = 1,400 cfm - 300 cfm - 100 cfm = 1,000
cfm
•Constant volume box to maintain total RA
•Total RA = RA from PE room + RA from ante room = 1,000 cfm + 250 cfm = 1,250 cfm
Thank You for attending this presentation
Don’t forget to collect your CPD certificate at the event from CPD
collection area
Organised by