Fire Water
Fire Water
Total
Equipment Description
Area Fire Protection
Fire Scenario
(Note 4) System
Dimensions (m)
Tag Orientation
L
V-1101 H 6.0
E-1201 H 5.0
Process Separator Area Firewater Deluge
V-1201 H 23.2
V-1202 H 23.1
Consumption Comments
(m3/h)
24
30
0
18 Assumed this will be on drilling rig??
18
10.8
0
Part 1
Determination of Firewater Demand Ra
Firewater Units
Relevant IPS Code Unit Flow Rate Unit Reference
IPS-E-SF-220 Hosereels 24 l/min IPS-E-SF-220 (page 18)
IPS-E-SF-220 Hydrants 2 way 1000 l/min
IPS-E-SF-220 Hydrants 4 way 2000 l/min
IPS-E-SF-140 Monitors 2000 l/min Shell DEP 120m3 is typical
Foam solution from Monitors/ branchpipes (to cover half bund area)
Part 1
Firewater Demand Rates
Fire Water
Total System / Deluge Additional Hydrants Hydrants Monitors Hosereels
For System Valve Total Equipment 2 Way 4 Way
(SUM) Needed
l/min l/min 1000 l/min 2000 l/min 2000 l/min 24 l/min
1085.80
264.40 1 no. monitor +
10647.80 1 no. 2-way 1000.00 - 2000.00 -
4657.39 hydrant
4640.21
Reference
IPS-E-SF-220 (page 18)
Part 1
Determination of Firewater Demand Rates
System / Entire
Fire Water
Equipment Description Firewater Deluge Surface Area for water Hydraulic Deluge Valve Additional Other Deluge System
Area Fire Protection Water Demand Total Hydrants Hydrants Monitors Hosereels System Total
Fire Scenario application Imbalance Total Equipment System Hydraulic Comments
(Note 4) System Dimensions (m) Density Wastage Factor For System (SUM) 2 Way 4 Way Imbalance
Needed
Tag Orientation
L Diameter l/min/m2 (%) m2 l/min (%) l/min l/min 1000 l/min 2000 l/min 2000 l/min 24 l/min (demand case only) % l/min m3/hr
V-1101 H 6.0 2.8 10.2 25.00% 77.42 987.09 10.00% 1085.80
E-1201 H 5.0 1.0 10.2 25.00% 18.85 240.36 10.00% 264.40 1 no. monitor
Process /
Separator Area Firewater Deluge 10647.80 + 1 no. 2-way 1000.00 - 2000.00 - 0.0% 13647.80 818.87
Area 4 V-1201 H 23.2 3.9 10.2 25.00% 332.08 4233.99 10.00% 4657.39 hydrant
V-1202 H 23.1 3.9 10.2 25.00% 330.85 4218.37 10.00% 4640.21
V-1203 H 20.0 3.8 10.2 25.00% 284.16 3623.07 10.00% 3985.38
V-1204 H 20.0 3.8 10.2 25.00% 284.16 3623.07 10.00% 3985.38 1 no. monitor
Process / Desalter Area
Firewater Deluge 8107.08 + 1 no. 2-way 1000.00 - 2000.00 - 0.0% 11107.08 666.42
Area 4 A-1201 package P-1201A Area 1.7 0.8 20.4 25.00% 1.36 34.68 10.00% 38.15 hydrant
P-1201B Area 2.5 1.4 20.4 25.00% 3.50 89.25 10.00% 98.18
C-3101 V 16.0 3.1 10.2 25.00% 182.56 2327.62 10.00% 2560.38 1 no. monitor
Process / Crude Oil Stabiliser
/ H2S Stripper area Firewater Deluge E-3102 H 4.8 1.0 10.2 25.00% 18.22 232.35 10.00% 255.59 4032.20 + 1 no. 2-way 1000.00 - 2000.00 - 0.0% 7032.20 421.93
Area 4
E-2601 H 9.1 2.4 10.2 25.00% 86.72 1105.67 10.00% 1216.24 hydrant
T-3602A (On-spec) V 30.0 4.1 0.00% 706.86 2898.12 0.00% 2898.12 2898.12 2898.12 173.89
Tanks 10.0m high
Storage Tank / See
Tank fire internal Base Injection System T-3602B (On-spec) V 30.0 4.1 0.00% 706.86 2898.12 0.00% 2898.12 2898.12 N/A - - - - 0.0% 2898.12 173.89 Application rate for Base Injection as per NFPA 11
Area 6 Comments
and as per IPS-E-SF-140
T-3601 (Off-spec) V 30.0 4.1 0.00% 706.86 2898.12 0.00% 2898.12 2898.12 2898.12 173.89
LLP1 Compressor Fire Firewater Deluge K-2601 17 x 11 - 10.2 10.00% 187 2094.40 10.00% 2303.84 4607.68 - - - 0.0%
LLP Compression 2 Hose
Area 1000.00 7590.00 455.30
Area Streams
LLP2 Compressor Fire Firewater Deluge K-2602 17 x 11 - 10.2 10.00% 187 2094.40 10.00% 2303.84 - - - 0.0%
LP Compressor 2 Hose
LP Compressor Fire Firewater Deluge K-2603 Area 27 x 20 - 10.2 10.00% 540 6048.00 0.10 6652.80 6652.80 1000.00 - - - 0.0% 7590.00 455.30
Area Streams
MP Compressor
MP Compressor Fire Firewater Deluge K-2604 Area 27 x 20 - 10.2 10.00% 540 6048.00 10.00% 6652.80 6652.80 - - - 0.0%
Area
Bund Area 4.00 IPS-E-SF-140 Monitors 2000 l/min Shell DEP 120m3 is typical
Foam solution from Monitors/ branchpipes (to cover half bund area)
FW
NO
BD
Part 2 Part 3
Line sizing Tank Capacity Sizing Foam discharge rate = 4 x pd /4 2
Ringmain 21754.88 0.36 3.50 0.10 0.18 7.26 14.53 14 Using the largest Firewater demand, Pump capacity can be selected. Duration based upon 45 minutes supply (flashpoint less than 40 0C - actual flash point -10C)
Storage facility can then be defined.
Separator Area
10647.80 0.18 5.00 0.04 0.11 4.25 8.50 8
Deluge Valve Nominal Pump Duty 1305 m3/hr \ Foam Solution Requirement = 2827 l/min x 45 mi
Desalter
8107.08 0.14 5.00 0.03 0.09 3.71 7.42 8
Deluge Valve Selected Pump Capacity 783 m /hr 3
= 127215 l
H2S Stripper Package (3x 60% duty pumps provided, to meet IPS-E-SF-220)
4032.20 0.07 5.00 0.01 0.07 2.62 5.23 6
Deluge Valve
LLP Compressor Area
4607.68 0.08 5.00 0.02 0.07 2.80 5.59 6 Note: it may be economical to specify 795 m3/hr, as this equates to 3500USgpm, a standard rating under NFPA 20.
Deluge valve
LP Compressor Area
6652.80 0.11 5.00 0.02 0.08 3.36 6.72 6
Deluge valve
MP Compressor Area
6652.80 0.11 5.00 0.02 0.08 3.36 6.72 6
Deluge valve
Seal gas Compressor
4435.20 0.07 5.00 0.01 0.07 2.74 5.49 6
Deluge Valve
Storage Tank Internal
2898.12 0.05 5.00 0.01 0.06 2.22 4.44 6
Base injection system Storage Capacity 16 Hrs at demand rate \ Foam Concentrate Storage Requirement = 127215 l x 0.01 (based on 1% freeze-protected AFFF)
Storage Tank Bund (using
12381.60 0.21 5.00 0.04 0.11 4.58 9.17 N/A (fed from mains)
monitors) Firewater Quantity 20880 m3 = 1272 l
Water Sizing Velocity (Ringmain only) = 3.5 m/s Fire water storage in 2 tanks, to allow for maintenance.
Water Sizing Velocity (all other piping) = 5.0 m/s = 1.27m3
Notes
1. Firewater quantity should not normally be not less than 820m 3/hr and not more than 1360m3/hr (under IPS )
2. Firewater demand is based upon activation of a single fire zone at any one time.
3. Foam will be applied using a semi-fixed system.
4. Areas are based upon those identified within the Key Plan for Equipment Layouts Drg. 39-00-PF-P56-00002 Rev 07