TECHNICAL SPECIFICATIONS

The DynacraftTM VAV Terminal Box DVS is a pressure independent terminal unit, designed for
volume flow control of primary air in variable air volume systems.

The terminal units are designed with a circular inlet spigot to ensure an uniform airflow over the
pressure measurement grid so as to provide an accurate measurement of effective pressure.

The outlet is rectangular to provide a larger discharge area and consequent lower discharge
velocity resulting in considerably reduced noise levels.

The multiple options offered permit appropriate selection of the terminal unit to meet project
specific control needs.

The terminal unit is constructed out of high quality galvanized sheet steel with a circular spigot
connexion on the high pressure side (inlet) and a rectangular (or optionally a circular)
connexion on the low pressure side (Outlet). The inlet is provided with a cross flow, multi-point
pressure sensor and a motorized control damper.

The entire unit is internally lined with fiberglass and covered with erosion resistant material to
provide effective thermal and acoustic insulation.

The controller-transducer-actuator package, together with a transformer is mounted on the


outside of the casing. The terminal unit is internally wired, tested and calibrated at the factory,
prior to shipment. Unit casing leakage does not exceed 0.6% at 4 inch wg (1000 pa)
inlet static pressure.

The air volume flow generates an effective pressure at the multi-point pressure sensor. This
effective pressure is transmitted to the transducer via the plastic control tubing. The transducer
converts the effective pressure into an electronic signal (0-2V DC to 10V DC). This signal is
relayed to the controller which then compares it to the set point value from the room
sensor. Any variance in the two will result in a signal from the controller to the actuator to adjust
the control damper appropriately.

The control damper is constructed out of galvanized sheet steel with gaskets. Shafts are of carbon
steel. The gasket and seals are designed for the operating temperatures to minimize shaft seal
heat transfer. The air leakage of the control damper is less than 1% at 4 inch WG (1000 pa) inlet
static pressure.

1
Dynacraft

The control enclosure is made of high quality galvanized sheet steel with double face plate design
and multiple wire conduit opening. This control enclosure is suitable for all controllers.

Reheat coils are available as an option. Where supplied, it shall be encased in a modular housing
design. Dynacraft™ offers two options: Hot water coil and Electric re-heat coil.

DynacraftTM can offer standard or customized modular plenums with multiple outlets. Standard
long case plenums are also offered for enhanced acoustic demands.

I DVS 1 -I SIZE I ~ CASING I -I OUTLET I -I CONN I -I CNT 1-I REHEAT I


I SIZE 125, 150, 175, 200, 225, 250, 300, 350, 400

I CASING S, X (Standard, Extended)

1 OUTLET I, M (Single, Multiple)

I CONN L, R (Left Side, Right Side) (Facing the outlet)

CNT 1,2,3 (t - Stand Alone, 2-DDC, 3- Bare Box)

I REHEAT HW, EC, ( Hot water coil, Electric Reheat)

Example: DVS -06-S-I-L-2-00

Dynacraft VAV Terminal Box, Size 06, with standard casing, single outlet with left side control
assembly with DDC control and no reheat.

2
Dynacraft

MODEL SELECTION PROCEDURE - MODEL DVS

Determine the minimum ventilation airflow rate and maximum airflow rate to meet the zone
cooling load (based on load calculations).

Refer to the AIR FLOW TABLE to select the appropriate unit for the application.

EXAMPLE:
Min Air Flow Rate = 280 CFM
Max Air Flow Rate = 800 CFM
Pr Drop Not to exceed 60 Pa.
NC not to exceed 40.
Static Pr 1.5 Inch WG

Refer to engineered performance data

You will note that Model DVS 175 cannot meet the maximum air flow rate. Model DVS 200 can
meet both minimum and maximum air flow rate value.

Interpolate pressure drop values or maximum air flow rate of 800 CFM. Pressure drop is
50 pa.case radiated NC is 25 and discharge sound is NC 35, both within specified limits.

3
Dynacraft

PHYSICAL DATA

The Dynacraft™ DVS VAV terminals are designed for use in low or medium pressure duct system.
They are available with several available accessories. Optional accessories include hot water
reheat, electric reheat., extended casing and multiple outlet plenums. Controls can be factory
fitted and wired by our trained personal.

Wiring schematics are affixed inside the control enclosure for field reference. The DVS VAV
terminals are widely used in many HVACsystem in all types of buildings.

Controller Disconnect switch Fuse Cross flow


velocity sensor

Transformer

(Inlet)
c:::::>

o
o E
.,.E
Ul

TB(terminal block)
51"
3 A
c (150mm)
(136mm)

Airflow Table
Model Airflow A B C D
CFM Inch Inch Inch Inch
(mm) (mm) (mm) (mm) (mm)

125 85 N 432 8.25 9 15.75 4.875


(0.04 N 0.20) (209) (228) (400) (124)

108 N 648 8.25 9 15.75 5.875


150
(0.05 N 0.31) (209) (228) (400) (149)
135 N 864 10.25 10.25 15.75 6.875
175
(0.06 N 0.41) (260) (260) (400) (175)
189 1134
N 10.25 10.25 15.75 7.875
200
(0.09 N 0.54) (260) (260) (400) (200)
238 N 1435 12.25 12.75 15.75 8.875
225
(0.11 N 0.68) (311) (324) (400) (226)

250 297 N 1782 12.25 12.75 15.75 9.875


(0.14 N 0.84) (311) (324) (400) (251)
432 N 2538 14.25 15.25 21. 75 11.875
300
(0.20 N 1.20) (362) (387) (552) (302)
567 N 3456 16.25 16.50 22.75 13.875
350
(0.27 N 1.63) (412) (419) (578) (352)

400 756 N 4536 18.25 19 23.75 15.875


(0.36 N 2.14) (463) (482) (603) (403)

4
Dynacraft

ENGINEERED PERFORMANCE DATA


Airflow Pressure Drop

Aiflow Air Pressure Drop inchs Wg (PA)


Model CFM
Standad With electric
(CMH) With 1 row coil With 2 row coil
VAV Box heating coil
76 0.01 0.03 0.06 0.01
(129) (2) (8) (14) (2)
108 0.02 0.05 0.07 0.02
(183) (5) (13) (18) (5)
216 0.07 0.12 0.17 0.07
125
(367) (17) (30) (43) (17)
324 0.13 0.23 0.33 0.13
(550) (33) (58) (81) (33)
432 0.22 0.37 0.51 0.22
(734) (54) (92) (128) (54)
216 0.03 0.08 0.12 0.03
(366) (8) (21) (31) (8)
324 0.07 0.17 0.27 0.07
(550) (18) (43) (66) (18)
432 0.12 0.28 0.42 0.12
150
(733) (31) (69) (105) (31)
540 0.21 0.43 0.62 0.21
(917) (51) (106) (153) (51)
648 0.31 0.58 0.74 0.31
(1101) (77) (143) (184) (77)
324 0.04 0.06 0.08 0.04
(550) (9) (14) (19) (9)
432 0.10 0.14 0.17 0.10
(733) (25) (35) (43) (25)
540 0.14 0.22 0.29 0.14
175 (917) (34) (54) (72) (34)
680 0.17 0.30 0.56 0.17
(1155) (42) (75) (139) (42)
756 0.22 0.43 0.62 0.22
(1284) (55) (106) (154) (55)
324 0.04 0.06 0.08 0.04
(550) (9) (14) (19) (9)
540 0.06 0.14 0.22 0.06
(917) (16) (36) (54) (16)
648 0.10 0.23 0.35 0.10
200 (1101) (24) (57) (88) (24)
756 0.17 0.37 0.57 0.17
(1284) (42) (93) (141) (42)
865 0.25 0.47 0.70 0.25
(1469) (61) (117) (173) (61)
324 0.02 0.07 0.11 0.02
(550) (4) (17) (27) (4)
540 0.04 0.12 0.20 0.04
(917) (11) (31) (49) (11)
225
756 0.10 0.22 0.34 0.10
&
(1284) (24) (54) (85) (24)
250
973 0.16 0.33 0.50 0.16
(1653) (40) (83) (124) (40)
1189 0.25 0.50 0.73 0.25
(2020) (63) (124) (182) (63)

5
Dynacraft

ENGINEERED PERFORMANCE DATA


Airflow Pressure Drop

Aiflow Airflow Pressure Drop Inch Wg (PA)

Model CFM
Standad With electric
(CMH) With 1 row coil With 2 row coi heating coil
VAVBox
648 0.02 0.06 0.09 0.02
(1101) (4) (14) (22) (4)
1081 0.04 0.14 0.23 0.04
(1836) (10) (35) (58) (10)
1513 0.05 0.26 0.45 0.05
300
(2570) (13) (64) (112) (13)
1945 0.08 0.45 0.80 0.08
(3305) (21) (112) (199) (21)
2377 0.13 0.71 1.25 0.13
(4039) (33) (176) (311) (33)
865 0.02 0.08 0.14 0.02
(1469) (6) (21) (34) (6)
1729 0.06 0.25 0.42 0.06
(2937) (15) (61) (104) (15)
2403 0.12 0.38 0.65 0.12
350 (94) (161) (29)
(4083) (29)
3077 0.19 0.62 1.05 0.19
(5228) (47) (153) (261) (47)
3509 0.24 0.80 1.37 0.24
(5962) (60) (200) (341) (60)
1081 0.02 0.06 0.09 0.02
(1836) (5) (15) (23) (5)
1945 0.06 0.17 0.25 0.06
(3305) (15) (43) (63) (15)
2810 0.12 0.32 0.52 0.12
400 (4774) (29) (80) (129) (29)
3674 0.20 0.56 0.99 0.20
(6242) (49) (138) (246) (49)
4323 0.27 0.76 1.36 0.27
(7345) (68) (189) (338) (68)

Notes
1. The Air Flow Pressure Drop is the pressure difference between inlet and outlet when
delivering the airflow shown with the primary damper in fully open position.
2. Damper leakage of series DVS is less than 1% at 4.0"wg (1000pa) inlet static pressure. Leakage
rate is the ratio of air volume through the damper when it is fully closed to air volume at
damper fully open position and face velocity is at 3000 FPM(15 m/s)
3. Pressure drop through the electric heaters is low, hence can be ignored.
4. Dynacraft™ suggests that the inlet static pressure of VAV Terminal, which is on the critical
position of the duct work system, should be no less than 0.50"wg (125Pa).

6
Dynacraft

ENGINEERED PERFORMANCE DATA


Radiated Sound Power & Noise Criteria Data (NC) DVS

.•• Ps=MIN .•• Ps-0.50in-wg (125Pa) .•• Ps-1.51in-wg (375Pa) .•• Ps-3.02in-wg (750Pa)
Sound Power (db) Sound Power (db) Sound Power (db) Sound Power (db)
Model CFM NC NC NC NC
By octave band (H) z By octave band (H) z By octave band (H) z By octave band (H) z
No. (m'/s)
125 250 500 100020004000 125250 500 100020004000 125 250 500 100020004000 125 250 500 100020004000
75 26 <20 40 38 25 <20 38 38 29 28 27 23 <20 44 43 38 33 34 33 <20
(0.04)
150
(0.07) 31 21 <20 46 39 28 - <20 46 46 35 30 30 25 <20 50 51 47 38 38 34 <20
125 300
(0.14) 45 39 47 24 22 <20 59 56 45 38 31 24 <20 55 52 41 38 33 25 24 60 60 53 44 39 36 29
400
(0.19) 51 45 33 29 27 25 <20 54 50 42 33 29 25 <20 60 57 47 41 35 32 25 64 62 54 46 41 38 31

100
(0.05)
28 - - <20 41 39 25 <20 42 43 34 29 29 24 <20 45 45 38 34 35 34 <20
200
(0.09)
32 23 - - <20 47 39 28 21 <20 51 51 40 31 31 26 <20 51 52 48 39 39 35 20
150
400
(0.19) 46 40 28 25 23 <20 60 57 46 39 32 25 <20 60 57 46 39 34 30 25 61 61 53 45 40 37 30
500
(0.24) 52 46 34 30 28 26 <20 55 51 43 34 29 26 <20 61 58 48 42 36 33 26 66 63 54 47 47 39 32

150
(0.07)
29 21 - <20 46 37 27 24 24 21 <20 48 45 36 31 29 27 <20 51 48 41 36 37 31 <20

175
300
(0.14)
37 28 21 - <20 50 40 32 25 23 20 <20 57 52 43 33 30 28 <20 60 58 52 43 38 34 26
600
(0.28) 47 41 31 27 25 24 <20 54 47 38 32 27 24 <20 62 54 47 39 35 31 24 68 62 54 47 43 40 31
800
(0.38) 51 45 33 29 28 26 <20 55 51 43 34 29 26 <20 64 58 49 42 38 33 26 69 63 55 48 44 39 32

200
(0.09)
30 22 - - <20 47 38 28 25 25 22 <20 49 46 37 30 31 29 <20 52 49 43 37 38 32 <20
500
(0.24)
38 29 23 - - <20 50 41 33 26 24 <20 58 53 44 34 31 29 <20 61 59 53 44 39 35 23
200
800
(0.38) 48 42 32 28 26 25 <20 55 48 29 33 28 25 <20 63 56 48 40 36 33 25 69 63 54 48 44 41 32
1000
(0.47) 54 47 38 33 31 29 <20 59 53 45 39 34 30 <20 66 59 50 43 39 34 29 70 64 56 49 44 40 34

400 32 26 <20 47 40 31 26 24 <20 51 53 45 34


38 36 20 55 56 55 48 43 42 27
(0.09)
800 43 36 30 27 23 <20 51 47 40 37 32 28 <20 57 55 47 42 38 38 22 59 61 56 52 46 45 30
(0.38)
225
1000
(0.47) 48 40 34 33 28 23 <20 54 50 40 35 32 30 <20 60 57 49 44 39 39 25 61 62 56 53 47 46 31
1200
(0.57) 52 44 37 37 33 28 <20 57 53 43 38 36 33 <20 62 58 50 45 41 40 26 64 63 57 53 47 46 32

400
(0.09)
32 26 - <20 47 40 31 26 24 - <20 51 53 45 38 36 34 20 55 56 55 48 43 42 27
800
(0.38)
43 36 30 27 23 - <20 51 47 40 37 32 28 <20 57 55 47 42 38 38 22 59 61 56 52 46 45 30
250
1000
(0.47) 48 40 34 33 28 23 <20 54 50 40 35 32 30 <20 60 57 49 44 39 39 25 61 62 56 53 47 46 31
1200
(0.57) 52 44 37 37 33 28 <20 57 53 43 38 36 33 <20 62 58 50 45 41 40 26 64 63 57 53 47 46 32

800
(0.38)
34 28 25 - <20 52 44 37 33 30 29 <20 60 56 50 43 40 39 24 63 61 58 52 48 47 31
1200
42 34 32 28 23 <20 54 47 39 33 31 30 <20 62 57 50 44 41 40 25 67 63 59 53 49 48 32
(0.57)
300
1600
(0.76) 48 40 38 34 30 24 <20 58 50 42 37 33 32 <20 64 58 51 45 42 41 26 69 64 60 54 50 49 34
2000
(0.94) 52 45 42 39 36 30 <20 62 53 45 41 37 35 <20 67 60 53 47 45 43 30 71 65 61 55 51 52 35

1200
(0.57)
35 29 26 20 - <20 53 45 38 33 30 30 <20 60 57 51 44 40 40 25 64 62 59 54 48 48 32
1600
(0.76)
43 36 33 29 24 - <20 56 48 40 34 32 31 <20 63 58 52 45 41 41 26 68 64 60 54 49 48 34
350
2000
(0.94) 49 41 39 35 31 24 <20 59 51 43 38 34 33 <20 65 59 52 46 42 42 27 70 65 61 55 50 49 35
2400
(1.13) 54 46 43 40 37 30 <20 62 54 46 42 38 36 <20 68 61 54 48 45 44 31 72 66 62 56 51 50 38

1500
(0.71)
32 26 - - <20 45 40 31 26 24 <20 51 53 45 38 36 34 20 55 56 55 48 43 42 27
2000 43 36 30 27 23 <20 47 40
51 37 32 28 <20 57 55 47 42 38 38 22 59 61 56 52 46 45 30
(0.94)
400
2500
(1.18) 48 40 34 33 28 23 <20 54 50 40 36 32 30 <20 60 57 49 44 39 39 25 61 62 56 53 47 46 31
30400
(1.42) 52 44 37 37 33 28 <20 57 53 43 38 36 33 <20 62 58 50 45 41 40 26 64 63 57 53 48 47 32

.•. Ps =Inlet static pressure Dash (-) indicates NC level less than 20

Notes:
1. NC levels are tested in accordance with ARI standard 885-98
2. Minimum static pressure required to deliver CFMshown above with the primary damper in fully
open position.
3. All NCsound data is based upon 10db room absorption plus applicable data.

7
Dynacraft

ENGINEERED PERFORMANCE DATA


Radiated Sound Power & Noise Criteria Data (NC) DVS

.•• Ps-MIN .•• Ps-0.50in-w9 (125Pa) .•• Ps-1.51in-w9 (375Pa) .•• Ps-3.02in-w9 (750Pa)
Sound Power (db) Sound Power (db) Sound Power (db) Sound Power (db)
Model CFM NC NC NC NC
By octave band (H)z By octave ba nd (H)z By octave band (H)z By octave band (H)z
No. (m'/s)
125250 500 100020004000 125 250 500 100020004000 125 250 500 100020004000 125 250 500 100020004000
75
(0.04)
34 - <20 54 43 39 38 33 31 <20 52 50 49 44 42 42 <20 59 56 53 50 51 49 <20
150 34 <20 61 61 56 48 43 43 <20 54 57 65 57 54 53 <20
37 26 22 21 <20 59 46 41 39 32
(0.07)
125
300
(0.14) 54 45 40 41 32 28 21 61 53 52 49 41 37 22 70 65 61 54 47 47 31 75 75 70 64 57 56 36
400
(0.19) 63 52 47 46 38 33 24 66 58 56 53 44 40 25 75 70 63 60 53 51 34 78 76 71 66 59 57 38

100 36 <20 57 50 42 39 37 37 <20 64 62 57 52 50 50 27 66 67 63 58 58 56 35


(0.05)
200 27 24 23 <20 59 50 46 43 39 39 <20 75 69 61 53 50 51 32 67 68 74 63 59 58 37
39
(0.09)
150 400
55 46 41 42 32 29 20 64 57 54 51 44 42 23 79 70 62 57 53 54 35 84 80 73 63 59 59 38
(0.19)
500
(0.24) 54 53 48 47 38 34 22 67 60 56 53 45 43 27 72 69 62 59 53 54 38 86 80 72 65 60 60 39

150 37 25 24 <20 56 48 41 38 36 36 <20 54 61 50 50 49 49 25 65 65 62 58 57 54 29


(0.07)
300 43 36 32 30 22 <20 58 49 46 42 38 38 <20 64 68 56 52 50 50 32 76 71 72 61 58 57 36
(0.14)
175
600 44 44 67 69 61 52 53 82 75 73 62 59 58 38
56 48 46 43 36 31 20 63 57 53 50 22 55 35
(0.28)
800
(0.38) 64 55 53 50 44 39 22 65 59 55 53 45 45 25 68 69 62 58 53 53 36 85 78 72 64 60 59 42

200 38 26 25 <20 57 50 42 39 37 37 <20 64 62 57 52 50 50 26 66 67 63 58 58 56 26


(0.09)
500 44 37 34 31 23 <20 59 50 46 43 39 39 <20 75 69 61 53 50 51 32 77 78 74 63 59 58 34
(0.24)
200
800 42 79 57 54 35 84 80 73 63 59 59 37
58 50 47 45 37 32 <20 64 57 54 51 44 22 70 62 53
(0.38)
1000
65 57 54 51 45 40 22 67 60 56 53 45 43 25 78 69 62 59 53 54 37 86 80 72 65 60 60 41
(0.47)

400 40 31 27 <20 56 49 45 40 37 38 <20 69 71 63 55 51 52 26 70 76 74 66 60 59 25


(0.09)
800 54 48 46 39 35 27 <20 62 56 51 46 41 41 <20 73 69 62 57 53 54 32 76 80 76 67 61 60 34
(0.38)
225
1000 42 23 75 69 62 58 54 54 35 78 79 73 66 61 61 38
(0.47) 60 54 52 45 40 36 21 64 58 53 58 42
1200
65 58 56 50 45 42 24 67 62 56 51 45 44 25 77 70 64 60 55 55 37 80 79 73 67 62 61 42
(0.57)

400
(0.09)
40 31 27 - <20 56 49 45 40 37 38 <20 69 71 63 55 51 52 26 70 76 74 66 60 59 25
800 54 48 46 35 27 <20 62 56 51 46 41 41 <20 73 69 62 57 53 54 32 76 80 76 67 61 60 34
39
(0.38)
250
1000 42 23 75 69 62 58 54 54 35 78 79 73 66 61 61 38
60 54 52 45 40 36 21 64 58 53 58 42
(0.47)
1200
65 58 56 50 45 42 24 67 62 56 51 45 44 25 77 70 64 60 55 55 37 80 79 73 67 62 61 42
(0.57)

800 43 38 37 27 23 <20 58 52 49 42 38 39 <20 69 66 64 57 52 54 26 73 75 73 66 60 59 32


(0.38)
1200 48 47 38 35 30 <20 63 57 53 47 43 42 22 71 67 65 58 53 55 33 76 75 73 68 62 61 39
52
(0.57)
300
1600 49 44 43 24 74 69 66 59 51 56 35 79 76 74 69 64 62 39
(0.76) 57 53 55 45 42 41 22 65 60 55
2000
63 57 55 50 47 45 25 69 64 61 54 49 48 28 76 71 68 61 55 57 37 81 77 74 68 63 62 41
(0.94)

1200 46 41 40 30 26 <20 60 54 51 44 40 41 21 69 66 64 57 52 54 25 75 77 75 68 62 61 34
(0.57)
1600 48 4B 38 35 32 <20 63 57 55 47 43 44 23 71 67 65 58 53 55 34 77 76 74 69 63 62 38
52
(0.76)
350
2000 46 46 26 74 69 66 59 54 56 36 79 76 74 69 64 62 39
57 53 55 45 42 41 21 67 61 58 51
(0.94)
2400
62 57 61 50 48 48 26 70 65 62 55 50 50 30 76 71 68 61 55 57 37 81 77 74 68 63 62 40
(1.13)

1500
(0.71)
45 40 39 29 25 - <20 61 55 52 45 41 42 21 70 67 65 58 53 55 31 76 78 76 70 63 60 35

2000 52 48 48 38 35 32 <20 63 57 55 47 43 44 23 71 67 65 58 53 55 32 77 76 74 69 63 62 37
(0.94)
400
2500 42 42 68 62 57 52 47 45 26 75 70 65 60 55 54 35 79 76 73 70 64 61 40
58 54 53 46 22
(1.18)
30400 74 62 41
62 57 61 50 48 48 26 70 65 62 55 50 50 31 76 71 68 61 55 57 37 81 77 68 63
(1.42)

.•. Ps =Inlet static pressure Dash (-) indicates NC level less than 20

Notes:
1. Ps is the inlet static pressure of VAV terminal
2. NC levels are calculated in accordance with ARI standard 885-98 as application data based on
the attenuation of environment, ceiling, tested room and ducts.
3. All NC sound data is based upon lOdb room absorption plus applicable data.

8
Dynacraft

ACCESSORIES
Multi - Discharge Attenuated Plenum
When the VAV Terminals need to be connected to down stream multiple diffusers, the
Multi-Discharge Plenum would be the ideal choice. The plenum adds additional attenuations to the
standard terminal performance. Connection size match the standard VAV terminals connection
size.

Multi-Discharge Silent Plenum Assembly

No. Accessory Standard Optional

1 Galvanized steel casting


V
2 1" (25.4mm) fiberglass insulation
V
3 Internal perforated galvanized steel wall V
4 Flanged inlet & outlet connections V
5 Outlet manual damper V
6 Round outlet V

Inlet S&D

\
Inlet S&D Box casing

\
Balance plate

==>c

900
Optional Ro~nd Outlets io---- H ----

A,B,C,D,E

Outlet type is as shown above. For example, A-12" round, C-8" round indicates that the
multiple outlet plenum consist of two outlets, they are A 12" round and C - 8" round.

9
Dynacraft

ACCESSORIES
Hot Water Reheat Coils
The hot water coil is available on DVS terminal units as an optional accessory. Frames are
constructed of galvanized steel. Coil dimension data is based on model DVS VAV terminals.
Although hot water reheat coil is typically applied on large projects, it is also suitable for small
AIC system where hot water is readily available.

Hot Water Reheat Coils Assembly

No. Accessory Standard Optional

1 Galvanized steel casting V


2 5/8" copper tubing V
3 Aluminum Corrugated Fins 0.145. 10FPI V
4 Diameter of water in and out is DN15 V
5 Fanged air inlet & outlet flanges V
6 Detecting valve V
7 Two-way control valve V
8 Three-way control valve V
9 Sand drive V
10 Strainer - balance valve assembly V
For other option products please notify in order.

Flange or S&D Purge Valve

co

1 ROW:31/S" A
Purge Valve
2 ROWS:42/S"

Model No. Coil Rows A B

125 1Rows/2Rows 8"'" (209mm) 9" (228mm)


150 1Rows/2Rows 8"'" (209mm) 9" (228mm)

175 1Rows/2Rows 1011'" (260mm) 10"'" (260mm)

200 1Rows/2Rows 1011<"


(260mm) 1011'" (260mm)

225 1Rows/2Rows 1211<"


(31lmm) 12'1'" (324mm)

250 1Rows/2Rows 121/" (31lmm) 12'1'" (324mm)

300 1Rows/2Rows 141/'" (362mm) 151/'- (387mm)

350 1Rows/2Rows 161/'" (412mm) 161/2" (419mm)

400 1Rows/2Rows 18"'" (463mm) 19" (482mm)

10
Dynacraft

ACCESSORIES
Performance Data of Hot Water heating Coils

Airflow CFM 100 200 300 400 500


(m3js) (0.05) (0.09) (0.14) (0.19) (0.24)
Model Coil Row GPM Head loss
No (LIs) in-wg t. Ps In-wg 0.031 0.051 0.098 0.150 0.209
(Pal (Pa) (7.8) (12.7) (24.5) (37.2) (51.9)
0.48 0.079 1.6 2.0 2.3 2.5 2.8
(0.03) (19.6) (5.5) (6.8) (7.9) (8.5) (9.6)
0.95 0.291 1.8 2.2 2.7 3.0 3.3
1 Row (0.06) (72.4) (6.1) (7.5) (9.2) (10.2) (11.3)
2.06 0.980 KW 2.1 2.6 3.2 3.8 4.0
(0.13) (243.8) (MBTU) (7.2) (8.9) (10.9) (13.0) (13.7)
5.07 3.350 2.4 3.3 4.0 4.5 5.0
(0.32) (833.1) (8.2) (11.3) (13.7) (15.4) (17.1)
125 t. Ps In-wg 0.051 0.091 0.189 0.291 0.402
& (Pa) (12.7) (22.5) (47.0) (72.4) (99.9)
150
0.95 0.079 2.6 3.6 4.3 4.9 5.4
(0.06) (19.6) (8.9) (12.3) (14.7) (16.7) (18.4)
2.06 0.291 3.1 4.3 5.1 5.8 6.4
2 Row (0.13) (72.4) KW (10.6) (14.7) (17.4) (19.8) (21.8)
5.07 1.461 (MBTU) 3.9 5.4 6.4 7.3 8.1
(0.32) (363.2) (13.3) ( 18.4) (21.8) (24.9) (27.7)
10.14 4.968 4.7 6.4 7.6 8.7 9.6
(0.64) (1235.5) (16.0) (21.8) (25.9) (29.7) (32.8)

Airflow CFM 300 400 500 630 700


Model (m3js) (0.14) (0.19) (0.24) (0.30) (0.33)
Call Row GPM Head loss
No (LIs) in-wg t. Ps In-wg 0.020 0.039 0.079 0.130 0.201
(Pal (Pa) (4.9) (9.8) (19.6) (32.3) (49.9)
0.48 0.110 2.7 3.0 3.2 3.5 3.7
(0.03) (27.4) (9.2) (10.2) (10.9) (11.9) (12.6)
0.95 0.370 3.2 3.5 3.8 4.1 4.4
1 Row (0.06) (92.0) (10.9) (11.9) (13.0) (14.0) (15.0)
2.06 1.280 KW 3.6 4.1 4.5 4.9
(MBTU) 5.3
(0.13) (318.2) (12.3) (14.0) (15.4) (16.7) (18.1)
5.07 4.350 4.5 5.2 5.7 6.2 6.6
(0.32) (1081.8) (8.2) (17.8) (19.5) (21.2) (22.5)
175 t. Ps In-wg 0.039 0.071 0.150 0.252 0.390
& (Pa) (9.8) (17.6) (37.2) (62.7) (96.9)
200
0.95 0.079 5.2 5.8 6.2 6.7 7.1
(0.06) (19.6) (17.8) (19.8) (21.2) (22.9) (24.2)
2.06 0.291 6.3 6.7 7.3 7.9 8.5
2 Row (0.13) (72.4) KW (21.5) (22.9) (24.9) (27.0) (29.0)
5.07 1.461 (MBTU) 7.6 8.4 9.2 10.0 10.7
(0.32) (363.2) (25.9) (28.7) (31.4) (34.1) (36.5)
10.14 4.968 9.0 9.9 10.9 11.9 12.7
(0.64) (1235.5) (30.7) (33.8) (37.2) (40.6) (43.4)

Airflow CFM 300 500 700 900 1100


Inlet Coil Row (m3js) (0.14) (0.24) (0.33) (0.42) (0.52)
GPM Head loss
Size (LIs) in-wg t. Ps in-wg 0.051 0.079 0.118 0.169 0.240
(Pal (Pa) (12.7) (19.6) (29.4) (42.1) (59.7)
0.48 0.051 3.0 3.7 4.3 4.8 5.3
(0.03) (12.7) (10.2) (12.6) (14.7) (16.4) ( 18.1)
0.95 0.531 3.5 4.4 5.2 5.8 6.3
1 Row (0.06) (132.2) (11.9) (15.0) (17.8) (19.8) (21.5)
2.06 1.799 KW 4.2 5.3 6.1
(MBTU) 6.9 7.5
(0.13) (447.4) (14.3) (18.1) (20.8) (23.6) (25.6)
5.07 5.118 5.3 6.6 7.7 8.6 9.4
(0.32) (1272.7) (18.1) (22.5) (26.3) (29.4) (32.1)
225 t. Ps in-wg 0.091 0.150 0.240 0.331 0.469
& (Pa) (22.5) (37.2) (59.7) (82.2) (116.5)
250
0.95 0.150 5.7 7.1 8.3 9.3 10.1
(0.06) (37.2) (19.5) (24.2) (28.3) (31.8) (34.5)
2.06 0.531 6.8 8.4 9.9 11.0 12.1
2 Row (0.13) (132.2) KW (23.2) (28.7) (33.8) (37.6) (41.3)
5.07 2.669 (MBTU) 8.5 10.7 12.4 13.9 15.2
(0.32) (663.7) (29.0) (36.5) (42.3) (47.5) (51.9)
10.14 7.079 10.1 12.7 14.7 16.5 18.0
(0.64) (1760.2) (34.5) (43.4) (50.2) (56.3) (61.5)

11
Dynacraft

ACCESSORIES
Performance Data of Hot Water heating Coils

Airflow CFM 600 800 1000 1200 1400


(m3js) (0.28) (0.38) (0.47) (0.57) (0.66)
Inlet Coil Rows GPM Head loss
Size (LIs) I:; Ps in-wg 0.039 0.071 0.098 0.150 0.201
i7;;~~ (Pa) (9.8) (17.6) (24.5) (37.2) (49.9)
0.48 0.209 4.6 5.2 5.7 6.2 6.7
(0.03) (51.9) (15.7) (17.8) (19.5) (21.2) (22.9)
0.95 0.701 5.4 6.2 6.8 7.4 7.9
(0.06) (174.3) (18.4) (21.2) (23.2) (25.3) (27.0)
1 Row KW 7.4 8.1 8.8 9.4
2.06 2.390 6.5
(MBTU) (22.2) (25.3) (27.7) (30.0) (32.1)
(0.13) (594.2)
5.07 7.130 8.1 9.3 10.2 11.1 11.9
(0.32) (1772.9) (27.7) (31.8) (34.8) (37.9) (40.6)
300 I:; Ps in-wg 0.071 0.142 0.189 0.291 0.390
(Pa) (17.6) (35.2) (47.0) (72.4) (96.9)
0.95 0.209 8.8 10.0 11.0 12.0 12.8
(0.06) (51.9) (30.0) (34.1) (37.6) (41.0) (43.7)
2.06 0.701 10.4 11.9 13.1 14.2 15.2
(0.13) (174.3) KW (35.5) (40.6) (44.7) (48.5) (51.9)
2 Row 14.9 16.5 17.8 19.1
5.07 2.539 (MBTU) 13.1
(0.32) (631.4) (44.7) (50.9) (56.3) (60.8) (65.2)
10.14 8.071 15.6 17.7 19.6 21.2 22.7
(0.64) (2006.9) (53.3) (60.4) (66.9) (72.4) (77.5)

Airflow CFM 800 1200 1600 2000 2400


(m3js) (0.38) (0.57) (0.76) (0.94) (1.13)
Inlet Coil Row GPM Head loss
Size (LIs) I:; Ps in-wg 0.059 0.118 0.181 0.209 0.272
i7;;~~ (Pa) (14.7) (29.4) (45.0) (51.9) (67.5)
0.48 0.240 5.6 6.7 7.7 8.5 9.2
(0.03) (59.7) (19.1) (22.9) (26.3) (29.0) (31.4)
0.95 0.831 6.7 8.0 9.1 10.1 10.9
(0.06) (206.6) (22.9) (27.3) (31.1) (34.5) (37.2)
1 Row KW 9.6 10.8 12.0 13.0
2.06 2.819 8.0
(700.9) (MBTU) (27.3) (32.8) (36.9) (41.0) (44.4)
(0.13)
5.07 8.618 10.0 12.0 13.6 15.1 16.3
(0.32) (2143.0) (34.1) (41.0) (46.4) (51.6) (55.6)
350 I:; Ps in-wg 0.110 0.209 0.350 0.402 0.520
(Pa) (27.4) (51.9) (87.1) (99.9) (129.2)
0.95 0.240 11.4 13.5 15.3 16.8 18.2
(0.06) (59.7) (38.9) (46.1) (52.2) (57.4) (62.1)
2.06 0.831 13.4 15.9 18.0 19.9 21.5
(0.13) (206.6) KW (45.7) (54.3) (61.5) (67.9) (73.4)
2 Row 16.7 19.5 22.5 24.8 26.9
5.07 3.189 (MBTU)
(0.32) (793.0) (57.0) (66.6) (76.8) (84.7) (91.8)
10.14 10.280 19.7 23.5 26.7 29.4 31.8
(0.64) (2556.1) (67.3) (80.2) (91.2) (100.4) (108.6)

Airflow CFM 1000 1400 1800 2200 2600


(m3js) (0.47) (0.66) (0.85) (1.04) (1.23)
Inlet Coil Row GPM Head loss
Size (LIs) I:; Ps in-wg 0.0359 0.071 0.110 0.150 0.201
i7;;~1g (Pa) (9.8) (17.6) (27.4) (37.2) (49.9)
0.48 0.299 6.9 8.0 8.9 9.7 10.5
(0.03) (74.4) (23.6) (27.3) (30.4) (33.1) (35.8)
0.95 0.925 8.1 9.5 10.6 11.6 12.5
(0.06) (230.1) (27.7) (32.4) (36.2) (39.6) (42.7)
1 Row KW 9.7 11.3 12.6 13.7 14.8
2.06 2.539
(631.4) (MBTU) (33.1) (38.6) (43.0) (46.8) (50.5)
(0.13)
5.07 9.059 12.2 14.1 15.8 17.2 18.6
(0.32) (2252.6) (41.7) (48.1) (53.9) (58.7) (63.5)
400 I:; Ps in-wg 0.071 0.142 0.189 0.291 0.390
(Pa) (17.6) (35.2) (47.0) (72.4) (96.9)
0.95 0.299 13.1 15.2 17.1 18.6 20.1
(0.06) (74.4) (44.7) (51.9) (58.4) (63.5) (68.6)
2.06 1.039 15.6 18.1 20.3 22.2 23.9
(0.13) (258.4) KW (53.3) (61.8) (69.3) (75.8) (81.6)
2 Row 19.6 22.8 25.5 27.8 30.0
5.07 4.248 (MBTU)
(0.32) (1056.3) (66.9) (77.8) (87.1) (94.9) (102.4)
10.14 10.902 23.3 27.0 30.3 33.1 35.7
(0.64) (2710.8) (79.5) (92.2) (103.4) (113.0) (121.9)

Correction Factor ForTemperature difference of entering hot water ( EWT DEG C - EAT DEG C)

~T (DEG F)
Correction Factor

T is the Temperature Range in deg. F. multiply correction factor by performance data to obtain required kw.

~ T (DEG C)
Correction Factor

12
Dynacraft

ACCESSORIES
Electric Reheat

Electric heaters are designed for use with Variable Air Volume Terminal Units. Normally electric
heaters are applied on small VAV systems, and it can also be used in the large VAV system where
hot water is not available.

Contaetor 5&0
Control enclosure

Airflow 8
'"
8

Manual
reset switch

gl"
8 .----A
(251mm)

A B
Model Inlet inch (mm) inch (mm)

8 1/4 9
125
(209) (228)
81/4 9
150 (209) (228)

10 1/4 10 1/4
175 (260) (260)

10 1/4 10 1/4
200 (260) (260)

12 1/4 12 3/4
225 (311) (324)

12 1/4 123/4
250 (311) (324)

14 1/4 15 1/4
300 (362) (387)

16 1/4 16 V2
350 (412) (419)

18 1/4 19
400 (463) (482)

13
Dynacraft

ACCESSORIES
Electric Reheat

Mounting external Cross flow


insulation towards Electric
velocity sensor
electric reheat heater
(filed mounting)

1-

(Inlet)
c:::::> Junction
0
0 box
0
Damper
L... o

LLi
(136mm)
C--------
(SOmm)
A
(lS0mm)

Airflow A B C D
Model
CFM inch inch inch inch
No
(m'/s) (mm) (mm) (mm) (mm)

85 - 432 8 1/4 9 21 3/4 4 7/8


125
(0.04 ~ 0.20) (209) (228) (552) (124)
108 - 648 81/4 9 21 3/4 57/8
150
(0.05 ~ 0.31) (209) (228) (552) (149)
135 - 864 10 1/4 10 1/4 21 3/4 67/8
175
(0.06 ~ 0.41) (260) (260) (552) (175)
189 - 1134 10 1/4 10 1/4 21 3/4 77/8
200
(0.09 ~ 0.54) (260) (260) (552) (200)
238 - 1435 12 1/4 12 3/4 21 3/4 87/8
225
(0.11 ~ 0.68) (311) (324) (552) (226)
297 - 1782 12 1/4 12 3/4 21 3/4 9 7/8
250
(0.14 ~ 0.84) (311) (324) (552) (251)
432 - 2538 14 1/4 15 1/4 27 '12 11 7/8
300
(0.20 ~ 1.20) (362) (387) (699) (302)
567 - 3456 16 1/4 16 '12 28 'h 137/8
350 (0.27 ~ 1.63) (419) (725) (403)
(412)
756 - 4536 18 1/4 19 15 7/8 157/8
400 (0.36 ~ 2.14) (482) (750) (750)
(463)

Performance Data of Electric Reheat Coils


Heating Capacity Pressure Difference P
Resistance at Max. Resistance at Max. Heating Stage
Model No Min.KW Max.KW
Airflow, Min. KW Airflow, Max. KW
125 0.5 <1.5 <0.020"wg(5Pa) <0.080"wg(20Pa) 2
150 0.5 <1.5 <0.020"wg(5Pa) <0.080"wg(20Pa) 2
175 1.0 2.0 <0.020"wg(5Pa) <0.080"wg(20Pa) 2
200 1.0 2.0 <0.020"wg(5Pa) <0.080"wg(20Pa) 2
225 1.0 4.0 <0.020"wg(5Pa) <0.080"wg(20Pa) 2
250 1.0 4.0 <0.020"wg(5Pa) <0.080"wg(20Pa) 2
300 1.3 6.5 <0.012"wg(3Pa) <0.060"wg(15Pa) 2
350 1.3 6.5 <0.012"wg(3Pa) <0.040"wg(10Pa) 2
400 1.3 7.8 <0.020"wg(5Pa) <0.040"wg(10Pa) 2

Notes:
Suggest airflow is no less than 70CFM(O.03M/s) per KW. If airflow is less than 70CFM (O.03M/S) per
KW, temperature will be too high and electric components life will be shorten. Temperature of airflow
is suggestion to be more than SOdeg.C.

14
Dynacraft

Formulas Formulas for Electric current

LAT = KW X 3160 + EAT Single phase I = KW X 1000


CFM V

KW = MBH / 30414 Three phase I = KW X 1000


V x 1. 73

Notes
KW Power of electric heater (KW)
L Air flow in heating is normally 20%'" 30% of maximum air flow
DT Temperature difference of inlet air of electric heater (deg.C).
V Rated voltage of electric heater is 220V/single phase.
I Rated electric current of electric heater (A)
LAT Leaving air temperature.
EAT Entering air temperature in deg. F.
CFM Air flow rate
KW Electric heater capacity.

15
Dynacraft

STORAGE

VAVTerminal must be stored in well ventilated and dry storerooms, preventing it from corrosive air
and damage. Dynacraft™ suggests that the products should be checked if storage is more than one
year. If the Relative humidity is more than 90% (RH), this will corrode and damage control
components ofVAVTerminals. When the relative humidity reaches 100%, for any period of time,
care must be taken before installation. Control components are not designed to operate in this
type of environment.

Notes for Installation:


1. A minimum of there duct diameters of straight duct upstream of inlet sensor is recommended.
2. VAVTerminal outlets are recommended to have internally lined insulation.
3. Unit installation, wiring between room sensor and VAV Terminals shall be provided by
others. Shielded cable is recommended.
4. Follow the wiring/piping diagram found on the inside of the control panel cover and
prevailing local codes.
5. All Control enclosures require adequate clearance to allow for field adjustments and service.

16