PVSYST V6.81
21/10/19
Page 1/5
Grid-Connected System: Simulation parameters
Project : Prince Pipes
Salempur Mahdad
Geographical Site
Situation Latitude
Time defined as Legal Time
Albedo
Meteo data: Salempur Mahdad
Country India
29.94" N Longitude 78.05° E
Time zone UT+5.5 Attitude 289m
0.20
Meteonorm 7.2 (1981-2010), Sat=100% - Synthetic
Simulation variant: Simulation-2
Simulation date
21/10/19 1746
Simulation parameters System type
4 orientations titsfazimuths
No 3D scene defined, no shadings
10°1-45", 10°84", 10749", 107-135"
Models used Transposition Perez Diftuse Perez, Meteonorm
Horizon Free Horizon
Near Shadings No Shadings
User's needs : Unlimited load (grid)
PV Arrays Characteristics (4 kinds of array defined)
PV module Sipoly Model Eldora VSP.72.330.05_U
Original PVsyst database Manufacturer Vikram Solar
Sub-array "Sub-array #1" Orientation #1 TivAzimuth 10°45
Number of PV modules Inseries 18 modules in parallel 109 strings
Total number of PV modules Nb. modules 1962 Unit Nom. Power 330 Wp
Array global power Nominal (STC) 647kWp _Atoperating cond, 587 kWp (50°C)
Array operating characteristics (50°C) Umpp 614V Impp 956 A
Sub-array "Sub-array #2" Ofientation #2 Tivazimuth —10"/-144
Number of PV modules Inseries 18 modules In parallel 60 strings
Total number of PV modules Nb, modules 1080 Unit Nom. Power 330 Wp
Array global power Nominal (STC) 356 kWp- At operating cond. 323 kWp (50°C)
‘Array operating characteristics (50°C) Umpp 614V Impp 526A
Sub-array "Sub-array #3" Orientation #3 TivAzimuth 40°/49"
Number of PV modules In series 18 modules In parallel 25 strings
Total number of PV modules Nb. modules 450 Unit Nom. Power 330 Wp
Array global power Nominal (STC) 149kWp At operating cond. 135 kWp (50°C)
Array operating characteristics (50°C) Umpp 614V Impp 219
‘Sub-array "Sub-array #4" Orientation #4 TilvAzimuth —10°/-136"
Number of PV modules Inseries 18 modules In parallel 10 strings
Total number of PV modules Nb. modules 180 Unit Nom. Power 330 Wp
Array global power Nominal (STC) 59.4 KWp Atoperating cond, 63.8 kWp (50°C)
Array operating characteristics (50°C) Umpp 614V Impp 88A
Total Arrays global power Nominal (STC) 1242 kWp Total 3672 modules
Module area 7114 m*
Inverter Model SG6OKTL
Original PVsyst database Manufacturer Sungrow
Characteristics Operating Voltage 570-950 Unit Nom. Power 60.0 kWac
Sub-array "Sub-array #1" Nb. of inverters. 9 units Total Power 540 kWac
Pom ratio 1.20
Sub-array "Sub-array #2" Nb. ofinverters 5 units Total Power 300 kWac
Pom ratio 1.19PVSYST V6.81
21/1019] Page 2/5
Grid-Connected System: Simulation parameters
Sub-array "Sub-array #3" Nb. of inverters 2 units Total Power 120 kWac
Pnom ratio 1.24
Sub-array "Sub-array #4” Nb. ofinverters 1 units Total Power 60 kWac
Pnom ratio 0.99
Total Nb. of inverters 17 Total Power 1020 kWac
PV Array loss factors
Array Soiling Losses Loss Fraction 3.0%
Thermal Loss factor
Wiring Ohmic Loss
Uc (const) 15.0 Wimek
Array#t1 141 mOhm
Array#2_-20 mOhm
Array#3 47 mOhm
Array#l4 117 mOhm
Uv (wind)
Loss Fraction
Loss Fraction
Loss Fraction
Loss Fraction
0.0 Wim? / mis
1.8 % at STC
1.5 % at STC
1.5 % at STC
1.8 % at STC
Global Loss Fraction 1.5% at STC
Module Quality Loss Loss Fraction -0.8 %
Module Mismatch Losses Loss Fraction 1.0 % at MPP
Strings Mismatch loss Loss Fraction 0.10 %
Incidence effect (IAM): Fresnel smooth glass, n= 1.526
° 30° 50° 60" 70° 75° 80° 3° 90°
x000_| 0.998 | a9i_| 0.048 | 0.862 | 0.776 | 0.636 | 0.403] 0.000
System loss factors
Wires: 3x1200.0 mm? 157m Loss Fraction 1.8 % at STC
Unavailabilty of the system 7.3 days, 3 periods Time fraction 2.0 %PVSYST V6.8 2110/19] Page 3/5
Grid-Connected System: Main results
Project : Prince Pipes
Simulation variant: _Simulation-2
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation A orientations TilvAzimuth = 10°/-48", 10°/-144", 10°/49", 10°/-136"
PV modules. Model Eldora VSP.72.330.05U nom 330 Wp
PV Aray Nb. of modules 3672 Prom total 1212 kWp
Inverter Model SGEOKTL Pnom 60.0 kW ac
Inverter pack Nb. of units 17.0 Prom total 1020 kW ac
User's needs
Unlimited load (grid)
Main simulation results
System Production
Produced Energy
Performance Ratio PR
1771 MWhlyear
76.28 %
Specific prod.
1462 kWh/kWplyear
Normalized productions (per Installed KY):
Nominal power 1212 kWp
a (u. E
WR a Perera 8
Simulation-2
Balances and main results
GtobHor | DiftHor | T_Amb | Globinc ] Giobéff ] EArray | EGrid | PR
vewiyme | tewhyme | ec | kwiyme | tetye | wh | Mw
January uss | 3083 | wse | u76 | 178 | 204 | 1180 | os
February 1303 | 3772 | 1597 | 1331 | 1236 | 1342 | i315 | osis
March 123 | 4927 | 2135 | issa | 1721 | 1785 | i747 | 0.783
April 2030 | 644s | 2701 | 2033 | 1908 | 1993 | 1952 | 0752
May z34 | seiz | 3057 | 227 | 1994 | 1984 | 1904 | 0739
June 120 | 9797 | 3020 | isia | 1693 | 1695 | asia | 0.689
uly 1sa7 | 9203 | 2938 | 1536 | 1a1 | 1467 | 1438 | 0773
August 1592 | 8998 | 2846 | 1590 | 1482 | 1526 | 1495 | 0.776
lseptember | 1539 | 7144 | 2680 | 1553 | 1447 | 1493 | 146.2 | 0.777
Joctober 105 | aio | 2388 | 1637 | 1526 | ise4 | issa | over
November x96 | 2496 | 1820 | 1339 | 1229 | 1327 | 167 | ons
December us2_|_ 2196 | 1408 | 1193 | 1088 | 1205 | 1095 | 0.757
Year 1979 | 71052 | 2324 | 19166 | 17034 | 18466 | i775 | 0.763
Legends: GlobHor Horizontal global irradiation Globe Effective Global, corr. for TAM and shadings
DiffHor Horizontal diffuse radiation Enrray Effective energy at the output ofthe array
TLAmb Ambient Temperature E.crid Energy injected into arid
GlobInc Global incdent in col plane PR Performance RatioPVSYST V6.81 2410/19| Page 4s
Grid-Connected System: Special graphs
Project : Prince Pipes
Simulation variant: Simulation-2
Main system parameters
PV Field Orientation
PV modules.
PV Array
Inverter
Inverter pack
User's needs
System type No 3D scene defined, no shadings
orientations TilAzimuth = 10°/-45°, 10°/-144°, 10°/49°, 10°7-135"
Model Eldora VSP.72.330.05_U
Nb. of modules 3672 Prom total
Model SG6OKTL
Nb. of units 17.0 Pnom total
Unlimited load (grid)
Pnom 330 Wp
1212 kWp
Pnom 60.0 kW ac
1020 kW ac
7000
Daily Input/Output diagram
6000
5000 +
4000
fo ont phy
3000
2000
1000
T T T T T
Values from 01/01 to 31/12
L L L L L La,
2 3 4 5 6
Global incident in coll plane [kWhimn? day]
System Output Power Distribution
60000
0000}
40000
30000}-
20000
ney
10000 }-
T T
Values from 01/01 to 31/12
200 400 600
Power injected into grid KW]
800PVSYST V6.81
21/1019] Page 515
Grid-Connected System: Loss diagram
Project : Prince Pipes
Simulation variant: Simulation-2
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation A orientations TilvAzimuth = 10°/-48", 10°/-144", 10°/49", 10°/-136"
PV modules: Model Eldora VSP.72.330.05 U Pnom 330 Wp
PV Array Nb. of modules 3672 Pnom total 1212 kWp
Inverter Model SGEOKTL Pnom 60.0 kW ac
Inverter pack Nb. of units 17.0 Phom total 1020 kW ac
User's needs Unlimited load (grid)
Loss diagram over the whole year
1898 Kin Horizontal global inaction
+1.0% Global incident in col plane
0.04% Globalinidert below tweshold
47% AM facta on global
3.00% Soling oss factor
789 kw 7114 mca Eftectivelradaton on collectors
efcionsy @ STC= 17.06% PV conerion
25 Mh Array nominal energy (at STC effi)
Ki.050% pViess du toiradiance level
12.69% PV Ios dv to temperature
40.75% Module alt bss
130% Mismatch ss, meddes and sings
101% Ohmic wing loss
126 wn Array val energy at MPP
1.18% Inverter Loss during operation (efficiency)
200% Invert Loss over nominal nv power
200% Inverter Loss due to mak input curent
200% Inverter Loss over nonal iv volage
2.0% Inverter Los de to power teshotd
0.50% Inverter Loes due to voliagetreshold
1825 Mm ‘Avallable Energy at Inverter Output
2.05% ‘System unavailability
088% AC ohmic ss
srt Mn Energy injected ino grid