T EC H N I C A L A N D A P P L I C AT I O N G U I D E
SafeGear®
5/15 kV, up to 50 kA arc-resistant
switchgear
2 S A F E G E A R ® 5/ 1 5 K V, U P TO 5 0 K A A R C - R E S I S TA N T S W I TC H G E A R T E C H N I C A L A N D A P P L I C AT I O N G U I D E 3
—
SafeGear is ABB’s ANSI arc- —
resistant metal-clad switchgear Table of contents
line for short circuit currents up to
50 kA at rated maximum voltages
of 5 and 15 kV
005 – 007 General overview
— —
Table of contents General overview
SafeGear® 5/15 kV, up to 50 kA arc-resistant
switchgear
SafeGear is ABB’s ANSI arc-resistant metal-clad switchgear line for short circuit currents
up to 50 kA and below at rated maximum voltages of 5 and 15 kV.
For 5 kV applications, SafeGear switchgear utilizes Rating tables and additional details for all instru- Accessories Please contact your local ABB representative for
ABB VIY-60 potential transformers. For 15 kV appli- ment transformers can be found in the Switchgear SafeGear switchgear is available with the following more information.
cations, SafeGear uses ABB VIZ-11 and VIZ-75 PTs. All Components and Accessories Technical and Appli- accessories:
PTs are available in wye-wye, open delta, line to line cations Guide (1VAL104601-TG) • Breaker accessory kit including breaker, PT and —
Other reference documents
and line to ground connections. CPT, racking handle, and lifting yoke
Document Document Number
• Lift truck
SafeGear Descriptive Bulletin 1VAL108001-DB
— • Test cabinet and test jumper
SafeGear ratings* SafeGear Flyer 1VAL108004-FL
• SmartRackTM remote racking device
Installation, Operation and 1VAL108001-MB
• Electrically operated ground and test device
Rated maximum voltage level Maintenance Manual for SafeGear
• Manually operated ground and test device
Characteristic Unit 5 kV 8.25 kV 15 kV ADVAC Breaker Technical Guide 1VAL050501-TG
6.9, 7.2, 8.4, 11, 12, 12.47, AMVAC Breaker Technical Guide 1VAL050601-TG
Rated nominal voltages kV 2.4, 4.16, 4.8 4.8, 6.9, 7.2 13.2, 13.8, 14.4 Testing
Switchgear Components and 1VAL104601-TG
Main bus continuous current A 1200, 2000, 3000, 4000** SafeGear is design tested per IEEE C37.20.2 and in- Accessories Technical Guide
Short term current (rms) kA 25, 31.5, 40, 50 cludes the following production tests: Plenum Application Guide 1VAL104602-TG
Rated frequency Hz 60*** • One second dielectric test of 1800 VAC for control REF615 Feeder Protection Relay 1MAC105361-PG
Low frequency withstand (rms) kV 19 36 36 circuits Product Guide
Configuration software
Medium Voltage Pro (MVP) has been developed to
be a switchgear design tool and helps design of-
fices in creating a switchgear lineup including front
elevations and floor plans. A version of this soft-
ware is available for consultants and designers.
8 S A F E G E A R ® 5/ 1 5 K V, U P TO 5 0 K A A R C - R E S I S TA N T S W I TC H G E A R T E C H N I C A L A N D A P P L I C AT I O N G U I D E 9
— —
Construction Compartment types
Doors Circuit breaker compartment
SafeGear front doors consist of the breaker compartment, auxiliary unit SafeGear circuit breaker compartments are designed for maximum
compartments and LV compartments. operator safety by providing viewing windows and automatic latching,
three-position closed door racking.
— These doors are provided standard as bolted doors Padlock provisions are available on all front and The circuit breakers have self-aligning, fully automatic Secondary disconnect system
01 Bolted doors
— for 10-cycle, Type 2, 2B, 2C and 2BC with a multi- rear doors. These padlock provisions are used to primary and secondary contacts allowing operators A dual (50-pin) self-aligning secondary disconnect
02 Multi-point latch doors point latch (MPL) version as an option. For 0.5s arc lock the door closed to prevent access inside the to keep the door closed throughout the entire racking for control circuitry is provided as a standard fea-
duration, all doors are MPL type only. Doors with compartment. On breaker compartment doors, operation, which maintains the arc-resistant protec- ture. The female portion resides in the circuit
MPL utilize two viewing windows while bolted doors padlock provisions are also supplied on the rack- tion of the switchgear. These features make SafeGear breaker module. The secondary contacts are re-
have only one. All doors are hinged on the left as ing release lever, to prevent racking of the easy to install, operate and maintain while making cessed and are touch safe. No manual connection
standard (when facing the doors). Right-hand breaker. safety a priority. of secondary contacts is required.
hinged doors are available as an option.
Breaker and auxiliary unit doors include viewing Unique racking system and interlocks Primary shutters
Rear doors on the SafeGear product are used to ac- windows used for observing the position and sta- The racking system is unique and features a three-po- Primary shutters automatically cover the primary
cess the high voltage cable compartments. These tus of the components inside the compartment sition closed door system for all circuit breakers. The contacts when the breaker is not in the connected
doors are available in the following configurations: with the door closed. These doors can also be racking mechanism is integral to the circuit breaker, position. The shutters may be grounded metal or
• Split doors (top compartment/bottom compart- provided with the SmartRack mounting provi- so all moving parts can be inspected and maintained optional Lexan material. Primary shutter opening
ment) hinged and bolted sions for remote racking applications. outside the circuit breaker compartment and away and closing is forced by the circuit breaker move-
• Bolted, non-hinged split doors are also available as from energized primary parts. A solid stationary ment, rather than relying on springs or gravity. An
an option Due to the small footprint design, installation of ground contact engages the grounding contact of the integral interlock prevents opening of the shutter
protection and control devices on the breaker and circuit breaker prior to the coupling of both the pri- when the circuit breaker is removed, and can be
All front and rear doors are constructed using auxiliary unit doors are not possible. mary and secondary contacts and is continuous padlocked for added safety.
12-gauge painted steel. during the racking operation.
— —
01 02
10 S A F E G E A R ® 5/ 1 5 K V, U P TO 5 0 K A A R C - R E S I S TA N T S W I TC H G E A R T E C H N I C A L A N D A P P L I C AT I O N G U I D E 11
—
C I R C U I T B R E A K E R C O M PA R T M E N T
Removable, reusable
Automatic secondary boots
Primary
contacts
Secondary
disconnect
— —
01 02
12 S A F E G E A R ® 5/ 1 5 K V, U P TO 5 0 K A A R C - R E S I S TA N T S W I TC H G E A R T E C H N I C A L A N D A P P L I C AT I O N G U I D E 13
— —
Compartment types Compartment types
Instrument compartment Instrument compartment
— ABB mounts all protection and control devices in a —
01 Low voltage instru- 01 Low voltage
ment module isolated dedicated low voltage compartment. Each low volt- door panel 38"
for maximum safety age instrument compartment is completely iso- —
when working with 02 Low voltage cabinet
low voltage circuits lated and segregated from high-voltage compo- door panel 57"
— nents which ensures the safety of the operations
02 Low voltage cabinet
door panel 19" and maintenance personnel while they work on con-
trol and auxiliary circuits.
— —
02 02
14 S A F E G E A R ® 5/ 1 5 K V, U P TO 5 0 K A A R C - R E S I S TA N T S W I TC H G E A R T E C H N I C A L A N D A P P L I C AT I O N G U I D E 15
—
Insulators
Rating SafeGear
(5/15 kV, 50 kA)
easily extended at both ends to facilitate future Primary Disconnect Bushing 1200A Standard Glass Polyester
Characteristic Epoxy specification
expansions. Option Porcelain
Flexural strength, psi 17,400-21,700
2000A Standard Glass Polyester
Tensile strength, psi 10,150-13,050
The bus is epoxy insulated with an advanced Option Porcelain
Impact strength, ft-lb/in2 4.75-7.15
powder coating system that eliminates voids and Thermal class F
3000A Standard Porcelain
other potential defects, resulting in maximum Dielectric strength > 580
Option None
integrity of the insulation system. Removable, (short time), V/mil 4000A Standard Porcelain
reusable boots are provided at each joint to Option None
simplify access and maintenance.
Characteristic Glass polyester Porcelain
Flexural strength, psi 15,000-27,000 10,500 —
Insulating standoffs rigidly support the bus. This
Tensile strength, psi 14,000 6,000 Main bus compartment
includes risers, the connections from stationary
Izod impact, ft-lb per 6-12 1.5
primary contacts to the main bus and runbacks the Continuous current Short-circuit rating (kA) Quantity/phase Size
inch of notch
connections from the stationary primary contacts 1200 A 25, 31.5, 40, 50 1 1/4" x 4"
Thermal shock, cycles 100+ 1
to line or bus terminations. Internal standoffs and 32°- 2300°F 1200 A 50 1 3/4" x 4"
inter-frame supports are polyester for 1200 A and Dielectric strength 350-375 300 2000 A 25, 31.5, 40, 50 1 3/4" x 4"
2000 A applications, porcelain for 3000 A (short time), V/mil
3000 A 25, 31.5, 40, 50 2 3/4" x 4"
applications, and epoxy for 4000 A applications. Dielectric constant 4-6 6
4000 A 25, 31.5, 40, 50 2 1/2" x 6"
Porcelain bus supports are available as an option.
Reusable boot
Main bus
Epoxy 3 phase
interframe support
—
01
Compartment types 02
Cable compartment
— The design of the cable compartments for SafeGear former up to 75 kVA, 3-phase or 50 kVA single
01 Cable compart-
ment (main bus - cover provides an efficient layout with ample room for phase.
installed) | Various stress cones and a choice of cable terminations and
application designs in
cable compartments lug types. Customers also have the flexibility of top or Primary cable compartments are provided with re-
bottom cable entry. Top and bottom connections can movable, non-painted stainless steel cover plates
also be made to bus duct. used to install conduit or cable sealing glands.
12-gauge type 304 stainless steel is used in
In two-high arrangements with stacked circuit break- Safegear for the cover plates. Cover plates are re-
ers, steel barriers separate the upper and lower cable quired for top and bottom of the cable compart-
compartments to isolate the primary circuits. All con- ment. All conduit/cable entries must be sealed to
figurations come standard with lug boots and have prevent arc-faults from leaking through the instal-
the option for cable supports to make field connec- lation at the cover plates. ABB recommends the use
tions more secure. of sealing glands for all primary cables to ensure
arc-resistant design integrity is not compromised.
Cable compartments are available with optional read-
—
ily accessible zero sequence (ground sensor) current 01 Surge arrestors
—
transformers, surge arrestors or capacitors and/or
02 Connection of up to
ground studs on the bus risers. When a draw-out fuse eight cables per phase
(three cable lugs shown).
compartment is installed in the front of the switch- Contact factory for more
gear, the rear cable compartment offers room for a than eight cables per
phase requiremments.
large three-phase floor-mounted control power trans-
Larger CPT specs avail-
able. contact factory if
larger sizes are needed.
—
03 Large fixed-mount
CPT up to 75 kVA 3-phase
or 50 kVA single-phase
Cable lug
adapters
36”
minimum
Riser bus space
for cable
terminations
Reusable
boot
Plated joint,
boot removed
—
01
—
03
18 S A F E G E A R ® 5/ 1 5 K V, U P TO 5 0 K A A R C - R E S I S TA N T S W I TC H G E A R T E C H N I C A L A N D A P P L I C AT I O N G U I D E 19
— —
Arc chamber Front door types
and plenum Circuit breaker doors
— A system of chambers inside the switchgear lineup Installation expertise is required to properly install — Bolted breaker door designs
01 Arc exhaust flowing 01 For type 2, 2B, 2C
through a typical serves as an exhaust system which vents arc gases and commission arc-resistant metal-clad switch- and 2BC 10-cycle arc
frame of switchgear away from personnel and the affected cubicle in gear. Consult with the factory for assistance. duration only with
— ratings up to 31.5 kA
02 Arc exhaust flow in a the case of an arc fault. Vents and flaps are located The vent chambers used for channeling arc faults —
typical switchgear lineup inside the chamber system which leads to a top- are also used as heat ventilation ducts during nor- 02 For type 2, 2B, 2C
and 2BC 10-cycle arc
mounted plenum on the enclosure. Once inside the mal operating conditions. Ventilation is necessary duration only with
plenum, the gases and pressure are directed to an to ensure equipment will operate within the ANSI ratings of 40 and 50 kA
—
area outside the building and away from personnel standard design temperature limits. These cham- 03 For 10-cycle arc
and other equipment. The plenum sections feature bers should not be blocked, or otherwise modified duration only with
ratings up to 31.5 kA
external flanges for ease of bolting sections to- to impede the normal flow of air. —
gether during installation. ABB developed this vent- 04 Required for 25-50
kA with 0.5s arc dura-
ing system which combines the internal chamber tion, type 2/2B only
and plenum and holds patents on the construction
details of this truly innovative design.
— —
Plenum exhaust clearance requirements 01 02
For proper and safe arc fault by-product exhaust-
ing, it is recommended that an eight foot cylinder
projecting out 15 feet be clear of all objects and
Single handle multi-point latch (MPL) breaker door designs
personnel at the point where the plenum exits the
building. Refer to the Plenum Technical Application
Guide, 1VAL1004602-TG, for more details.
—
01
— —
03 04
Notes:
1. Doors in figures 1-3 cannot be used when 0.5s arc duration is required.
2. When MPL breaker doors are supplied (Fig.3&4), all low voltage instrument compartment doors will be supplied with matching door handles.
3. When bolted breaker doors are supplied (Fig.1&2), all low voltage instrument compartment doors will be single handle style.
4. PT, CPT and CPT fuse auxiliary unit doors will utilize the same door securing method (bolted vs. MPL) as shown on the breaker doors.
5. When type 2C or 2BC is required, arc duration is limited to 10-cycles and all front doors
except low voltage/instrument compartment must be bolted type.
—
02
20 S A F E G E A R ® 5/ 1 5 K V, U P TO 5 0 K A A R C - R E S I S TA N T S W I TC H G E A R T E C H N I C A L A N D A P P L I C AT I O N G U I D E 21
— —
Available frame types Available frame types
One-high frames Two-high frames
Description — Description Application notes
Dimensions
The one-high, bottom mounted device frame con- The two-high breaker frame consists of two 38- 1. Arrangements shown are available for all ratings
Frame Width (in) Height (in)* Depth (in)
sists of a 57-inch instrument compartment stacked inch breaker compartments with a 19-inch instru- except as noted
2000/3000/4000 36 129.5 86.5 or 93.5
over a 38-inch breaker, PT, CPT or draw-out fuse ment compartment in between for two breakers in 2. Maximum cumulative load at main bus limited
A breaker
compartment. All other frames 36 118 86.5 or 93.5
a single frame. See page 20 for information on di- to 2500A. Refer to IEEE C37.20.2, section
mensions and available options. 8.4.2.3, for further details on determining load-
— * Height includes plenum ing of these frame configurations
Cable termination information —
Options 3. Maximum cumulative load at main bus limited
Cable size # of terms # of terms GCT Cable termination information
single pad bifurcated option
• Ground CTs to 3000 A if main bus rating is 3000A. If 3200 A
Cable size # of terms GCT option
per phase pad per • Surge arrestors single pad
or higher main bus is used, then maximum cu-
phase* -- Distribution per phase mulative load is 3200 A. Refer to IEEE C37.20.2,
#2 AWG 4 8 BYZ-S -- Intermediate #2 AWG 4 BYZ-S section 8.4.2.3, for further details on determin-
#4 AWG 4 8 BYZ-S -- Station #4 AWG 4 BYZ-S ing loading of these frame configurations
500 MCM 4 8 BYZ-S • Surge capacitor 500 MCM 4 BYZ-S 4. Available for 10-cycle arc duration only
750 MCM 4 8 BYZ-L • Ground studs 750 MCM 4 BYZ-L 5. Available for 0.5s arc duration only
1000 MCM (2-hole) 2 4 BYZ-S • Space heaters 1000 MCM (2-hole) 2 BYZ-S 6. Available for 40-50kA, 10-cycle type 2C/2BC
1000 MCM (4-hole) 1 2 BYZ-S • Cable supports 1000 MCM (4-hole) 1 BYZ-S only
7. For Type 2C/2BC applications, all doors are of
* Bifurcated lug pad requires 93.35-inch depth frame
bolted type
All ratings (refer to page 19 for door details and pages 36-43 for floorplans)
All ratings refer to page 19 for door details and pages 36-43 for floorplans
— —
Available frame types
Available frame types Breaker and auxiliary frames
Breaker and auxiliary frames All ratings refer to page 19 for door details, page 21 for application notes and pages 36-43 for floorplans
Description — —
Dimensions 01 Less than or equal to
The two-high breaker and auxiliary frame consists 31.5 kA (breaker below)
Frame Width (in) Height (in)* Depth (in)
of two 38-inch compartments with a 19-inch instru- —
2000/3000 A 36 129.5 86.5 or 93.5 02 Less than or equal to
ment compartment in between for one breaker and 31.5 kA (breaker below)
breaker
an auxiliary device in a single frame or one 38-inch All other frames 36 118 86.5 or 93.5
compartment with 19-inch low voltage and two 19-
inch auxiliary compartments for equipment with * Height includes plenum
All ratings refer to page 19 for door details, 21 for application notes and pages 36-43 for floorplans
—
02 See note 4 See note 4 See note 4
— —
01 02
24 S A F E G E A R ® 5/ 1 5 K V, U P TO 5 0 K A A R C - R E S I S TA N T S W I TC H G E A R T E C H N I C A L A N D A P P L I C AT I O N G U I D E 25
— —
Available frame types Available frame types
Breaker and auxiliary frames Breaker and auxiliary frames
Refer to page 21 for application notes and pages 36-43 for floorplans Refer to page 21 for application notes and pages 36-43 for floorplans
— —
01 Less than or equal to 01 Greater than or equal
31.5 kA (breaker below) to 40 kA (breaker above)
—
02 Less than or equal to
31.5 kA (breaker above)
—
03 Greater than or equal
to 40 kA (breaker below)
— —
See note 4
01 02
— See notes 5 and 6 See notes 5 and 6 See notes 5 and 6
01
— —
Available frame types
Available frame types Auxiliary frames
Description —
Dimensions
The two-high auxiliary frame consists of compart-
Frame Width (in) Height (in)* Depth (in)
ments with a 19-inch instrument compartment in
All frames 36 118 86.5 or 93.5
between multiple auxiliary devices per frame.
— * Height includes plenum
CPT=control power
transformer Options
—
LVC=low voltage
• Space heaters
compartment/instru- • Incoming/outgoing cables
ment compartment
—
• Surge arrestors
PT=potential transformer -- Distribution
—
DOF=drawout fuse
-- Intermediate
-- Station
• Ground studs
• Cable supports
• IR windows
• SmartRack® remote racking system
• SwitchgearMD™ 24x7 monitoring system
All ratings refer to page 19 for door details and page 21 for applciation notes and pages 36-43 for floorplans
— —
Available frame types Available frame types
Auxiliary frames Auxiliary frames
Greater than or equal to 40 kA (refer to page 19 for door details, page 21 for application notes and pages 36-43 for floorplans)
Refer to page 19 for door details and page 21 for application notes and pages 36-43 for floorplans
—
01 Less than or
equal to 31.5 kA
—
02 Greater than or
equal to 40 kA, Type
2C/2BC, 10-cycle and
all 0.5s ratings
See note 4
See notes 5 and 6 See notes 5 and 6 See notes 5 and 6 See notes 5 and 6 See notes 5 and 6
See notes 5 and 6 See notes 5 and 6 See notes 5 and 6 See notes 5 and 6 See notes 5 and 6
— —
Typical arrangements Typical arrangements
Main-Tie-Main: 1200 A/2000 A, up to and including 50 kA Main-Tie-Main: 3000 A and 4000 A, up to and including 50 kA
Arrangements are the same for 5, 8.25 and 15 kV (refer to page 19 for door details and page 21 for application notes) Arrangements are the same for 5, 8.25 and 15 kV (refer to page 19 for door details and page 21 for application notes)
8.119
21.000
95.000 INSTRUMENT INSTRUMENT INSTRUMENT INSTRUMENT INSTRUMENT INSTRUMENT 94.997 INSTRUMENT INSTRUMENT INSTRUMENT INSTRUMENT INSTRUMENT INSTRUMENT
LPT LPT
LINE LINE
SIDE SIDE
LPT LPT
1200A 1200A 1200A 1200A LINE LINE
SIDE SIDE
1200A 1200A 1200A 1200A
— —
Typical arrangements Typical arrangements
Main-Tie-Main: 3000 A and 4000 A, 40 kA and 50 kA Main-Tie-Main: 1200 A/2000 A, 40 kA and 50 kA
Arrangements are the same for 5, 8.25 and 15 kV (refer to page 19 for door details and page 21 for application notes) Arrangements are the same for 5, 8.25 and 15 kV (refer to page 19 for door details and page 21 for application notes)
8.119
21.003
LPT LPT
BPT BPT
2000A 2000A 2000A
1200A 1200A C AUT ION C AUT ION C AUT ION 1200A 1200A
See notes 6 and 7 See notes 6 and 7 See notes 5 and 6 See notes 5 and 6
LPT LPT
LINE LINE
SIDE SIDE
— —
Typical arrangements Typical arrangements
Main with Feeders: 1200 A/2000 A, 40 kA and 50 kA Main with Feeders: 3000 A and 4000 A, up to and including 50 kA
Arrangements are the same for 5, 8.25 and 15 kV (refer to page 19 for door details and page 21 for application notes) Arrangements are the same for 5, 8.25 and 15 kV (refer to page 19 for door details and page 21 for application notes)
8.119 8.119
21.003
21.000
INSTRUMENT
3000A
1200A 1200A 1200A
STORAGE
See note 4
LPT
LINE 1200A 1200A 1200A
SIDE
BPT
BUS
SIDE
PT
LINE
SIDE
1200A 1200A 1200A
2000A 1200A 1200A 1200A 1200A
PT
BUS
SIDE
— —
Civil engineering details Civil engineering details
Typical side views, floor plans, and clearances Typical side views, floor plans, and clearances
SafeGear switchgear two-high frames SafeGear switchgear breaker and auxiliary
Circuit breaker: 1200 A/1200 A Circuit breaker: 2000 A
Refer to page 19 for door details Refer to page 19 for door details
Refer to page 45 for frame weights Refer to page 45 for frame weights
93.350 93.350
86.350 86.350
40.375 40.375
1.000
CLOSED
9.093
OPEN
PLENUM
4.863 1.000
21.000 20.000 22.000
VENT VENT
PLENUM
2.000 2.000
2.000 2.000
VENT
19.000 PT
38.000
NEMA
4 HOLE VENT VENT FLAP
LUG PAD AUTO CLOSES
1200A MAIN BUS
DURING ARC
BREAKER
MAIN BUS
INSTRUMENT
VENT CHAMBER
COMPARTMENT
38.000 WIRING
19.000 INSTRUMENT COMP VENT CHAMBER
95.000 NEMA
VENT FLAP
6 HOLE
INTERCONNECT VENT 95.000 INTERCONNECT LUG PAD
WIRING
WIRING
VENT
59.000
NEMA
4 HOLE
LUG PAD
38.000 40.000
39''[990.63 mm]
38.000
1200A 2000A
BREAKER BREAKER
VENT FLAP
AUTO CLOSES
DURING ARC
SECTION VIEW DETAIL
SECTION VIEW DETAIL
93.350
93.350 86.350
86.350 25.500
25.500
0.375 18.500 18.500
0.375
1.000 2.250 CABLE BARRIER
1.000
1.000 1.000
1.000 1.000 36.000 27.000
36.000 27.000
1.000
1.000
— —
Civil engineering details Civil engineering details
Typical side views, floor plans, and clearances Typical side views, floor plans, and clearances
SafeGear switchgear breaker and auxiliary SafeGear switchgear one-high frames
Circuit breaker: 2000 A, with double set of PTs Circuit breaker: 3000 A or 4000 A
Refer to page 19 for door details Refer to page 19 for door details
Refer to page 45 for frame weights Refer to page 45 for frame weights
93.350 93.350
86.350
86.350
40.375
40.375
CLOSED
CLOSED 9.093
9.093 OPEN
OPEN
4.863 VENT BOX
4.863 1.000
1.000
PLENUM PLENUM
2.000 2.000
VENT FLAP
PT
COMMUNICATION
WIRING
COMMUNICATION
WIRING
VENT FLAP
VENT FLAP
INSTRUMENT INTERCONNECT
VENT CHAMBER NEMA 95.000
95.000 19.000 COMPARTMENT 6 HOLE WIRING
LUG PAD
VENT
INTERCONNECT VENT
WIRING
NEMA
4 HOLE
LUG PAD
39.000 38.000
38.000
2000A
BREAKER
VENT FLAP
AUTO CLOSES VENT FLAP
DURING ARC AUTO CLOSES
SECTION VIEW DETAIL SECTION VIEW DETAIL DURING ARC
93.350 93.350
86.350 86.350
25.500 25.500
18.500 18.500
0.375 0.375
1.000 1.000
1.000 1.000
CONTROL CABLE ENTRY AREA FLOOR PLAN DETAIL CONTROL CABLE ENTRY AREA FLOOR PLAN DETAIL
NOTE: NOTE:
CABLE CONDUIT ENTRY HOLE CABLE CONDUIT ENTRY HOLE
MUST BE WITHIN AREA MUST BE WITHIN AREA
OUTLINED WITH A 1.00 OUTLINED WITH A 1.00
CLEARANCE AROUND THE CLEARANCE AROUND THE
CABLE CUTOUT CABLE CUTOUT
FOR CONDUIT CAP AND GLAND FOR CONDUIT CAP AND GLAND
40 S A F E G E A R ® 5/ 1 5 K V, U P TO 5 0 K A A R C - R E S I S TA N T S W I TC H G E A R T E C H N I C A L A N D A P P L I C AT I O N G U I D E 41
— —
Civil engineering details Civil engineering details
Typical side views, floor plans, and clearances Seismic applications
REAR OF SWGR
Note: Vent box assembly used only for 2000 - 4000 A ratings BUS & CABLE COMPT. BUS & CABLE COMPT. BUS & CABLE COMPT.
—
Typical civil engineering dimensions - inches (mm)
Depth (D)
SafeGear 86.5 or 93.5" for 0.5s or if
0.5s MPL doors are used
SafeGear 85 or 92" for 10-cycles with
bolted door design
CIRCUIT BREAKER COMPT. CIRCUIT BREAKER COMPT. CIRCUIT BREAKER COMPT.
Dimension H:
• 24 inches for 1200 A lineups
• 40 inches for 2000 A/3000 A lineups
— —
Civil engineering details Civil engineering details
Seismic applications Seismic applications
REAR OF SWGR
REAR OF SWGR
5.000
TYP
—
03 Weld Location
— for Ip = 1.0
02 Bolt Location 2X– Front on each frame
for Ip = 1.5 BUS & CABLE COMPT. BUS & CABLE COMPT. BUS & CABLE COMPT. 2X– Rear on each frame
2X– Front on each frame
2X– Middle on each frame
2X– Rear on each frame
—
02 E70 WELD
TYPICAL FRAME 1/8" FILLET X 5"LG
FRONT OF SWGR FRONT OF SWGR TYP
—
03
44 S A F E G E A R ® 5/ 1 5 K V, U P TO 5 0 K A A R C - R E S I S TA N T S W I TC H G E A R T E C H N I C A L A N D A P P L I C AT I O N G U I D E 45
—
Civil engineering details
—
Seismic applications Frame weights calculation
All frame styles
04 Weld Location
for Ip = 1.5 To calculate the weight of a frame, identify the cur- Basic frame Circuit breaker Weight
Left End Shipping Split
rent rating for each module. Select the weights configuration (rating) lbs kg
2X– Front on each frame
3X– Left and Right from the appropriate column in the adjoining table One circuit 1200 2023 918
side of shipping split
for SafeGear components. breaker
2X– Rear on each frame 2000 2441 1107
Intermediate Ship-
3000 3331 1511
ping Split
A frame consists of one bus and cable module and
2X– Front on each frame 4000 3461 1570
3X– Right side of the appropriate circuit breaker and auxiliary mod-
shipping split Two circuits 1200/1200 3013 1367
ules. The weight of the circuit breaker is given sep- breakers
2X– Rear on each frame 1200/2000 3302 1498
Right End Shipping Split arately and must be added.
2X– Front on each frame One circuit 1200 2440 1107
3X– Right side of breaker, one VT 2000 2858 1296
shipping split Low voltage modules may contain significant
2X– Rear on each frame 3000 3748 1700
amount of secondary equipment and wiring. De-
One circuit 1200 2859 1297
pending on the extent of secondary protection and
breaker, two VTs 2000 3277 1486
control equipment, ABB recommends adding 20%
REAR OF SWGR to 50% of the empty weight of the module. One circuit 1200 3210 1456
breaker, one VT 2000 3628 1646
Typical frame weights are listed in the adjoining ta- One circuit 1200 2590 1175
breaker, one CPT 2000 3008 1364
ble. Weights include all modules and components fuse
previously listed.
Note: These weights do not include the circuit break-
ers. Please reference the AMVAC or ADVAC breaker
technical guides for more information
BUS & CABLE COMPT. BUS & CABLE COMPT. BUS & CABLE COMPT.
10
LEFT END ONE , TWO OR THREE INTERMEDIATE ONE , TWO OR RIGHT END ONE , TWO OR
FRAME SHIPPING SPLIT THREE FRAME SHIPPING SPLIT THREE FRAME SHIPPING SPLIT
FRONT OF SWGR
—
04
46 S A F E G E A R ® 5/ 1 5 K V, U P TO 5 0 K A A R C - R E S I S TA N T S W I TC H G E A R T E C H N I C A L A N D A P P L I C AT I O N G U I D E 47
—
Heat dissipation
All frame styles
To calculate the total heat dissipation, in watts by 5-15 kV ADVAC Device or CB Bussing and Total
frame, select the proper element from the and AMVAC CBs enclosure
adjoining table for SafeGear components. 1200 A CB 413 713 1426
2000 A CB 845 1145 2290
Breakers can be either ADVAC or AMVAC and are 3000 A CB 845 1520 3040
assumed to operate at full rated current. 4000 A CB 1502 2702 5404
CTs (sets of 3)
600:5 23 45
1200:5 45 90
2000:5 75 150
3000:5 113 225
4000:5 150 300
Auxiliary frames 150 300
Main bus per frame
1200 A 108 216
2000 A 180 360
3000 A 115 230
4000 A 204 409
CPTs
CPT - 5 KVA, 1 60 120
Phase
CPT - 10 KVA, 1 115 230
Phase
CPT - 15 KVA, 1 175 350
Phase
CPT - 25 KVA, 1 295 590
Phase
CPT - 50 KVA, 1 450 900
Phase
CPT - 45 KVA, 3 520 1040
Phase
CPT - 75 KVA, 3 885 1770
Phase
Heaters - 300 75 75
WATT heater at 75
WATTS (each)