Professional Documents
Culture Documents
Transformer Protection
Transformer Protection
Transformer Protection
AND
SWITCHYARD
PROTECTION
INTRODUCTION:
1) TRANSFORMER PROTECTIONS
2) BUS-BAR PROTECTIONS
3) LINE PROTECTIONS
These type of faults are of serious nature and may generate large amount of
gases which operate both alarm & trip mercury switches of buchholz relays.
SUDDEN PRESSURE RELAYS:
Serious faults inside the transformer may cause heavy pressure rise
due to generated gases and may rupture the tank and consequent risk of fire.
Hence a pressure relief device provided on top of the transformer which
opens to allow discharge of oil if pressure exceeds the setting value and also
extend tripping command, but closes automatically as soon as the internal
pressure falls below the critical level. This will avoid tank oil exposure to
the atmosphere for long time.
OVERCURRENT PROTECTION:
The over current protection relays are provided in addition to
differential relays to take care of through faults and as back-up to differential
protection.
Instantaneous over current units should be high set to avoid mal-operation.
The setting of an instantaneous over current relay on the
Primary side of transformer should be high enough to over ride magnetizing
inrush current. Same set of current transformers should not be used for
differential protection and over current protection as the CT requirements
are different.
DIFFERENTIAL PROTECTION:
Following problems are experienced in case of transformer
differential protection.
1. The transformer voltage rating is different for primary and
secondary. So, voltage rating of CT used in primary and secondary are
different. The non-identical CT may cause high spill current to flow through
the relay in case of external fault which calls for unwanted tripping. This can
be avoided by biased transformer differential relay. I.e by the use of
restraining coil
2. The full load currents of the transformer on primary and secondary
sides are different. The ratio of the CT used on both the sides, have to be so
selected that secondary currents are same. To avoid this, CT of standard
ratios are employed with interposing CT. The interposing CT are low
voltage and have a non standard ratio.
3. Inherent phase shift of currents in the transformers:
The primary and secondary currents are not in phase in delta star
transformer. This problem can be taken care of by proper connections of CT
on both the sides, by connecting CT on delta side of the transformer in star
and those on star side of the transformer in delta.
4. Tap changing:
Power transformers are always provided with the tapping to regulate the
output voltage. Some spill current will flow through the operating coil of the
relay in this case. So, biased differential relay must be used to avoid such
uncalled tripping.
5. Magnetizing inrush current of the transformer:
Any condition that calls for an instantaneous change in flux linkages in
power transformer will cause abnormally large magnetizing currents to flow
and these will produce an operating tendency in a differential relay. Such
inrush currents are large in magnitude.
And since this current exists only on the source side, the current will appear
in the operating coil of the differential relay and operate the relay.
Solutions for the same is as follows.
1. Even harmonic cancellation
2. Harmonic restraint
3. Harmonic blocking
A popular method is harmonic restraint.
Harmonic restraint is obtained from the tuned circuit which will permit only
fundamental component to enter the operating coil and harmonic being
diverted to the harmonic restraint coil.
Y
B
BIAS
2nd RECTIFIER &
HIGH SET 5th hormonic
hormonic SMOOTHING
filter
filter CKT
TRIP Polarized
COMPARATOR
relay
FIG -1
RESTRICTED EARTH FAULT
Power transformers are generally provided with restricted earth fault
scheme. The REF protection which employs principle of circulating
differential protection, responds to the internal earth faults in any one of the
windings. For external faults the time graded earth faults are used.
IR PRIMARY CURRENT
IN
R
FIG -2
(B) EXTERNAL EARTH FAULT
In
PRIMARY CURRENT
FIG -3
In Fig. 3 shows earth fault beyond the protected transformer. For REF
protection Bushing CTs are used.
For external earth fault in R phase current is flowing in the same direction as
other two phases. And current through neutral CT is also in the same
direction so no current will flow through the relay and hence no operation of
the relay occurred.
Irelay = Ir-In
2) BUS BAR PROTECTION
INTRODUCTION
With ever increasing short circuit levels and growing complexities of the
supply system, bus bar protection is becoming increasingly relevant even at
medium voltage level also. Damage resulting from one un cleared fault may
very extensive. Serious damage to or destruction of the installation would
probably result in widespread and prolonged supply interruption. So high
speed bus bar protection is required in order to maintain the system stability.
FAULT S1 S2 I3
87
B
52F1 FAULT
S1
I1 I2 I1+I2+I3 P1
87
A S2
P2
87
G1 GL1&ZL1 CH GL2&ZL2 G2
DIFFERNTIAL PROTECTION
52
52 52
If=1500
S1 1000/1 S1 S1
P1 Ir =1.5A
87
0.4 0.5 0.6
P2 FIG -5
S2 S2
S2
ALL CTs SEE INFLOW OF
CURRENT IN TO THE BUS
400 500 600
For internal earth fault in to the bus, the nearest feeder feed the maximum
fault current compared to other one. Here according to the magnitude of the
fault current , the secondary current of the CTs of respective feeders and
lines summed to 1.5 A. This 1.5 A current is sufficient to operate the
differential relay.
The setting of the relay is 0.4 A .
CURRENT DISTRIBUTION FOR
EXTERNAL FAULT
BUS
87 =differential relay
1000/1 S1 S1 S1
P1 P1 P1 D S
87 P1 P2
87 B
96
B
96A
TO TRIP 52F1/F2
TO TRIP 52F3/F4
96B
TO TRIP 52 BS
96A
87A/B- A/B zone diff. relay
87CH - check zone diff relay FIG -8
96B
96A/B- Trip relay for busA/B
sections
As per the control circuit the tripping of the faulty bus circuit is enabled
only when both 87 CH and either of 87A or 87B are operating
simultaneously.
It energises the 96A/96B master trip relay to trip the connected feeders of
that bus and bus-coupler.
3) LINE PROTECTION
Z3B(III)
Z2B(II)
A B Z1B(I) C D
20%
80%
Z1C
t2 Z1C
Z1B
G1 t3 Z2C G2
Z3C
FIG -09
SETTINGS :
Using OFF-Set MHO relay the admittance of the transmission line segment is seen
by giving the CT and PT inputs. For fault discrimination time settings with respect to
the sensed admittance introduced in such a manner that faulty section is isolated
within the given time setting.
Unnecessary isolation of the healthy section is prevented in Z2 and Z3 protected
area. In Z1 area fault is cleared instantaneously and also the relay gives tripping
command to receiving end respective breaker through PLCC ( Carrier Tripping).
OFF SET MHO CHARECTERISTICS
X A
Zl
ZR
R
FIG -13
The offset MHO characteristic encloses the origin providing a small coverage for
faults behind relaying point for reverse offset. The offset MHO characteristic. when
provided with reverse offset is used for Zone 3 primarily as a back up against Bus
bar faults.
TWO ZONE BUSBAR PROTECTION WITH CHECK FEATURE
Simple arrangement ofB
distance
A BUS B
BUS A 6mtr. P2
P1 protection
B/C
FAULT S1 S2 I3
A B
87 ZL
Zs CT
B
52F1 FAULT
S1
I1 I2 I1+I2+I3 P1
VT Zs=Source impedance
G ZL=Line impedance
R Zload=load impedance Z load
87
A relay S2
Distance
If
P2
87=Z load (ZL is very less than Zload)
Healthy condition:- Zrelay =V/I
G1 GL1&ZL1 CH GL2&ZL2 FIG -11 G2
On Fault :- Zrelay = Vf/If =ZL (Z load is shunted by fault) FIG -10
UNPROTECTION ZONE BY DIFF. PROT. AT SLPP
IMPEDANCE CHARACTERISTIC
Zrela > Zset
X y
Relay
does not operates
B
ZL
R
O
Zrelay < Zset
Relay
operates
FIG -12
Draw Back :
BUSBAR
Rst
Stabilizing Resistor
87
DIFF. RELAY
FIG -6