Vector Group Test of Power
Transformer
on 24/2/2012 & Updated on Thursday 3rd of
May 2018 at 04:35:17 PM

Vector Group Test of Transformer


The vector group of transformer is an
essential property for successful parallel
operation of transformers. Hence every electrical
power transformer must undergo through vector
group test of transformer at factory site for
ensuring the customer specified vector group of
transformer.
The phase sequence or the order in which the
phases reach their maximum positive voltages,
must be identical for two paralleled transformers.
Otherwise, during the cycle, each pair of phases
New Articles
will be short circuited.

The several secondary connections are Electrical …

available in respect of various primary three Top

https://www.electrical4u.com/vector-group-test-of-power-transformer/ 1/8
24/10/2018 Vector Group Test of Power Transformer

phase connection in a the three phase


transformer. So for same primary applied three Magnet a…
phase voltage there may be different three
phase secondary voltages with various
magnitudes and phases for different internal Electricity
connection of the transformer.

Impedance

Permittivity

Articles on Transfor…

Transformer Testing

Winding Resistance …

Ratio Test of Transfo…

OC & SC Test

Transformer Polarity…
Let's have a discussion in detail by example for Vector Group Test
better understanding.
Dielectric Test
We know that, the primary and secondary coils
on any one limb have induced emfs that are in Temperature Rise Test

time-phase. Let's consider two transformers of Impulse Test


same number primary turns and the primary SFRA Test
windings are connected in star. The secondary
More Articles on Tra…
number of turns per phase in both transformers
Transformer Basics
are also same. But the first transformer has star
connected secondary and other transformer has Single Phase Transf…
delta connected secondary. If same voltages are Three Phase Transf…
applied in primary of both transformers, the Transformer Type
secondary induced emf in each phase will be in Top
Instrument Transfor…

https://www.electrical4u.com/vector-group-test-of-power-transformer/ 2/8
24/10/2018 Vector Group Test of Power Transformer

same time-phase with that of respective primary Installation of Transf…


phase, as because the the primary and Transformer Access…
secondary coils of same phase are wound on
Transformer Oil
the same limb in the core of transformer. In first
transformer, as the secondary is star connected, Maintenance of Tran…

the secondary line voltage is √3 times of induced Transformer Protection


voltage per secondary phase coil. But in case of Articles Categories
second transformer, where secondary is delta
connected, the line voltage is equal to induced
voltage per secondary phase coil. If we go
Home
through the vector diagram of secondary line
voltages of both transformer, we will easily find
that there will be a clear 30o angular difference
between the line voltages of these transformers.

Related pages
Basic Electrical
Transformer Testing | Type Tests and Routin…

Transformer Winding Resistance Measureme…

Voltage and Turn Ratio Test of Transformer


Electric
Open and Short Circuit Test on Transformer Transformer
Transformer Polarity Test

Vector Group Test of Power Transformer

Insulation Dielectric Test of Transformer


Electric
Transformer Oil and Winding Temperature R… Generator

Impulse Test of Transformer

Sweep Frequency Response Analysis Test | …

Now, if we try to run these transformers in Electric Motor


parallel then there will be a circulating current Top

https://www.electrical4u.com/vector-group-test-of-power-transformer/ 3/8
24/10/2018 Vector Group Test of Power Transformer

flows between the transformers as because


there is a phase angle difference between their
secondary line voltages. This phase difference
Electrical MCQ
can not be compensated. Thus two sets of
connections giving secondary voltages with a
phase displacement can not be intended for
parallel operation of transformers.
The following table gives the connections for
which from the view point of phase sequence
Engineering
Calculators
and angular divergences, transformer can be
operated parallel. According to their vector
relation, all three phase transformers are divided
into different vector group of transformer. All
electrical power transformers of a particular Video Lectures
vector group can easily be operated in parallel if
they fulfill other condition for parallel operation of
transformers.

Electrical
Generation

Electric
Transmission

Switchgear

GROUP Connection Connection Top

https://www.electrical4u.com/vector-group-test-of-power-transformer/ 4/8
24/10/2018 Vector Group Test of Power Transformer

0 Yy0 Dd0
(0o)
Electric
Protection

Electrical
Measurement

Electronics
Yd1 Dy1 Devices

1 Power
Electronics
( 30o)

Digital
Electronics

6 Yy6 Dd6
( 180o)

Top

https://www.electrical4u.com/vector-group-test-of-power-transformer/ 5/8
24/10/2018 Vector Group Test of Power Transformer

Yd11 Dy11

11
( - 30o)

Procedure of Vector Group Test of


Transformer

Top

https://www.electrical4u.com/vector-group-test-of-power-transformer/ 6/8
24/10/2018 Vector Group Test of Power Transformer

Let’s have a YNd11 transformer.


1. Connect neutral point of star connected
winding with earth.

2. Join 1U of HV and 2W of LV together.

3. Apply 415 V, three phase supply to HV


terminals.

4. Measure voltages between terminals 2U-1N,


2V-1N, 2W-1N, that means voltages between
each LV terminal and HV neutral.

5. Also measure voltages between terminals


2V-1V, 2W-1W and 2V-1W.

For YNd11 transformer, we will find,


2U-1N > 2V-1N > 2W-1N
2V-1W > 2V-1V or 2W-1W .
The vector group test of transformer for other
group can also be done in similar way.

Please Rate this Article


5

5 4
3
2
⚑ 1 total 1

★ ★ ★ ★ ★
Transformer Polarity Test Dielectric Test Top

https://www.electrical4u.com/vector-group-test-of-power-transformer/ 7/8
24/10/2018 Vector Group Test of Power Transformer

Connects Contents

Facebook Articles

Youtube MCQs

Videos 343

© 2011 - 2018 www.electrical4u.com The content is copyrighted to www.electrical4u.com


and may not be reproduced on other websites.

Top

https://www.electrical4u.com/vector-group-test-of-power-transformer/ 8/8

You might also like