NEK 606 (1997)

2. edition

NEK-standard
CABLES FOR OFFSHORE INSTALLATIONS
HALOGEN-FREE, OR MUD RESISTANT

NEK-norm
KABLER FOR OFFSHORE INSTALLASJONER
HALOGENFRIE, ELLER BOREVLESKEBESTANDIGE

Prepared by NEK Standards Committee I BA


Utarbeidet av NEK Normkomite I BA

© NEK har opphavsretten ti! denne norm.


lngen de! av r:iaterialet ma reproduseres pa noen form for medium. For opphevelse av
NEK's Copyright kreves i hvert enkelt tilfelle skriftlig avtale med NEK.

NORSK E.LEKTROTEKNISK KOMITE


Harbitzalleen 2 A - Postboks 280 Sk0yen, 0212 Oslo 2
Norsk nasjonalkomite for
International Electrotechnical Commission, IEC
Comite Europeen de Normalisation Electrotechnique, CENELEC
Page 1

Clause

1 SCOPE 3

2. REFERENCES AND GENERAL REQUIREMENTS 4


2.1 Standards and Regulations 4

2.2 Flame Retardance 5

2.3 Fire Resistance 6

2.4 Content of Halogen 6

2.5 Smoke Emission 6

2.6 Oil Resistance 6

2. 7 Core Identification 7

2.8 Typical number of cores and cross-sectional areas 8

2.9 Sheath Marking 9

2.10 Sheath Colours 10

2.11 Cable code designation 11

3. CABLE DESCRIPTION 12

3.1 Cable type Pl RFOU/fFOU 0,6/1 kV 12

3.2 Cable type P2 RFOU/fFOU 3.6/6 kV 13

3.3 Cable type P3 RFOU/fFOU 6/10 kV 14

3.4 Cable type P4 RFOU/fFOU 8,7115 kV 15

3.5 Cable type PS BFOU 0,6/lkV 16

3.6 Cable type P6 BFOU 3,6/6 kV 17

3.7 Cable type P7 BFOU 6/10 kV 18

3.8 Cable type PS RFOB/fFOB 0,611 kV 19

3.9 Cable type P9 RFOB/fFOB 3.6/6 kV 20

3.10 Cable type PlO RFOB/fFOB 6/10 kV 21

3.11 Cable type Pll RFOB/fFOB 8,7/15 kV 22

3.12 Cable type P12 BFOB 0,6/lkV 23

3.13 Cable type P13 BFOB 3,6/6 kV 24


Page 2

3.14 Cable type P14 BFOB 6/10 kV 25

3.15 Cable type PlS UX/RX 0,6/1 kV 26

3.16 Cable type P16 IFLI 250V 27

3.17 Cable type St RFOU(i) 250V 28

3.18 Cable type S2 RFOU(c) 250V 29

3.19 Cable type S3 BFOU(i) 250V 30

3.20 Cable type S4 BFOU(c) 250V 31

3.21 Cable type SS RFOB(i) 250V 32

3.22 Cable type S6 RFOB(c) 250V 33

3.23 Cable type S7 BFOB(i) 250V 34

3.24 Cable type SS BFOB(c) 250V 35

3.25 Cable type S9 IYXI(c) 36

3.26 Cable type SlO IYOI(c) 37

4. REQUIRED INFORMATION AND DATA 38


4.1 General 38

4.2 Electrical Data for Cables for control, lighting and power. 38

4.3 Electrical Data for Cables for instrumentation and telecommunication. 38

4.4 Mechanical and Physical Data 39

4.5 Proposed Tests 39

5. INSPECTION AND TESTING 40


5.1 General 40

5.2 Type Tests 40

6. PREPARATION FOR DELIVERY 40


6.1 General 40

6.2 Cable Drum Identification 40


Page 3

1 Scope

This specification covers the basic requirements for halogenfree


and mud-resistant low and high voltage power, control,
lighting, instrumentation and telecommunication cables.

This specification does not cover special Radio Frequency


telecommunication cables or optical fibre cables.
Page 4

2. REFERENCES AND GENERAL REQUIREMENTS

2. 1 Standards and Regulations

Unless otherwise specified, all cables shall be in accordance


with all applicable sections of the latest editions of the
following Codes, Standards and Regulations, and their current
amendments:

Std. /Reg. Designation Title Reference

Norwegian Regulations for Electrical FEA-M 1990


Water Resources Installations
and Energy Martime Installations
Administration

Det Norske Rules for classification


Veritas of steel ships
Part 4, chapter 4,
section 7,
clause A504
and section 10,
clause GlOO.

International All publications related


Electrotechnical to the cables specified.
Commision ( IEC) Particular attention shall
be paid to the following
publications:

Electrical installation in
ships:
Part 3 Cables (Construction,
testing and installation) IEC 92-3

Part 350: Low-voltage ship-


board power cables. (General
construction and test requi-
rements) IEC 92-350

Part 351: Insulating materials


for shipboard power cables. IEC 92-351

Part 353: Single and multicore


cables with extruded solid
insulation for rated voltages
0,6/1 and 1,8/3 kV. IEC 92-353
Page 5

Std./Req. Designation Title Reference

Part 354: Single and three-core


power cables with extruded solid
insulation for rated voltages
6 kV, 10 kV and 15 kV. IEC 92-354

Part 359: Sheathing materials


for shipboard power and tele-
communication cables. IEC 92-359

Part 375: General instrument-


ation, contrtol and communica-
tion cables. IEC 92-375

Conductors of insulated
cables IEC 228

Fire resisting characteristics


of electrical cables IEC 331

Test on electrical cables under


fire conditions. (Flame retard-
ant characteristics for elec-
trical cables) . IEC 332-1
and IEC 332-3

Extruded solid dielectric in-


sulated power cables for rated
voltages from lkV up to 30kV. IEC 502

Test on gases evolved during


combustion of electric cables IEC 754

Common test methods for insul-


ating and sheathing materials
of electric cables. IEC 811

Measurement of smoke density of


electric cables burning under
defined conditions IEC 1034
Part 1: Test apparatus
Part 2: Test procedure and requirements

2.2 Flame Retardance

The cables shall withstand the test specified in IEC 332-3.


Single, earth and bonding wires shall withstand the test
specified in IEC 332-1.
Page 6

2.3 Fire Resistance

Fire resistant cables shall be tested accodring to IEC 331.

2.4 Content of Halogen

As a rule all cables shall be halogen-free according


to IEC 754-1, maximum content of halogen = 5 mg/g.
For mud resistant cables a halogen content necessary to
achieve diesel based mud resistance, will be acceptable.

2.5 Smoke Emission

During a cable fire smoke emmision shall be kept to a minimum.


The smoke emission according to IEC 1034-2 with the following
values:

1 cable 70% transmittance


2-3 cables: 60% II

14 cables: 50% II

21 cables: 40% II

2.6 Oil Resistance

All thermoset sheathed cables shall be suitable for an oil


production installation.The oil resistance properties shall be
demonstrated by a test according to IEC 92-359 Table II Clause 3.

For cables with thermoplastic sheath material there are no


requirements for oil resistance properties.

2.6.1 Mud Resistance

Mud resistant cables shall be designed with sheathing compounds


suitable for installation and operation on contact with MUD unless
otherwise specified.

The MUD resistance properties shall be demonstrated by the


following test procedure:

The cables shall be immersed in MUD at 70°C, and tested for changes
of elongation at break, tensile strength, volume swelling, weight
increase and oxygen index after 56 days.

Requirements:

elongation at break ± 25 %
tensile strength ± 25 %
volume swelling max 20 %
weight increase max 15 %
oxygen index minimum 25 %
Page 7

2. 7 Core Identification

2.7.1 For the 250V cables the identification of insulated


conductors (cores) shall be in accordance with IEC 92-375,
Paragraph 14.2, Method 2: Colour Code.

Pair: Black, Light blue


Triple: Black, Light blue, Brown

Pairs/triples are numbered with numbered tape or by


numbers printed directly on the insulated conductors.

2.7.2 For the 0,6/1 kV cables the identification of insulated


conductors (cores) shall be:

1 core Off-white (Grey)


2 cores Off-white - Black
3 cores Off-white - Black - Red
4 cores Off-white - Black - Red - Blue

Above 4 cores Black numbers on white base.

Earthing core Yellow/Green

2.7.3 For the 3,6/6(7,2)kV, 6/10(12)kV and 8,7/15(17,5)kV


cables the identification of insulated conductors
(cores) shall be:

1 core Off-white insulation + black semi-


conducting layers

3 cores Off-white insulation + black semi-


conducting layers.
Off-white (Grey) - Black - Red
tape/thread in spiral around the
cores.

Earthing core : Yellow/Green


Page 8

2.8 Typical number of cores and cross-sectional areas

2.8.1 For the 250V 0,75, 1 and 1,5 mm2 cables:

1 pair I 1 triple
2 pairs I 2 triples
4 pairs I 4 triples
8 pairs I 8 triples
12 pairs I 12 triples
16 pairs I 16 triples
24 pairs I 24 triples *
32 pairs I 32 triples *

* Two cables (12 and 16 pair) in parallel is an alternative that


can be used.

2.8.2 For the cable types 89 and 810, coductor size 0,5 mm0.

1 pair
2 pairs
4 pairs
10 pairs
20 pairs
30 pairs
50 pairs

2.8.3 For the 0,6/lkV wires· and cables:

1 x 16 mm 2 2 x 1,5 mm 2 3 x 1,5 mm 2 4 x 1,5 mm 2 7 x 1,5 mm 2


1 x 25 mm 2 2 x 2,5 mm 2 3 x 2,5 mm 2 4 x 2,5 mm 2 12 x 1,5 mm 2
1 x 50 mm 2 3 x 6 mm 2 4 x 6 mm 2 19 x 1,5 mm 2
1 x 95 mm 2 3 x 16 mm 2 4 x 16 mm 2
1 x 150 mm 2 3 x 25 mm 2 4 x 25 mm 2
1 x 240 mm 2 3 x 50 mm 2 4 x 50 mm 2
1 x 300 mm 2 3 x 95 mm 2 4 x 95 mm 2
3 x120 mm 2 +E
3 x150 mm 2 +E

For 2 and 3 core cables the braiding is used as earth


conductor.
Dimensioned in accordance with ET regulation FEA-M 1990
paragraph 1238.5.

When yellow/green earth conductor is used the braiding is


dimensioned in accordance with IEC 92-350 8ubclause 7.2.

2.8.4 For the 3,6/6(7,2)kV and 6/10(12)kV cables:


1 x 150 mm2 3 x 25 mm2 + E
1 x 240 mm2 3 x 50 mm2 + E
1 x 300 mm2 3 x 95 mm2 + E
(+ E means yellow/green earth conductor)
Page 9

2.8.5 For the 8,7(17,5)kV and 12/20(24)kV cables:

1 x 150 mm2 3 x 50 mm2 + E


1 x 240 mm2 3 x 95 mm2 + E
1 x 300 mm2 3 x 150 mm2 + E *
(+ E means yellow/green earth conductor)

2.9 Sheath Marking

The sheath shall be clearly marked with:

Manufacturers name
Cable designation (basic type)
Voltage rating
Number of cores I pairs I triples
Cross-section of conductors
For power cables, cross-section of braid in addition.
Year of manufacture

The marking shall be repeated at least every 1,0 m.

Example:ABBNK RFOU 250V 2 PAIR 0,75 mm2


ABBNK RFOU 250V 2 x 2 x 0,75 mm2
ALCATEL KABEL RFOU 0,6/lkV 3 x 95/50 mm2
Page 10

2. 10 Sheath Colours

2.10.1 Cables up to an including 250V shall have a GREY


sheath, except:

Cables for Intrinsically safe signals shall have a BLUE


sheath.

Mud resistant cables for Intrinsically safe signals can


have a BLACK sheath but then with a BLUE stripe painted
along its entire length.

Mud resistant cables for Non-Intrinsically safe signals


can have a BLACK sheath but then with a GREY stripe
painted along its entire length.

2.10.2 Cables for 0,6/lkV shall have a BLACK sheath.

2.10.3 Cables for HIGHER voltages shall have a RED


sheath, except:

Mud resistant cables can have a BLACK sheath but then


with a RED stripe painted along its entire length.
Page 11

2. 11 Cable code designation

A cable code of 2- 4- letters is used to describe the construction.


Additional abbreviation for instrumentation cables: Collective screen=
(c) , Individual pair or triple screen= (i)
The interpretation (per letter) can be read from the table below:

Materials 1. letter: 2. letter 3. letter 4. letter.


Insulation Beddding/ Armour/ Outer
Inner sheath Screen Sheath
Fire resistant tape+ insulation (Hal.free) B
Ethylenepropylene rubber - EPR R
Cross-linked polyethylene XLPE T
Thermoplastic compound (Hal.free) I
Halogen-free thermoset compound EMA or EVA u
Bedding or taping (Hal.free) F
Screen (poss. with PE or PP) y
Aluminium (laminated to outer jacket) L
No armour x
Copper wire braid (Tinned or bare) 0
Thermoplastic compound (Hal.free) I
Halogen-free thermoset compound EMA or EVA u
Hydrocarbon resistant sheath B
Page 12

3. CABLE DESCRIPTION

3.1 Cable type P1 RFOUITFOU 0,611 kV

Cables for control, lighting and power


Flame retardant, low smoke and halogenfree.
Design and construction in accordance with
IEC 92-353.

Basic type RFOU / TFOU

Rated voltage 0,6/1 kV

Max. operating 85°C


temperature

Conductor Tinned stranded copper in accordance with IEC 228,


class 2.

Insulation Ethylene propylene rubber (EPR) or


Crosslinked P9lyethylene (XLPE) .
Thickness - Table 1.

Bedding Halogen-free compound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with Clause 3.8, and the cross-sectional
area with NVE regulation FEA-M 1238.5.

Outer sheath Halogenfree thermoset compound in accordance with


type SHF2.
Thickness - Sub.Clause 3.7.3a.
Page 13

3.2 Cable type P2 RFOU/TFOU 3.616 kV

High voltage power cables.


Flame retardant, low smoke, halogen-free.
Design and construction in accordance with
IEC 92-354.

Basic type RFOU I TFOU

Rated voltage 3,6/6(7,2) kV

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper in accordance


with IEC 228, class 2.

Conductor screening Semi conducting material.

Insulation Ethylene propylene rubber (EPR) or


Cross-linked Polyethylene (XLPE) .
Thickness - Table 1.

Insulation screening: Semi conducting material and tinned copper wire


braid.

Bedding Halogen-£ree compound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with IEC 92-354, clause 16.

Outer sheath Halogen-free thermoset compound


in accordance with type SHF2.
Thickness - Sub-Clause 15.2a.
Page 14

3.3 Cable type P3 RFOUffFOU 6110 kV

High voltage power cables.


Flame retardant, low smoke, halogen-free.
Design and construction in accordance with
IEC 92-354.

Basic type RFOU / TFOU

Rated voltage 6/10(12) kV

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper in accordance


with IEC 228, class 2.

Conductor screening Semi conducting material.

Insulation Ethylene propylene rubber (EPR) or


Cross-linked Polyethylene (XLPE) .
Thickness - Table 1.

Insulation screening: Semi conducting material and tinned copper wire


braid.

Bedding Halogen-·free compound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with IEC 92-354, clause 16.

Outer sheath Halogen-free thermoset compound


in accordance with type SHF2.
Thickness - Sub-Clause 15.2a.
Page 15

3.4 Cable type P4 RFOU/TFOU 8,7115 kV

High voltage power cables.


Flame retardant, low smoke, halogen-free.
Design and construction in accordance with
IEC 92-354.

Basic type RFOU / TFOU

Rated voltage 8,7/15(17,5) kV

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper in accordance


with IEC 228, class 2.

Conductor screening Semi conducting material.

Insulation Ethylene propylene rubber (EPR) or


Cross-linked Polyethylene (XLPE) .
Thickness - Table 1.

Insulation screening: Semi conducting material and tinned copper wire


braid.

Bedding Halogen-·free compound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with IEC 92-354, clause 16.

Outer sheath Halogen-free thermoset compound


in accordance with type SHF2.
Thickness - Sub-Clause 15.2a.
Page 16

3.5 Cable type P5 BFOU 0,6/1kV

Cables for control, lighting and power


Fire resistant, flame retardant, low smoke
and halogen-free. Design and construction in
accordance with IEC 92-353.

Basic type BFOU

Rated voltage 0,6/1 kV

Max. operating 85°C


temperature

Conductor Tinned stranded copper in accordance with IEC


228, class 2.

Insulation Fire resistant tape.


Ethylene propylene rubber (EPR) or
Cross-linked Polyethylene (XLPE) .
Thickness - Table 1.

Bedding Halogen-free compound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with Clause 3.8, and the cross-sectional
area with NVE regulation FEA-M 1238.5.

Outer sheath Halogen-free thermoset compound in accordance


with type SHF2.
Thickness -Sub-Clause 3.7.3a.
Page 17

3.6 Cable type P6 BFOU 3,616 kV

High voltage power cables.


Fire resistant, flame retardant, low smoke
and halogenfree.
Design and construction in accordance with
IEC 92-354.

Basic type BFOU

Rated voltage 3,6/6(7,2) kV

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper in accordance


with IEC 228, class 2.

Insulation Fire resistant tape.


Ethylene propylene rubber (EPR) .
Thickness - Table I

Insulation screening: Semi conducting material and tinned copper wire


braid.

Bedding Halogen-free compound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with Clause 16.

Outer sheath Halogen-free thermoset compound in


accordance with type SHF2.
Thickness - Sub~Clause 15.2a
Page 18

3.7 Cable type P7 BFOU 6110 kV

High voltage power cables.


Fire resistant, flame retardant, low smoke
and halogenfree.
Design and construction in accordance with
IEC 92-354.

Basic type BFOU

Rated voltage 6/10(12) kV

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper in accordance


with IEC 228, class 2.

Insulation Fire resistant tape.


Ethylene propylene rubber (EPR) .
Thickness - Table I

Insulation screening: Semi conducting material and tinned copper wire


braid.

Bedding Halogen-free compound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with Clause 16.

Outer sheath Halogen-free thermoset compound in


accordance with type SHF2.
Thickness - Sub-Clause 15.2a
Page 19

3.8 Cable type PB RFOBITFOB 0,611 kV

Cables for control, lighting and power


Flame retardant and mud resistant.
Design and construction in accordance with
IEC 92-353.

Basic type RFOB I TFOB


Rated voltage 0,6/1 kV

Max. operating 85°C


temperature

Conductor Tinned stranded copper in accordance with IEC 228,


class 2.

Insulation Ethylene propylene rubber (EPR) or


Crosslinked Polyethylene (XLPE) .
Thickness - Table 1.

Bedding Halogen-free compound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with Clause 3~8, and the cross-sectional
area with NVE regulation FEA-M 1238.5.

Outer sheath Mud resistant thermoset compound in accordance with


type SEl
Thickness - Sub.Clause 3.7.3a.

Or a composite of thermoset compound and an


outer mud resistant covering.
Page 20

3.9 Cable type P9 RFOB/TFOB 3.616 kV

High voltage power cables.


Flame retardant, low smoke, halogen-free.
Design and construction in accordance with
IEC 92-354.

Basic type RFOB I TFOB


Rated voltage 3,6/6(7,2) kV

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper in accordance


with IEC 228, class 2.

Conductor screening Semi conducting material.

Insulation Ethylene propylene rubber (EPR) or


Cross-linked Polyethylene (XLPE) .
Thickness - Table 1.

Insulation screening: Semi conducting material and tinned copper wire


braid.

Bedding Halogen-free compound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with clause 16.

Outer sheath Mud resistant thermoset compound


in accordance with type SEl.
Thickness - Sub-Clause 15.2a.

Or a composite of thermoset compound and an


outer mud resistant covering.
Page 21

3. 10 Cable type P10 RFOB/TFOB 6110 kV

High voltage power cables.


Flame retardant, low smoke, halogen-free.
Design and construction in accordance with
IEC 92-354.

Basic type RFOB / TFOB

Rated voltage 6/10(12) kV

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper in accordance


with IEC 228, class 2.

Conductor screening Semi conducting material.

Insulation Ethylene propylene rubber (EPR) or


Cross-linked Polyethylene (XLPE) .
Thickness - Table 1.

Insulation screening: Semi conducting material and tinned copper wire


braid.

Bedding Halogen-free co~pound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with clause 16.

Outer sheath Mud resistant thermoset compound


in accordance with type SEl.
Thickness - Sub-Clause 15.2a.

Or a composite of thermoset compound and an


outer mud resistant covering.
Page 22

3. 11 Cable type P11 RFOBITFOB 8, 7115 kV

High voltage power cables.


Flame retardant, low smoke, halogen-free.
Design and construction in accordance with
IEC 92-354.

Basic type RFOB I TFOB


Rated voltage 8,7/15(17,5) kV

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper in accordance


with IEC 228, class 2.

Conductor screening Semi conducting material.

Insulation Ethylene propylene rubber (EPR) or


Cross-linked Polyethylene (XLPE) .
Thickness - Table 1.

Insulation screening: Semi conducting material and tinned copper wire


braid.

Bedding Halogen-free compound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with clause 16.

Outer sheath Mud resistant thermoset compound


in accordance with type SE 1.
Thickness - Sub-Clause 15.2a.

Or a composite of thermoset compound and an


outer mud resistant covering.
Page 23

3. 12 Cable type P12 BFOB 0, 611 kV

Cables for control, lighting and power


Fire resistant, flame retardant, low smoke
and mud resistant. Design and construction in
accordance with IEC 92-353.

Basic type BFOB

Rated voltage 0,6/1 kV

Max. operating 85°C


temperature

Conductor Tinned stranded copper in accordance with IEC


228, class 2.

Insulation Fire resistant tape.


Ethylene propylene rubber (EPR) or
Cross-linked Polyethylene (XLPE) .
Thickness - Table 1.

Bedding Halogen-free compound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with Clause 3.8, and the cross-sectional
area with NVE regulation FEA-M 1238.5.

Outer sheath Mud resistant thermoset compound in accordance


with type SEl.
Thickness -Sub-Clause 3.7.3a.

Or a composite of thermoset compound and an


outer mud resistant covering.
Page 24

3.13 Cable type P13 BFOB 3,616 kV

High voltage power cables.


Fire resistant, flame retardant, low smoke
and mud resistant.
Design and construction in accordance with
IEC 92-354.

Basic type BFOB

Rated voltage 3,6/6(7,2) kV

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper in accordance


with IEC 228, class 2.

Insulation Fire resistant tape.


Ethylene propylene rubber (EPR) .
Thickness - Table I

Insulation screening: Semi conducting material and tinned copper wire


braid.

Bedding Halogen-free compound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with Clause 16.

Outer sheath Mud resistant thermoset compound in


accordance with type SEl.
Thickness - Sub-Clause 15.2a

Or a composite of therrnoset compound and an


outer mud resistant covering.
Page 25

3.14 Cable type P14 BFOB 6110 kV

High voltage power cables.


Fire resistant, flame retardant, low smoke
and mud resistant.
Design and construction in accordance with
IEC 92-354.

Basic type BFOB

Rated voltage 6/10(12) kV

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper in accordance


with IEC 228, class 2.

Insulation Fire resistant tape.


Ethylene propylene rubber (EPR) .
Thickness - Table I

Insulation screening: Semi conducting material and tinned copper wire


braid.

Bedding Halogen-free compound.


Thickness - Table 2, (inner covering).

Braid armour Tinned copper wire braid in accordance


with Clause 16.

Outer sheath Mud resistant thermoset compound in


accordance with type SEl.
Thickness - Sub-Clause 15.2a

Or a composite of thermoset compound and an


outer mud resistant covering.
Page 26

3.15 Cable type P15 UXIRX 0,611 kV

Earthing wire, bonding wire and single wire.


Flame retardant, low smoke and halogenfree.

Basic type ux I RX
Rated voltage 0,6/1 kV

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper in accordance


with IEC 228, class 2.

Insulation Halogen-free thermoset compound.


Thickness in accordance with
IEC 92-353 - Table 1

Colour

1) When used as
protective earth
(PE) wire Yellow/green

2) When used as
single wire Off-white, Black, Red or Blue
Page 27

3.16 Cable type P16 IFLI 250V

Cables for living quarter and office areas.


Flame retardant, low smoke and halgen-free.

Basic type IFLI

Rated voltage 250V

Max. operating 85°C


temperature

Conductor Circular stranded copper in accordance with


IEC 228, class 2. 1,5 and 2,5 mm 2

Number of cores 2 and 3 core cables.

Insulation Halogen-free thermoplastic compound.


Thickness - IEC 92-3, Table XV

Bedding Halogen-free thermoplastic compound.

Metal screen Longitudinal aluminium tape, thickness 0,2 mm


in contact with a stranded copper earth
conducto:r.

Outer sheath Halogen-free thermoplastic compound in


accordance with IEC 92-3, Table XVII, first
case.
Page 28

3.17 Cable type S1 RFOU(i) 250V

Cables for instrumentation and


telecommunication.

Individually screened pairs/triples


Flame retardant, low smoke, halogen-free.
Design and construction in accordance with IEC
92-3 and IEC 92-359 for the sheath material.

Basic Type RFOU (i)

Rated voltage 250V

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper 0,75mm2 in


accordance with IEC 228, class 2.

Insulation Ethylene propylene rubber (EPR) in accordance


with amendment no.3, type E85.
Thickness - Table XIV (0.80 mm).

Twinning Colour coded cores twisted together and wrapped


with polyester tape. Pairs/triples are screened
by copper backed polyester tape in contact with
a stranded tinned copper drain wire 0,75 mm2.
Pairs/triples are numbered with numbered tape
or by numbers printed directly on the insulated
conductors.

Bedding Halogen-free compound.


Thickness - IEC 502, Sub-Clause 6.6,
(inner covering) .

Braid armour Tinned copper wire braid in accordance


with Sub-Clause 10.19.

Outer sheath Halogen-free thermoset compound in accordance


with type SHF2.
Thickness - Table XVII, first case.
Page 29

3.18 Cable type 52 RFOU(c) 250V

Cables for instrumentation and


telecommunication.
Collectively screened pairs/triples
Flame retardant, low smoke and halogenfree.
Design and construction in accordance with IEC
92-3 and IEC 92-359 for the sheath material.

Basic type RFOU(c)

Rated voltage 250V

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper 0,75mm2 in


accordance with IEC 228, class 2.

Insulation Ethylene propylene rubber (EPR) in accordance


with amendment no.3, type E85.
Thickness - Table XIV (0.80 mm).

Twinning Colour coded cores twisted together and wrapped


with polyester tape. Pairs/triples are layed up
and collectively screened by copper backed
polyeste~ tape in contact with a stranded
tinned copper drain wire 0,75 mm2.
Pairs/triples are numbered with numbered tape
or by numbers printed directly on the insulated
conductors.

Bedding Halogen-free compound.


Thickness - IEC 502, Sub-Clause 6.6,
(inner covering).

Braid armour Tinned copper wire braid in accordance


with Sub-Clause 10.19.

Outer sheath Halogen-free thermoset compound in accordance


with type SHF2.
Thickness - Table XVII, first case.
Page 30

3.19 Cable type S3 BFOU(i) 250V

Cables for instrumentation and


telecommunication.
Individually screened pairs/triples. Fire
resistant,flame retardant, low smoke and
halogen-free. Design and construction in
accordance with IEC 92-3 and IEC 92-359 for the
sheath material.

Basic type BFOU(i)

Rated voltage 250V

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper 0,75mm2 in


accordance with IEC 228, class 2.

Insulation Fire resistant tape.


Ethylene propylene rubber (EPR) in accordance
with amendment no.3, type E85.
Thickness - Table XIV (0.80 mm).

Twinning Colour coded cores twisted together and wrapped


with polyester tape. Pairs/triples are screened
by copper backed polyester tape in contact with
a stranded tinned copper drain wire 0,75 mm2.
Pairs/triples are numbered with numbered tape
or by numbers printed directly on the insulated
conductors.

Bedding Halogen-free compound.


Thickness - IEC 502, Sub-Clause 6.6,
(inner covering) .

Braid armour Tinned copper wire braid in accordance


with Sub-Clause 10.19.

Outer sheath Halogen-free thermoset compound in accordance


with type SHF2.
Thickness - Table XVII, first case.
Page 31

3.20 Cable type S4 BFOU(c) 250V

Fire resistant cables for instrumentation and


telecommunication.
Collectively screened pairs/triples
Fire resistant, flame retardant, low smoke and
halogen-free. Design and construction in
accordance with IEC 92-3 and IEC 92-359 for the
sheath material.

Basic type BFOU (c)

Rated voltage 250V

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper 0,75mm2 in


accordance with IEC 228, class 2.

Insulation Fire resistant tape.


Ethylene propylene rubber (EPR) in accordance
with amendment no. 3, type E85.
Thickness - Table XIV (0.80 mm).

Twinning Colour coded cores twisted together and wrapped


with polyester tape .. Pairs/triples are layed
up and collectively screened by copper backed
polyester tape in contact with a stranded
tinned copper drain wire 0,75 mm2.
Pairs/triples are numbered with numbered tape
or by numbers printed directly on the insulated
conductors.

Bedding Halogen-free compound.


Thickness - IEC 502, Sub-Clause 6.6,
(inner covering) .

Braid armour Tinned copper wire braid in accordance


with Sub-Clause 10.19.

Outer sheath Halogen-free thermoset compound in accordance


with type SHF2.
Thickness - Table XVII, first case.
Page 32

3.21 Cable type S5 RFOB(i) 250V

Cables for instrumentation and


telecommunication.
Individually screened pairs/triples
Flame retardant and mud resistant
Design and construction in accordance with
IEC 92-3.

Basic type RFOB(i)

Rated voltage 250V

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper 0,75mm2 in


accordance with IEC 228, class 2.

Insulation Ethylene propylene rubber (EPR) in accordance


with amendment no.3 type E85.
Thickness - Table XIV (0.80 mm).

Twinning Colour coded cores twisted together and wrapped


with polyester tape. Pairs/triples are screened
by copper backed polyester tape in contact with
a stranded tinned copper drain wire 0,75 mm2.
Pairs/triples are numbered with numbered tape
or by numbers printed directly on the insulated
conductors.

Bedding Halogen-free compound.


Thickness - IEC 502, Sub-Clause 6.6,
(inner covering) .

Braid armour Tinned copper wire braid in accordance with


Sub-Clause 10.19.

Outer sheath Mud resistant thermoset compound in accordance


with type SEl.
Thickness - Table XVII, first case.

Or a composite of thermoset compound and an


outer mud resistant covering.
Page 33

3.22 Cable type S6 RFOB(c) 250V

Cables for instrumentation and


telecommunication.
Collectively screened pairs/triples
Flame retardant and mud resistant.
Design and construction in accordance with
IEC 92-3.

Basic type RFOB(c)

Rated voltage 250V

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper 0,75mm2 in


accordance with IEC 228, class 2.

Insulation Ethylene propylene rubber in accordance with


amendment no.3, type E85.
Thickness - Table XIV (0.80 mm).

Twinning Colour coded cores twisted together and wrapped


with polyester tape .. Pairs/triples are layed
up and collectively screened by copper backed
polyester tape in contact with a stranded
tinned copper drain wire 0,75 mm2.
Pairs/triples are numbered with numbered tape
or by numbers printed directly on the insulated
conductors.

Bedding Halogen-free compound.


Thickness - IEC 502, Sub-Clause 6.6,
(inner covering) .

Braid armour Tinned copper wire braid in accordance


with Sub-Clause 10.19.

Outer sheath Mud resistant thermoset compound in accordance


with type SEl.
Thickness - Table XVII, first case.

Or a composite of thermoset compound and an


outer mud resistant covering.
Page 34

3.23 Cable type S7 BFOB(i) 250V

Cables for instrumentation and


telecommunication.
Individually screened pairs/triples.
Fire resistant, flame retardant and mud
resistant. Design and construction in
accordance with IEC 92-3.

Baise type BFOB(i)

Rated voltage 250V

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper 0,75mm2 in


accordance with IEC 228, class 2.

Insulation Fire resistant tape.


Etylene propylene rubber (EPR) in accordance
with amendment no. 3, type E85.
Thickness - Table XIV (0.80 mm).

Twinning Colour coded cores twisted together and wrapped


with polyester tape. Pairs/triples are screened
by copper backed polyester tape in contact with
a stranded tinned copper drain wire 0,75 mm2.
Pairs/triples are numbered with numbered tape
or by numbers printed directly on the insulated
conductors.

Bedding Halogen-free compound.


Thickness - IEC 502, Sub-Clause 6.6,
(inner covering) .

Braid armour Tinned copper wire braid in accordance with


Sub-Clause 10.19.

Outer sheath Mud resistant thermoset compound in accordance


with type SEl.
Thickness - Table XVII, first case.

Or a composite of thermoset compound and an


outer mud resistant covering.
Page 35

3.24 Cable type SB BFOB(c) 250V

Cables for instrumentation and


telecommunication.
Collectively screened pairs/triples
Fire resistant, flame retardant and mud
resistant. Design and construction in
accordance with IEC 92-3.

Basic type BFOB(c)

Rated voltage 250V

Max. operating 85°C


temperature

Conductor Circular tinned stranded copper 0,75mm2 in


accordance with IEC 228, class 2.

Insulation Fire resistant tape.


Ethylene propylene rubber (EPR) in accordance
with amendment no. 3, type E85.
Thickness - Table XIV (0.80 mm).

Twinning Colour coded cores twisted together and wrapped


with polyester tape. Pairs/triples are layed up
and collectively screened by copper backed
polyester tape in contact with a stranded
tinned copper drain wire 0,75 mm2.
Pairs/triples are numbered with numbered tape
or by numbers printed directly on the insulated
conductors.

Bedding Halogen-free compound.


Thickness - IEC 502, Sub-Clause 6.6,
(inner covering) .

Braid armour Tinned copper wire braid in accordance with


Sub-Clause 10.19.

Outer sheath Mud resistant thermoset compound in accordance


with type SEl.
Thickness -Table XVII, first case.

Or a composite of thermoset compound and an


outer mud resistant covering.
Page 36

3.25 Cable type S9 IYXl(c)

Cables for instrumentation and


telecommunication for indoor use.
Collectively screened pairs/triples
Flame retardant, low smoke and halogenfree.

Basic type IYXI (c)

Conductor Solid tinned stranded copper 0,5mm0

Insulation Halogen-free thermoplastic compound.

Twinning Colour coded cores laid up in pairs. Pairs are


cross-stranded to finished cable or 10 pair
units. The units are stranded to 20 - 30 - 50
pair cables.

NB! 2 pair are starnded as a star quad.

Wrapping The cable core is wrapped with polyester tape.

Screening The cable core is screened by copper backed


polyester tape in contact with a solid tinned
drain wire, diameter = 0,5 mm0.

Outer sheath Halogen-free thermoplastic compound in


accordance with IEC 92~359 type SHFl.
Page 37

3.26 Cable type S10 IYOl(c)

Cables for instrumentation and


telecommunication for indoor use.
Collectively screened pairs/triples
Flame retardant, low smoke and halogenfree.

Basic type IYOI (c)

Conductor Solid tinned stranded copper 0,5mm0

Insulation Halogen-free thermoplastic compound.

Twinning Colour coded cores laid up in pairs. Pairs are


cross-stranded to finished cable or 10 pair
units. The units are stranded to 20 - 30 - 50
pair cables.

NB! 2 pair are starnded as a star quad.

Wrapping The cable core is wrapped with polyester tape.

Screening The cable core is screened by copper backed


polyester tape in contact with a solid tinned
drain wire, diameter = 0,5 mm0.

Inner sheath Halogen-·free thermoplastic compound in


accordance with IEC 92-359 type SHFl.

Braid armour Copper wire braid.

Outer sheath Halogen-free thermoplastic compound in


accordance with IEC 92-359 type SHFl.
Page 38

4. REQUIRED INFORMATION AND DATA

4.1 General

All information and data shall be in English language and in SI


units. The supplier shall list all the following information
together with the quotation.

4.2 Electrical Data for Cables for contro/1 lighting and power.

- Maximum continuous current rating at ambient temperature of


45°C in accordance with FEA-M clause 1881 Table IV

- Derating factors in accordance with FEA-M clause 1881.5 - 1881.11

- Reactance at 60 HZ in Ohm/km

- Impedance at 60 HZ in Ohm/km

- Short time rating and end temperature

4.3 Electrical Data for Cables for instrumentation and telecommunication.

- Inductance between conductors with screen grounded in Mh/km

- Mutual capacitance in nF/km

- Capacitance unbalances in pF/km


(pair-pair and pair-screen)

- The test voltage to be applied during testing,


ref. IEC 540, par. 16.2

- For type S9 and SlO:

- Mutual capacitance:
1 pair max. 90 nF/km
2 pairs max. 80 nF/km
4 pairs and above max. 70 nF/km

- Test voltage 1500V DC in 2 minutes.


Page 40

5. INSPECTION AND TESTING

5.1 General

All cables shall be routinely tested in accordance with relevant


IEC publictions. All cables shall be delivered with an original
test certificate with reference to the different tests.

5.2 Type Tests

A complete list of all type tests granted shall be furnished with


the quotation and shall include:

- Flame retardancy test (IEC 332-1 and IEC 332-3)

- Fire resistancy test (IEC 331)

- Compliance with IEC 92-353 and IEC 92-354 for low voltage
and high voltage power cables respectively

- Compliance with IEC 92-3 for 250V instrumentation and


telecommunication cables

6. PREPARATION FOR DELIVERY

6.1 General

Cable shall be delivered, if not otherwise specified, in 250, 500


or 1000 meter lengths.

All drum lengths shall be continuous. Cable or conductor jointing


in any form is unacceptable. ·

Cable ends shall be fitted with heat shrink end caps to prevent
entry of moisture into the cable.

Cable drum to be mechanically protected.

6.2 Cable Drum Identification

Cable drum shall be indelibly marked as follows:

- Company

- Drum No.

- Cable type and dimension

- Length of cable on the drum (m)

- Total weight of cable and drum (in kg)


Page 39

4.4 Mechanical and Physical Data

- Weight in kg/km

- Cable diameter under braiding in mm (with tolerances)

- Thickness of braiding in mm

- Cable diameter overall in mm (with tolerances)

- Minimum installation temperature in °C

- Minimum bending radius in mm at minimum installation


temperature

- Maximum pulling tension that can be safely applied

- Cable length, weight and dimension of each drum

- Minimum ordering lengths

- Drawing of each cable type showing conductor, insulation,


braiding, armouring and sheating arrangement, including filler
cores, if used.

4.5 Proposed Tests

The manufacturer's proposed tests on a completed cable shall be


specified as part of the quotation.