,, Units 4 & 5 Venture Works, Charleywoorl Road

Knowslcy Industrial Estate North


Merseyside, L33 7SG
! GLOBB HBAT TRBATmenT I Tel: +44 (0)1515485281
dHhchel f:tihofmaH.(llHl
\ SERVICES LTD---- '\Yww.glohe]u.'aLcom

Test & Inspection Certificate

Tvne: 50 KVA 6 Way Mobile Transformer with Built in P256


CUSTm'1ER: A Star PO NUMBER: Robert
DATE: 15/08/2012 UNIT SERIAL NUMBER: GT50-256

Insulation Resistance Reading to Earth

Primary Input L1 ""L2 425.2 L2rvL3 423.2 L1,.,.,L3 424


Windinq
Secondary Winding L1 241.1 L2 247.1 L3 242.8
To Neutral
Volts Secondary L1 ,.,., L2 115.4 L2 r>J L3 115 U,.,.,L3 115.4

Volts Secondary to L1 66.6 L2 66.4 L3 66.5


Neutral

Channel Channel Channel 3 Channel Channel Channel


1 2 4 5 6
Manual Test @
200°C
v v v v v v
Manual Test @
600°C
v v v v v v
Auto Profile Test
v v v v v v
Reverse TC Test
v v v v v v
Output Test 65V
v v v v v v
Primary Tapping Board Checked v Secondary Output Connections v
Test Trip Circuit v Secondary 110v Auxiliary Outputs v
Circulating Fans in Operation v Main MCB Connections Tested v
Front Panel Labelled v Earth Point and Earth Strap Check v
Serial Plate Attached v Secondary Cables Tied Correctly v
Inspection & Test Stickers Affixed v
This is to certify that the above mention unit has passed all the necessary checks that
comply with the Globe Heat Treatment test procedures.

Coil Number: 15666/13

P256 Serial Number: 34676

Test Engineer 1: D. Carr

Test Engineer 2: E.Krumins

Quality Control Engineer: R. Brookfield

Date: 15/08/2012

Copyright of this certificate is owned by the issuer and may not be reproduced excect with
the prior written approval of the issuer.

This Certificate complies with the requirements of B.S.5781 Part 11992 (ISO 10012-11992)