Planning Analysis and Designing of Multi

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

IJSRD - International Journal for Scientific Research & Development| Vol.

6, Issue 09, 2018 | ISSN (online): 2321-0613

Planning, Analysis and Designing of Multi-Speciality Hospital Building


C. Priyanka1 M. Priyanka2 V. Kumaran3
1,2
BE Student 3Assistant Professor
1,2,3
Department of Civil Engineering
1,2,3
Loyola Institute of Technology, India
Abstract— The aim of the project “Planning, Analysis and and displacement along the member indicates variation in
Design of Multi-Speciality Hospital Building” is to develop a different zone using a comparative analysis. The earthquake
multi-speciality hospital building with economical design loads were analysed by equivalent static method with base
using manual design techniques and computer aided design. shear criteria. The G+3 structure was analysed for structure
The project summary report emphasizes the structural stability towards considered forces.
analysis and design finding of hospital building. The main
B. Literature 2
scope of this project is to apply class room knowledge in the
real world designing of a hospital building there building 1) Planning, Analysis & Design of Hospital Building Using
require large and clear area unobstructed by columns. Here Staad Prov8
the hospital building is of four story RCC structure with 300 Dr.Ashok kumar N, Navaneethan M, Naviya B,
no. of beds and capacity of 22500sq.m which is planned using Gopalakrishnan D, Atun RoyChoudhury
AUTOCAD for floor plan and STAAD PRO for analysis. The The study aims at identifying and optimum
multi-speciality hospital building is located in Avadi. The structural shape of building which could withstand the forces
basic requirements of hospital building is taken from): IS under consideration. This study shows that STAAD.Pro is
12433 (part3-2001) and the member are designed using IS more flexible when compared to ETABS software in terms of
456:2000. analysis of structure. The shear force and bending moment
Key words: STAAD PRO, AUTOCAD, Planning, Analysis over each component of building was calculated for different
and Designing combination of loads. Beams and columns were modelled as
frame elements. It represents the strength and deformation
I. INTRODUCTION capacity of members and the properties to be assigned are
cross sectional dimensions, reinforcement details and the type
Hospital is a health care institution providing patient of materials used are determined.
treatment with specialized medical and nursing staff and
medical equipment...The medical facility smaller than a C. Literature 3
hospital is generally called a clinic. Hospital have a range of 1) IJESRT-Design of g+4 Hospital Building for Earthquake
department (e.g: surgery and urgent care) and specialist units Resistant
such as cardiology” J.Sankar, E.V.Raghava Rao, N.Chennakesavulu
Types of hospital: This chapter deals with the modelling RC plane frames of
1) Academic Medical Centre G+3 storey building and analysed by using STAAD.Pro. all
2) Acute Hospital loads acting on building such as dead load and live load were
3) Ambulatory Surgery Centre considered except the wind load. It was assumed that wind
4) Childrens Hospital load will not governed the demands on the members and
5) Clinic storey level. The unit weight of some material are taken from
6) Fedral hospital Table 1, IS 875(part-1):1987. To represent the structural
7) Multi-specialty hospital aspects of typical frame in a building and exhibit its
8) Government hospital behaviour under external loading.
9) General funded hospital
D. Critical Summary on Literature
II. LITERATURE REVIEW  Adequate space occupied by per person has been
determined.
A. Literature 1
 Based on direction of span, the slab has been designed as
1) MVK.Sathish etal (2017) :Planning , Analysis and Design one way and two way slab.
of (G+5) Hospital Building using STAAD. Pro  Member forces were determined using structural
This paper is about design of G+3 hospital building and its analysis.
facility arrangements reaction to various loads were study  The planning and designing other facilities are designed
using STAAD.Pro . By applying suitable loads and section on applicable codes as a part of normal professional
details to the components to achieve the factors using practice
STAAD.Pro for analysis. The hospital building analysed by a
substitute frame using software over manual method and
comparative analysis were determined.
The dead loads and live loads were taken from
BS6399:1997 and seismic loads intensity is based on
equivalent static force in UBC 1994. The result of the
building can withstand of any intensity of earthquake located
near the epicentre of earthquake. By calculating base shear

All rights reserved by www.ijsrd.com 80


Planning, Analysis and Designing of Multi-Speciality Hospital Building
(IJSRD/Vol. 6/Issue 09/2018/022)

III. METHODOLOGY V. ANALYSIS

Fig. 3: Reaction of Beam

VI. DESIGNING
No of Slab 11
10x9m
Fig. 1: 9x5m
10x5m
IV. PLANNING 10x10m
10x8m
Slab sizes 10x12m
5x5m
8x5m
5x4m
10x4m
12x5m
No of Beam 2
Beam size 300mmx600mm
No of Column 3
Column size 450mmx600mm
Footing 1
Footing depth 450mm
SBC 150 kN/mm2
Table 1: Specification
A. Design of Slab
1) Design of Floor Slab (S1) (Rectangle)
a) Data For Design
Lx = 9m,
Ly = 10m
Fck =20N/mm2
Fy = 415N/mm2
Ly/Lx = 10/9 =1.1.
Therefore it should be designed as two way slab.
Fig. 2: Ground Floor b) Cross Sectional Dimension
Effective depth, d =320mm
d’ =30 mm
Overall depth, D = 350mm
b =1000mm
c) Effective Span
Effective span = 9320mm
d) Load Calculation

All rights reserved by www.ijsrd.com 81


Planning, Analysis and Designing of Multi-Speciality Hospital Building
(IJSRD/Vol. 6/Issue 09/2018/022)

Self-weight of slab = 8.75 kN/m2 Slab load = 54.92kN/m


Live load = 2.5 N/m2 W =51.26kN/m
Floor finish = 1 kN/ m2 Wur = 44.4kN/m
Total load = 12.25 kN/m2 c) Ultimate Moment
e) Bending Moment & Shear Force Mu.max = 140.21kN.m
Vu = 85.75x103N Mu.max = 192.027kN.
Mux =59.13x106 N-mm Mu.max>Mu
Muy = 51.14106 N-mm Section is under reinforcement. Therefore assistance of
f) Check For Section flange need not to be considered, it can be designed as
Mulim = 282.5X106N-mm ordinary beam.
Mulim> Mux Vu =128.15kN
The section has to be designed as under reinforced section. d) Tension Reinfoceme
g) AST Calculation Ast = 706.21mm2
Astx =530mm2 ast = 113.04mm2
astx =3.14/4X122=113mm2 No of bars = 4 bars
Spacing =200mmc/c Astpro = 791.28mm2
Provide 12ϕ @ 200mmc/c e) Check For Shear Stress
Asty = 456mm2 τc =0.927N/mm2
asty = 113mm2 Pt = 57.33%
Spacing =200mmc/c Refer table 19 of IS 456:2000
Provide 12ϕ @ 200 mm c/c τv = 0.54N/mm2
h) Distribution Reinforcement τc>τv
Mux =59.13x106 N-mm Hence shear reinforcement should be provided
i) Distribution Reinforcement Vus =84.335x103N
Ast =285mm2 Sv = 184.84mm
ast =50.4mm2 But spacing of stirrups should not be greater than 0.75xd or
Spacing =150mm c/c 300mm whichever less is
Provide 8ϕ @ 150mm c/c Sv = 412.5mm or 300mm
j) Reinforcement For Edge Strip Provide 10mm dia 2 legged stirrups @300mm centres
Lx/8 =1125mm throughtout length of beam
Ly/8 =1250mm f) Check For Deflection Control
k) Torsion Reinforcement Pt = 0.57%
=75 % of Astx (L/d) = 9.0
=397.5mm2 (L/d)max = 22
Provide 8ϕ @ 100 mm c/c =9.09<22
l) Check For Shear Stress Deflection control is satisfactory.
τc =0.26 N/mm2
C. Design of Column
Pt = 0.16%
τv =0.28N/mm2 1) Design of Axially Loaded Column
τ v <τc Length, l = 3000mm
Hence it is under reinforcement Size of column = 450mmx600mm
m) Check For Service DX =600mm
(l/d)max =36 DY = 450mm
(l/d)act =28.12 Characteristic load, P =2325.83 kN
(l/d)max> (l/d)act Pu =3488.75kN
The design is with in permissible limit. M20 and Fe415
a) Permissile Sresses
B. Design of Beam Fck =20N/mm2
1) Simply Supported (One End Fixed & Other End Fy =415N/mm2
Continous) b) Check For Slenderness Ratio
B =300mm le = 1950mm
D = 600mm λx = 3.25<12
l =5m λY = 4.22 <12
fck =20N/mm2 c) Check For Eccentricity
Fy = 415 N/mm2 eymin = 26mm > 20mm
a) Cross Section Dimension eminy = 21mm > 20mm
Effective depth = 250mm Allowable eccentricity = 30mm
Effective span = 5230mm ex > eminx
b) Load Calculation hence the eccentricity within limits along X-direction
Self-weight of beam = 3.45kN/m ey =23
Wall =12.42kN/m ey>eminy

All rights reserved by www.ijsrd.com 82


Planning, Analysis and Designing of Multi-Speciality Hospital Building
(IJSRD/Vol. 6/Issue 09/2018/022)

Hence the eccentricity within limits along Y-direction τc =57N/mm2


The above column can be designed as short axially loaded shear resisted by concrete
column Vuc = 256.5x103N
d) Longitudinal Reinforcement X =(2.88-0.6)/2
Pu = 0.4fckAc+0.67fyAsc = 1.1m
Ag =270x103mm2 Y =1.035m
Asc =4920mm2 Shear force, Vu = 145.67KN
Provide 25mm dia bars Vuc > Vu
asc = 490.625mm2 Hence safe in one way shear
No of bars =10nos
E. Design of Ramp
e) Design Of Lateral Ties
Dia of lateral ties = 6.25mm Floor height = 3m
f) Spacing Going distance = 4000mm
Least lateral dimension = 450mm Fck = 20 N/mm2
16x dia of longitudinal reinforcement = 16x25=400mm Fy = 415N/mm2
300mm a) Depth Calculation
Choose the least value= 300mm Span /d = 28
d = 125mm
D. Design of Footing D = 150mm
a) Load Calculation b) Effective Span Calculation
Size of column = 0.23m0.6m Effective span = 7m
M20 and F415 grade concrete and steel Effective width of ramp=1.75m
Load = 899.67 KN c) Load Calculation
Self- weight of footing=10% Self-weight= 5.625kN/m2
Total load = 989.637KN Live load = 2kN/m2
b) Size Of Footing Floor finish = 1kN/m2
Area of footing = 6.6m2 Total load = 8.625kN/m2
LxB = 6.6 Design load =12.94kN/m2
Assume, L = 1.25B Design of bending moment and shear force calculation
B = 2.3m Mu =4.95x106kN/m2
L = 2.88m Shear force =25.88 N
Upward soil pressure= 149.40kN/m2 d) Check For Depth
c) Bending Moment Calculation dreq = 34.57mm
Maximum Bending moment along Y- direction dreq< d
Muy = 18.61kN-m Hence ok
Maximum Bending moment along X-direction e) AST Calculation
Mux =6.45kN-m Ast =109.69mm2
d) Depth Of Footing Provide 10mm dia bars
Assume overall thickness of footing as 500mm ast =78.5mm2
D = 500mm f) Check For Shear
d =450mm τv =0.338N/mm2
e) Shear Force Pt =8%
Shear force, V =968.44KN τc = 0.28N/mm2
Normal shear stress: Condition is satisfied
τc =14.03N/mm2
τv =2.8N/mm2 VII. RESULTS & DISCUSSION
τv < τc 1) Implementation of theoretical and class knowledge in
Hence safe real time project.
f) Reinforcement Details 2) Gathered technical information for designing and
Along X- direction analysis of Ramp using codal provisions (APPENDIX A
Ast = 113.96mm2 to Part 1191)
Along Y-direction 3) Manual calculations of design of septic tank.
Ast = 280mm2 4) Gained knowledge in designing number of columns
Minimum reinforcement manually using computer software.
Ast min = 540mm2 5) Planning and analysis on each design were determined
Provide 12mm dia bars using codal provisions of (IS 875-part 1&2, IS 456-2000,
ast = 113.09mm2 IS 12433 -part3-2001)
Spacing = 300 mm
g) Check For One Way Shear
Pt = 0.6%
Refer table 19 of IS456

All rights reserved by www.ijsrd.com 83


Planning, Analysis and Designing of Multi-Speciality Hospital Building
(IJSRD/Vol. 6/Issue 09/2018/022)

REFERENCES
[1] Dr.S.R.Karve and Dr.V.L.Shah(2001, fourth edition)
“Illustrated design of reinforced concrete buildings.
[2] IS 456:2000(2000, Fourth Revision) “Plain &
Reinforced Concrete-Code of Practice”.
[3] IPHS-Indian Public Health Standards (Guidelines 2012)
for health care centres.
[4] Krishnaraju.N (2003, third edition) “Design of
Reinforced Concrete Structures”.
[5] Ramamrutham.S(1993) “Design Of Reinforced Concrete
Structures”.
[6] IS 12433 (Part-3:2001) “Basic Requirements of Hospital
Building”.
[7] Planning , Analysis and Design of (G+5) Hospital
Building using STAAD.Pro MVK.Sathish etal (2017)
G+3,Hospital building
[8] Planning, Analysis and Design of Hospital Building
Using Staad Prov8i(Dr.Ashok kumar N, Navaneethan M,
Naviya B, Gopalakrishnan D, Atun RoyChoudhury)
[9] IJESRT-Design of g+4 Hospital Building for Earthquake
Resistant (J.Sankar, E.V.Raghava Rao,
N.Chennakesavulu)

All rights reserved by www.ijsrd.com 84

You might also like