CHL 92.

1SP - 460/3/60
INDUSTRIAL PROCESS CHILLER 460/3/60 - 92,1 TONS

Reference
Internal Code : 09648
short description : 1404us
reference : CHL 1404us - 460/3/60
Detailled Description : INDUSTRIAL PROCESS CHILLER 460/3/60 - 92,1 TONS

Unit Performance
Cooling Capacity (Tons) : 92,1
Cooling Capacity (Btu.h) : 1 105 534
Cooling Capacity (kW) : 324,0
EER (Btu.h / W) : 8,7

Refrigerant Gas
Gas refrigerant : R410A

Power Supply
Power Output (V/Phase/Frequency) : 460/3/60
Total Power Input (kW) : 147,4
Starting current - FLA (A) : 309,4

Working Conditions
Max. pressure (PSI) : 580
Max. Inlet T° (°F) : 95
Max. Ambient T° (°F) : 108

Compressor Data
Number of compressors : 4
Compressors type : Scroll
Independant Gas circuit : 2
Step of Capacity : 4

Compressor Power Input (kW) : 126,8


Absorbed Current (A) : 176,8

Hydraulic Datas
Number of tank : 1
Water tank content (US Gallons) : 264,2
Water fittings : 4"
Evaporator type : patented No Frost - Immerged on Water tank

Number of water pump : 1


Pump type : Centrifugal
Waterflow (GPM) : 245,4
Pump pressure (PSI) : 43,5
Pump motor power input (HP) : 10,1

Aeraulics Datas
Number of fans : 6
Fans type : Axial
Fans Power Input (kW) : 13,1
Total Airflow (SCFM) : 62 860

Dimensions, Weight & Sound Pressure


Length (inch) : 185,0
Depth (inch) : 78,7
Height (inch) : 87,8
Weight (Lbs) : 5 940
Sound Pressure (db(A)) : 64,1

Conditions : Ambient Air 95°F - Inlet water temperature 55°F - Outlet water temperature 45°F