3611-VK-FP-DT - 000 - 2 - 00 - 0001-Is04-Process Units
3611-VK-FP-DT - 000 - 2 - 00 - 0001-Is04-Process Units
3611-VK-FP-DT - 000 - 2 - 00 - 0001-Is04-Process Units
NOTES
5 & 29
5, 10
5,10
6,10
2,10
9,10
10
13
13
5
5
GROUP
RESET
SERIAL No.
223-4101
223-4103
223-4103
223-4104
223-4104
223-4105
223-4105
223-4105
223-4105
223-4105
223-4107
223-4107
223-4108
223-4108
223-4105
211-4104
223-4108
223-4108
223-4108
223-4108
223-4108
223-4108
223-4108
223-4108
223-4110
223-4110
223-4110
223-4110
223-4108
223-4107
223-4107
223-4107
223-4107
223-4107
223-4107
223-4107
223-4108
P&ID
-
ACTION
De-Activate
De-Activate
De-Activate
De-Activate
Permissive
Cause & Effects
Activate
Activate
Alarm
Alarm
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Open
Open
Open
UNIT 223
EFFECTS
Start
Start
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Trip
Trip
Trip
Trip
"Tail Gas Treating Unit, Train 1"
"BURNER-ON" Indication
Fuel gas first block valve
Deleted
Deleted
Deleted
valve
Tag No.
XYH-0006
XYH-0007
XYH-0002
XYH-0003
XYH-0004
XYH-0005
XA-0036D
XA-0723A
XA-0733A
XL-0027D
XL-0029D
XYL-0002
XYL-0003
XYL-0004
XYL-0005
XYL-0006
XYL-0007
XYL-0010
SCV-002
XY-0001
XY-0008
XY-0030
XY-0011
XY-0009
XY-0015
XY-0017
XY-0016
XY-0012
XA-0036
XY-0013
XY-0014
XY-0032
XY-0033
XY-0034
XY-0035
XY-0030
XY-0047
BL-001A
BL-001B
XY-0031
CAUSE
XL-0027
XL-0029
-
-
P&ID SERIAL
NO.
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
INTERLOCK No. SERVICE TAG No. FUNCT. MO NOTES
9
No.
ESD Level 0 (PESD) 1
701 Desup. Contact Cond. V-223-002 (Chimney Tray) LT-0003 LL 223-4103 Yes 2 X X A I
710 Rich HS 101 to AGSU Flash Drum V-211-003 PT-0010 LL 223-4105 Yes 3 11 S S A I
PB
719 Incinerator Shutdown HS-0009B/C 223-4108 10 & 18 23 X X X X X X X X X X X X X X X X X X X X X X X
(Aux-Console)
720 Deleted 24
721 220 SRU Trip - Trip - 9 25 T T X
Deleted 27
723 Deleted 33
723 Deleted 03 34
780 Turbine bearing High High temperature-Non drive end TT-0037 HH 223-4107 21 & 26 45 X X X X
781 Turbine bearing High High temperature- drive end TT-0037 HH 223-4107 21 & 26 46 X X X X
100 ESD level 3- Proc / Util Systems Shutdown (NCCR) 210-HS-0103 PB 210-4101 64 X X X X X X X X X X X X X X
100 Group 3 ESD Reset, Units 223 & 224 (NCCR) HS-0012 PB 220-4101 65 R R R R R R R R R R R R R R R
UNIT SPECIFIC NOTES 15. Shutdown cause shall act with a 2003 voting system.
1. All instrument tag nos prefixxed'223-'except where noted. 16. Shutdown causes shall be bypassed until burner light on; the bypass shall be removed as soon as the indication "BURNER ON" is active and burner flame proving timer is expired.
2. Ignition system for incinerator ME-223-001 updated based on vendor information. 17. Shutdown cause shall act with a 2002 voting system.
3. Two S's (i.e standby) are required to activate function. 18. Tag number suffixed with "B" symbol will be located on NCCR-SDC and tag number suffixed with "C" shall be located on S-SIH.
4. One flame failure will alarm only, 2-out-of-2 will shutdown Incinerator package ME-223-001. 19. Trip at 105 deg C, Pre-alarm at 95 deg C.
5. Actuator Type C 20. Vibration monitoring: Measuring range 0-25.4 mm/sec (RMS); Alarm at 8.8 mm/s (RMS) for more than 10 seconds; Trip at 11 mm/s (RMS) for more than 1 seconds.
6. Actuator Type B 21. Trip at 121 deg C, Pre-alarm at 110 deg C.
7. Deleted 22. Each overspeed channel failure activates a common alarm at DCS if any of the following conditions occures:
8. Selection of 1-pump as Standby or Duty automatically deselects the other pump. -MPU Failure while running;
9. Delay of 20 to 30 minutes (adjustable) after incinerator shutdown. -Speed not detected within start override timer. 03
03
10. Cause & Relevant Effects Updated based on incinerator Package vendor information. - Power supply failure; -Watch dog failure; -High high speed detected.
11. Pilot interlocks shall activate an Incinerator shutdown when the pilot is on and the burner is off ("Pilot ON" Indication active and "Burner ON" Indication not active). They shall be bypassed otherwise. 23. The Overspeed trip signal is a 2003 voting of single channel failure.
12. Shutdown cause automatically bypassed as long as the upstream on-off valve are closed; the bypass shall be removed 20 second (to be confirmed during commissioning and start-up activities) after the opening of relevant valves. 24. The Governor common alarm signal is actuated by any of the following conditions: Any input or output signal fault; Power supply failure; High High speed detected.
13. Bleed valve will be opened 5 seconds after the closure of the two block valves. 25. The Governor trip signal is actuated by any of the following conditions: Both governor MPU failure; Power supply failure; Watch dog failure; High High speed detected.
14. Logic bypassed until pilot light-on; the bypass shall be removed as soon as the indication" PILOT ON" is active and pilot flame proving timer is expired. 26. Every trip implies an alarm at DCS.
27. Trip at 100 deg C, Pre-alarm at 90 deg C.
28. For safety interlocks of the motor pls.refer to the IOM manual of the motor supplier. Local authority rules and local safety requirements for mechanical and electrical equipment shall be complied with when main motor is switched off.
29. Hydrogen Valve XV-0001 to close after time delay of 1-2 min after the Interlock activation.