LOAD SCHEDULE AND COMPUTATIONS

CKT. NO.
LOAD DESCRIPTION NO. OF OUTLETS
VOLTS WATTSAMPERESCKT. BREAKER
1 Lighting Outlet 6 230 360 1.57 15 AT
2 Lighting Outlet 8 230 480 2.09 15 AT
3 Lighting Outlet 230 0 0 15 AT
4 Lighting Outlet 230 0 0 15 AT
5 Convenience Outlet 9 230 1,620 7.04 30 AT
6 Convenience Outlet 230 0 0 30 AT
7 Convenience Outlet 230 0 0 30 AT
8 ACU Outlet 1 230 746 3.24 30 AT
9 Spare 230
10 Spare 230
TOTAL 230 3,206 13.94

COMPUTATION
IT = 3206/230 @ 0.80DF = 11.15 AMP
MAIN CKT. PROTECTION:
MAIN FEEDER:
SIZE OF WIRE CONDUIT
2 - 3.5mm^2 15mmø PVC
2 - 3.5mm^2 15mmø PVC
2 - 3.5mm^2 15mmø PVC
2 - 3.5mm^2 15mmø PVC
2 - 3.5mm^2 15mmø PVC
2 - 3.5mm^2 15mmø PVC
2 - 3.5mm^2 15mmø PVC
2 - 5.5mm^2 20mmø PVC

11.15