CABLE CURRENT TRANSFORMERS

types: KOLMA, KOLA, KOKM, KOKU, KOLT

Catalogue
CONTENT page

1. KOLMA, KOLA
Description ........................................................................... 3
How to select the correct residual current transformers ..... 3
Technical data ...................................................................... 4
Installation ............................................................................ 4
Ordering data ....................................................................... 6
Overall dimensions ............................................................... 6

2. KOKM ...................................................................................... 9
Technical data ...................................................................... 9
Ordering data ..................................................................... 10
Instruction for installation .................................................. 10
Overall dimensions ............................................................. 12

3. KOKU..................................................................................... 17
Technical data .................................................................... 17
Overall dimensions ............................................................. 19

4. KOKM (for ZX panells) ......................................................... 22


Technical data .................................................................... 22
Overall dimensions ............................................................. 23

5. KOLT ...................................................................................... 31
Dimensional drawing .......................................................... 31
Technical data .................................................................... 32

2 ABB
Cable Current Transformers, indoor
types: KOLMA, KOLA

Description
Transformers, KOLMA_ and KOLA_ are suitable for the measurement of the sum
of three-phase currents in a 3-phase cable. Under normal operating conditions
this sum is zero. In the event of an earth-fault the sum of the currents is equal to
the earth-faul current and a corresponding current flows in the secondary.
These transformers are used together with static earth-fault relays. The cable
current transformers can generally be used when measuring the residual current
e.g. to prewarn of, or locate an earth-fault. An uninsulated busbar or low voltage
cable serves as the primary conductor.

How to select the correct residual current transformers


The transformer for an earth-fault relay is selected according to dimension of the
window, and construction of the transformer.
For types KOLMA 06 A1, and KOLMA 06 D1, the number of turns used in the
secondary winding is selected according to the relay setting value, and the earth-
fault current or the required current ratio.
In addition correct functioning of the earthfault protection relays for KOLMA
06 A1 and KOLMA 06 D1 is easy to test by means of the test winding (termi-
nals P1x - P2x) of the transformer. The test winding is rated for 6 A max.
continuous current.

ABB 3
Table 1 Selection of residual current transformers

Type Window diam. Construction Weight


mm kg
KOLMA 06 A1 90 Ring core, multi-tap secondary 7.0
KOLMA 06 A2 58 Ring core 2.9
KOLMA 06 B2 100 Ring core 5.4
KOLMA 06 D1 180 Ring core, multi-tap secondary 11.5
KOLMA 06 D2 180 Ring core 11.4
KOLA 06 B2 100 Split ring core 6.0
KOLA 06 D2 180 Split ring core 11.0

Technical data
The primary winding of indoor type cable current transformers is either a cable or
a busbar, which is insulated for the application voltage.
The secondary winding and ring shaped iron core is cast in resin which has good
electrical and mechanical properties.

Rated voltage 0.72 kV (1)


Insulation test voltage
50 Hz 1 min 3 kV (IEC 60044-1)
Cable current transformers, types KOLMA_ Frequency 50 Hz (60 Hz)
Rated thermal current 1.2 x Ipn
Short-time withstand current Ith 1 s 60 x Ipn (2)
Peak withstnad current Idyn 2.5 x Ith
Secondary terminals For 6 mm2 conductor
Operating temperature range –5...+40 °C
(1)
The insulation level of the primary conductor determines the
maximum operating voltage.
(2)
KOLA 06 B2 is type tested for 10 kA 3 s.

Installation
The KOLMA-types must be installed before the cables and cable terminations
are connected.
With the KOLA 06 B2 and KOLA 06 D2 -types, the ring core can be opened and
thus the transformer can be installed eventhough the cable is already connected.
The two halves of the ring core are tightened together with four screws which
also guide the halves to the correct position. The secondary winding is distrib-
uted over both halves of the core. The two sections of the winding are connected
together with two connecting pieces.
Cable current transformers are fastened either by means of the fixing base or by
the nuts cast into the transformer frame. When installing the transformer, the
effect of the current in the metal armour or in the protective conductor must be
eliminated. In case the metal armour or the protective conductor is drawn through
the transformer, the earthing conductor must be drawn back through the trans-
former for earthing. The earthing conductor between the cable termination box
and the transformer, must not be connected to conductive structures, and the
metal cable termination box must be insulated from the supporting structures.
On a multi-ratio transformer the unconnected secondary winding terminals and
test winding must not be short circuited.

4 ABB
Number of turns and terminal markings
Cable
P1 P2
KOLMA 06 A1
KOLMA 06 D1
10 20 70 50 20

S1 S2 S3 S4 S5 P1x P2x

Test winding
Cable
KOLMA 06 A2
KOLMA 06 B2 P1 P2
KOLMA 06 D2
KOLA 06 B2 100
KOLA 06 D2 S1 S2

Table 2. Current ratios and rated burdens


for accuracy class 10 P 10
Design data.
Types KOLMA 06 A1 and KOLMA 06 D1

Current Secondary Burden / VA


ratio terminals Type
A KOLMA 06 A1 KOLMA 06 D1
50/1 S4 - S5 1.0 0.5
70/1 S3 - S4 2.0 1.0
100/1 S1 - S4 2.5 2.0
150/1 S1 - S5 5.0 4.0
50/5 S1 - S2 1.0 0.5
100/5 S2 - S3 2.5 1.5
150/5 S1 - S3 4.0 3.0
250/5 S4 - S5 7.5 5.0
350/5 S3 - S4 10.0 7.5
500/5 S1 - S4 15 10
600/5 S3 - S5 20 15
750/5 S1 - S5 20 15

Table 3. Current ratios and rated burdens


for accuracy class 10 P 10
Design data.
Types KOLMA 06 A2, KOLMA 06 B2, KOLMA 06 D2 and KOLA 06 B2

Type Current ratio Secondary terminals Burden


A VA
KOLMA 06 A2 100/1 S1 - S2 2.0
KOLMA 06 B2 100/1 S1 - S2 2.5
KOLMA 06 D2 100/1 S1 - S2 2.0
KOLA 06 B2 100/1 S1 - S2 2.0
KOLA 06 D2 100/1 S1 - S2 2.0

Openable residual current transformers, type KOLA 06


B2 complete with fixing base KOLMA-ZK 1 and
terminal cover KOK-ZAX 14.

ABB 5
Ordering data for accessories
– quantity
– type
Accessores shall be ordered separately.
Table 4. Selection of accessories for KOLMA_ and KOLA_
Description of accessory Type Suitable for use
together
with transformer
Fixing base KOLMA-ZK 1 KOLMA 06 A1
Fixing base KOLMA-ZK 1 KOLMA 06 A2
Fixing base KOLMA-ZK 1 KOLMA 06 B2
Fixing base KOLMA-ZK 1 KOLA 06 B2
Fixing base KOLMA-ZK 2 KOLMA 06 D1
Fixing base KOLMA-ZK 2 KOLMA 06 D2
Fixing base KOLMA-ZK 2 KOLA 06 D2
Secondary terminal cover KOK-ZAX 14 KOLMA 06 A2
Secondary terminal cover KOK-ZAX 14 KOLMA 06 B2
Secondary terminal cover KOK-ZAX 14 KOLA 06 B2
Secondary terminal cover KOK-ZAX 14 KOLA 06 D2

Overall dimensions

KOLMA 06 A1 KOLMA 06 A2, B2


52
M8 M5 KOK-ZAX 14

12,5
78
39

C
AB
KOLMA-ZL 2,3

14
P1 M8 18
52 65 KOLMA-ZK1

245 238
90

145 175
113

14
18 78
96 D
186 KOLMA-ZK1
Type Dims./mm
KOLMA A B C D
06 A2 58 177 196 140
06 B2 100 229 249 196

6 ABB
KOLMA 06 D1, D2

KOLMA-ZL2,3 80
25
23
17

P1

180 335

140

15
18
115
130
145
150
190 KOLMA-ZK2
270

KOLA 06 B2 KOLA 06 D2

M5
M5 KOK-ZAX 14
KOK-ZAX 14 7
7

M5 P1
M5 P1
153
109
0
18 a b

10 0 293 315
219 238
a b

140
110
16

18 3
14
150 18
52 KOLMA-ZK 2 M10
KOLMA-ZK1 M8 130
11

20

20 85 115 145
85
1 2

20 36
36
228 315

ABB 7
KOLA 06 J2_
75
113
M6 16

17
ø15
a2 a1

6
40

462
370

300
10
4
0
R4

20
b2 b1

4
+3
497

R1
0

20 570

610

P1
S1

62
90

a2 a1 S2

P2

ø 22,5
619 M5

P1 P2
a1 a2 b2 b1

S1 S2

Table 5 KOLA 06 J2
Standards parameters for KOLA 06 J2 f = 50 Hz

Type Window diameter Ratio Accuracy Burden


[mm] [A] Class [VA]
KOLA 06 J2 300x497 100/1 10P10 1
KOLA 06 J2 300x497 200/5 10P10 2
KOLA 06 J2 300x497 300/1 10P10 5
Note: If you need other electrical parameters than given in tables please contact with our sales
department.

8 ABB
Cable Current Transformers
types: KOKM (indoor type)

Current transformer series KOKM


for measuring of phase currents
KOKM current transformers are suitable for measuring of phase currents in low voltage
switchgear. An uninsulated busbar or low voltage cable serves as the primary conduc-
tor. Series KOKM current transformers can also be used for measuring the phase
current at voltages even higher than 0,72 kV (for KOKM 06) or 1,2 kV (for KOKM 1), if the
insulation of the high voltage primary conductor fulfils the respective standards for the
operating voltage. The secondary winding and ring shaped iron core is cast in resin
which has good electrical and mechanical properties.

Technical data
Transformer type KOKM 06 KOKM 1

Rated voltage Um [ kV ] 0.72 (1) 1.2 (1)


Power frequency test voltage Up 1min [ kV ] 3 6
Lighting test voltage Upp [ kV ] - -
Frequency fn [ Hz ] 50 and 60
Max. primary current Ipn [A] 2 000 10 000
Rated secondary current Isn [A] 1 and 5
Rated thermal current Icont [A] 1,2 x Ipn (2)
Short-time withstand current Ith 1s [ kA ] 60 x Ipn (3)
Peak withstand current Idyn [ kA ] 2,5 x Ith (4)
Secondary terminals For 6 mm2 conductor
Operating temperature range [ °C ] - 5 … + 40
Transport and storage [ °C ] - 25 … + 55
Electrical standards IEC, VDE, ANSI, BS, AS, CAN
(1)
The insulation level of the primary conductor determines the maximum operating voltage.
(2)
Max. Icont for KOKM 06 Icont = 2 400 A, for KOKU 072 G4 Icont = 1 000 A, for KOKM Icont= 10 000 A
(3)
Max. Ith = 90 kA,
(4)
Max. Idyn = 225 kA

ABB 9
Ordering data
Enquires for these transformers should mention the following data:
1.Quantity,
2.Type, (example: KOKM 1 DC 10 (1), KOKU 1 KL 12 (2), KOKM 06 J29 (3),
KOKU 072 G4 (4))
3.Current ratio Ipn/Isn (A),
4.Burden (VA),
5.Accuracy class,
6.Electrical standards,
7. Window dimension (mm),
8.Other limiting data such as instrument security, dimensions of transformer,
fixing of transformer (fixing base) etc.,
9.Indoor or outdoor use.
(1)
Other name of Type for KOKM 1 you can choose from table 6.
(2)
Other name of Type for KOKU 1 you can choose from table 8.
(3)
Other name of Type for KOKM 06 you can choose from table 7.
(4)
Electrical parameters and window dimension for KOKU 072 G4 include table 9.

KOKM 06 J

Terminal markings

P1 P2 P1 P2 P1 P2
S1 S2 S1 S2 S3 1S1 1S2 2S1 2S2

one secondary winding multi-tap secondary winding two secondary windings


example: 100/1 [A/A] example: 50-100/1 [A/A] example: 800/5/5 [A/A/A]

Instructions for installation


Mounting of the cable current transformers
The cable current transformer may be installed either in vertical or in horizontal posi-
tion. It can be mounted either by using bottom inserts or by using a separate fixing
base, which in turns is fixed to the bottom inserts. When using the bottom inserts for
mounting, the screws (M8) shall not be tightened in excess of the nominal torque; 9
Nm, for the screws (M6) 3.3 Nm, otherwise damage may occur. Use a torque span-
ner if necessary. The current transformer can be fastened to the cable which acts as
primary conductor by means of a special fixing piece. In such cases it must be
insured that the cable endures the strain caused by the weight of the transformer,
especially in circumstances where vibration is involved. The secondary terminal
screws, size M5, must not be tightened in excess of 2.5 Nm (M4 1.0 Nm).
Fastening of the primary cable
KOKM 1 FC6 The cable acting as primary winding shall be entered through the opening in the
cable current transformer. This must be done before the cable box belonging to the
cable inserted through the primary opening is installed. If the cable box can be
entered through the primary opening even when it is installed on the cable, the
installation of the cable box can also be done before. With the KOLA 06 J2, the
cable current transformer can be opened and thus the transformer can be in-
stalled even though the cable is already connected. The two halves of the ring core
are tightened together with four screws which also guide the halves to the correct
position. The secondary winding is distributed over both halves of the core. The
two section of the winding are connected together with two connecting pieces.
Note:
The secondary terminals of the current transformer should never be left open-
circuited, because in that case hazardous high voltages will be induced between
the secondary terminals.
Instructions for maintenance
Cable current transformers do not need to be maintained. However, excessive dust or
other kind of dirt can be brushed off the transformer. Dirty transformers can be cleaned
with water, spirit, petrol or toluene. Traces of arcs and minor surface damages can be
easily removed with sandpaper after which the surface is to be treated with silicone
paste. Epoxy resin surfaces of the current transformer have also a high resistance to
chemicals.

10 ABB
The transformers can be used in areas, where the atmosphere includes corrosive
gases such as sulphuric and nitrogenous compounds provided that secondary termi-
nals and fixing base of the transformers have been ordered to meet the demands of
the operating atmosphere. Instructions for repairing greater surface damages (such
as cracks) must be requested from the manufacturer.
Storage instructions
For current transformers, the allowed storage temperature is - 40°C …+ 55°C.
The transformers shall be protected against direct sun light.
Package, Transport and Storage
Transformers assigned for export are packed in wooden cases lined with the asphalt
building paper. During the transport of transformers one should pay attention to
proper position of wooden cases in accordance with inscription and marks given on
them and their protection against the influence of weather conditions. Transformer
should be stored in dry and clean accommodations, protecting direct influence of
precipitation and frost.
KOKM 1 RL 8
Warranty
The factory grants 24 months of warranty from the day of put to use of the trans-
former, but no longer than 36 months from the day of sell. The warranty concerns
only manufacturing defects and does not include defects arose because of:
– improper transport,
– improper storage,
– not abiding of the instruction before installing and during operating
of the transformers,
– improper selection of the transformer for the electric power system.
Procedure regarding the products after the end of their use.
The manufacturer gets back or indicates the store place for instrument transformers
of its own production, which the period of use is finished, in order to their recycling.

Table 6. KOKM 1
example KOKM 1 DC 10
Transformers width 10 = 100 mm (possibility 6, 8, 10, 12, 14, 16, 18, 20, 22, 24)
Outer diameter C = 148 mm
Hole diameter D = 60 mm
Rate voltage 1 = 1.2 kV (06 and 072 = 0.72 kV)
Type KOKM – indoor use, (KOKU – outdoor use)

Casting height
Hole diameter (mm)

height (mm)
Total height

Hole center
Outer
(mm)

(mm)
diameter A B D E F G H K N R U W X Y Z Drawing
(mm)
33 42 60 70 85 90 100 120 155 180 250 360 400 450 500
60 60 60 60 60
C 148 160 160 160 160 160 KOKM 1 _C _ 183 236 112
60 60 60 60 60 60 60 Range of transformers width
F 186 160 160 160 160 160 160 160 KOKM 1 _F _ 213 266 131
80 80 80 80 80 80 80 80
H 200 180 180 180 180 180 180 180 180 KOKM 1 _H _ 235 288 138
80 80 80 80 80 80 80 80 80
K 250 200 200 200 200 200 200 200 200 200 KOKM 1 _K _ 275 328 158
80 80 80 80 80 80 80 80 80 80
L 270 200 200 200 200 200 200 200 200 200 200 KOKM 1 _L _ 297 350 158
80 80 80 80 80 80 80 80 80 80
M 280 240 240 240 240 240 240 240 240 240 240 KOKM 1 _M _ 297 350 158
80 80 80 80 80 80 80 80 80 80
P 340 200 200 200 200 200 200 200 200 200 200 KOKM 1 _P _ 379 432 204
80 80 80 80 80 80 80 80
T 450 200 200 200 200 200 200 200 200 KOKM 1 _T _ 465 500 225
80 80 80 80 80 80 80 80 80 80
W 590 200 200 200 200 200 200 200 200 200 200 KOKM 1 _W _ 605 653 300

ABB 11
Overal dimensions

KOKM 1_C_ KOKM 1_F_


124

20
20 52

B±2 (1000...160)
11
B ±2 (120...160)

C
C

40
B ±2 (60...100)

B±2(60...80)

40
11
52
75
1 140
M6 113
M5 16 1
113 75
M6
M5 16
17

23

17

23
6
P1

6
P1
40
40
236 ±3
183 ±2

+2

266 ±3
Di
0

213 ±2
+3 0

Di

P1 P2
112 ±2

P1

131 ±2
P2 186

M8 S1 S2
14

14
18

S1

18
S2
M8
148 170
KOKM 1 _ F __
KOKM 1 _ C __
Di = 33 42 60 70 85 Di = 33 42 60 70 85 90 100
A B D E F G H
A B D E F
6 8 10 12 14 16
6 8 10 12 14 16
B = 60 80 100 120 140 160 B= 60 80 100 120 140 160 Note:
C= 80 100 120 Note: C= 60 80 100 120
1) KOKM 1_F6 without the cover
1) KOKM 1_C6 without the cover

KOKM 1_H_ KOKM 1_K_


20

14
B±2 (100...180)

B ±2

C
C

40
150
246
B±2 (80)

113 75
40
11

M6 M5 16

52
17

23

140

M6
75 P1 6
113
40
16
M5
17

P1
40
328±3

275±2

+3
Di
0
288 ±3

+30
235±2

Di
158 ±2

P1 P2
138 ±2

200 0
250 -2
M8 S1 S2
14

15

P1 P2
18

18

170
M8 S2
S1
270
KOKM 1 _ H _
Di = 33 42 60 70 85 90 100 120
A B D E F G H K KOKM 1 _ K _
Di = 33 42 60 70 85 90 100 120 155
A B D E F G H K N
8 10 12 14 16 18

B= 80 100 120 140 160 180 8 10 12 14 16 18 20


C= 60 80 100 120 140 B = 80 100 120 140 160 180 200
C = 40 60 80 100 120 140 160

12 ABB
KOKM 1_L_ KOKM 1_M_

20

14
20

14

B ±2
C
B±2

40
40
150
150 246
75
246
113
M6 16
113 74 M5
M6
M5 16

17

23
17

6
23
P1
40

6
P1
40

P1

350 ±3
P2

297 ±2
+3
Di
0
P1
350 ±3

P2
297 ±2

+3 S1 S2
Di
0

S1 S2

158 ±2
0
280 -2
158 ±2

15
270 -2

18
15

M8
270
18

M8
270

KOKM 1 _ L _ KOKM 1 _ M _
Di = 33 42 60 70 85 90 100 120 155 180 200 Di = 33 42 60 70 85 90 100 120 155 180
A B D E F G H K N R S A B D E F G H K N R

8 10 12 14 16 18 20 8 10 12 14 16 18 20 22 24

B = 80 100 120 140 160 180 200 B= 80 100 120 140 160 180 200 220 240
C = 40 60 80 100 120 140 160 C= 40 60 80 100 120 140 160 180 200

KOKM 1_P_ KOKM 1_T_


M8
20

15
14

B ±1
B ±2

C
C

40

0
450 -3

M6 113
75
M5
75
113 16
M6 M5 16 17

P1

23
17

6
23

40
6

P1
40

+4
500

0
Di
465 ±3
432 ±3

P1 P2
379 ±2

+3
0
Di
S1 S2
204 ±2

225 ±3

0
340 -2
15
18

P1 P2
15

M8
270
180 S1 S2

225
KOKM 1 _ P _
Di = 42 60 70 85 90 100 120 155 180 250 KOKM 1 _ T _
B D E F G H K N R U Di = 85 90 100 120 155 180 250 350
F G H K N R U W
8 10 12 14 16 18 20

B= 80 100 120 140 160 180 200 8 10 12 14 16 18 20


C= 40 60 80 100 120 140 160 Note:
B = 80 100 120 140 160 180 200 Without fixing base. Fix directly to floor
C = 50 70 90 110 130 150 170

ABB 13
KOKM 1_W_
M12

C 25
B ±3
0
590 -3

M5 142 M5
64
97 IP23
Pk 16

48
17
Pr 22,5
Pg 16 P1

+ 40

Di

605 ±3
300 ±3

15
200
250 P1 P2

KOKM _1 _W
Di = 90 100 120 155 180 250 350 400 450 500 S1 S2
G H K N R U W X Y Z

8 10 12 14 16 18 20
Note:
B = 80 100 120 140 160 180 200 Witout fixing base. Fix directly to floor.
C = 30 50 70 90 110 130 150

Table 7. KOKM 06
Standards parameters for KOKM 06 J_ (window type) f = 50 Hz
Type Window diameter Ratio Accuracy Burden
[mm] [A] Class [VA]
KOKM 06 J2 300x500 50/5 10P10 0.5
KOKM 06 J2 300x500 100/1 10P10 2
KOKM 06 J2 300x500 100/5 10P10 1.5
KOKM 06 J2 300x500 100/5 3 2
KOKM 06 J2 300x500 250/5 10P10 1
KOKM 06 J2 300x500 400/5 10P10 5
KOKM 06 J2 300x500 500/1 5P20 10
KOKM 06 J2 300x500 500/5 10P10 5
KOKM 06 J2 300x500 2000/5 0.5 15
KOKM 06 J21 500x150 30/1 10P10 0.5
KOKM 06 J21 500x150 50/1 10P10 1
KOKM 06 J21 500x150 100/1 10P10 1
KOKM 06 J21 500x150 100/5 10P10 1
KOKM 06 J21 500x150 150/1 10P10 1
KOKM 06 J21 500x150 500/5 10P10 10
KOKM 06 J22 300x200 100/1 10P10 2
KOKM 06 J22 300x200 300/1 5P10 15
KOKM 06 J22 300x200 1000/5 5P10 15
KOKM 06 J23 600x200 50/1 10P10 1
KOKM 06 J23 600x200 60/1 10P10 1
KOKM 06 J23 600x200 100/1 10P10 3
KOKM 06 J23 600x200 200/1 10P10 2
KOKM 06 J23 600x200 300/5 5P10 2
KOKM 06 J24 300x250 50/1 10P10 1
KOKM 06 J24 300x250 150/1 10P10 2
KOKM 06 J29 450x650 50/1 10P10 1
KOKM 06 J29 450x650 50/5 10P10 1
KOKM 06 J29 450x650 100/1 10P10 1
KOKM 06 J29 450x650 100/5 10P10 1
KOKM 06 J29 450x650 400/1 5P10 10
14 ABB
KOKM 06 J2 KOKM 06 J21_
113
113 75
75
M6 M5 16 M6
M5 16

17

23
15

17
Æ

23
6
15
40 Æ

6
40

462
300
370
10
4

0
R4
20

665
500 +30
4

+3
R1

500

573
613
0

20 573

613
80

P1 P2
S1 S2

0
R4
20
150

4
R1
20 220

260

P1 P2
S1 S2

80

KOKM 06 J22 KOKM 06 J23

113 113
75 75
M6 M5 16 M6 M5 16
17

17
23

23
15 15
Æ Æ
6

6
40 40
462
300
370
410

0
R4
765
0
+3
600
673
713
20

4
R1

200

20 270

310

P1 P2
S1 S2
0
80

R4
20

4
R1 200

20 270

310
P1 P2
S1 S2
80

ABB 15
KOKM 06 J24 KOKM 06 J29_
113 113
75 75
M6 M5 16
M6 M5 16

17

23
15
Æ

17

6
23
40
15
Æ

6
40

612
560

520
450
462
300
370
410

0
R4

0
R4

20

4
650 +30

R1
20 720
20

760

P1 P2
4

S1 S2
R1

250

80
20 320

360

P1 P2
S1 S2
80

16 ABB
Cable Current Transformers
type KOKU (outdoor type)

Current transformer series KOKU


for measuring of phase currents
KOKU current transformers are suitable for measuring of phase currents in low volt-
age switchgear. An uninsulated busbar or low voltage cable serves as the primary
conductor. Series KOKU current transformers can also be used for measuring the
phase current at voltages even higher than 0,72 kV (for KOKU 072 G4) or 1,2 kV
(for KOKU 1), if the insulation of the high voltage primary conductor fulfils the respec-
tive standards for the operating voltage. The secondary winding and ring shaped iron
core is cast in resin which has good electrical and mechanical properties.

Technical data
Transformer type KOKU 072 G4 KOKU 1

Rated voltage Um [ kV ] 0.72 (1) 1.2 (1)


Power frequency test voltage Up 1min [ kV ] 3 6
Lighting test voltage Upp [ kV ] - -
Frequency fn [ Hz ] 50 and 60
Max. primary current Ipn [A] 800 10 000
Rated secondary current Isn [A] 1 and 5
Rated thermal current Icont [A] 1,2 x Ipn (2)
Short-time withstand current Ith 1s [ kA ] 60 x Ipn (3)
Peak withstand current Idyn [ kA ] 2,5 x Ith (4)
Secondary terminals For 6 mm2 conductor
Operating temperature range [ °C ] - 5 … + 40
Transport and storage [ °C ] - 25 … + 55
Electrical standards IEC, VDE, ANSI, BS, AS, CAN
(1)
The insulation level of the primary conductor determines the maximum operating voltage.
(2)
Max. Icont for KOKM 06 Icont = 2 400 A, for KOKU 072 G4 Icont = 1 000 A, for KOKU 1 Icont= 10 000 A
(3)
Max. Ith = 90 kA,
(4)
Max. Idyn = 225 kA

ABB 17
Table 8. KOKU 1

example KOKU 1 KL 12
Transformers width 12 = 120mm (possibility 8, 10, 12, 14, 16, 18, 20, 22, 24)
Outer diameter L = 270mm
Hole diameter K = 120mm
Rate voltage 1 = 1.2kV (06 and 072 = 0.72 kV)
Type KOKU – outdoor use, (KOKM – indoor use)

Casting height
Hole diameter (mm)

height (mm)
Total height

Hole center
Outer

(mm)

(mm)
diameter A B D E F G H K N R U W X Y Z Drawing
(mm)
33 42 60 70 85 90 100 120 155 180 250 360 400 450 500
80 80 80 80 80
C 148 160 160 160 160 160 KOKU 1 _C _ 183 249 112
80 80 80 80 80 80 80 Range of transformers width
F 186 160 160 160 160 160 160 160 KOKU 1 _F _ 213 279 131
80 80 80 80 80 80 80 80
H 200 180 180 180 180 180 180 180 180 KOKU 1 _H _ 235 301 138
80 80 80 80 80 80 80 80 80
K 250 200 200 200 200 200 200 200 200 200 KOKU 1 _K _ 275 341 158
80 80 80 80 80 80 80 80 80 80
L 270 200 200 200 200 200 200 200 200 200 200 KOKU 1 _L _ 297 363 158
80 80 80 80 80 80 80 80 80 80
M 280 240 240 240 240 240 240 240 240 240 240 KOKU 1 _M _ 297 363 158
80 80 80 80 80 80 80 80 80 80
P 340 200 200 200 200 200 200 200 200 200 200 KOKU 1 _P _ 379 445 204
80 80 80 80 80 80 80 80
T 450 200 200 200 200 200 200 200 200 KOKU 1 _T _ 465 513 225
80 80 80 80 80 80 80 80 80 80
W 590 200 200 200 200 200 200 200 200 200 200 KOKU 1 _W _ 605 653 300

Table 9.
Standards parameters for KOKU 72 G4
Type Window Total Hole Ratio Accuracy Burden Short Standard
diameter height center Class circuit
height current
Ith, 3s
[mm] [mm] [mm] [A] [VA] [kA]
KOKU 072 G4 ∅135 230 125 600/1 5P10 3 25 IEC 60044-1
Note: If you need other electrical parameters than given in tables please contact with our sales department.

18 ABB
Overal dimensions
KOKU 1_C_ KOKU 1_F_
124
52

20

B±2 (160)
(1000...160)
11
B ±2 (120...160)

80
C
B
C

±2
40

B±2 (60...140)
B±2(80)
B ±2 (80...100)

78

20
40
11
52 11
52
140 18 75 70
64 8
142
16
M5 97 M5 M5 142
97 M5
IP44 64 8
Pk 16
Pr 22,5 Pk 16 16
Pr 22,5
17
Pg 16
PG 16
P1 P1 IP44

17
249 ±3

279 ±3

213 ±2
+3 0
183 ±2

+2
0 Di
Di

131 ±2
112 ±2

186
P1 P2 P1 P2
M8

14
14

18
S1 S2
18

170
S1 S2 KOKU 1 _ F __
M8
148 Di = 33 42 60 70 85 90 100
A B D E F G H
KOKU 1 _ C __
Di = 33 42 60 70 85 8 10 12 14 16
A B D E F
B= 80 100 120 140 160
C= 80 100 120
8 10 12 14 16
B= 80 100 120 140 160
C= 80 100 120

KOKU 1_H_ KOKU 1_K_


20

14
B±2 (100...180)

B ±2

C
C

40
150
246
64 8
B±2 (80)

M6 142 M5
40
11

97 16

Pk 16
52 Pr 22,5 IP44
Pg 16
140
17

64 8
P1
M5 142 M5
16
97
Pk 16
Pr 22,5 IP44
Pg 16
17

P1
341 ±3

275±2

+3
Di
0
301 ±3

+3
235±2

0
Di
158 ±2

P1 P2
138 ±2

0
200 250 -2

M8 S1 S2
15
14

P1 P2
18
18

170 M8
S1 S2
270
KOKU 1 _ H _
Di = 33 42 60 70 85 90 100 120
A B D E F G H K KOKU 1 _ K _
Di = 33 42 60 70 85 90 100 120 155
A B D E F G H K N
8 10 12 14 16 18

B= 80 100 120 140 160 180 8 10 12 14 16 18 20


C= 60 80 100 120 140 B = 80 100 120 140 160 180 200
C = 40 60 80 100 120 140 160

ABB 19
KOKU 1_L_ KOKU 1_M_

20

20

14
14

B ±2
B±2

C
C

40
40
150
150
246
246 64 8
64 8 142 16
142 M5 IP44
16 97 M5
M6 97 M5

Pk 16 IP44
Pk 16

17
Pr 22,5 Pr 22,5
Pg 16 Pg 16

17
P1
P1

363 ±3
P1 P2

297 ±2
+3
363±3

0
P1 P2 Di
297 ±2

+3 S1 S2
Di
0

S1 S2

158 ±2
0
280 -2
158 ±2

15
270 -2

18
15

M8
270
18

M8
270

KOKU 1 _ L _ KOKU 1 _ M _
Di = 33 42 60 70 85 90 100 120 155 180
Di = 33 42 60 70 85 90 100 120 155 180 200 A B D E F G H K N R
A B D E F G H K N R S
8 10 12 14 16 18 20 22 24
8 10 12 14 16 18 20
B= 80 100 120 140 160 180 200 220 240
B = 80 100 120 140 160 180 200 C= 40 60 80 100 120 140 160 180 200
C = 40 60 80 100 120 140 160

KOKU 1_P_ KOKU 1_T_


M8
15
20

14

B ±1
B ±2

C
C

40

0
450 -3
M5 142 M5
97 64 8
16
142 Pk 16
64 8 IP44
Pr 22,5
M5 97 16 Pg 16
M5
P1 17
Pk 16 IP44
Pr 22,5
.
Pg 16
17

P1

+4
513

0
Di
465 ±3
445 ±3

P1 P2
379 ±2

+3
0
Di

S1 S2
225 ±3
204 ±2

0
340 -2

P1 P2
15
18

15

180 S1 S2
M8
270
225

KOKU 1 _ T _
KOKU 1 _ P _ Di = 85 90 100 120 155 180 250 350
Di = 42 60 70 85 90 100 120 155 180 250 F G H K N R U W
B D E F G H K N R U

8 10 12 14 16 18 20 8 10 12 14 16 18 20
Note:
B= 80 100 120 140 160 180 200 B = 80 100 120 140 160 180 200 Without fixing base. Fix directly to floor
C= 40 60 80 100 120 140 160 C = 50 70 90 110 130 150 170

20 ABB
KOKU 1_W_ KOKU 072 G4
M12

C 25
B ±3

P2

0
590 -3

5
13
M5 142 M5 Æ
64
97 IP23

230
Pk 16

48
17
Pr 22,5
Pg 16

111
P1

125
S1 S2

150 45
M12X60
+ 40 210
Di

605 ±3
Rating plate

Cable, length 1,6 m


300 ±3

S1 = 1
S2 = 2

Æ13,3
1 2

S1 S2
15

200
250 P1 P2
M5 M5
KOKU _1 _W
Di = 90 100 120 155 180 250 350 400 450 500 S1 S2
G H K N R U W X Y Z

8 10 12 14 16 18 20
Note:
B = 80 100 120 140 160 180 200 Witout fixing base. Fix directly to floor.
C = 30 50 70 90 110 130 150

ABB 21
Cable Current Transformers
type KOKM (for ZX panels)

KOKM 1 EB – is the indoor, cable, low voltage current transformer in resin


insulation.Transformers of KOKM type are suitable for measurement of phase
currents in low voltage switchgears. As the primary conductor is used the non-
insulated busbar or the low voltage cable. Current transformers of KOKM series
can be also used for measurement of the phase current at voltages even higher
then 1,2 kV, if the insulation of the high voltage primary conductor fulfils the
equirements of elevant standards relating to the working voltage.
Technical data:
Type ................................................................................................... KOKM 1EB
Maximum number of windings .......................................................................... 1
Level of insulation ....................................................................................... 1/6/-
Highest permissible voltage of the current transformer Ur ........................ 1,2 kV
Rating test voltage of insulation (50 Hz, 1 min Up) ....................................... 6 kV
Rating frequency ....................................................................................... 50 Hz
Rating thermal current ............................................................................ 1,2 x Ipn
Short-time withstand thermal current Ith, 1s ............................................. 60 x Ipn
Rating peak current Idyn ........................................................................... 2,5 x Ith
Working temperature range ................................................................ -5...+40°C
Conformity with standards -PN-EN, EN, VDE, ANSI, BS, AS, CAN
Example of an order:
In the order shall be specified: type, ratio, Ith , load, class and number of
pieces, for example:
KOKM1EB 8 150/1A/A, Ith = 60 x Ipn ,1VA 10P10 - 3 pieces

22 ABB
Table for selecting current transformers KOKM 1 EB
Maximum permissible load [VA]
Primary Secondary current Isn = 1 [A] Secondary current Isn = 5 [A]
Current Measurement class Protection class Measurement class Protection class
Ipn [A] FS Fa FS Fa
0,5 1 10P10 5P10 5P20 0,5 1 10P10 5P10 5P20
50 – – 0,5 0,5 0,5 – – 0,5 – –
60 – – 0,5 0,5 0,5 – – 0,5 0,5 –
70 – 0,5 1 1 0,5 – 0,5 0,5 0,5 –
75 – 1 1 1 0,5 – 1 1 1 –
100 – 2,5 1,5 1,5 0,5 – 1,5 1 1 –
110 0,5 4 1,5 1,5 0,5 – 2,5 1 1 –
120 1 4,5 1,5 1,5 0,5 0,5 3 1,5 1,5 –
140 1 4,5 1,5 1,5 0,5 1,5 7 2 2 0,5
150 1,5 6 2 2 0,5 1,5 7 2 2 0,5
200 5,5 8,5 2,5 2,5 0,5 2,5 12 2,5 2,5 1
240 5,5 20 2,5 2,5 0,5 8 25 3,5 3,5 1
250 4,5 25 3 3 0,5 11 28 3,5 3,5 1
300 12 40 3 3 0,5 15 40 4,5 4,5 1,5
350 9 27 5 5 1 22 45 5 5 1,5
400 22 40 4,5 4,5 1,5 30 60 6 6 2
500 35 50 6 6 2 45 60 6 6 1,5
600 60 60 6 6 1 60 60 5,5 5,5 –
630 60 60 5 5 0,5 60 60 6 6 –
800 60 60 5 5 – 60 60 7 7 –
1000 60 60 6 6 – 60 60 – – –
At special request can be delivered also current transformers with values of sec-
ondary current different these given in the table above (e.g. 2 a or 4,3 A) and
current transformers for frequency 60 Hz.

Overal dimensions
KOKM 1 EB version 01 KOKM 1 EB version 02
74

60

77
56
14,5

19
32

72
0,5°

Æ
70
205
170

Æ72

~5m
M6
70

70

56 100
A 80
100 128 M6
B
128

58

40 2=S2
1=S1
M6
40

12

24,5

M5 M3

8 56 80
KOKM 1 EB ... A B

ABB 23
KOKM 1 EB version 03

ok. 5000
74

max 6
32
90

0,5°
170

Æ72
70
M6

A
KOKM 1 EB 8 ver. 1 100 18 156 180
B
128
16 136 160
14 116 140
3S
12 96 120
2S
10 76 100
130
90

1S
8 56 80
50

KOKM 1 EB ... A B

KOKM 06 NN – is the indoor, cable, low voltage current transformer in resin


insulation. Transformers of KOKM type are suitable for measurement of phase
currents in low voltage switchgears. As the primary conductor is used the non-
insulated busbar or the low voltage cable. Current transformers of KOKM series
can be also used for measurement of the phase current at voltages even higher
then 0,72 kV, if the insulation of the high voltage primary conductor fulfils the
equirements of elevant standards elating to the working voltage.
Technical data:
Type ............................................................................................... KOKM 06 NN
Maximum number of windings .......................................................................... 1
Level of insulation .................................................................................... 0,6/3/-
Highest permissible voltage of the current transformer Ur ...................... 0,72 kV
Rating test voltage of insulation (50 Hz, 1 min Up) ....................................... 3 kV
Rating frequency ....................................................................................... 50 Hz
Rating thermal current ............................................................................ 1,2 x Ipn
Short-time withstand thermal current Ith, 1s ............................................. 60 x Ipn
Rating peak current Idyn ........................................................................... 2,5 x Ith
Working temperature range ................................................................ -5...+40°C
Conformity with standards - PN-EN, EN, VDE, ANSI, BS, AS, CAN
Example of an order:
In the order shall be specified: type, ratio, load, class and number of pieces,
for example:
KOKM 06 NN; 12 150/1 A/A, Ith = 60 x Ipn,1 VA 10P10 - 3 pieces

24 ABB
Table for selecting current transformers KOKM 06 NN
Maximum permissible load [VA]
Primary Secondary current Isn = 1 [A] Secondary current Isn = 5 [A]
Current Measurement class Protection class Measurement class Protection class
Ipn [A] FS Fa FS Fa
0,5 1 10P10 10P20 5P10 5P20 0,5 1 10P10 10P20 5P10 5P20
50 – – 3,5 1,5 – – – – 3 1 – –
60 – – 4 2 – – – – 3,5 1,5 – –
70 – – 5 2,5 – – – – 4,5 1,5 – –
75 – – 5,5 2,5 – – – – 5 2 – –
100 – – 7 3,5 7 1 – – 6 2,5 6 1
110 – – 7,5 4 7,5 1,5 – – 7 3 7 1,5
120 – – 8 4 8 4 – – 7 2,5 7 2,5
140 – – 10 5 10 5 – – 9 3,5 9 3,5
150 – – 10 5 10 5 – – 9 4 9 4
200 – 8 14 7 14 7 – 9 13 5,5 13 5,5
240 – 15 17 8,5 17 8,5 – 16 15 6,5 15 6,5
250 – 19 18 9 18 9 – 19 16 7 16 7
300 – 31 21 10 21 10 – 31 20 8 20 8
350 0,5 50 25 12 25 12 – 50 22 10 22 10
400 15 60 28 13 28 13 15 55 25 11 25 11
500 35 90 34 16 34 16 35 60 31 14 31 14
600 60 90 41 17 41 17 60 90 38 15 38 15
630 60 90 42 18 42 18 60 90 39 16 39 16
800 90 90 52 23 52 23 90 90 49 21 49 21
1000 90 90 66 28 66 28 90 90 63 26 63 26
1200 90 90 80 34 80 34 90 90 77 32 77 32
1250 90 90 82 35 82 35 90 90 79 33 79 33
1500 90 90 90 40 90 40 90 90 90 40 90 40
At special equest can be delivered also current transformers with values of sec-
ondary current different these given in the table above (e.g. 2 a or 4,3A) and
curent transformers for frequency 60 Hz.

KOKM 1 NN
95.5
M5 69
A 26.5
13
22
60

10
420
310

KOKM 1 NN 12
15
55

15
65
2 x Messingrohr 12x1,5
235

30
12 120
9 90
0.5

6 60
∅2

KOKM 06 NN ... A

ABB 25
KOKM 06 LM – is the indoor, cable, low voltage current transformer in resin
insulation. Transformers of KOKM type are suitable fo measurement of phase
currents in low voltage switchgears. As the primary conductor is used the non-
insulated busbar or the low voltage cable. Current transformers of KOKM series
can be also used for measurement of the phase current at voltages even higher
then 0,72 kV, if the insulation of the high voltage primary conductor fulfils the
equirements of elevant standards relating to the working voltage.
Technical data:
Type ............................................................................................... KOKM 06 LM
Maximum number of windings .......................................................................... 1
Level of insulation .................................................................................... 0,6/3/-
Highest permissible voltage of the current transformer Ur ...................... 0,72 kV
Rating test voltage of insulation (50 Hz, 1 min Up) ....................................... 3 kV
Rating frequency ....................................................................................... 50 Hz
Rating thermal current ............................................................................ 1,2 x Ipn
Short-time withstand thermal current Ith, 1s ............................................. 60 x Ipn
Rating peak current Idyn ........................................................................... 2,5 x Ith
Working temperature range ................................................................ -5...+40°C
Conformity with standards - PN-EN, EN, VDE, ANSI, BS, AS, CAN

Example of an order:
In the order shall be specified: type, ratio, load, class and number of pieces,
for example:
KOKM 06 LM 12 150/1 A/A, Ith = 60 x Ipn, 1 VA 10P10 - 3 pieces
Table for selecting current transformers KOKM 06 LM

Maximum permissible load [VA]


Primary Secondary current Isn = 1 [A] Secondary current Isn = 5 [A]
Current Measurement class Protection class Measurement class Protection class
Ipn [A] FS Fa FS Fa
0,5 1 10P10 10P20 5P10 5P20 0,5 1 10P10 10P20 5P10 5P20
50 – – 3,5 1,5 – – – – 3 1 – –
60 – – 3,5 1,5 – – – – 3,5 1,5 – –
70 – – 5 2,5 – – – – 4,5 1,5 – –
75 – – 5 2,5 5 – – – 5 2 – –
100 – – 7 3,5 5 1,5 – – 6 2,5 6 1,5
110 – – 8 4 8 3,5 – – 7 3 7 2,5
120 – – 8 4 8 4 – – 7 3 7 3
140 – – 10 5 10 5 – – 9 3,5 9 3,5
150 – – 11 5 11 5 – – 9 4 9 4
200 – 11 13 7 13 7 – 11 13 5,5 13 5,5
240 – 20 16 8,5 16 8,5 – 20 15 6,5 15 6,5
250 – 23 18 9 18 9 – 23 16 7 16 7
300 – 35 21 10 21 10 – 35 20 8 20 8
350 12 55 25 12 25 12 12 55 22 10 22 10
400 20 60 28 13 28 13 20 60 25 11 25 11
500 40 90 34 16 34 16 40 90 31 14 31 14
600 60 90 41 17 47 17 60 90 38 15 38 15
630 60 90 42 18 42 18 60 90 39 16 39 16
800 90 90 52 23 52 23 90 90 49 21 49 21
1000 90 90 66 28 66 28 90 90 63 23 63 23
1200 90 90 80 34 80 34 90 90 77 32 77 32
1250 90 90 82 35 82 35 90 90 79 33 79 33
1500 90 90 90 40 90 40 90 90 90 40 90 40

26 ABB
KOKM 1 LM
95.5

A M5 69
26.5

17
22

400
280
130

KOKM 1 LM 12
15
55

65 15
210 2 x Messingrohr 12x1,5

30
12 120
9 90
.5
∅20

6 60
KOKM 06 LM ... A

KOKM 1LH – is the indoor, cable, low voltage current transformer in resin insula-
tion. Transformers of KOKM type are suitable for measurement of phase currents
in low voltage switchgears. As the primary conductor is used the non-insulated
busbar or the low voltage cable. Current transfo mers of KOKM series can be
also used for measurement of the phase current at voltages even higher then 1,2
kV, if the insulation of the high voltage primary conductor fulfils the equirements
of elevant standards relating to the working voltage.
Technical data:
Type ................................................................................................ KOKM 06 LH
Maximum number of windings .......................................................................... 1
Level of insulation ....................................................................................... 1/6/-
Highest permissible voltage of the current transformer Ur ........................ 1,2 kV
Rating test voltage of insulation (50 Hz, 1 min Up) ....................................... 6 kV
Rating frequency ....................................................................................... 50 Hz
Rating thermal current ............................................................................ 1,2 x Ipn
Short-time withstand thermal current Ith, 1s ............................................. 60 x Ipn
Rating peak current Idyn ........................................................................... 2,5 x Ith
Working temperature range ................................................................ -5...+40°C
Conformity with standards - PN-EN, EN, VDE, ANSI, BS, AS, CAN
Example of an order:
In the order shall be specified: type, ratio, Ith, load, class and number of pieces,
for example:
KOKM 1 LH 12 150/1 A/A, Ith = 60 x Ipn, 1 VA 10P10 - 3 pieces

ABB 27
Table for selecting current transformers KOKM 06 LH
Maximum permissible load [VA]
Primary Secondary current Isn = 1 [A] Secondary current Isn = 5 [A]
Current Measurement class Protection class Measurement class Protection class
Ipn [A] FS Fa FS Fa
0,5 1 10P10 10P20 5P10 5P20 0,5 1 10P10 10P20 5P10 5P20
50 – – 2 1 0,5 0,5 – – 1,5 1 0,5 0,5
60 – – 2 1 0,5 0,5 – – 2 1 1 0,5
70 – – 2,5 1 1,5 1 – – 2,5 1 1,5 1
75 – – 2,5 1 1,5 1 – – 2,5 1,5 2 1
100 – 1,5 3,5 1,5 3,5 1,5 – 1,5 3 1,5 3 1,5
110 – 3 4 1,5 4 1,5 – 2,5 3,5 1,5 3,5 1,5
120 – 3,5 4 1,5 4 1,5 – 3,5 3,5 1,5 3,5 1,5
140 – 6 5 1,5 5 2 – 7,5 4,5 2 4,5 2
150 – 8,5 5,5 2 5,5 2 – 8,5 5 2 5 2
200 4 20 7,5 2 7,5 3 2,5 11 7 2,5 7 2,5
240 9 30 8,5 3,5 8,5 3,5 9 29 8,5 3 8,5 3
250 10 32 9 3,5 9 3,5 10 33 9 3,5 9 3,5
300 17 50 11 4 11 4 19 50 10 4,5 10 4,5
350 29 60 12 4,5 12 4,5 29 60 12 5,5 12 5,5
400 60 90 12 3 12 3 39 60 14 6 14 6
500 60 90 15 4 15 4 50 90 18 8 18 8
600 60 90 18 5,5 18 5,5 60 90 21 8,5 21 8,5
630 60 90 19 5,5 19 5,5 60 90 21 8,5 21 8,5
800 90 90 20 5,5 20 5,5 90 90 26 9 26 9
1000 90 90 26 7 26 7 90 90 27 5,5 27 5,5
1200 90 90 31 8,5 31 8,5 90 90 30 6 30 6
1250 90 90 31 8 31 8 90 90 32 6,5 32 6,5
At special request can be delivered also current transformers with values of sec-
ondary current different these given in the table above (e.g. 2 a or 4,3A) and
current transformers for frequency 60 Hz.

KOKM 1 LH version 01 KOKM 1 LH version 02


126
60 126
70
14.5

19

26
37
37

90

30
Æ1
235
235

Æ130
117,5

M8
117.5

Æ11
Æ11 M8
37
37

10

90
10

90 126 B
126 B 180 A
180 A 200
200 200

200

58 40

40
II II
37
31

II II
30,5
40

12

24,5

12 120 90 12 120 90
M5 M5
M5 M3
9 90 60 9 90 60
6 60 30 6 60 30
KOKM 1 LH ... A B KOKM 1 LH ... A B

28 ABB
KOKM 1 NJ – is the indoor,cable, low voltage current transformer in resin insula-
tion. T ansformers of KOKM type are suitable for measurement of phase currents
in low voltage switchgears. As the primary conductor is used the non-insulated
busbar or the low voltage cable. Current transformers of KOKM series can be
also used for measurement of the phase current at voltages even higher then 1,2
kV, if the insulation of the high voltage primary conductor fulfils the equirements
of elevant standards elating to the working voltage.
Technical data:
Type .................................................................................................. KOKM 1 NJ
Maximum number of windings .......................................................................... 1
Level of insulation .................................................................................... 0,6/3/-
Highest permissible voltage of the current transformer Ur ........................ 1,2 kV
Rating test voltage of insulation (50 Hz, 1 min Up) ....................................... 6 kV
Rating frequency ....................................................................................... 50 Hz
Rating thermal current ............................................................................ 1,2 x Ipn
Short-time withstand thermal current Ith, 1s ............................................. 60 x Ipn
Rating peak current Idyn ........................................................................... 2,5 x Ith KOKM 1 NJ 8 ver. 1
Working temperature range ................................................................ -5...+40°C
Conformity with standards - PN-EN, EN, VDE, ANSI, BS, AS, CAN
Example of an order:
In the order shall be specified: type, ratio, Ith, load, class and number of pieces,
for example:
KOKM 1 NJ 12 150/1 A/A, Ith = 60 x Ipn, 1 VA 10P10 - 3 pieces
Table for selecting current transformers KOKM 1 NJ
Maximum permissible load [VA]
Primary Secondary current Isn = 1 [A] Secondary current Isn = 5 [A]
Current Measurement class Protection class Measurement class Protection class
Ipn [A] FS Fa FS Fa
0,5 1 10P10 10P20 5P10 5P20 0,5 1 10P10 10P20 5P10 5P20
50 – – 2 1 0,5 0,5 – – 2 0,5 0,5 0,5
60 – – 2,5 1 0,5 1 – – 2,5 1,5 0,5 0,5
70 – – 3 1,5 1,5 1,5 – – 3 1,5 1 1
75 – – 3,5 1,5 2 1,5 – – 3 1,5 1,5 1
100 – 0,5 4,5 2 4 2 – 0,5 4 1,5 4 1,5
110 – 2 5 2,5 4,5 2,5 – 1,5 4,5 2 4,5 2
120 – 3,5 5,5 2,5 5,5 2,5 – 3 5 2 5 2
140 – 5 6,5 3 6,5 3 – 4,5 6 2,5 6 2,5
150 – 6,5 7 3 7 3 – 5 6,5 3 6,5 3
200 1,5 8 8 3,5 8 3,5 1 9 9 4 9 4
240 4,5 13,5 9,5 4,5 9,5 4,5 4,5 14 10 5 10 5
250 5 15 10 4,5 10 4,5 5 15 11 5 11 5
300 9 23 12 5,5 12 5,5 11 26 13 6 13 6
350 18 35 14 6,5 14 6,5 18 32 15 7 15 7
400 29 50 16 7,5 16 7,5 20 40 18 8 18 8
500 35 80 20 9 20 9 30 60 20 10 20 10
600 50 90 24 11 24 11 45 90 25 12 25 12
630 50 90 25 11 25 11 50 90 26 12 26 12
800 60 90 31 14 31 14 90 90 30 13 30 13
1000 90 90 38 16 38 16 90 90 38 14 38 14
1200 90 90 42 18 42 18 60 90 40 13 40 13
1250 90 90 45 18 45 19 60 90 40 12 40 12
At special request can be delivered also current transformers with values of sec-
ondary current different these given in the table above (e.g. 2 a or 4,3A) and
current transformers for frequency 60 Hz.

ABB 29
KOKM 1 NJ version 01 KOKM 1 NJ version 02
105
60 105
70

2
14.5
19

26
55
55
55

247
Æ1

240
Æ155

120
120
M8
Æ11 M8 Æ11

55
55

10
10

90 90 B
B
A 105 A
105
215
215
235
235
235
235

93
40
58
40

31

37
55
30.5
40

12

24.5

M5 M5
M5 M3

12 120 90 123
12 120 90
9 90 60 93
9 90 60
6 60 30 63
6 60 30
KOKM 1 NJ ... A B C
KOKM 1 NJ ... A B

KOKM 1 ED
8

ok 5000

74
max 6
32
90

0,5°
170

Æ72
70

M6

A
120
B
148
130
90
50

30 ABB
Current Transformers
type KOLT
For Oil-immersed Transformers

Dimensional drawing

1S... 2S... ...S... 1S5 1S4 1S3 1S2 1S1


D
Rating plate

Rating plate

Rating plate

ÆA
ÆB

P1

ABB 31
Technical data
Primary current range Ipn [A] ..................................................... 100A to 2 500A
Rated secondary current Isn [A] ........................................................... 1A or 5A
Insulation level .................................................................................... 0.72 / 3 / -
Range of rated output Sn [VA] ..................................................... 1VA to 90VA
Number of windings ................................................................................... 1 to 4
Conformity with Standards IEC, PN-EN, SEV, VDE, ANSI, BS, CAN, CSA, GOST
Accuracy class acc. to IEC .................... 0.2s; 0.5s; 0.2; 0.5; 1; 3; 5; 5P; 10P; PX
FS ................................................................................................................ 5; 10
ALF ....................................................................................... 5; 10; 15; 20; 25; 30
Rated frequency f [Hz] ............................................................................... 50, 60
Short-time withstand thermal current, 1s Ith [A] ................... 100xIpn max. 100kA
Peak withstand current Idyn [A] ........................................... 2,5xIth max. 250kA
Insulation class acc. to IEC .............................................................................. B
Min. inside diameter f A [mm] ................. min. 30 mm depending on parameters
Max. outside diameter f B [mm] .......... max. 900 mm depending on parameters
Height h [mm] ...................................... max. 900 mm depending on parameters
KOLT 072 115 x 235 x 60 Length of leads D [mm] ......................... 1m, other length at the client’s request
Transformers with other dimensions and parameters are available at the client’s
request.
1. Versions available
- single phase
- with one or several windings
- with one or several tappings
- insulation – cotton tape + impregnating varnish
- without housing
- without primary winding
2. Application
The current transformers type KOLT are suitable for mounting inside power trans-
formers and are suitable for operating immersed in oil, under conditions of mod-
erate and tropical climate. These current transformers are designed for supply-
ing measurement and protection circuits of power systems operating under rated
frequency of 50 Hz.
3. Marking
Each current transformer is fitted with rating plate in accordance with IEC 60044-
1 Standard. Values of rated voltage and rated power frequency test voltage of
insulation – stated on the rating plate – relate to the insulation of secondary
windings. Primary and secondary terminals are directly marked on the current
transformer.
4. Description
Current transformers type KOLT have neither housing nor primary winding. Un-
der operating conditions the primary winding is the power transformer’s bushing
insulator, which is at the same time the main insulation of the current trans-
former. The secondary windings are evenly wound on the circumference of the
toroidal core.
Secondary winding insulation is made of polyester tape (torlen).
Current transformers with the weight of approx. 100kg or more consist of several
parts – to facilitate both transport and installation. Each separate part contains
the following information: a serial number which coincides with the one stated on
the rating plate as well as markings of primary and secondary winding terminals.
5. Transport
KOLT 072 230x260x45
While transported current transformers must be protected against humidity and
heavy shocks. Current transformers with the weight exceeding 50kg and current
transformers especially sensitive to shocks are transported on wooden pallets.

32 ABB
6. Installation
During installation of current transformers observe the following instructions:
- Secondary winding marked 1S1- 1S2 should be placed on the top;
- Pay special attention to keep the same polarization for all parts of the current
transformer (P1 – P2 – P1 – P2 markings); .
- Avoid shocks.
7. Compliance with Standards
Current transformers meet the requirements of the following standards:
IEC 60044-1
At the client’s request we manufacture current transformers meeting the require-
ments of SEV, VDE, ANSI, BS, CAN, CSA, GOST Standards
8. Ordering
The order must contain the following:
- name and type of current transformer
- rated primary current / rated secondary current Ipn/Isn [A]
- short-time thermal current, 1 s Ith [kA]
- rated output power and accuracy class of each winding Sn [VA]
- limit transformer dimensions (min. inside diameter, max. outside diameter,
max. height)
- length of leads
- standard
- quantities.
9. Order example
Current transformer type KOLT
1200/5/1/1 A
Ith = 72 kA
I. 15VA , class 0.5 FS10
II. 60VA , class 5P15
III. 60VA , class 5P20
min. inside diameter A = ∅150 mm
max. outside diameter B = ∅300 mm
max. height h = 200 mm
length of leads 1,5 m
Standard IEC 60044-1
quantity – 9 pcs.