QATAR TRANSMISSION SYSTEM EXPANSION - PHASE-9

GTC/240/2008
S2-2 PACKAGE

BATTERY SHORT CIRCUIT CURRENT

NOMINAL SYSTEM VOLTAGE , (EB) = 110 V


NUMBER OF CELLS = 85 Nos.
CELL DISCHARGE DURATION = 10 Hrs

BATTERY SHORT CIRCUIT CURRENT (I sc) = EB / RTB 1


1
TOTAL RESISTANCE OF BATTERY CIRCUIT, RTB = RB + RC 2
2
BATTERY RESISTANCE ,RB (mW ) = (31 X EB) / I 10hr 3

BATTERY CONNECTORS RESISTANCE ,RC = 2.25 mW (ASSUMED VALUE)

1 132/11KV QATAR LEADERSHIP ACADEMY SUBSTATION :

110V BATTERY BANK RATING IS ( I10hr) = 625 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 5.456 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 7.706 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 14274.59 A

= 14.27 KA (Approx)

2 132/11KV UMM QARIN SUBSTATION :

110V BATTERY BANK RATING IS ( I10hr) = 625 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 5.456 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 7.706 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 14274.59 A

= 14.27 KA (Approx)

3 132/11KV SEMAISMA SUBSTATION :

110V BATTERY BANK RATING IS ( I10hr) = 625 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 5.456 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 7.706 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 14274.59 A

1 of 10
= 14.27 KA (Approx)

2 of 10
QATAR TRANSMISSION SYSTEM EXPANSION - PHASE-9
GTC/240/2008
S-4 PACKAGE

BATTERY SHORT CIRCUIT CURRENT

NOMINAL SYSTEM VOLTAGE , (EB) = 110 V


NUMBER OF CELLS = 85 Nos.
CELL DISCHARGE DURATION = 10 Hrs

BATTERY SHORT CIRCUIT CURRENT (I sc) = EB / RTB 1


1
TOTAL RESISTANCE OF BATTERY CIRCUIT, RTB = RB + RC 2
2
BATTERY RESISTANCE ,RB (mW ) = (31 X EB) / I 10hr 3

BATTERY CONNECTORS RESISTANCE ,RC = 2.25 mW (ASSUMED VALUE)

1 66/11KV GRAND HAMAD AVENUE NEW SUBSTATION :

110V BATTERY BANK RATING IS ( I10hr) = 830 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 4.11 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 6.36 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 17299.86 A

= 17.30 KA (Approx)

2 66/11KV UMM GHUWALINA SUBSTATION :

110V BATTERY BANK RATING IS ( I10hr) = 830 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 4.11 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 6.36 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 17299.86 A

= 17.30 KA (Approx)

3 66/11KV KHALIFAT SUBSTATION (REPLACEMENT):

110V BATTERY BANK RATING IS ( I10hr) = 900 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 3.79 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 6.04 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 18215.27 A

= 18.22 KA (Approx)

3 of 10
QATAR TRANSMISSION SYSTEM EXPANSION - PHASE-9
GTC/240/2008
4 66/11KV OLD GHANIM SUBSTATION (REPLACEMENT):

110V BATTERY BANK RATING IS ( I10hr) = 830 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 4.11 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 6.36 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 17299.86 A

= 17.30 KA (Approx)

5 66/11KV NAEEJA LOCAL SUBSTATION (UPGRADE):

110V BATTERY BANK RATING IS ( I10hr) = 525 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 6.495238 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 8.745238 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 12578.27 A

= 12.58 KA (Approx)

4 of 10
QATAR TRANSMISSION SYSTEM EXPANSION - PHASE-9
GTC/240/2008
S-6 PACKAGE

BATTERY SHORT CIRCUIT CURRENT

NOMINAL SYSTEM VOLTAGE , (EB) = 110 V


NUMBER OF CELLS = 85 Nos.
CELL DISCHARGE DURATION = 10 Hrs

BATTERY SHORT CIRCUIT CURRENT (I sc) = EB / RTB 1


1
TOTAL RESISTANCE OF BATTERY CIRCUIT, RTB RB + RC 2
=
2

BATTERY RESISTANCE ,RB (mW ) = (31 X EB) / I 10hr 3

BATTERY CONNECTORS RESISTANCE ,RC = 2.25 mW (ASSUMED VALUE)

1 66/11KV MERGHAB AL REMATH SUBSTATION (REPLACEMENT):

110V BATTERY BANK RATING IS ( I10hr) = 690 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 4.94 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 7.19 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 15294.71 A

= 15.29 KA (Approx)

2 132/33KV DUKHAN-2 SUBSTATION :

110V BATTERY BANK RATING IS ( I10hr) = 830 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 4.11 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 6.36 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 17299.86 A

= 17.30 KA (Approx)

3 132/11KV DUKHAN JUMAILIYAH JUNCTION SUBSTATION :

110V BATTERY BANK RATING IS ( I10hr) = 690 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 4.94 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 7.19 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 15294.71 A

5 of 10
= 15.29 KA (Approx)
QATAR TRANSMISSION SYSTEM EXPANSION - PHASE-9
GTC/240/2008
4 132/11KV AL NASRANIYA SUBSTATION :

110V BATTERY BANK RATING IS ( I10hr) = 505 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 6.75 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 9.00 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 12218.86 A

= 12.22 KA (Approx)

5 132/11KV AL JIFARA SUBSTATION :

110V BATTERY BANK RATING IS ( I10hr) = 690 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 4.942029 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 7.192029 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 15294.71 A

= 15.29 KA (Approx)

6 of 10
7 of 10
QATAR TRANSMISSION SYSTEM EXPANSION - PHASE-9
GTC/240/2008
S-7 PACKAGE

BATTERY SHORT CIRCUIT CURRENT

NOMINAL SYSTEM VOLTAGE , (EB) = 110 V


NUMBER OF CELLS = 85 Nos.
CELL DISCHARGE DURATION = 10 Hrs

BATTERY SHORT CIRCUIT CURRENT (I sc) = EB / RTB 1


1
TOTAL RESISTANCE OF BATTERY CIRCUIT, RTB = RB + R C 2
2
BATTERY RESISTANCE ,RB (mW ) = (31 X EB) / I 10hr 3

BATTERY CONNECTORS RESISTANCE ,RC = 2.25 mW (ASSUMED VALUE)

1 132/11KV AL S'HALAH SUBSTATION (REPLACEMENT):

110V BATTERY BANK RATING IS ( I10hr) = 690 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 4.94 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 7.19 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 15294.71 A

= 15.29 KA (Approx)

2 132/11KV AL KAR'ANA SUBSTATION :

110V BATTERY BANK RATING IS ( I10hr) = 690 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 4.94 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 7.19 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 15294.71 A

= 15.29 KA (Approx)

3 132KV GULF CEMENT SWITCHING SUBSTATION :

110V BATTERY BANK RATING IS ( I10hr) = 625 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 5.46 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 7.71 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 14274.59 A

8 of 10
= 14.27 KA (Approx)

9 of 10
QATAR TRANSMISSION SYSTEM EXPANSION - PHASE-9
GTC/240/2008
4 33/11KV AL KHARSA'A SUBSTATION :

110V BATTERY BANK RATING IS ( I10hr) = 461 Ah

BATTERY RESISTANCE ,RB as per eqn..3 = 7.40 mW

TOTAL RESISTANCE OF BATTERY CIRCUIT as per eqn..2 = 9.65 mW

BATTERY SHORT CIRCUIT CURRENT (I sc) as per eqn..1 = 11402.55 A

= 11.40 KA (Approx)