Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Proceedings of The Thirteenth (2003) International Offshore and Polar Engineering Conference

Honolulu, Hawaii, USA, May 25 –30, 2003


Copyright © 2003 by The International Society of Offshore and Polar Engineers
ISBN 1 –880653 -60 –5 (Set); ISSN 1098 –6189 (Set)

AC Flashover Performance of Artificial Iced and Polluted Insulators


At High Altitude Districts
Lichun Shu, Xingliang Jiang, Caixin Sun, Yuchun Tian Masoud Farzaneh, Yu Li, Jianhui Zhang
The Key Lab. of High Voltage Eng. and Electrical New Technology NSERC/Hydro-Québec/QUAC Industrial Chair on
of Ministry of Education, Chongqing University Atmospheric Icing of Power Network Equipment (CIGELE)
Chongqing, P. R. China Université du Québec à Chcoutimi Chicoutimi, Québec, Canada

ABSTRACT This paper presents the effects of several environmental flashover performance of iced insulators under the simultaneous
parameters such as ice weight, atmospheric pressure and pollution presence of low atmospheric pressure and pollutants (Zhang, 1991; Shu,
severity on the flashover performance of two types of short string Sun, Zhang, and Gu, 1991; Li, Farzaneh and Zhang, 1998; Farzaneh, Li,
suspension insulators and short post insulator. The relationship between Fikke and Mercure, 1999; Shu, Farzaneh, Li and Sima, 2001).
the critical flashover voltage of the insulators and insulator profile,
amount of ice built up, pollution severity and atmospheric pressure was In order to clarify some of the above questions and to acquire a better
determined. Moreover, the mathematical expression of minimum idea of the effects of air pressure and contamination on the critical
flashover voltage of a short string of the suspension insulator units was flashover voltage of ice-covered insulators, a joined investigation
given. The results obtained are helpful for the insulation design of between the University of Quebec in Chicoutimi, Canada, and
transmission lines located at icing and high altitudes regions. Chongqing University in China was carried out. In this study, the
flashover voltages of several types of insulators were determined under
KEY WORDS: Icing; atmospheric pressure; pollution; insulator; the simultaneous presence of the pollution, ice and low air pressure.
flashover; high altitudes. And some experimental results are provided in this paper, which could
be used as a reference for the insulation design of power systems under
INTRODUCTION such environmental conditions.

One of the most serious problems associated with ice and pollution EXPERIMENTAL FACILITIES AND PROCEDURES
accreted on power transmission lines as well as low atmospheric
pressure is the loss in electrical performance of outdoor insulators. The For Short Porcelain Suspension Insulator Strings
presence of ice together with contamination and low air pressure
sometimes produce insulator flashovers and consequent power outages, In the High Voltage Laboratory of Chongqing University in China,
which have been reported from several countries (Cherney, 1980; several types of porcelain insulators were tested in a small cylindrical
Charneski, Gaibrois and Whitney, 1982; Farzaneh and Kiernicki, 1995; climate chamber, 3.8 m in length and 2 m in diameter, where the air
Su, Jia, Wang, and Li, 1999). temperature can be adjusted between 20 and –40 °C and the air pressure
between 101.3 and 34.7 kPa, respectively. The wind velocity is about 3
This problem has allured attention of many researchers and, m/s. The short strings of three units with three types of suspension
consequently, a number of studies have been carried out separately on insulators (Type A and C in Tab. 1) were used in the tests. The profile
the electrical strength of insulators under icing (Fujimura, Naito, and dimension of these insulators are shown in Tab.1. Insulators of type
Hasegara and Kawaguchi, 1979; Phan and Matsuo, 1983; Matsuda, A and type C were used for pre-contaminated flashover tests, i.e., the
Komuro and Takasu, 1991; Farzaneh and Drapeau, 1995; Wu, Halsan insulators string was firstly contaminated with a layer of mixture of salt
and Fikke, 1996; Farzaneh, Zhang and Chen, 1997; Farzaneh and and kieselguhr. In this case, several salt deposit density (SDD) levels
Kiernicki, 1997; Farzaneh and Zhang, 2000), pollution (Zhang, 1991; were chosen as 0.015, 0.03, 0.05 and 0.10mg.cm-2. When the pollution
Rizk, 1995) or/and low atmospheric pressure (Fryxell and Schei, 1996; layer was dry, the pre-contaminated insulator string was vertically
Meier and Niggli, 1968; Kawamura, Ishii, Akbar and Nagai, 1982; suspended in the climate chamber and was covered with an ice layer at
Kawamura, Ishii, Akbar and Nagai, 1982; Rudakova and Tikhodeev, an air temperature of –12°C. Insulator type B was used for polluted ice
1989; Guan and Huang, 1994) conditions in several countries. However, tests, i.e., NaCl was added directly to the water used to form the ice to
in spite of these efforts, some questions on this flashover phenomenon simulate the pollution. In this case, the conductivity of water, σ, had
on insulators has never been answered because it is complicated and is values of 300 and 630 µS.cm-1, respectively. For both kinds of tests, the
influenced by many factors and parameters such as the insulator profile, ice density covered on the insulators was about 0.8∼0.9 g.cm-3. The air
the test method, the atmospheric pressure, the pollution severity and the pressure was adjusted between 98.5 and 62.4 kPa, corresponding to the
ice type and quantity. Particularly, very little study has been done on the altitude varying from 232 to 4000 m.

403
The AC power supply used consists of a 1000 kVA regulator and a 900 cylindrical shape, a diameter of 610 mm and a height of 760 mm, was
kVA/150 kV transformer with a maximum short-circuit current of about constructed to simulate low air pressure at high altitude. The evacuated
30 A. In order to determine the minimum flashover voltage of the chamber was presented in the previous work (Li, Farzaneh and Zhang,
insulator string during melting period, the “U” curve method was used 1998; Farzaneh, Li, Fikke and Mercure, 1999). Air pressure in the
(Shu, Sun, Zhang, and Gu, 1991), which can be summarized as follows: chamber can be adjusted between 101.3 and 30 kPa, corresponding to
once the ice layer was formed on insulators, the airtight door of the altitudes varying from 0 to 9,000 m respectively. The chamber is
climate chamber was opened to rise the air temperature for a certain transparent to make possible visual observation and photography. In
degrees and make the ice melt. Then, the door was closed again. The air order to control the ambient temperature, the evacuated chamber is
pressure was then dropped to a pre-determined value and a voltage was placed in a climate room (Farzaneh and Drapeau, 1995). The artificial
applied immediately to the insulator string and increased uniformly at a ice with a radial thickness of 15 mm, measured on a rotating monitoring
rate of 3 kV.s-1 until a flashover occurred. These steps were repeated cylinder, was accreted on this post insulator placed in the climate room.
every several minutes until a minimum flashover voltage appeared Once the ice layer was formed, an air gap of 1 cm was made near the
which was considered as the critical flashover voltage of the insulator upper electrode by cutting out a small fragment of ice. This air gap
string under the experimental conditions. could simulate the free ice zones on actual high voltage insulators
created by the heating effect of partial arcs, rise in air temperature
Tab. 1. The porcelain insulators used to perform the flashover tests. and/or ice falling during or after ice accretion (Farzaneh and Drapeau,
1995). The AC high voltage system used consists of a 240kVA, 120kV
Dimensions of insulators, mm transformer and a 240kVA regulator. The overall short-circuit current of
Insulator configuration the HV system is about 28 A at maximum operating voltage of 120 kV.
Shed Unit Leakage In order to determine the maximum withstand (VWS) and minimum
diameter spacing distance flashover (VMF) voltages of the insulator tested, a method based on and
developed from the method described in the standard IEC 507 was used.
This method was described in the previous studies (Farzaneh and
Drapeau, 1995; Li, Farzaneh and Zhang, 1998).
255 146 295
EXPERIMENTAL RESULTS AND DISCUSSION

Type A Influence of Insulator Profile

The obtained results show that the anti-pollution insulator (Type C) has
a short shed space and is more rapidly bridged by icicles than the
standard insulator (Type A). Therefore, the flashover is easier to occur
255 155 305 on this kind of insulator (see Tab. 2). As presented in Tab. 2, the rate of
decrease in minimum flashover voltage of anti-pollution insulator
becomes more significant as the ice weight decrease. The lower the
Type B atmospheric pressure, the more obvious the effect of insulator profiles.

Tab. 2. Comparison of minimum flashover voltage between the short


string of 3 suspension standard insulators (Type A) and anti-pollution
insulators (Type C).

255 146 400 ∆VMF1


Ice weight w
SDD (mg/cm2) P=98.5 kPa P=89.7 kPa
(kg)
(H=232m) (H=1000m)
0.5 10.7% 13.1%
Type C: Anti-pollution 0.015
2.0 2.2% 8.5%
insulator
0.5 9.4% 10.5%
0.03
2.0 1.9% 7.2%
0.5 9.0% 9.8%
0.10
2.0 4.7% 7.0%
VMF , insulator A − VMF , insulator C
where ∆VMF1 = .
155 240 670 VMF , insulator A

Influence of Ice Weight

The amount of ice built up on the insulators has an obvious influence on


Type D: Post insulator the minimum flashover voltage of tested insulators. It may be noted that
the minimum flashover voltage, VMF, of three types of ice-covered
For Short Porcelain Post Insulator suspension insulators tested decreases with an increase of the ice weight,
and then present a tendency of saturation. Tab. 3 shows the influence of
In the CIGELE Laboratories at the University of Quebec in Chicoutimi, the ice weight on the minimum flashover voltage of insulator type A.
Canada, a series of tests were carried out in an evacuated chamber using
a short post insulator (Type D in Tab. 1). This chamber, having a

404
Tab. 3. Influence of the ice weight for the short string of 3 suspension conductivity increases. This variation tendency of exponent m may be
insulator units (Type A) due to the fact that the arc sometimes propagates in air instead of along
ice surface. During the flashover tests, it was observed that the arc
∆VMF2 propagation from one electrode to another might occur in two different
SDD Ice weight w
(mg.cm-2) (kg) P=98.5 kPa P=89.7 kPa ways: along the ice surface or in the air. Sometimes both situations
(H=232m) (H=1000m) could occur on one arc, i.e., part of the arc along the ice surface and the
1.0 9.4% 9.3% other part in air. When the arc propagates in air, the arc length increases
0.015 2.0 17.9% 17.6% and, consequently, the flashover distance is longer resulting in a higher
3.0 22.6% 22.1% flashover voltage. In the present study, it was observed that, for the
1.0 9.9% 10.3% lower SDD or freezing water conductivity, the arc was always
0.03 2.0 19.0% 19.4% propagated along the ice surface at the standard pressure while
3.0 23.8% 24.3% propagated in air at lower atmospheric pressure. This results in a lower
1.0 9.8% 10.0% decrease rate of flashover voltage and, accordingly, in a lower m value.
0.10 2.0 18.6% 19.1% For the higher SDD or freezing water conductivities, the arc always
3.0 23.5% 23.9% propagated in air at standard pressure and all other low air pressure
values. This causes a higher decrease rate of flashover voltage and a
VMF , w=0.5 − VMF , w higher value of exponent m.
where ∆VMF 2 = .
VMF , w=0.5
65
Influence of Air Pressure
60 Insulator type A
The atmospheric pressure is one of the factors that considerably 2
influence the minimum flashover voltage of insulators. The relationship SDD=0.015mg/cm
between the critical flashover voltage of polluted insulators and the air 55

V MF (kV)
pressure is normally expressed by the following equation (Mercure,
1989; Sundararajan and Nowlin, 1996)
w (kg)
50
m 1.0
V  P 
(1) 45
= 
V0  P0 

2.0
40
where P0 and P are the standard pressure (101.3 kPa) and the pressure at
3.0
high altitude; V0 and V are the critical flashover voltages of insulators
corresponding to air pressure P0 and P, respectively; the exponent m is a 35
constant the value of which characterizes the influence of air pressure 60 70 80 90 100
on the critical flashover voltage of insulators and depends on several P (kPa)
factors and parameters including insulator profile, voltage polarity and
pollution severity(Huang, Guan and Zhang, 1993; Rizk and Rezazada, (a)
1996).

Figs.1~2 show the minimum flashover voltages of insulator strings of 55


types A and B, respectively, as a function of the atmospheric pressure.
Fig. 3 presents the minimum flashover voltage of the short post 50 Insulator type A
insulator as a function of atmospheric pressure for various freezing
water conductivities measured at 20°C. From the results presented in SDD=0.10mg/cm
2
Figs.1~2, it may be noted that the minimum AC flashover voltage, VMF, 45
V MF (kV)

of ice-covered suspension insulators tested decreases with a reduction


in atmospheric pressure. The decrease rate in minimum flashover 40
voltage of insulator type A, insulator type B and insulator type D w (kg)
becomes more significant as SDD or σ increase (see Tab.4). As
mentioned in the introduction, the influence of atmospheric pressure on 35 1.0
the critical flashover voltage of polluted and ice-covered insulators can
be evaluated from Eq.1. In this equation, exponent m characterizes the 30 2.0
effect of atmospheric pressure on the flashover voltage of insulators and
constitutes an important parameter for the insulation design of 3.0
transmission lines located at high altitudes.
25
60 70 80 90 100
Using the regression analysis method (i.e., the least square method) to P (kPa)
the test results obtained in the present study, the values of exponent m
as a function of ice amount, SDD and freezing water conductivity were (b)
determined as presented in Tab. 5.
Fig. 1. Minimum AC flashover voltage of a string of three
From the above results, it may be noted that the value of exponent m for suspension insulator units (Type A) as a function of
three types of insulator increases with SDD or freezing water atmospheric pressure.

405
Tab. 4. Comparison of minimum flashover voltage between standard
50
pressure and low air pressure.
Ice weight
Insulator type B SDD (mg/cm2) ∆VMF3
45 σ=300 µS /cm w (kg)
Short string of 3 0.015 14.2%
1.0
suspension 0.10 18.7%
40
V MF (kV)

insulator units 0.015 17.9%


σ=630 µS /cm 2.0
(Type A) 0.10 23.6%
35 0.015 19.8%
3.0
0.10 25.9%
Ice Weight
30 Ice weight, w=2.2kg σ (µS/cm) ∆VMF4
Short string of 3 w (kg)
suspension 300 16.8%
2.2
25 insulator units 630 28.4%
50 60 70 80 90 100 110 120 (Type B) 300 17.1%
3.0
P (kPa) 630 26.9%
Ice
(a) thickness ε σ (µS/cm) ∆VMF5
Short post
45 insulator (mm)
σ=300 µS /cm (Type D) 80 29.0%
Insulator type B 15
250 33.0%
40 V MF , P =98.5 − V MF , P = 70.4
where ∆V ,
MF 3 =
V MF , P =98.5
V MF (kV)

σ=630 µS /cm V − VMF , P = 62.4 , and


35 ∆VMF 4 = MF , P =98.5
VMF , P =98.5
VMF , P =101.3 − VMF , P = 45.0 .
∆VMF 5 =
30 VMF , P =101.3
Ice weight, w=3.0kg

25 Tab. 5. Typical values of the exponent m.


50 60 70 80 90 100 110 120
Ice weight W (kg) SDD (mg.cm-2) Exponent m
P (kPa)
0.015 0.42
(b) Short string of 1.0
0.10 0.53
3 suspension
Fig.2. Minimum AC flashover voltage of a string of three 0.015 0.53
insulator units 2.0
suspension insulator units (Type B) as a function of 0.10 0.60
(Type A)
atmospheric pressure. 0.015 0.58
3.0
0.10 0.63
Ice weight w (mm) σ (µS.cm-1) Exponent m
Short string of
300 0.40
35 3 suspension 2.2
630 0.72
insulator units
σ=80 µS /cm 300 0.42
30 (Type B) 3.0
630 0.70
25 Ice thickness ε
Short post σ (µS.cm-1) Exponent m
V MF (kV)

(mm)
20 insulator
σ=250 µS /cm 80 0.40
(Type D) 15
250 0.53
15
Insulator type D
10
Ice thickness, ε=15 mm Influence of Pollution Severity
5 From the test results, it can be seen that the pre-contamination layer
30 40 50 60 70 80 90 100 110 120 130 reduces the flashover voltage of insulators under icing conditions. The
higher the pollution levels, the lower the minimum flashover voltage of
P (kPa) ice-covered insulators (see Tab.6). Also, Tab. 6 show that the decrease
in minimum AC flashover voltage with the increase of SDD or freezing
Fig. 3. Minimum AC flashover voltage of post insulator (Type D) water conductivity is more significant at high altitude than at sea level
as a function of atmospheric pressure. (standard pressure).

406
Tab. 6 Typical values of reduction in minimum flashover voltage as The coefficient α depends on the pollution flashover voltage (VF, kV) of
pollution severity increase. the insulators under ice free condition; the exponent β is a constant
Ice weight w related to the pre-contamination severity. It can be obtained as β=0.143
Pressure P (kPa) ∆VMF6
(kg) from the statistical calculation of test results presented for various SDD
70.4 27.9% at standard air pressure. By definition, the coefficient α is
Short string 1.0 89.7 24.2%
of 3
98.5 23.9% α = kVF
suspension
70.4 29.5%
insulator
2.0 89.7 25.0% where k is a constant. Using the regression analysis method, the k can be
units
(Type A) 98.5 24.2% calculated approximately as k=1.31. Therefore, Eq.5 may be written in
70.4 30.2% the form
3.0 89.7 25.4%
98.5 27.9% V0 = 1.31VF ⋅ w−0.143 (6)
Short string Ice weight w
Pressure P (kPa) ∆VMF7
of 3 (mm)
At standard pressure, the relation between the pollution flashover
suspension 62.4 20.8%
2.2 voltage of insulators, VF, and SDD can normally be characterized by
insulator 98.5 8.5%
units 62.4 20.2%
(Type B) 3.0
98.5 9.4% VF = γ ⋅ S − λ (7)
Ice thickness
Short post Pressure P (kPa) ∆VMF8 where S is the SDD (mg.cm-2) of pollution insulators (ice free); the
ε (mm)
insulator coefficient γ and exponent λ are constants, and can be obtained from the
45.0 27.0%
(Type D) 15 statistical analysis on the obtained results. Thus
101.3 23.0%

VMF , ESDD = 0.015 − VMF , ESDD = 0.1 , VF = 16.72 ⋅ S −0.246 (8)


where ∆V
MF 6 =
VMF , ESDD = 0.015
Finally, combining Eqs.4, 6 and 8 leads to Eq.9, i.e., the minimum
V − VMF ,σ = 630 , and
∆VMF 7 = MF ,σ =300 flashover voltage of short strings of 3 pre-contaminated insulators (Type
VMF ,σ =300 A) at icing and low atmospheric pressure conditions can be calculated
VMF ,σ =80 − VMF ,σ = 250 . by
∆VMF 8 =
VMF ,σ =80
Calculation of Minimum Flashover Voltage at Low Air VMF = 21.9 S −0.246 w−0.143 (1 - 0.63 ∆P ) (9)
Pressure
Fig. 4 shows the test results as well as the calculated results from
If we define ∆P = ( P0 − P) / P0 , Eq.1 can be rewrite as the Eq.9. In Fig.4, the maximum error between the calculated
results and the experimental results is about 4.5%. At the same
V = V0( 1 − ∆P)m (2) conditions, when SDD equals to 0.015, 0.05 and 0.10 mg.cm-2
respectively, the maximum errors are about 10.7%, 12.3% and
Deploying Eq.2 to Taylor Series and omitting with the high-order terms 13.1%. It can be seen that there is a concordance between the
of ∆P, the above relation becomes minimum flashover voltage calculated with Eq.9 and the test
results obtained in the laboratory.
V = V0( 1 − m ⋅ ∆P ) (3)
80
From Eq.3 it can be found directly that the flashover voltage depends on Insulator type A
the exponent m and decrease as the pressure decrease (i.e., ∆P increase). 70
_____
The larger the m, the more significant the effects of air pressure on V. calculation results
Normally, the dispersity of minimum flashover voltage of insulators is 60 + o * experiment results
V MF (kV)

large due to the effect of many factors. Therefore, for the sake of power
system safety, the maximum value of exponent m is used in engineering
consideration. Accordingly, for the pre-contaminated and ice-covered 50 w (kg)
standard insulators (type A), the effect of air pressure on minimum 1.0
flashover voltage, VMF, may be estimated by 40
2.0
VMF = V0 (1 - 0.63∆P ) (4) 3.0
30 2
SDD=0.03mg/cm
where V0 (kV) is the minimum flashover voltage of insulators at
standard air pressure (sea level), which depends on the ice weight, w 20
(kg), and the pollution severity. The relation between V0 and w may be 60 70 80 90 100
expressed as P (kPa)

V0 = α ⋅ w− β (5) Fig.4 Calculated and test results of the minimum flashover of


short strings of 3 suspension insulator units (Type A).

407
CONCLUSION Fryxell and Schei, (1996) “Influence of high altitude on the flashover
voltage of insulators”, Elteknik, Vol. 9, Sweden, pp. 1-3.
Laboratory investigations for determining AC flashover performance of Fujimura, Naito, Hasegara and Kawaguchi, (1979) “Performance of
three types of insulators covered with artificial ice at low atmospheric insulators covered with snow or ice”, IEEE Trans. on PAS, Vol.
pressure were carried out. This study made it possible to determine the PAS-98, No. 5, 1979, pp. 1621-1631.
relationship between the critical flashover voltage of ice-covered Guan and Huang, (1994) “Discharge performance of different models at
insulators and the pollution as well as the air pressure. Although there is low pressure air”, Proceedings of 4th ICPADM, Brisbane, Australia,
some difference between the laboratory investigations in the University pp. 463-466.
of Quebec in Chicoutimi and in Chongqing University, some common Huang, Guan and Zhang, (1993) “Influence of air pressure on AC
conclusions may be drawn from the obtained results: flashover voltage of polluted post insulators for high altitude
(1) The insulators (Type C) with a short shed space are more rapidly regions”, Proceedings of 8th ISH, Japan, Paper No. 46.01.
bridged by icicles under icing condition than the standard IEC International Standard Publication 507 (1991).“Artificial pollution
insulator and, therefore, are easier to have flashover. tests on high voltage insulators to be used on AC systems” .
(2) Comparing with the standard insulator (Type A), the decrease in Ishii, Shimada, Kawamura and Matsumoto, (1983) “Flashover of
minimum flashover voltage of anti-pollution insulator (Type C), contaminated surface under low atmospheric pressure”, Proceedings
as the atmospheric pressure reduce or the ice weight decrease, is of 4th ISH, Greece, Paper No. 46.02.
more significant. Kawamura, Ishii, Akbar and Nagai, (1982) “Pressure dependence of DC
(3) The minimum flashover voltage, VMF, of three tapes of ice- breakdown of contaminated insulators”, IEEE Trans. on Electrical
covered suspension insulators decreases obviously with an Insulation, Vol. EI-17, No. 1, pp. 39-45.
increase of ice weight, and then present a saturation tendency. Li, Farzaneh and Zhang, (1998) “Critical flashover voltage of short HV
(4) The air pressure has a definite effect on the AC minimum insulator covered with ice at low atmospheric pressure”, Proceedings of
flashover voltage of insulators, VMF, under icing conditions. The International Conference on Power System Technology, Beijing,
lower the atmospheric pressure the lower the VMF. China, pp. 520-523.
(5) The VMF of the tested insulators decreases with the increase in Matsuda, Komuro and Takasu, (1991) “Withstand voltage
SDD or freezing water conductivity, σ. In addition, the reduction characteristics of insulator strings covered with snow or ice”, IEEE
rate of VMF, with a decrease in atmospheric pressure, becomes Trans. on Power Delivery, Vol. 6, pp. 1243-1250.
more significant as SDD or σ increases. The decrease in VMF with Meier and Niggli, (1968) “The influence of snow and ice deposits on
an increase in SDD or σ is more obvious at high altitudes than at super tension transmission line insulator strings with special
sea level. reference to high altitude operation”, Proceedings IEEE Conference,
(6) The value of the exponent m depends on the insulator profile, London, Vol. 44, pp. 386-395.
SDD, σ and the amount of ice accreted. It increases when the Mercure, (1989) “Insulator pollution performance at high altitude:
major trends”, IEEE Trans. on Power Delivery, Vol. 4, pp. 1461-
SDD or σ increases.
1468.
(7) A mathematical expression of minimum flashover voltage of a
Phan and Matsuo, (1983) “Minimum flashover voltage of iced
short string of the suspension insulators (i.e., Type A) was
insulators”, IEEE Trans. Elec. Insulation, Vol. EI-18, pp. 605-618.
obtained and was validated with the experimental results. There is
Rizk, (1995) “Review of the effect of pollution on high-voltage
a concordance between the calculated minimum flashover voltage
insulators and Metal-Oxide arresters”, Proceedings of 9th ISH,
and the experimental results.
Austria, Paper 9003.
Rizk and Rezazada, (1996) “Modeling of altitude effects on AC
REFERENCES flashover of polluted high voltage insulators”, IEEE/PES Winter
Meeting, Paper 96 WM 104-0 PWRD.
Charneski, Gaibrois and Whitney, (1982) “Flashover tests on artificially Rudakova and Tikhodeev, (1989) “Influence of low air pressure on
iced insulators”, IEEE Trans. on PAS, Vol. PAS-101, pp. 2429-2433. flashover voltages of polluted insulators: test data, generalization
Cherney, (1980) “Flashover performance of artificially contaminated attempts and some recommendations”, IEEE Trans. on Power
and iced long-rod transmission line insulators”, IEEE Trans. on PAS, Delivery, Vol. 4, No. 1, pp. 607-613.
Vol. PAS-99, pp. 46-52. Su, Jia, Wang, and Li, (1999) “Artificial rime covering and discharge
Farzaneh and Drapeau, (1995) “Flashover performance of insulators tests of 500 kV insulator strings”, Proceedings of the CSEE, Vol. 19,
covered with artificial ice”, IEEE Transactions on Power Delivery, No. 2, pp. 75-78.
Vol. 10, pp. 1038-1051. Shu, Sun, Zhang, and Gu, (1991) “AC flashover performance of iced
Farzaneh and Kiernicki, (1995) “Flashover problems caused by ice and polluted insulators for high altitude regions”, Proceedings of 7th
build-up on insulators”, IEEE Electrical Insulation Magazine, Vol. ISH, Vol. 4, Germany, pp. 303-306.
11, pp. 5-17. Shu, Farzaneh, Li and Sima, (2001) “AC flashover performance of
Farzaneh and Kiernicki, (1997) “Flashover performance of IEEE polluted insulators covered with artificial ice at low atmospheric
standard insulators under ice conditions”, IEEE Trans. on Power pressure”, Proceedings of IEEE Conference on Electrical Insulation
Delivery, Vol. 12, pp. 1602-1613. and Dielectric Phenomena (CEIDP), Kitchener, Canada, pp.609-612.
Farzaneh, Li, Fikke and Mercure, (1999) “DC flashover of artificial ice- Sundararajan and Nowlin, (1996) “Effect of altitude on the flashover
covered insulators at low atmospheric pressure”, Proceedings of 9th voltage of contaminated insulators”, Proceedings of IEEE CEIDP,
IOPEC, Brest, France, pp. 612-615. San Francisco, USA, pp. 433-436.
Farzaneh and Zhang, (2000) “Modeling of DC discharge on ice surface”, Wu, Halsan and Fikke, (1996) “Artificial ice tests for long insulator
IEE Proceedings – Generation, Transmission and Distribution, Vol. strings”, Proceedings of 7th IWAIS, Chicoutimi, Canada, pp. 67-71.
147, pp. 81-86 Zhang, (1991) “Study on flashover mechanism and affecting factors of
Farzaneh, Zhang and Chen, (1997) “Modeling of the AC arc discharge polluted insulators”, Ph. D Thesis.
on ice surfaces”, IEEE Trans. on Power Delivery, Vol. 12, pp. 325-
338.

408

You might also like