The document provides details for the structural design of a proposed six-story reinforced concrete building, including loads and materials. It specifies dead and live loads for the roof and floors, noting a total live load of 5,360 Pa or 5,400 Pa for design. Concrete strength is 27.5 MPa with modulus of elasticity of 25 GPa, and reinforcing steel yield strength is 410 MPa. Wind loads for Zone II are based on a 200 kph design wind speed. Seismic loads for Zone 4 are specified using a response modification factor of 4 and seismic intensity VIII.
The document provides details for the structural design of a proposed six-story reinforced concrete building, including loads and materials. It specifies dead and live loads for the roof and floors, noting a total live load of 5,360 Pa or 5,400 Pa for design. Concrete strength is 27.5 MPa with modulus of elasticity of 25 GPa, and reinforcing steel yield strength is 410 MPa. Wind loads for Zone II are based on a 200 kph design wind speed. Seismic loads for Zone 4 are specified using a response modification factor of 4 and seismic intensity VIII.
The document provides details for the structural design of a proposed six-story reinforced concrete building, including loads and materials. It specifies dead and live loads for the roof and floors, noting a total live load of 5,360 Pa or 5,400 Pa for design. Concrete strength is 27.5 MPa with modulus of elasticity of 25 GPa, and reinforcing steel yield strength is 410 MPa. Wind loads for Zone II are based on a 200 kph design wind speed. Seismic loads for Zone 4 are specified using a response modification factor of 4 and seismic intensity VIII.
The document provides details for the structural design of a proposed six-story reinforced concrete building, including loads and materials. It specifies dead and live loads for the roof and floors, noting a total live load of 5,360 Pa or 5,400 Pa for design. Concrete strength is 27.5 MPa with modulus of elasticity of 25 GPa, and reinforcing steel yield strength is 410 MPa. Wind loads for Zone II are based on a 200 kph design wind speed. Seismic loads for Zone 4 are specified using a response modification factor of 4 and seismic intensity VIII.
for the PROP. SIX (6) – STOREY R.C BUILDING A. LOADS: ROOF DECK:
FLOOR COVERING -------------------------------------- 50 Pa
CONCRETE FRAME ------------------------------------- 5,917 CEILING---------------------------------------------------- 250 MECHANICAL & ELECTRICAL-------------------------- 500 MISCELLANEOUS----------------------------------------- 220 -------------------------- DEAD LOAD = 6,937 Pa FLOORS: 6TH/5TH 4TH 3RD/2ND FLOOR COVERING 50 Pa 50 50 CONCRETE COVER 6,109 6,510 6,547 CEILING 250 250 250 PORTION 1,000 1,000 1,000 MECHANICAL & 500 500 500 ELECTRICAL MISCELLANEOUS 200 220 220 DEAD LOAD 8,129 Pa 8,530 Pa 8,567 Pa
EXTERIOR WALL ------------------------------ 200
LIVE LOAD (OFFICE SPACE) ------------------ 2,400 Pa PORTION (LIVE LOAD) ------------------------ 960 ELEVATOR (LIVE LOAD) ----------------------- 1,000 ELSCALATOR (LIVE LOAD) -------------------- 1,000 -------------------- TOTAL LIVE LOAD = 5,360 Pa or 5,400 Pa NOTE FLOOR LOADS:
1. IT WILL BE ASSUMED THAT THE BASIC LIVE LOAD FOR THE
ESCALATOR IS 2.40 Kpa (50psf). AN ADDITIOMAL ELEVATION & ESCALATOR LIVE LOADS OF 0.96 Kpa (42psf): AND A PARTION LIVE LOAD OF 0.96 Kpa (20psf) ARE TO BE SPECIFIED BECAUSE THE LOCATION & ALSO THE CORRIDOR ARE NOT KNOWN: HENCE WILL BE SUBJECTED TO CHANGE, THE ENTIRE FLOOR WILL BE DESIGNED FOR A LIVE LOAD OF 5.36 Kpa or SAY, 5.40 Kpa (113psf.)
2. THERE WILL BE NO REDUCTION FOR LIVE LOADS GREATER THAN 4.80
Kpa (REFER TO SEC. 205 – 5 on p. 2 – 15 OF NSCP 2015 ED.)