Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

Reyrolle

Reydisp Evolution

Restricted © Siemens AG 2015 All rights reserved. siemens.com


Reydisp Evolution

SIEMENS
REYROLLE
ENTER to CONTROL

Reydisp Evolution

Available to download free from


www.siemens.com/reyrolle

Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 2 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution

Functionalities
Manage the project.
Add devices.
Import third-party ICDs.
Add station.
Add time server.
Setting editor - manage
settings.
Reylogic Express – create logic.
Export files.
Update devices.
Sync the project with the
devices.

Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 4 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution

Relay Configuration.
Setting manipulation.
Text Displays.
Protocol Data Relay Control.
Information. Commands.
Curves. Time Synchronisation.
Clear Flags/Data.
Viewing. Capture Disturbance
Relay Settings. Record.
Disturbance Records.
Events.
Fault Records.
Instruments.

Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 5 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
Relay Connection

The USB port allows ‘plug and play’ connection to


Reydisp from default settings.

Standard Communication Ports.


COM 1 (Rear RS485).
COM 2 (Front USB).

Protocols.
IEC 60870-5-103 and ASCII are available on all Type-A USB Plug Type-B USB Plug
Ports.
MODBUS-RTU and DNP-3 are available on all
Ports except the USB.
IEC 61850 is available as an option.
REYDISP is compatible with IEC 60870-5-103
and can be used on all ports providing that
protocol.

Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 6 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
Buttons Bar and Menus

This bar can be configured to the user’s most used commands.

You can customise


colours etc.
Templates
Can be shown in
different views.

Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 7 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
Templates

Working Off-
Off-line
Open the template of the relay you are using
from the list available.

This then allows you to change settings and


work without being connected to the relay.

You can then save the file in a Reydisp


format ready to be up-loaded to a relay at a
later date.

File: save as,


The files can be saved in different formats for different
applications:
RSF2 - New Reydisp format.
SET - Old Reydisp format.

Export formats:
CSV - Excel spreadsheet format.
RTF - User + setting table – template for site.
Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 8 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
RTF file

You are given options for what the text


will contain.
e.g. setting/default/range

This RTF file shows all of the relay


settings in a word document and in a
user friendly format, allowing for
checks to be made on the relay as it is
a hard copy of the relay settings.

Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 9 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
Connection Manager

To use Reydisp with the relay you must first connect to it. This is done via the USB port located
at the front of the relay.

For some relays when you


When you have a relay click connect you must have
connected via USB, an the correct properties on the
icon will appear here to relay, such things as the
connect to that relay. baud rate and parity may
need to be adjusted.

Highlight the relay and click


connect.

Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 10 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
Relay Settings

You are given a list of the relay settings (shown below).

You can also change the


input/output settings via
this menu, this is an
You can now alternative way of setting
change or enter the commands instead of
You can change everything in this menu a new value. looking at the matrix.
by simply clicking onto the cell you wish to
change.
The settings can be changed in the
template offline or when connected to the
When you change something it becomes
device. The changes only occur when they
highlighted so you can clearly see what
are sent.
you have changed.
Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 11 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
Matrix

Viewing the matrix makes it easier to see what is happening The LED Matrix is
within the relay. similar as it gives you
the option to self-
reset the LEDs and
more. The layout is in
the same format as
input & output view.
remains when
The Text

scrolling

The matrix allows you to customise the outputs. In the example above, when the protection is
healthy, binary output 1 is closed and LED’s 7, 8 and 9 are engaged.
Note: Settings changed in any view will be reflected in all other views.
Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 12 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
Events

IEC number is
displayed.
The events are
things that have
happened while the
relay has been in
service. They are
shown in this
events window.
The events are a good way of
seeing what has happened
The time the event inside the relay as it gives you
happens is the time the event happened
recorded. and a description of how they
preformed.
Format:
HH:MM:SS.SSS,dd/mm
/yyyy
Note: If you select 2 different
events it will show you the time
difference between them.

Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 13 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
Waveform Records

When clicking on the icon you will be given a choice of the different waveforms that have been
created. Once you select the waveform you want to view you will be given the following screen:

Cursors on the graph


allow you to look
closer at a specific
part of the waveform,
and it gives the time of
the sample.

Zoom commands
are also available to
look closer at the
wave.

From the record you can see what is happening within the relay, in this example you can see
that Binary output 1, LEDs 7, 8 and 9 are on/raised.

Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 14 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
Views

You can configure the view of the waveforms


looking at digital and analogue signals
individually, or all together.

You can also combine the


waveforms to show all of them
on one graph. You can also
look at the different harmonics
of a waveform by viewing the
properties.

You can trigger a waveform showing the current state of the relay.

Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 15 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
Configure View

Allows you to choose what signal


you want to look at and allows
you to look at the harmonics of a
wave.

The title defines the


name on the tab for your
custom views.

Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 16 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
Monitor Instruments

By clicking on ‘Available’ it
In monitor mode you can see in real-time the status
allows you to add more
of the relay.
things to monitor.

The red ball is


constantly
monitoring the
relay and
updating this
table to the right,
showing the
state of the
relay.

Any changes will show up in the monitor mode. i.e. if


binary output 5 is activated a 1 would show in this
location, indicating binary output 5 is raised.

Note: you
Restricted can only
© Siemens AGuse
2015 this command
All rights reserved.when Protection notice / Copyright notice.
connected
Page 17 to the relay. Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
Auto Pole

Auto pole continuously polls for spontaneous events from the relay and shows them in real time
if binary output 2 is operated, this would show up as an event in the list below as the change
happens.

It is monitoring the relay


and displays any
changes automatically,
similar to the events
record.

Note: you can only use this command when connected to the relay.
Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 18 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution
General Features

Save
Settings
Events
Waveforms types - Comtrade
etc

Print
Commands – Teletype, close output, GI
etc
Time synch – From computer

Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 19 Sales TLQ Training EM EA SPDL RSS
Reydisp Evolution

Quick start - Auto


Quick start is simply a reclose
different view to look
Quick start -
at and change the
Protection
settings of the relay.

Send the settings

Drop down menus

If the relay has


Its is designed to be
this type of view it
easy to use and
will automatically
quicker.
appear in tabs.

It allows you to The greyed out


Enable and Disable parts mean that
settings and change the function is not
there values. active.

Restricted © Siemens AG 2015 All rights reserved. Protection notice / Copyright notice.
Page 20 Sales TLQ Training EM EA SPDL RSS
Siemens Protection Devices Limited
Further Information

All current information is available from the website: -


www.siemens.com/reyrolle
Catalogue Sheets
Product Flyers
Technical Manual
Wiring Diagrams
Panel Drilling Drawings
Quarterly Newsletter ‘Current Matters’
Reference Lists / User Lists
Software & Firmware
Reydisp Templates
Marketing posters / roller banner etc

For all Technical Queries contact:


Phone: + 49 180 524 7000
Fax: + 49 180 524 2471
E-mail: support.ic@siemens.com