Professional Documents
Culture Documents
EN - Electric Motor Testing Diagnostic Chart - Static
EN - Electric Motor Testing Diagnostic Chart - Static
8 000
Dielectric strength
of insulation
Operational
voltage
MegOhm Failure (Over Failed groundwall Isolate the location of the Insulation failure resulting in an overcurrent during a low Step voltage testing should include at least ive (5) voltage
High and Low Moisture or contamina- Check all connection Typically faults associated with resistance will present as current) insulation ground wall failure. voltage (at or below line voltage) insulation resistance test steps to ensure a linear change can be deinitively observed.
Resistance tion at connections points for corrosion, an imbalance in the circuit. Refer the “Resistive Imbalance” Repair/Replace motor as means the motor should not be started and will likely
contamination, and section above for these indications. required require rewind and repair.
High resistance contacts proper torque
A reference value and winding correction temperature must High Potential Test Insulation breakdown at Isolate source of ground. Motors with breakdown voltages at or near bus voltage
Improper temperature Verify temperature be employed to validate high or low resistance values. If the Overcurrent Trip indicated voltage Repair/Replace motor as should be replaced immediately. If the insulation breakdown
correction correction motor was recently rebuilt, verify proper wire used. required voltage is well above nominal bus voltage the motor may
start. It should be noted that attempting to start a motor
Improper winding Verify comparison refer- When comparing values to references/baselines, ensure with a weak insulation system could result in additional
connection ence value that the reference applies to the motor under test. If the damage to the stator if the motor were to fail on start.
Low PI Contamination, insulation Clean / Dry Insulation A clean dry insulation system should have a PI > 2.0. This
motor has been changed out variations in resistance will
deterioration system / Overhaul means that the measured current has been reduced by half
Improper reference value Verify the same motor is likely be present.
from the 1 minute to the 10 minute measurement. Contam-
being tested
ination and moisture can signiicantly reduce this ratio due
to parallel leakage paths. It is not uncommon for example to
Perform groundwall
have PI readings of 1.5 in high humidity environments.
insulation testing for low
High Line to Line Surge Rotor Inluence, Copper Verify motor leads are Line to line comparison: L - L EAR% (Error Area Ratio) is used
ground resistance
For small motors (<100Hp), and motors with very little Comparison Ratio to copper insulation connected properly. If not to evaluate each phase circuit’s response to the surge impulse
detectable polarization, like VFD insulation systems, a Die- failure rotor inluence repair/ while the motor is disassembled and the rotor is removed
High and Low Improper winding, Verify comparison refer- Changes in inductance are caused by a change in the number lectric Absorption test (DA) may be more representative of replace motor. from the stator. This is due to the secondary rotor impedance
Inductance connection ence value of turns/loops/coils in the circuit under test. Hard shorts or the insulation’s ability to polarize. A DA is performed for only inluencing the stator circuit. A balanced winding will have
internal connection issues can indicate both high and low 3 minutes. The inal reading is compared to the 30 second identical surge ringing patterns that should overlay on top of
Improper reference value Verify the same motor is value changes. reading. each other. Because the rotor has to be removed for this test,
being tested line to line comparison is rarely used as a ield test.
Typically faults associated with inductance will present as an
Perform groundwall insu- imbalance in the circuit. Refer the “Inductive Imbalance”
lation testing for low section above for these indications. High PI Delamination of asphaltic If motor winding is older Motors with modern insulation system can have very high PI
ground resistance insulation than 1970, rewind other- values. This is not an indication of a problem with the sys- Unstable Pulse to Pulse Weak insulation Test motor more Pulse to pulse comparison (PP EAR%) is used to evaluate
When comparing values to references/baselines ensure that wise no action required. tem. Older asphaltic insulation systems from before 1970 between coil turns, frequently the winding insulation when the motor is fully assembled.
PP EAR [%]
the reference applies to the motor under test. If the motor could delaminate causing increased air spaces in the insula- 12 ground insulation Variation in PP EAR indicates an instability which is usually
has been changed out variations will likely be present. Verify tion build. This increased the capacitance of the circuit and weakness caused by weak turn-to-turn insulation. Up to 80% of winding
0
comparisons are made at the same test frequency. therefore increased the PI values >6.0 0 10 20 30 40 50 60 70 failures begin as turn to turn weakness, progressing to
Number of pulses
phase to phase or groundwall failure. PP EAR values should
be <5% and the curves should have no spikes.
Ground capacitance change Contamination/Delami- Perform groundwall insu- As motor contamination builds up the effective capacitance
nation, Insulation failure, lation resistance test and of the circuit will increase. Insulation degradation in the
Capacitor degradation if PI/DA to aid in evaluation. form of embrittlement and cracking may lead to decreased
present When evaluating motors, capacitance readings with no corresponding reduction in High Partial Discharge Voids in the insulation Continue to monitor PD Partial discharge inception voltage (PDIV) is the voltage at
all power factor correction insulation resistance. Delamination of older asphaltic PI Graph Shapes activity which partial discharge events begin to occur within the
capacitors should be insulation systems (1970 or older) can exhibit an increase Surge voltage [V] insulation due to voids or surface effects. While performing
3 000
removed from the circuit in insulation capacitance resulting in increased PI/DA Contamination Moisture Aging 2 500 Test motor more surge testing, the gases in the voids are energized and will
2 000
in order to properly evalu- ratios > 6.0. 1 500 frequently discharge internally within the insulation adding high fre-
Current Current Current
ate the motor winding. 1 000
500
quency signals on the surge waveform. As the insulation
0
-500
Repair or Replace as degrades and internal defects such as cracks form, PDIV will
Contamination causes a flat curve
Insulation aging causes the curve -1 000 necessary begin to decrease. As PDIV and RPDIV begin to approach
-1 500
to flatten over time -2 000 bus voltage, the number of discharges increases signii-
Rotor Inluence Testing Broken rotor bar, eccen- If motor is in service per- Rotor inluence testing should be treated with caution. The -2 500
cantly, degradation accelerates, and then the PDIV and
Moisture causes an erratic curve -3 000
Resistance, Inductance, Impedance, tricity, rotor porosity, low form dynamic testing to data can vary based on motor design. The effect of rotor 0 1 2 3 4 5 6 7 8
RPDIV will increase, signalling imminent breakdown; action
Phase angle vs. Rotor Position magnetic signature validate the static rotor position on the circuit characteristics is evaluated for bal- Time [µs]
should be taken to repair or replace the motor.
test indings. Trend data ance and symmetry. Resistance values are commonly tem- Aging
Inductance [mH]
47,5
47,0
for evidence of further perature corrected to 25 or 40C. Temperature correction is Normal curve Normal curve
46,5 degradation. used to compare the measured value to a standard and Initial curve
46,0
45,5
should have no effect on the balance of the circuit. Time Time Time
45,0
44,5
44,0
0 50 100 150 200 250 300 350
Degrees
skf.com
® SKF is a registered trademark of the SKF Group.
© SKF Group 2016
The contents of this publication are the copyright of the publisher and may not be reproduced (even extracts) unless prior written permission is granted. Every care has been taken to ensure the accu-
racy of the information contained in this publication but no liability can be accepted for any loss or damage whether direct, indirect or consequential arising out of the use of the information contained
herein.
PUB 54/P4 17011 EN.US · November 2016