LEGEND AND NOTES :

1 1

2 2

3 3
PANEL INPUT & OUTPUT NEW

4 4

5 5
INCOMING OUTGOING
FROM INPUT TO PANEL BYPASS
EXTERNAL MCCB 3P/160A
COS 4P/160A EXISTING
BYPASS MCCB 3P/160A 3Ph+N
6 INPUT UPS 6
PANEL BYPASS 50Hz
OUTGOING

EXISTING 400Vac
3Ph+N EXTERNAL BYPASS

50Hz
7 7
400Vac

PANEL BYPASS SYSTEM PANEL MSB-1-UPS


8 MCCB 3P/250A EXISTING EXISTING 8

9 EXTERNAL BYPASS UPS 9

PANEL MSB-1-UPS 0 12-08-2019 FOR PROPOSE


EXISTING
UPS 1 EXISTING DISTRIBUSI
REV DATE REMARKS

10 10 Pemilik/Owner
OUTGOING
TO DISTRIBUTION
MCCB 3P/250A MCCB 3P/125A MCCB 3P/125A MCCB 3P/250A 3Ph+N DISTRIBUSI
INCOMING
400VAC
11 FROM PLN 11
50Hz
3Ph+N
400VAC PROJECT
MAIN INPUT UPS INPUT UPS 1 OUTPUT UPS 1 MAIN OUTPUT UPS DISTRIBUSI DISTRIBUSI
50Hz
12 12

UPS 2 EXISTING
DISTRIBUSI ELECTRICAL UPS
MODULYS GP 2.0
13 13

CONTRACTOR
MCCB 3P/125A MCCB 3P/125A
DISTRIBUSI

14 14

INPUT UPS 2 OUTPUT UPS 2 PT. Laplasindo Pratama

NAMA GAMBAR
15 15

MIGRATION PREPARATION SINGLE LINE DIAGRAM


UPS
16 16
NAMA TTD TANGGAL

Disetujui

17 17

Digambar LPEFT 12-08-2019

JENIS GAMBAR
18 18
SHOP DRAWING
SKALA NO.GAMBAR NO.LEMBAR UKURAN

1
NTS