Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

DETAILS OF TOP SLAB SECTION

F.G.L.

150
Check Valve

150
CROSS SECTION OF B-B F.G.L.
DETAILS OF 'Y'

WATER STOP JOINT


F.G.L. Y

CROSS SECTION-X,X

NOTE:

1. ALL DIMENSIONS ARE IN MM. UNLESS OTHERWISE MENTIONED.


TYPICAL CROSS SECTION OF A-A 2. MINIMUM CLEAR COVER FOR RCC WORK WILL BE , RAFT-50 MM, WALL-30 MM,
SLAB-25MM.
3. INSIDE & OUTSIDE PLASTER WILL BE 12 TH. WITH 1:6 CEMENT SAND
MORTAR WITH NET PUNNING,.
4. PCC WORK WILL BE M15.
REINFORCEMENT DETAIL
B FOR MAN HOLE OPENING
5.
6.
RCC WORK WILL BE M25
REINFORCEMENT STEEL USED FE 500+ HYSD ASPER IS 1786
X 7. BACK FILLING SHALL BE DONE USING CNS SOIL, ENSURING PROPER COMPACTION AS
PER SPECIFICATION.
8. WATER PROOFING ADMIXTURE CONFORMING TO IS2645 SHALL BE ADDED TO THE
CONCRETE,ANY LEAKAGES AT LATER STAGES SHALL BE RECTIFIED BY MEANS OF
NJECTING NON SHRINK POLYMERIC WATERPROOF GROUTING COMPOUND FROM
X X INSIDE ALONG WITH AN APPLICATION OF WATER PROOF PLASTER ON EXTERNAL
X SURFACES AS APPROVED MANUFACTURER'S SPECIFICATION.
9. WATER PROOFING WITH BITUMEN FELT TYPE-3 OF GRADE -II CONFORMING TO
A A IS-1322 TOGETHER WITH BONDING MATERIAL & PRIMER UP TO 3 M DEPTH-2 LAYERS
(COATS)
10. APPROVED WATER STOP JOINT TO BE USED AT CONSTRUCTION JOINT.
11. BASE RAFT IS DESIGNED AS RESTING ON HARD STATA WITH SBC OF 44T/M2 , ANY
ABRUPT CHANGED IN SOIL PROPERTY AT FOUNDATION LEVEL IS TO BE BROUGHT IN
THE NOTICE OF ENGINEER IN CHARGE.

REV.NO DATE DESCRIPTION REVISED BY CHECKED BY APPROVED BY

CUSTOMER :
TITLE: WATER RESERVOIR

TYP. WALL CORNER DETAILS


PROJECT CAPACITY :XXXXXXXXXXXX
PROJECT LOCATION:
DWG NO. REV.NO :00
NAME DATE SIGNATURE

DRAWN BY

B DESIGNED BY

CHECKED BY
SCALE : NTS
CLIMBING LADDER
PLAN OF WATER RESERVOIR SHEET 1
: OF 1 APPROVED BY