BCEG’s response to
EME’s first site visit
Deficiencies
&
Commissioning issues.
Royal Commission Headquarters,
Yanbu Al Sinayah, Kingdom of Saudi Arabia
Submitted by:
Muhammad Sajjad.
Mechanical Engineer.
MEP department, BCEG.
sajjad.bceg@gmail.com
053‐2022676.
Royal Commission for Jubail and Yanbu
Headquarters, Yanbu, KSA
The FSD sleeves at the wall penetrations are required to have a gap around them. The gap
is generally 1/8 inch per foot of duct, with a minimum of 1/4" per the instructions. The gap
is required to permit expansion of the damper during a fire and alleviate the damper from
racking due to expansion. The masonry walls appear to be mortared solid to all damper
sleeves.
The retaining angles are fastened to the sleeve by pop rivets. It is unclear if the pop rivets
are aluminum or steel. The only loose pop rivets on the project that EME observed were
aluminum. EME did not remove and test any pop rivets. The installation instructions
permits fastening with 3/8" steel pop rivets.
BCEG’s Response.
All duct work and dampers installation is as per approved RFC drawing. Nothing mentioned in
spec section 15050 section 2.3.T sleeves.
Dampers are UL approved. Retaining angles are used with Aluminum rivets. BCEG will work on
changing the Aluminum rivets with St. Steel rivets.
Non Commissioning Issues Page 1 of 2
Royal Commission for Jubail and Yanbu
Headquarters, Yanbu, KSA
2 It is assumed that the kitchen hood is a type I hood (serves grease laden vapors, not just
moisture). The kitchen design is not yet available. A FD was observed in the Kitchen
hood at the top of the shaft. The damper is installed per construction drawing. The shaft
that encloses the kitchen hood exhaust duct serves other ducts. 506.3.11 of the IMC
prohibits installing fire or smoke dampers in this duct and requires the duct to be in its own
shaft.
BCEG’s Response.
All duct work and damper installation is as per approved RFC drawing. Nothing
mentioned in spec section 15840 section 2.3.1, C. Low Pressure Duct (Above Ground).
The black steel duct riser installation in the same shaft that serves other ducts is as per
site condition.
3 It is assumed that the kitchen hood is a type I hood (serves grease laden vapors, not just
moisture). The duct serving the kitchen hood has no access doors in it, or in the shaft that
encloses it. 506.3.8 of the IMC essentially requires access doors every 20 feet (6.1m) and
every 10 feet (3.05m) at changes of direction greater than 45 degrees. Specification
158403.2 requires access panels at 2-meter intervals and at changes of direction.
BCEG’s Response.
Access doors are shown on duct penetration. BCEG will coordinate with site for AD installation.
Further AD can be installed on horizontal duct in kitchen area at every 20 ft.
4 There is no FSD at the exhaust duct penetration of the shaft to the heat recovery units. It
appears that the IMC would require the FSD.
BCEG’s Response.
No FSD is shown on any EAD throughout the building. For HRU a FD is shown on the
EAD penetration from riser to HRU.
PMT’s reply against RFI‐842 says that no FSD is required for general Exhaust duct for the
building.
5 Dirt and dust have penetrated the ductwork, AHUs, heat recovery units, etc. throughout the
building. The project team may want to pursue cleaning the ductwork and AHUs in
accordance with the Assessment, Cleaning and Restoration of HVAC Systems (ACR)
standard developed as an international standard by the National Air Duct Cleaners
Association. ACR was previously transmitted to Parsons for review.
BCEG’s Response.
BCEG has performed a thorough cleaning of all the duct work and removed the dust
and dirt from HVAC duct, machines and all associated equipment.
BCEG also using the MERV 8 temporary filters recommended by PMT for temporary use
for startup and pre‐commissioning activities.
A picture through access door. This shows the quality of duct cleanliness from inside.
MERV 8 filter installed inside AHU to trap the dust and dirt from system.
BCEG cleans the temporary filter every 2 weeks and changes the filter every 2 months.
6 Specification 16050 2.2 C, D requires rigid (RGS) conduit in wet or damp locations and at
locations exterior to the building. Cable tray and EMT is used in the open area where the
cooling towers are located.
BCEG’s Response.
BCEG will paint the EMT conduits with weather proof paints (Primer, intermediate coat
and top coat) to close this issue. The proposal to paint the steel surfaces in high
corrosive and humid environment is approved under submittal 1801‐05500‐005‐R02.
7 The plumbing above grade plastic drainage piping is about 10 foot on-center between
supports (3.05 m). 15050 3.2 F 3 requires a maximum spacing of 2.5m. It is noted that the
International Plumbing Code section 305 requires supports at 4 feet on center (1.2m) for
horizontal run of PVC piping).
BCEG’s Response.
BCEG has installed the hanging supports for all PVC horizontal pipes per approved
drawing 1801‐PG‐A1‐00008. The schedule in drawing shows the support at 3 meters
distance for pipes above 4”.
Non Commissioning Issues Page 5 of 2
Royal Commission for Jubail and Yanbu
Headquarters, Yanbu, KSA
8 Detail 9 on sheet 0751A-PG-A1-067 does not include a P trap for the roof drains. Traps
are installed. It appears that these traps will collect sand over time and clog.
All the P‐traps for roof drain & planter drain has been removed per IFC drawing 0751A‐
PG‐A1‐067.
9 Some of the traps on the floor drains observed has a dimension from the drain outlet to the
trap weir greater than 24" (0.61 m). This violates section 1002 of the IPC.
Traps in Cooling Tower area were observed to have pipe vertical length from drain
outlet to P‐trap more than 24”. This is per site condition. BCEG has removed the P‐Trap
per IFC drawing 0751A‐PG‐A1‐067.
10 Pump P-07, serving the condenser water side stream filter, was noted to not have electrical
bonding. EME noted that all other major HVAC equipment (pumps, AHUs, HRUs, etc.)
are connected via electrical bonding for lightning protection.
The bonding for side stream filter pump P‐07 is done.
Non Commissioning Issues Page 7 of 2
Royal Commission for Jubail and Yanbu
Headquarters, Yanbu, KSA
PlanGrid report – RCHQ
Prepared by: EME Group
Report date: Tuesday, February 19, 2019
Items in this report: 32 tasks
Contents
#1 ‐ Chilled & Condenser Water Piping Supports.................................................................................. 3
#2 ‐ Chilled Water Valve Insulation ...................................................................................................... 4
#3 ‐ Valve Installation .......................................................................................................................... 5
#4 ‐ Chilled & Condenser Water Pressure Gauge Assembly .................................................................. 6
#5 ‐ Pump Lubrication.......................................................................................................................... 7
#6 ‐ Pump Drain Piping ........................................................................................................................ 8
#7 ‐ Piping Vibration Control ................................................................................................................ 9
#9 ‐ VAV Box Support......................................................................................................................... 10
#10 ‐ HRU Filter Section ..................................................................................................................... 11
#11 ‐ AHU G6 Access Doors Blocked .................................................................................................. 12
#12 ‐ Return Air Sensors Installed on Fresh Air Duct........................................................................... 14
#13 ‐ AHU CHW Coil Sections Installed Backwards ............................................................................. 15
#14 ‐ Chilled Water Coil Clearance ..................................................................................................... 17
#15 ‐ Fan Guards Not Installed........................................................................................................... 18
#16 ‐ Fan Coil Spring Isolated Hangers Not Installed........................................................................... 19
#17 ‐ Unions Installed on System Side of Isolation Valve .................................................................... 20
#18 ‐ AHU Air Flow Sensor Installation ............................................................................................... 22
#19 ‐ CH‐1 Damaged Insulation.......................................................................................................... 24
#20 ‐ Heat Recovery Units ‐ Damaged Heat Pipe Fins ......................................................................... 25
#21 ‐ AHU‐B3 Condensate Piping ....................................................................................................... 27
#22 ‐ AHU‐15 Fan Vibration Isolation ................................................................................................. 28
#23 ‐ AHU‐31 VAV Access .................................................................................................................. 29
#24 ‐ AH‐32 Shipping Blocks............................................................................................................... 30
#25 ‐ HRU‐04 Interior Cable Severed.................................................................................................. 31
#26 ‐ Core 5 Fresh Air Duct Motorized Damper Installation................................................................ 32
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#27 ‐ AHU CHW Coil Connection Assembly ........................................................................................ 33
#28 ‐ HRU‐01 Flex Connection at Fan Outlet ...................................................................................... 34
#29 ‐ AHU Flex Connectors Torn ........................................................................................................ 35
#30 ‐ Chilled Water Field Device Insulation ........................................................................................ 36
#31 ‐ Chiller Pressure Relief Valve with Manual Ball Valve ................................................................. 37
#32 ‐ Internal AHU Wiring Not Protected ........................................................................................... 38
#33 ‐ Refrigerant Storage Tank .......................................................................................................... 39
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#1 ‐ Chilled & Condenser Water Piping Supports
Status
List Open
Cx Deficiency
Type
Created Issue
1/9/2019 at 3:02 AM
tjuliana@emegroup.com
Location Assignees
Plant Room Beijing Construction
Engineering
Last updated
2/15/2019 at 2:25 PM
Description
Per Specification 15050 section 3.2.F.3, hanger spacing shall in no case be less than one hanger per
2.5m. Pipe hangers observed in multiple locations at spacing in excess of 3m.
Photos
The hanger spacing for CHW piping is as per approved shop drawing "CHW piping HVAC standard details" 1801‐HV‐
A1‐00003.
The hanger spacing for drainage piping is as per approved shop drawing “Plumbing standard details” 1801‐PG‐A1‐
00008.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
Photos:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#2 ‐ Chilled Water Valve Insulation
List Status
Cx Deficiency Open
Created Type
1/9/2019 at 4:10 AM Issue
tjuliana@emegroup.com
Location Assignees
Plant Room Beijing Construction
Engineering
Last updated
2/15/2019 at 2:25 PM
Description
Per Specification 15250 section 3.2.B, fittings and valves shall be insulated. Triple duty valves
throughout the plant room were observed to be uninsulated.
Photos
BCEG’s response: Status: Closed, Date: July, 24 2019, By: sajjad.bceg@gmail.com
All the TDV’s have been insulated.
Photos:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#3 ‐ Valve Installation
List Status
Cx Deficiency Open
Created Type
1/9/2019 at 4:39 AM Issue
tjuliana@emegroup.com
Location Assignees
Basement Plant Room, AHU Beijing Construction
Rooms Engineering
Last updated
2/15/2019 at 2:25 PM
Description
Per Specification 15080 section 3.2.1.G, all valves located 1.8 meters above finished grade shall be
furnished with permanent ladders or operating chains. Valves installed throughout the basement
(including plant room and TES connections) were observed to be above the specified height criteria
and do not have operating chains or permanent ladders installed. The logical compliance method
appears to be chain‐driven operation based on valve locations, however the existing valve handles do
not appear to be suitable for chain installation.
Photos
There are over 20 valves in plant room with a height above 1.8 meters.
Further to the site condition and a thorough site visit, BCEG together with
PMT reached to a suggestion to use 3 portable Aluminum ladders (hook type)
on either side of chillers and heat exchanger side.
Photo:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#4 ‐ Chilled & Condenser Water Pressure Gauge Assembly
List Status
Cx Deficiency Open
Created Type
1/9/2019 at 5:04 AM Issue
tjuliana@emegroup.com
Location Assignees
Plant Room Beijing Construction
Engineering
Last updated
2/15/2019 at 5:42 PM
Description
Per Material Submittal 15050‐028, manufacturer installation instructions indicate snubbing element is
to be placed in the line immediately before the pressure gauge. Siphons (pigtail) are recommended
when a gauge is to be used in a steam application as they will become clogged with debris in a
hydronic system. Gauge assembly installations were observed to include both snubbing element and
siphon, with snubbing element installed immediately after the line tap. Placing the snubber after the
isolation valve allows for maintenance staff to clean the element in the case of clogging.
Photos
BCEG’s response: Status: Closed,
This issue has been resolved by placing the snubber immediately after the pressure gauge. The said construction
is followed for the whole building.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#5 ‐ Pump Lubrication
List Status
Cx Deficiency Open
Created Type
1/9/2019 at 5:49 AM Issue
tjuliana@emegroup.com
Location Assignees
Plant Room Beijing Construction
Engineering
Last updated
2/15/2019 at 2:25 PM
Description
Per Specification 15540 section 3.2.I, pumps shall be lubricated before start‐up. Per BCEG,
manufacturer start‐up has begun but the pumps were observed to not be lubricated.
BCEG’s response: Status: Closed, Date: July, 24 2019, By: sajjad.bceg@gmail.com
The delivered pumps are factory lubricated. BCEG will further keep lubricating the pumps and motor
bearings according to lubrication schedule, sent from supplier.
There are two types of CHW pumps (Horizontal Split‐case – HS) & (End Suction – NK)
End Suction – NK
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
Horizontal Split‐case – HS
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#6 ‐ Pump Drain Piping
List Status
Cx Deficiency Open
Created Type
1/9/2019 at 5:52 AM Issue
tjuliana@emegroup.com
Location Assignees
Plant Room Beijing Construction
Engineering
Last updated
2/15/2019 at 2:25 PM
Description
Per Specification 15540 section 3.2.F, drains shall be provided for pump bases and seals, piped to and
discharging into floor drains. Drains were observed to be installed, however no piping to floor drains
were installed. In some instances, hoses were connected and routed to the floor drains.
Photos
Pumps drain piping is connected to nearest floor drain. The drain connection is done for all the following
equipment.
1. Pumps
2. Strainers
3. Chiller
4. Heat exchangers
5. Blow down.
6. AHU’s, FCU’s & HRU’s.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
Photos
Heat Exchanger drain
CHW pumps drain
RCHQ – Cx Issues Log
Chiller drain drain
RCHQ
Yanbu, Saudi Arabia
#7 ‐ Piping Vibration Control
List Status
Cx Deficiency Open
Created Type
1/9/2019 at 6:20 AM Issue
tjuliana@emegroup.com
Location Assignees
Plant Room Beijing Construction
Engineering
Last updated
2/15/2019 at 2:25 PM
Description
Per Specification 15050 sections 3.2.1.B.1.a and 3.2.1.B.2.a, the first three hangers away from any
spring isolated piece of equipment shall have hangers with same static deflection as equipment
isolators. No spring isolated hangers were observed within the plant room associated with spring
isolated equipment.
Photos
The Hangers are installed against the details shown in approved shop drawing. HVAC standard details‐2 (Chilled
water piping) 1801‐HV‐A1‐00003.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
BCEG is working to install the first three hangers with spring isolators of same deflection as used for equipment
base.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#9 ‐ VAV Box Support
List Status
Cx Deficiency Open
Created Type
1/31/2019 at 3:05 PM Issue
tjuliana@emegroup.com
Location Assignees
Various Beijing Construction
Sheet Engineering
O751A‐HV‐A1‐149 Standard Details
‐ Sheet 6
Last updated
2/15/2019 at 2:25 PM
Description
Per design documents, VAV boxes are to be supported with two hangers. Field installation provides a
single hanger.
Photos
The current installation method is approved by PMT under RFI ‐1541.
As the VAV has rigid connection on one side so one hanger was assumed to be enough as per site condition.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#10 ‐ HRU Filter Section
List Status
Cx Deficiency Open
Created Type
1/31/2019 at 3:20 PM Issue
tjuliana@emegroup.com
Location Assignees
Core 1 & Core 2 ‐ 21st Floor Beijing Construction
Sheet Engineering
O751A‐HV‐A1‐149 Standard Details
‐ Sheet 6
Last updated
2/15/2019 at 4:35 PM
Description
Heat Recovery Units were observed to contain a single filter rack installed on the fresh air intake.
Design documents indicate 3 filter sections are to be installed ‐ pre‐filter, bag filter, and carbon filter.
BCEG’s response: Status: Closed, Date: July, 25 2019, By: sajjad.bceg@gmail.com
The HRU is approved under submittal 1801‐15656‐008 with the following construction.
A pre filter and bag filters are used for the approved model TW series.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
Spec 15653
Cleanable (Washable) Permanent
Panel Filters.
The filter media shall be made of
metal strips or metal strips coated
with viscous substance.
Filter: 30 – 35% efficiency
Spec 15653
High Efficiency Filters/Bag Filters:
High efficiency, extended surface
pocket type, consisting of galvanized
steel holding frame and replaceable
Filter: 90 – 95% efficiency MERV15
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#11 ‐ AHU G6 Access Doors Blocked
List Status
Cx Deficiency Open
Created Type
1/31/2019 at 3:26 PM Issue
tjuliana@emegroup.com
Location Assignees
Basement AHU Room Beijing Construction
Sheet Engineering
Bsmt Fl 1801‐HV‐A1‐BS101 2 of 2
Last updated
2/15/2019 at 2:25 PM
Description
CHW piping/hangers block unit access doors from opening. Raising the piping run approximately
15cm would provide sufficient clearance for unit access.
Photos
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
BCEG’s response: Status: Closed, Date: July, 25 2019, By: sajjad.bceg@gmail.com
This issue has been resolved. CHW pipe has been lifted upward to provide enough passage for AHU‐G6
access door.
Photo:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#12 ‐ Return Air Sensors Installed on Fresh Air Duct
List Status
Cx Deficiency Open
Created Type
1/31/2019 at 3:37 PM Issue
tjuliana@emegroup.com
Location Assignees
Basement AHU Room Beijing Construction
Sheet Engineering
Bsmt Fl 1801‐HV‐A1‐BS101 2 of 2 Last updated
2/15/2019 at 2:26 PM
Description
Return Air Sensors (temp, flow, & CO2) for AHUs 15, 25, & 35 are installed on the fresh air purge duct
rather than the return air duct.
Photos
This issue is resolved the replacing the BMS field devices from Fresh air duct to return air duct.
Photo:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#13 ‐ AHU CHW Coil Sections Installed Backwards
List Status
Cx Deficiency Open
Created Type
2/1/2019 at 10:48 AM Issue
tjuliana@emegroup.com
Location Assignees
Basement Plant Room, Core 3 Beijing Construction
First Floor AHU MER Engineering
Last updated
2/18/2019 at 11:42 AM
Description
Chilled water coil sections in AHUs B3 & 31 were observed to be installed backwards with the drain
pan extended in the upstream side of the coil. The coil is located off‐center in the section to allow for
proper absorption distance and prevent carry over from entering the fan section. The current
orientation will not allow condensate to be properly collected and drain from the unit.
Photos
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
BCEG’s response: Status: Closed, Date: July, 27 2019, By: sajjad.bceg@gmail.com
This issue is resolved. Cooling coil section for AHU B3 and 31 has been rotated per right flow
direction.
Photos:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#14 ‐ Chilled Water Coil Clearance
List Status
Cx Deficiency Open
Created Type
2/1/2019 at 11:10 AM Issue
tjuliana@emegroup.com
Location Assignees
Floor 21, Core 4 AHU Rooms Beijing Construction
Engineering
Last updated
2/15/2019 at 2:26 PM
Description
AHUs 41 & 42, HRUs 01, 02, 03, & 04 chilled water coils installed with insufficient clearance to pull coil
for maintenance/repair as required per design documents
Photos
Confirmed on site, Coil can be removed from connection side by twisting it along vertical axis.
Furthermore as per Zamil confirmation during pre‐commissioning, coil can be removed from either side of AHU.
Further, BCEG can demonstrate on site by removing the coil from other side of equipment.
Photo:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#15 ‐ Fan Guards Not Installed
List Status
Cx Deficiency Open
Created Type
2/1/2019 at 11:21 AM Issue
tjuliana@emegroup.com
Location Assignees
Core 1 & Core 2 ‐ 22nd Floor Beijing Construction
Sheet Engineering
22nd Fl 1801‐HV‐A1‐22001
Last updated
2/15/2019 at 2:26 PM
Description
Stair and elevator shaft pressurization fans on Core 1 & 2 roof MER do not have screens/guards
installed at fan inlet. Fans were observed to be spinning freely.
Photos
Mesh screen installed for fans protection from birds and insects..
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#16 ‐ Fan Coil Spring Isolated Hangers Not Installed
List Status
Cx Deficiency Open
Created Type
2/1/2019 at 12:16 PM Issue
tjuliana@emegroup.com
Location Assignees
Various Beijing Construction
Sheet Engineering
O751A‐HV‐A1‐148 Standard Details
‐ Sheet 5
Last updated
2/15/2019 at 2:26 PM
Description
Spring isolated hangers required for FCU installations per design documents. FCUs were observed to
be rigidly mounted.
Photos
The FCUs are installed based on approved method statement described in RFI 1606.
BCEG prepared a mockup before proceeding towards FCUs installation. All the installation is based on that
approved method statement described in RFI‐1606.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#17 ‐ Unions Installed on System Side of Isolation Valve
List Status
Cx Deficiency Open
Created Type
2/1/2019 at 12:26 PM Issue
tjuliana@emegroup.com
Location Assignees
Various Beijing Construction
Engineering
Last updated
2/18/2019 at 12:08 PM
Description
Dielectric unions at several locations were observed to be installed on the system side of isolation
valves. Sample locations include the potable water tanks and fan coil units. The current installation
does not allow for isolating the unit and disconnecting it from the system piping. The isolation valve
should be located on the system side of the union.
Photos
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
BCEG has solved this issue by installing di‐electric unions on both side of isolation valve for Potable water
transfer pumps and Cooling Tower water transfer pumps.
For FCUs, the system side unions are kept as it is because the machines can be isolated from flange type, double
bowl, rubber flexible connections.
Photos:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#18 ‐ AHU Air Flow Sensor Installation
List Status
Cx Deficiency Open
Created Type
2/1/2019 at 12:50 PM Issue
tjuliana@emegroup.com
Location Assignees
Various Beijing Construction
Engineering
Last updated
2/15/2019 at 2:26 PM
Description
AHU flow sensor (supply & return) installation locations do not have laminar flow and violate
manufacturer installation requirements for upstream/downstream straight duct runs.
Photos
These devices are installed under the supervision of Honeywell engineer as per site condition. Further to the
discussion with Honeywell, the location of devices will be changed where required during the testing &
commissioning phase.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#19 ‐ CH‐1 Damaged Insulation
List Status
Cx Deficiency Open
Created Type
2/13/2019 at 2:54 PM Issue
tjuliana@emegroup.com
Location Assignees
Basement Plant Room Beijing Construction
Sheet Engineering
1801‐HV‐A0‐BS111 Last updated
2/15/2019 at 2:26 PM
Description
CH‐01 insulation was observed to have minor damage
Photos
The damaged insulation is rectified.
Photos:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#20 ‐ Heat Recovery Units ‐ Damaged Heat Pipe Fins
List Status
Cx Deficiency Open
Created Type
2/13/2019 at 2:59 PM Issue
tjuliana@emegroup.com
Location Assignees
21st Floor HRU Rooms Beijing Construction
Sheet Engineering
21st Fl 1801‐HV‐A1‐21002
Last updated
2/15/2019 at 2:26 PM
Description
HRUs 01 through 04 were observed to have minor damage to the aluminum fins in the heat pipe
section
Photos
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
All known damaged fins have been rectified as of today.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#21 ‐ AHU‐B3 Condensate Piping
List Status
Cx Deficiency Open
Created Type
2/13/2019 at 3:05 PM Issue
tjuliana@emegroup.com
Location Assignees
Basement Plant Room Beijing Construction
Sheet Engineering
1801‐HV‐A0‐BS111 Last updated
2/15/2019 at 2:26 PM
Description
Condensate drain pipe was observed to be back pitched from unit to p‐trap
Photos
Condensate drain piping is done for AHU B3.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#22 ‐ AHU‐15 Fan Vibration Isolation
List Status
Cx Deficiency Open
Created Type
2/13/2019 at 3:35 PM Issue
tjuliana@emegroup.com
Location Assignees
Basement AHU Room Beijing Construction
Sheet Engineering
Bsmt Fl 1801‐HV‐A1‐BS101 2 of 2
Last updated
2/15/2019 at 2:26 PM
Description
One of the mounting bolts on the fan vibration isolator was observed to be cockeyed, impeding free
movement of the isolator.
Photos
All the crooked, uneven spring vibration isolators have been adjusted for all the AHUs.
Photos:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#23 ‐ AHU‐31 VAV Access
List Status
Cx Deficiency Open
Created Type
2/13/2019 at 3:46 PM Issue
tjuliana@emegroup.com
Location Assignees
Floor 3, Core 1 AHU Room Beijing Construction
Sheet Engineering
3rd Fl 1801‐HV‐A1‐03100
Last updated
2/15/2019 at 2:26 PM
Description
Placement of fire protection piping & sprinkler head is in conflict with VAV access/maintenance
Photos
BCEG’s response: Status: Closed , Date: July, 27 2019, By: sajjad.bceg@gmail.com
This issue has been solved. NAFFCO pipe blocking the VAV has been adjusted.
Photo:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#24 ‐ AH‐32 Shipping Blocks
List Status
Cx Deficiency Open
Created Type
2/13/2019 at 3:55 PM Issue
tjuliana@emegroup.com
Location Assignees
Floor 3, Core 2 AHU Room Beijing Construction
Sheet Engineering
3rd Fl 1801‐HV‐A1‐03100
Last updated
2/15/2019 at 2:26 PM
Description
Shipping blocks observed to remain installed on fan vibration insulator
BCEG’s response: Status: Closed, Date: July, 27 2019, By: sajjad.bceg@gmail.com
Shipping blocks are removed.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#25 ‐ HRU‐04 Interior Cable Severed
List Status
Cx Deficiency Open
Created Type
2/13/2019 at 4:11 PM Issue
tjuliana@emegroup.com
Location Assignees
21st Floor, Core 2 HRU Room Beijing Construction
Sheet Engineering
21st Fl 1801‐HV‐A1‐21002
Last updated
2/15/2019 at 2:26 PM
Description
Liquid tight flexible cable serving interior lights was observed to be severed and repaired with
electrical tape. No grommets observed on cable pass‐through between unit sections.
Photos
BCEG electrical team has repaired all the severed cables wherever found. The cable is running through
flexible hose in above picture. Flexible hose is repaired with electrical tape.
Photo:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#26 ‐ Core 5 Fresh Air Duct Motorized Damper Installation
List Status
Cx Deficiency Open
Created Type
2/14/2019 at 4:03 PM Issue
tjuliana@emegroup.com
Location Assignees
Core 5 AHU Rooms Beijing Construction
Sheet Engineering
7th Fl 1801‐HV‐A1‐07102
Last updated
2/18/2019 at 12:10 PM
Description
Fresh air duct motorized damper is located above the supply duct and is not readily accessible.
Witnessed installation on floors 7 and 5, appears to be consistent on all Core 5 AHUs per the
drawings. The contractor should verify the installation location (upstream of the CO2 VAV takeoff
branch) is appropriate for unit operation.
Photos
BCEG observed FAD take‐off branch and MVD wrong installation at 5th, 6th and 7th floor of core 05. The
installation was based on wrong drawing sent by PUSA. However, BCEG has rectified these issues.
Photo:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#27 ‐ AHU CHW Coil Connection Assembly
List Status
Cx Deficiency Open
Created Type
2/15/2019 at 12:21 PM Issue
tjuliana@emegroup.com
Location Assignees
Various Beijing Construction
Sheet Engineering
2nd Fl 1801‐HV‐A1‐02103
Last updated
2/15/2019 at 2:27 PM
Description
AHU/FCU chilled water coil connection assembly detail indicates a drain cock is to be installed at the
unit outlet. Assembly installation was noted to be in progress during the time of EME's inspections,
however drain cocks were not observed. BCEG to confirm intent to install based on approved
connection drawing detail.
Photos
The installation is done per IFC‐Rev00 which doesn’t show drain cock in valve package. The said valve was included
later in IFC‐Rev01. However, BCEG has started installation of drain cock at the supply line lower level.
Photos
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#28 ‐ HRU‐01 Flex Connection at Fan Outlet
List Status
Cx Deficiency Open
Created Type
2/15/2019 at 2:05 PM Issue
tjuliana@emegroup.com
Location Assignees
Core 1, 21st Floor HRU Room Beijing Construction
Sheet Engineering
21st Fl 1801‐HV‐A1‐21001
Last updated
2/15/2019 at 2:27 PM
Description
Flexible connection at fan outlet is installed improperly. Flex connection is squished, and will not
provide the intended sound attenuation and vibration isolation.
Photos
BCEG has taken all measures to possibly identify and fix such issues by either repairing or replacing the defected
parts.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#29 ‐ AHU Flex Connectors Torn
List Status
Cx Deficiency Open
Created Type
2/15/2019 at 2:09 PM Issue
tjuliana@emegroup.com
Location Assignees
Various Beijing Construction
Engineering
Last updated
2/15/2019 at 2:27 PM
Description
Flex connectors on return and supply duct connections to AHUs were observed to be torn/damaged in
multiple locations. Flex connectors should be reviewed and repaired as necessary during unit start ups.
Photos
BCEG Has rectified all the similar flex connector issues known as of today, perhaps, this may occur somewhere
again with passage of time. BCEG will continue repairing all such issues, whenever occur.
Photo:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#30 ‐ Chilled Water Field Device Insulation
List Status
Cx Deficiency Open
Created Type
2/15/2019 at 2:20 PM Issue
tjuliana@emegroup.com
Location Assignees
Basement Plant Room Beijing Construction
Engineering
Last updated
2/15/2019 at 2:25 PM
Description
Insulation around CHW field devices (gauges, sensors, etc.) was observed to not be filled in and sealed
after device installation. Insulation should be sealed to prevent excess heat loss and condensation.
Photos
BCEG has rectified this issue. Most of the field devices have insulation around them. The remaining ones are
being insulated.
Photo:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#31 ‐ Chiller Pressure Relief Valve with Manual Ball Valve
List Status
Cx Deficiency Open
Created Type
2/19/2019 at 12:14 PM Issue
tjuliana@emegroup.com
Location Assignees
Basement Plant Room Beijing Construction
Sheet Engineering
1801‐HV‐A0‐BS111
Last updated
2/19/2019 at 12:16 PM
Description
The chiller's (CH‐1 through 3) pressure relief valve assembly includes an additional manual isolation
ball valve between the unit and the PRV, which is noted as a safety concern. Should the PRV open to
relieve pressure during an event and the manual valve is mistakenly left closed, the chiller may suffer
significant damage.
Photos
The ball valve is there for Chiller’s evaporator and condenser vessel’s pressure and vacuum testing with ranges
above the PRV rating. Now the testing is done and piping is installed, we will keep the valve open and remove
the handle.
Photos:
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#32 ‐ Internal AHU Wiring Not Protected
List Status
Cx Deficiency Open
Created Type
2/19/2019 at 4:15 PM Issue
tjuliana@emegroup.com
Location Assignees
AHU/HRU Rooms Beijing Construction
Engineering
Last updated
2/19/2019 at 4:17 PM
Description
Internal wiring in AHUs/HRUs were observed to be unprotected. Wires are run through openings
between unit sections without proper grommets, sleeves, or other protection. Over time, wires will
rub against the metal, potentially leading to shorting out. Observed in every AHU/HRU.
Photos
BCEG’s electrical team has installed grommet kind of protection for all the internal electrical wiring passing
through sharp edges.
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
RCHQ – Cx Issues Log
RCHQ
Yanbu, Saudi Arabia
#33 ‐ Refrigerant Storage Tank
List Status
Cx Deficiency Open
Created Type
2/19/2019 at 4:31 PM Issue
tjuliana@emegroup.com
Location Assignees
Basement Plant Room Beijing Construction
Engineering
Last updated
2/19/2019 at 4:32 PM
Description
Per Specification 15680 Section 2.3.K.4 a free‐standing refrigerant storage tank and pump out unit
shall be provided. No storage tank is currently installed.
BCEG’s response: Status: Closed, Date: July, 28 2019, By: sajjad.bceg@gmail.com
A free standing refrigerant storage tank is placed at its designated location in plant room.
Photo:
RCHQ – Cx Issues Log