Professional Documents
Culture Documents
2VAA000334 en S Turbine Auto Synchronizer AS800 Product Guide
2VAA000334 en S Turbine Auto Synchronizer AS800 Product Guide
TRADEMARKS
All rights to other trademarks reside with their respective owners.
TABLE OF CONTENTS
1.3 Terminology............................................................................................................ 12
2. INTRODUCTION................................................................................................. 13
2.1 Product Overview ................................................................................................... 13
3. INSTALLATION .................................................................................................. 17
3.1 Termination Base Unit Connections..................................................................... 17
3.2 Modules................................................................................................................... 17
4. CONFIGURATION .............................................................................................. 19
4.1 Before You Start ..................................................................................................... 19
5. OPERATION ....................................................................................................... 43
5.1 General Description ............................................................................................... 43
5.8 Synchronizing a Live Bus to a Dead Bus Using the AS800 ................................ 55
6. MAINTENANCE.................................................................................................. 64
6.1 Preventive Maintenance......................................................................................... 64
7. SPECIFICATIONS .............................................................................................. 70
7.1 AS800 Product Specifications............................................................................... 70
1.1 Overview
This book provides a description of the AS800 modules and termination unit. It provides instructions for installation, start-
up, and information regarding capacity and performance. This book is not intended to be the sole source of instruction for
the AS800 I/O system.
This section provides introductory and background information including guidelines about how to find information in the
manual related documentation.
The Configuration section provides details for customizing the units to meet the requirements of individual applications.
The main information is structured as follows:
• Design considerations and guidelines.
• Capacity and performance.
The Operation section describes the various start modes and operating modes available for each installation.
The Maintenance section focuses on maintaining the modules and detecting faults. It explains system status displays in
operator stations and LEDs on modules.
In the Specifications section you will find a data sheet that lists the capacities of all of the components of the AS800
module.
A tip icon indicates advice on, for example, how to design your project or
how to use a certain function.
Although Warning hazards are related to personal injury, and Caution hazards are associated with equipment or property
damage, it should be understood that operation of damaged equipment could, under certain operational conditions, result
in degraded process performance, leading to personal injury or death. Therefore, comply fully with all Warning and
Caution notices.
1.3 Terminology
The following is a list of terms associated with the AS800 that you should be familiar with. The list contains terms and
abbreviations that are unique to ABB or have a usage or definition that is different from standard industry usage.
Term Description
Title Description
2. INTRODUCTION
The Auto Synchronizer AS800 provides automatic breaker closure during generator to grid synchronization or during peer
to peer bus synchronization in switchyard applications.
The AS800 compares and identifies the voltage, frequency, and phase between two buses, typically a line and generator.
It sends control signals used to adjust voltage and turbine speed in order to synchronize the two buses. It is also capable
of detecting a dead bus while initiating safe breaker closure.
The AS800 provides flexibility to operate efficiently in all turbine control environments. The module supports two voltage
ranges (e.g. 0-130 VAC and 0-50 VAC) operating at either 50 or 60 Hz (40-70Hz).
The AS800 can either be operated in harmony with a Profibus capable master controller, or it can operate independently
with hard-wired digital inputs and serial communication via a RS-232 physical interface.
In addition to the normal operating mode, the AS800 may be operated in Stand-Alone mode. The configuration
parameters are set to the proper values via a serial interface, either directly through the use of a terminal program or
through the use of the Modbus protocol. The current I/O values and status may also be retrieved via the Modbus protocol.
A Common Processor Module (CPM810) and an Auto-synchronization module (ASM810) plug into a Termination Base
Unit (TBU810) to form the basic AS800. One or more Relay Output Modules (ROM810) may be connected to the basic
AS800 to provide digital output signals. An Extended I/O Module (EIM810) may be connected to the basic AS800 to
provide an additional digital output signal in Stand-Alone mode. A Serial Interface Module (SIM810) may be connected to
the basic AS800 to provide connections to the serial interface.
The TBU810 can be mounted on a standard DIN rail. It has a mechanical latch to lock the TBU810 to the DIN rail. The
latch can be released with a screwdriver.
The TBU810 has two mechanical locking devices that lock the modules in place.
The ROM810 can be mounted on a standard DIN rail. It has a mechanical latch that locks the ROM810 to the DIN rail.
The latch can be released with a screwdriver.
The ROM810 has a connector that plugs directly into the TBU. To install the ROM810 simply place the ROM810 on the
DIN rail to the right of the TBU, and then slide it to the left until it is fully seated. Then secure the latch.
2.4.2 Communication
Profibus DPV0
Media 2 – Wire, Terminated RS-485
Baud Rate Up To 12 Mbits/sec
Data In Configuration and Control Values
(see section 3 for further details)
Data Out Reported Values
(see section 3 for further details)
RS-232 (via SIM810)
Media 3 – Wire, (Rx, Tx, Gnd)
Baud Rate 115.2 Kbits/sec
Data In Software & Firmware Upgrades
Configuration and Control Values (stand-alone)
Data Out Debug Information
Reported Values (stand-alone)
• Peer/Peer Synchronization
3. INSTALLATION
On the left side of the TBU810 are two ports for serial communication with a SIM810.
3.2 Modules
Install modules by aligning the connectors of the TBU810 and module, and then pushing the units together. Install the
CPM810 module into the left slot of the TBU810. Install the ASM810 module into the right slot of the TBU810.
Ensure that the module is fully engaged into the TBU810. Partial engagement may produce
unexpected results
After connection to the TBU810, lock the module in place using the Module Locking Device. Figure 3-2 shows how to
lock a module in place. In this example the CPM810 module is locked in place and the ASM810 module is not locked in
place.
The CPM810 module is used for several products. Each of these products pairs it with a
different companion module. When the CPM810 first powers up with a different type of
companion module, it will take about 1 minute longer to initialize. If the CPM810 is not allowed
to complete its initialization, it will not function properly.
Place the ROM810 on the DIN rail to the right of the TBU810, a previously installed EIM810, or a previously installed
ROM810. Slide the unit to the left until it is fully seated.
If an EIM810 is part of the AS800 installation, it must be connected to the TBU810. In this case, install the EIM810 before
installing any ROM810 modules.
Place the EIM810 on the DIN rail to the right of the TBU810 or a previously installed EIM810. Slide the unit to the left until
it is fully seated. At this time the AS800 only makes use of a single EIM810.
If an EIM810 is part of the AS800 installation, it must be connected to the TBU810. In this case, install the EIM810 before
installing any ROM810 modules.
Place the SIM810 on the DIN rail to the left of the TBU810, and then slide it to the right until it is fully seated.
Connect the serial communication cable to the connector labeled MA.
4. CONFIGURATION
4.2 TBU810
The terminals of the TBU810 provide the connections for module power, field I/O power, and all of the field I/O signals of
the AS800, except for the digital outputs. Figure 4-2 shows the terminals of the TBU810.
The two terminals labeled 24V + are connected together internally on the TBU810. The two terminals labeled 24V – are
connected together internally on the TBU810. The output of a 24V power supply must be connected between one of the
24V + terminals and one of the 24V – terminals to supply power to the modules. The other pair of 24V ± terminals may be
used to connect the 24V power to the L1 terminals or to another module.
The two terminals labeled L1 + are connected together internally on the TBU810. The two terminals labeled L1 – are
connected together internally on the TBU810. These terminals provide a fused connection to several terminals of the A
2VAA000334 Auto Synchronizer AS800 19
21BTBU810 2BCONFIGURATION
row of terminals in order to supply power to field devices, such as digital inputs. Terminals A1, A5, A7, A9, and A11 are
connected to the L1 + terminals via a fuse. Terminals A2, A6, A8, A10, and A12 are connected directly to the L1 –
terminals. Power sources up to 24 VDC may be connected to the L1 ± terminals.
The B and C row of terminals provide the field I/O signal connections. Table 4-1 lists the field I/O terminals used by the
AS800, the signals to connect to them, and the associated status LED on the CPM810.
TBU TBU
CPM810
+ – Signal Description
LED Label
Terminal Terminal
C1 B1 Auto-Sync Enable LV3
C2 B2 Frequency Match Enable LV5
C3 B3 Breaker Close Enable LV6
C4 B4 Voltage Match Enable LV4
C5 B5 Primary Relay Feedback LV1
C6 B6 Independent Relay Feedback LV2
C7 B7 Bus B HV2
C8 B8 Bus A HV1
C9 B9 Breaker Feedback DI2
C10 B10 Dead Bus Enable DI1
TBU810
Description
Terminal
A1 I/O Power
A2 I/O Common
A3 not used by the AS800
A4 not used by the AS800
A5 I/O Power
A6 I/O Common
A7 I/O Power
A8 I/O Common
A9 I/O Power
A10 I/O Common
A11 I/O Power
A12 I/O Common
The four sets of 3-post headers that are accessible through the hole in the upper right section of the TBU810 are used to
select whether or not the Profibus signals are passed on to the next TBU810 in a redundant configuration. The AS800 is
not capable of a redundant configuration, therefore, set all of the selection settings to the DO NOT PASS position. Table 4-3
lists the valid selections.
The following sections provide guidelines for how to connect various commonly used types of field I/O devices to the
TBU810.
Warning: improper connection of the Bus inputs can cause serious and expensive equipment
damage.
TBU810
Note: System Redundancy requires a backup address to be n+64; therefore the highest possible primary address with
System Redundancy enabled is 61 for a backup address of 125.
The AS800 does not implement a Redundant Mode configuration. Set the leftmost switch, labeled “1”, of the DIP switch of
the CPM810 to the 0 position (“OFF” or “OPEN”).
The two terminals labeled C1 and C2 are connected together internally on the ROM810 and provide a connection to the
positive wire of the power source. The two terminals labeled B1 and B2 are connected together internally on the ROM810
and provide a connection to the negative wire of the power source. The output of a 24V power supply must be connected
either between the C1 / B1 pair of terminals or between the C2 / B2 pair of terminals to supply power to the module and
the relay coils. The other pair of terminals may be used to connect the 24V power to another module.
The two terminals labeled A1 and A2 are connected together internally on the ROM810 and are connected to earth
ground internally. These two terminals may be used to land shield wires.
The ROM810 has two relays which provide up to two digital outputs. These relays are 2 form C type relays, which provide
two sets of normally open and normally closed contacts, activated by a single coil. Figure 4-10 shows the relay contact
terminals of the ROM810. Relay K1 is the relay located closer to the digital output selection jumpers and relay K2 is the
relay located closer to the terminals.
K2 K2 K1 K1
C3 C4 C5 C6 C7 C8 C9 C10
B3 B4 B5 B6 B7 B8 B9 B10
The two terminals labeled A3 and A4 are connected together internally on the ROM810. The two terminals labeled A5
and A6 are connected together internally on the ROM810. The two terminals labeled A7 and A8 are connected together
internally on the ROM810. The two terminals labeled A9 and A10 are connected together internally on the ROM810.
None of these terminals are connected to anything else in the ROM810 module. They may be used to jumper wires
together.
The ROM810 has two sets of jumper pins to select which digital output from the AS800 activates each relay. Each set of
jumper pins has three columns with three pins each. These two sets of jumper pins are located together in one corner of
the ROM810. The left set, labeled J1 – J3, select the digital output to assign to relay K1. The right set, labeled J4 – J6,
select the digital output to assign to relay K2.
The AS800 can activate up to 6 digital outputs using the jumper selections of an ROM810 module. Each jumper selection
has an assigned function, which is listed in Table 4-5. The other jumper selections of the ROM810 module are not used.
The four terminals labeled 24 + are connected together internally on the ROM810. The four terminals labeled 24 – are
connected together internally on the ROM810. The output of a 24V power supply must be connected between one pair of
the 24 + terminals (positive output) and the 24 – terminals (common) to supply power to the module and the relay coils.
The other pairs of 24 + and 24 – terminals may be used to connect the 24V power to another module or to wet the relay
contacts.
The two terminals labeled are connected together internally on the ROM810 and are connected to earth ground
internally. These two terminals may be used to land shield wires.
The ROM810 has two relays which provide up to two digital outputs. These relays are 2 form C type relays, which provide
two sets of normally open and two sets of normally closed contacts, activated by a single coil. Figure 4-12 shows the
relay contact terminals of the ROM810. Relay K1 is the relay located closer to the digital output selection dipswitch and
relay K2 is the relay located closer to the terminals.
K2 K2 K1 K1
C1 C2 C3 C4 C5 C6 C7 C8
B1 B2 B3 B4 B5 B6 B7 B8
The ROM810 contains three internal relays that provide indication of the status of the module power and the state of the
K1 and K2 relays. These relays indicate the state of the condition that they monitor through the use of a pair of dry
contacts, each of which is connected to two of the module’s terminals.
The two terminals labeled A1 and A2 are used to monitor the status of power on the module. These contacts will be
closed when the module power is OK.
The two terminals labeled A3 and A4 are used to monitor the status of the K2 relay coil. When the coil is energized, these
contacts will be closed.
The two terminals labeled A5 and A6 are used to monitor the status of the K1 relay coil. When the coil is energized, these
contacts will be closed.
The two terminals labeled A7 and A8 are connected together internally on the ROM810. The two terminals labeled A9
and A10 are connected together internally on the ROM810. None of these terminals are connected to anything else in the
ROM810 module. They may be used to jumper wires together.
The ROM810 has a dipswitch to select which digital output from the VP800 activates each relay. The leftmost three
switches, labeled 1 – 3, select the digital output to assign to relay K1. The rightmost three switches, labeled 4 – 6, select
the digital output to assign to relay K2.
The AS800 can activate up to 6 digital outputs using the dipswitch selections of an ROM810 module. Each dipswitch
selection has an assigned function, which is listed in Table 4-5. The other dipswitch selections of the ROM810 module
are not used.
ROM810 ROM810
Digital
Rev A V 2.0 Relay
Output
Jumper Dipswitch Function
Selection
Setting Setting
0 Raise Volts
1 Lower Volts
2 Breaker Close
3 Raise Speed
4 Lower Speed
Independent
5
Check
Multiple ROM810 modules may be cascaded together to provide additional digital outputs or additional connections to a
digital output.
Table 4-6 lists the wiring assignments for the terminals of the EIM810.
EIM810
Signal Signal Description
Terminal
C5 NC No connection
C6 NC No connection
EIM810
Signal Signal Description
Terminal
The EIM810 has one LED located next to the DIP switch. The LED lights GREEN when the board is functioning correctly
and RED when the internal microcontroller detects an error.
A3 +24
C7 +
Digital Output 1
C8 -
A5 Com
EIM810
A3 +24
C7 +
+ 24VDC
- -
C8
Digital Output 1
A5 Com
EIM810
Profibus communication is divided into 3 parts, parameter data sent once when the I/O module begins operating, live data
sent to the I/O module periodically, and live data reported by the I/O module periodically. The live data period is set by the
controller. The AS800 only receives and transmits live data. It does not utilize the Profibus parameters.
All of the live data values sent to the AS800 must lie within the valid range established for each value, even if the feature
with which they are associated is not being used. For example, if the dead bus closure feature is not being used, the dead
bus voltage and frequency must still be set to valid values. The valid range for each value sent to the AS800 is listed in
Section 4.7.1.
Typ.
ID Signal Purpose Type EU Min Max
Val.
Typ.
ID Signal Purpose Type EU Min Max
Val.
Typ.
ID Signal Purpose Type EU Min Max
Val.
0 Line/Generator, Stand-Alone.
In Peer To Peer modes use this parameter to specify the amount of time to wait after activation of the Independent check
relay before activating the primary breaker closure relay in units of seconds.
When dead bus closure control in enabled, this parameter indicates when the live bus meets the criteria established by the
Dead Bus Match Voltage (D18) parameter.
When dead bus closure control in enabled, this parameter indicates when the live bus meets the criteria established by the
Dead Bus Match Frequency (D19) parameter.
5. OPERATION
The Analog Inputs typically come from Potential Transformers (PT’s) that step down the bus level voltage. The module
reads the RMS voltage and frequency from the PT’s. In addition, the module compares the phase difference between the
two busses.
The AS800 sends digital outputs to the ROM810 relay module to control the bus voltage and frequency by sending raise
or lower voltage pulses, and raise or lower speed pulses. Additionally, these signals are sent to the controller via Profibus.
The AS800 utilizes another relay to initiate breaker closure when it determines that the buses are properly aligned. The
independent checking function uses another digital output to provide verification that the buses are properly aligned.
Several digital inputs indicate breaker status, relay status checking, and optional hard-wired permissive signals used in the
stand-alone mode.
5.1.1 AC Inputs
The AC inputs of the AS800 accept 0-130 VAC, 40-70 Hz signals from either bus input. The AS800 reads the bus voltage
and frequency, and it calculates the phase difference between the two bus frequencies. The AS800 uses the voltage,
frequency, and phase difference between the buses for control and initiation of breaker closure.
To take advantage of the redundant synchronization check, connect the close breaker relay and
the independent check relay in series.
5.1.6 Communication
The AS800 uses Profibus for its main channel of communication with the system controller. The controller uses the
Profibus to configure the AS800 and to monitor its operation.
The AS800 uses RS-232 serial communication when operating in stand-alone mode. The AS800 may be configured and
monitored using the Modbus protocol or by means of terminal commands.
There are three main scenarios for when a breaker will be closed, a generator is to be connected to a line bus, two peer
buses are to be connected, or a live bus is to be connected to a dead or de-energized bus, sometimes referred to as a
black bus. Each of these cases has its own variations to the basic criteria that must be met before attempting to close a
breaker.
There are three basic criteria that govern the synchronization process, phase angle matching, frequency matching, and
voltage matching. These three criteria establish the conditions that must be met in order to safely close the breaker. The
scope of the criteria varies for each of the different scenarios.
The most critical part of the synchronization process is making sure that the two buses are in phase when the breaker is
closed. The process used to ensure that this condition is met is referred to as phase angle matching. Every bus that has
a live AC signal present will have an associated phase angle. When two buses have the same phase angle, then a
breaker between them may be closed without incurring any damage. If the breaker is closed when the two buses are not
in phase, then an arc will bridge the gap between the contacts of the breaker as they approach each other. An arc
between the contacts will damage one or both of the contacts. The severity of the damage depends on the amount of
energy in the arc, which increases as the difference in phase angles increases, with 180° out of phase being the worst
case. If the breaker breaks apart while closing, then there will be a significant risk of bodily harm to any personnel in the
vicinity.
If the breaker is closed out of phase when connecting a generator to an established line, then the buses must resolve the
phase difference to remain connected. The strength of the line will force the generator to be the one that attempts to
adjust itself to conform to the other. This means that the generator will suddenly try to rotate into the position that would
be aligned with the line bus, which will generate a torque force. The generator is not designed to handle large amounts of
torque, so normally it will incur damage if it is connected to the line significantly out of phase. The amount of potential
damage increases as the phase difference increases. Most likely, the turbine will suffer damage too.
When attempting to close a breaker between two buses, the difference in phase angle between the two buses is
monitored to determine when to initiate breaker closure. A phase angle difference of 0° indicates that the buses are in
phase. It is the goal of the synchronization process to have the contacts of the breaker meet when the phase angle
difference is 0°.
The nature of what constitutes successful phase angle matching is different for the three synchronization scenarios. The
specifics of what the criteria are for each scenario are explained in the subsequent sections dedicated to each scenario.
Frequency matching is a broad term that is used to refer to the process of ensuring that the frequencies of two buses that
are to be connected are compatible before attempting to close the breaker. Two considerations come into play
surrounding the frequency of buses that are to be connected. First, the frequencies of the buses must be near the
standard frequency established by the applicable regulatory body. Second, the difference in frequency between the two
buses will dictate the rate of change in their phase angle difference. The frequency of one bus may be manipulated in
order to facilitate successful phase angle matching. The nature of what constitutes successful frequency matching is
different for the three synchronization scenarios. The specifics of what the criteria are for each scenario are explained in
the subsequent sections dedicated to each scenario.
Voltage matching is a broad term that is used to refer to the process of ensuring that the voltage levels of two buses that
are to be connected are compatible before attempting to close the breaker. Two considerations come into play
surrounding the voltage level of buses that are to be connected. First, the voltage levels of the buses must be near the
standard voltage established by the applicable regulatory body. Second, it may be desired that the voltage level of a
generator bus be higher than the line in order to avoid the condition where the generator would behave like a motor and
present a load to the bus after the breaker is closed. The nature of what constitutes successful voltage matching is
different for the three synchronization scenarios. The specifics of what the criteria are for each scenario are explained in
the subsequent sections dedicated to each scenario.
5.2.1.4 Synchroscope
A commonly used tool to monitor the phase angle difference between two buses is a synchroscope. A synchroscope is a
meter with a circular face that is gradated into 360 degrees, beginning with 0°, where 0° is located in the “12 o’clock”
position and the angles increase in the counterclockwise direction, concluding at the 0° position. A needle indicates the
phase angle difference between the two buses. The direction that the needle moves indicates which bus has a higher
frequency, and the rate of movement of the needle is directly proportional to the rate of change in the phase angle
difference between the two buses. The buses are in phase when the needle points to the 0° position. Figure 5-1
illustrates a synchroscope whose needle indicates that the two buses are in phase.
However, this synchronization scenario provides the advantage of being able to control the frequency and voltage level of
the generator, so the generator bus can easily be brought into alignment with the line, and thus make the synchronization
process go smoother with less likelihood of closing the breaker out of phase or presenting a motor load to the line. If the
frequency of the generator is fixed at a different rate than the line, then the rate of change in the phase angle difference
between the two buses will be constant, so the appropriate time to initiate closure of the breaker can readily be predicted,
based on the rate of change and the time it takes for the breaker to close.
Typically, the frequency of the generator is set to be slightly faster than the line frequency. This practice provides two
situations that allow the synchronization process to operate more smoothly. First, the phase angle difference will be
changing at a relatively constant rate, which will shorten the time required to achieve a phase match and allow the proper
time to initiate closure of the breaker to be accurately predicted. Second, when the turbine slows down to align itself to the
frequency of the line bus after the breaker is closed, the generator is less likely to present a motor load to the line bus.
The difference in frequency between the line and generator is referred to as the slip frequency.
The concept of frequency matching when synchronizing a generator to a line bus refers to achieving the desired slip
frequency on the generator. Typically, a window is defined around the target slip frequency, and the generator frequency
is considered to be matched whenever it falls within this window.
Typically, the voltage level of the generator is set to be the same as or slightly higher than the line voltage. This practice
helps to ensure that the generator is less likely to present a motor load to the line bus after the breaker is closed. The
difference in voltage between the line and generator is referred to as the offset voltage.
The concept of voltage matching when synchronizing a generator to a line bus refers to achieving the desired offset
voltage on the generator. Typically, a window is defined around the target offset voltage, and the generator voltage is
considered to be matched whenever it falls within this window.
The actual slip frequency of the generator will dictate the rate of change in the phase angle difference. Smaller slip
frequencies will result in slower rates of change, while larger slip frequencies will result in faster rates of change. As the
rate of change increases, so does the phase angle difference at which to initiate breaker closure in order to achieve a
phase angle difference of 0° when the breaker contacts meet.
The concept of phase matching when synchronizing a generator to a line bus refers to achieving the calculated angle at
which to initiate breaker closure. Typically, a window is defined around the calculated angle at which to initiate breaker
closure that constitutes a range of angles that will be acceptable to serve as the initiation angle. The phases of the
generator and line are considered to be matched whenever their difference falls within this window.
5.2.2.4 Synchroscope
For the synchronization of a generator to a line bus application, a synchroscope is wired so that the needle will move in
the clockwise direction when the generator has a higher frequency than the line bus. This allows the synchroscope to
show the phase angle difference between the buses decreasing toward 0° when a frequency match is achieved.
An angle is determined by calculation as the appropriate angle at which to initiate breaker closure. The breaker closure
will then be initiated when the needle of the synchroscope points to the computed angle. When done properly, the needle
will continue to move, and the contacts of the breaker will meet when the needle reaches the 0° position.
Figure 5-2 illustrates what a conventional synchroscope would show during the generator to line synchronization process.
In this snapshot of the synchroscope the needle indicates a phase angle difference of about 140°, and the needle is
moving toward the angle at which to initiate breaker closure.
The breaker will be the most likely piece of equipment to suffer damage if an attempt is made to close the breaker out of
phase, when synchronizing two peer buses.
The concept of frequency matching when synchronizing one bus to a peer bus refers to confirming that the difference in
frequency between the two buses lies within the acceptable range. Typically, a window is defined to set the bounds of
what constitutes an acceptable difference in frequency, and the bus frequencies are considered to be matched whenever
the difference in their frequencies falls within this window.
The concept of voltage matching when synchronizing one bus to a peer bus refers to confirming that the difference in
voltage between the two buses lies within the acceptable range. Typically, a window is defined to set the bounds of what
constitutes an acceptable difference in voltage, and the bus voltages are considered to be matched whenever the
difference in their voltages falls within this window.
The concept of phase matching when synchronizing one bus to a peer bus refers to confirming that the difference in phase
between the two buses lies within the acceptable window for the designated length of time. The phases of the two buses
are considered to be matched whenever this criterion is met.
The concept of frequency matching when synchronizing a live bus to a dead bus refers to confirming that the frequency of
the live bus lies within the acceptable range. Typically, a threshold level is defined to set the lower bound of what
constitutes an acceptable frequency, and the frequency of the live bus is considered to be matched whenever it is above
this threshold.
The concept of voltage matching when synchronizing a live bus to a dead bus refers to confirming that the voltage of the
live bus lies within the acceptable range. Typically, a threshold level is defined to set the lower bound of what constitutes
an acceptable voltage, and the voltage of the live bus is considered to be matched whenever it is above this threshold.
• The bus voltage must be between 50% and 110% of the expected voltage, as specified by the Secondary
Voltage Bus A (D15) and Secondary Voltage Bus B (D23) parameters.
• The bus frequency must be within the window around the value specified by the Expected Frequency (D24.1)
parameter, whose bounds are selected by the Frequency Lower Limit (D16) and Frequency Upper Limit (D17)
parameters, as shown below.
The AS800 considers a voltage match to be achieved when the generator voltage moves into the inner voltage match
window. After a voltage match is achieved, it will persist until the generator voltage falls outside of the outer voltage match
window. Figure 5-3 illustrates the voltage match windows and the matching process.
The bounds of the inner voltage match window used to establish that a voltage match has been achieved are set by the
Bus A (line) voltage and the Offset Voltage (D12) and Dead Band Voltage (D10) parameters, according to the following
formulas.
The bounds of the outer voltage match window used to establish that a voltage match has been lost are also set by the
Bus A (line) voltage and the Offset Voltage (D12) and Dead Band Voltage (D10) parameters, but according to the
following formulas.
Allowable Generator
Voltage Deadband
50% Generator
Voltage Voltage Match Lost
Deadband
Voltage Difference
Offset
Line Target
Voltage Generator
Voltage
Likewise, the AS800 considers a frequency match to be achieved when the generator frequency moves into the inner
frequency match window. After a frequency match is achieved, it will persist until the generator frequency falls outside of
the outer frequency match window. Figure 5-4 illustrates the frequency match windows and the matching process.
The bounds of the inner frequency match window used to establish that a frequency match has been achieved are set by
the Bus A (line) frequency and the Slip Frequency (D11) and Dead Band Frequency (D9) parameters, according to the
following formulas.
The bounds of the outer frequency match window used to establish that a frequency match has been lost are also set by
the Bus A (line) frequency and the Slip Frequency (D11) and Dead Band Frequency (D9) parameters, but according to
the following formulas.
Allowable Generator
Frequency Deadband
50% Generator
Frequency Frequency Match Lost
Deadband
Frequency Difference
Slip Frequency
Line Target
Frequency Generator
Frequency
The AS800 considers a voltage match to be achieved when the Bus B voltage falls within the voltage match window.
The bounds of the voltage match window used to establish that a voltage match has been achieved are set by the Bus A
voltage and the Dead Band Voltage (D10) parameter, according to the following formulas.
Upper Bound = Bus A voltage + (Bus A voltage x Dead Band Voltage / 100 / 2)
Lower Bound = Bus A voltage – (Bus A voltage x Dead Band Voltage / 100 / 2)
Likewise, the AS800 considers a frequency match to be achieved when the Bus B frequency falls within the frequency
match window.
The bounds of the frequency match window used to establish that a frequency match has been achieved are set by the
Bus A frequency and the Dead Band Frequency (D9) parameter, according to the following formulas.
The lower bound of the voltage match window is set to a percentage of the target voltage. The target voltage is specified
by the Secondary Voltage Bus A (D15) parameter or the Secondary Voltage Bus B (D23) parameter, depending on
which bus is the live bus. The percentage to apply to the target voltage is specified by the Dead Bus Match Voltage
(D18) parameter. The upper bound of the voltage match window is set to 110 % of the target voltage. The calculation of
the bounds is performed according to the following formulas.
The criteria to establish that a bus is de-energized are that the voltage level of the bus is below the minimum allowed
voltage for a dead bus, as specified by the Dead Bus Voltage (D20) parameter, that the frequency of the bus is below the
minimum allowed frequency for a dead bus, as specified by the Dead Bus Frequency (D21) parameter, and that both of
these conditions persists for 10 s.
Many of the error status values will persist in order to allow them to be recognized. Some of these error status values will
prevent the control functions from further operation. Reset the Auto-Sync Enable (D24.3) parameter to 0 to clear the
status value to no error.
• The Bus A frequency is reported by the Actual Frequency Bus A (R3) output parameter.
• The calculated Bus A primary voltage is reported by the Actual Voltage Bus A Primary (R8) output parameter.
This value is calculated as the product of the Actual Voltage Bus A Secondary (R2) value and the ratio of the
Primary Voltage Bus A (D14) parameter to the Secondary Voltage Bus A (D15) parameter.
• The Bus B secondary voltage is reported by the Actual Voltage Bus B Secondary (R4) output parameter.
• The Bus B frequency is reported by the Actual Frequency Bus B (R5) output parameter.
• The calculated Bus B primary voltage is reported by the Actual Voltage Bus B Primary (R9) output parameter.
This value is calculated as the product of the Actual Voltage Bus B Secondary (R4) value and the ratio of the
Primary Voltage Bus B (D22) parameter to the Secondary Voltage Bus B (D23) parameter.
• The phase angle difference between the two buses is reported by the Phase Difference (R6) output parameter.
2VAA000334 Auto Synchronizer AS800 51
31BSynchronizing a Generator to a Line Bus Using the AS800 3BOPERATION
The generator to line bus automatic synchronization function operates according to the convention that the line input
signal is connected to the Bus A terminals of the TBU810 and the generator input signal is connected to the Bus B
terminals of the TBU810.
Set the Application Mode (D2) parameter to a value of 0 to enable the generator to line bus automatic synchronization
function in Stand-Alone mode or to a value of 8 to enable the generator to line bus automatic synchronization function in
Profibus communication mode.
The generator to line bus automatic synchronization function provides three control functions to facilitate achieving the
conditions necessary to close the breaker.
Closing the breaker is handled by the breaker closure control function. This function must be enabled for the AS800 to
initiate closure of the breaker. When enabled, it calculates the angle at which to initiate closure, based on the rate of
change in the phase angle difference and the time to close the breaker as specified by the Breaker Close Time / Hold
Time (D13) parameter, and tracks the phase angle difference until it reaches the calculated closure angle, when it will
initiate breaker closure.
The generator to line bus automatic synchronization function provides an optional control function to set the voltage level
of the generator. When enabled, it pulses raise and lower digital output signals to change the voltage level of the
generator until a voltage match is achieved. If this function is not used, then the voltage level of the generator must be
manipulated external to the AS800 in order to achieve a voltage match. The conditions that constitute a voltage match are
given is Section 5.3.3.1.
The generator to line bus automatic synchronization function provides an optional control function to set the frequency of
the generator. When enabled, it pulses raise and lower digital output signals to change the speed of the turbine, and thus
the frequency of the generator, until a frequency match is achieved. If this function is not used, then the frequency of the
generator must be manipulated external to the AS800 in order to achieve a frequency match. The conditions that
constitute a frequency match are given is Section 5.3.3.1.
The AS800 sets the value of the Increase Voltage (R10.10) output parameter to 1 whenever the Raise Volts Digital
Output is activated, and sets the value of the Decrease Voltage (R10.11) output parameter to 1 whenever the Lower
Volts Digital Output is activated. These output parameters may be used to manipulate the voltage level of the generator
through external means in lieu of the Digital Outputs.
Section 5.3.3.1 provides an explanation of the criteria used to establish a voltage match for the generator to line bus
automatic synchronization function.
The AS800 sets the value of the Increase Speed (R10.5) output parameter to 1 whenever the Raise Speed Digital Output
is activated, and sets the value of the Decrease Speed (R10.6) output parameter to 1 whenever the Lower Speed Digital
Output is activated. These output parameters may be used to manipulate the frequency of the generator through external
means in lieu of the Digital Outputs.
Section 5.3.3.1 provides an explanation of the criteria used to establish a frequency match for the generator to line bus
automatic synchronization function.
If the AS800 does not detect that the phase angle difference passes through the 0° position for 2 minutes without losing
frequency match, indicating that the rate of change has become near stagnant, then it will issue a single Raise Speed
Digital Output pulse and rearm the timer.
The AS800 monitors the state of the breaker after initiating closure to verify that the breaker actually closed. If the breaker
closes, the AS800 suspends the synchronization process and sets the value of the Last Phase at Closure (R7) output
parameter to the phase angle difference at which breaker closure was initiated. If the breaker fails to close, the AS800 will
make additional attempts to close the breaker, until the number of attempts exceeds the value of the Attempts Breaker
Close (D1) parameter.
The island mode generator to line bus automatic synchronization function ensures that all of the criteria associated with
this type of synchronization are met before any attempt is made to close the breaker, including ensuring that the two
buses have good quality and that both a voltage match and a frequency match are achieved. Unlike the standard
generator to line bus automatic synchronization function, this function does not require that the value of the Slip
Frequency (D11) parameter be greater than 0 Hz, thus allowing the phase angle difference to move in either direction.
Since the phase angle difference may move in either direction, the stability window and maximum closure angle are
mirrored on the other side of 0°. This function ensures that the generator’s output signal remains stable through the
stability window and that the maximum closure angle is not exceeded.
The island mode generator to line bus automatic synchronization function operates according to the convention that the
line input signal is connected to the Bus A terminals of the TBU810 and the generator input signal is connected to the
Bus B terminals of the TBU810.
Set the Application Mode (D2) parameter to a value of 1 to enable the island mode generator to line bus automatic
synchronization function in Stand-Alone mode or to a value of 16 to enable the island mode generator to line bus
automatic synchronization function in Profibus communication mode.
The island mode generator to line bus automatic synchronization function provides three control functions to facilitate
achieving the conditions necessary to close the breaker.
Closing the breaker is handled by the breaker closure control function. This function must be enabled for the AS800 to
initiate closure of the breaker. When enabled, it calculates the angle at which to initiate closure, based on the rate of
change in the phase angle difference and the time to close the breaker as specified by the Breaker Close Time / Hold
Time (D13) parameter, and tracks the phase angle difference until it reaches the calculated closure angle, when it will
initiate breaker closure.
The island mode generator to line bus automatic synchronization function provides an optional control function to set the
voltage level of the generator. When enabled, it pulses raise and lower digital output signals to change the voltage level of
the generator until a voltage match is achieved. If this function is not used, then the voltage level of the generator must be
manipulated external to the AS800 in order to achieve a voltage match. The conditions that constitute a voltage match are
given is Section 5.3.3.1.
The island mode generator to line bus automatic synchronization function provides an optional control function to set the
frequency of the generator. When enabled, it pulses raise and lower digital output signals to change the speed of the
turbine, and thus the frequency of the generator, until a frequency match is achieved. If this function is not used, then the
frequency of the generator must be manipulated external to the AS800 in order to achieve a frequency match. The
conditions that constitute a frequency match are given is Section 5.3.3.1.
The AS800 sets the value of the Increase Voltage (R10.10) output parameter to 1 whenever the Raise Volts Digital
Output is activated, and sets the value of the Decrease Voltage (R10.11) output parameter to 1 whenever the Lower
Volts Digital Output is activated. These output parameters may be used to manipulate the voltage level of the generator
through external means in lieu of the Digital Outputs.
Section 5.3.3.1 provides an explanation of the criteria used to establish a voltage match for the generator to line bus
automatic synchronization function.
The AS800 sets the value of the Increase Speed (R10.5) output parameter to 1 whenever the Raise Speed Digital Output
is activated, and sets the value of the Decrease Speed (R10.6) output parameter to 1 whenever the Lower Speed Digital
Output is activated. These output parameters may be used to manipulate the frequency of the generator through external
means in lieu of the Digital Outputs.
Section 5.3.3.1 provides an explanation of the criteria used to establish a frequency match for the generator to line bus
automatic synchronization function.
If the AS800 does not detect that the phase angle difference passes through the 0° position for 2 minutes without losing
frequency match, indicating that the rate of change has become near stagnant, then it will issue a single Raise Speed
Digital Output pulse and rearm the timer.
The AS800 monitors the state of the breaker after initiating closure to verify that the breaker actually closed. If the breaker
closes, the AS800 suspends the synchronization process. If the breaker fails to close, the AS800 will make additional
attempts to close the breaker, until the number of attempts exceeds the value of the Attempts Breaker Close (D1)
parameter.
Set the Application Mode (D2) parameter to a value of 2 to enable the peer to peer automatic synchronization function in
Stand-Alone mode or to a value of 32 to enable the peer to peer automatic synchronization function in Profibus
communication mode.
The peer to peer automatic synchronization function provides one control function to facilitate achieving the conditions
necessary to close the breaker.
Closing the breaker is handled by the breaker closure control function. This function must be enabled for the AS800 to
initiate closure of the breaker. When enabled, it calculates the angle at which to initiate closure, based on the rate of
change in the phase angle difference and the time to close the breaker, and tracks the phase angle difference until it
reaches the calculated closure angle, when it will initiate breaker closure.
The conditions that constitute a voltage match and a frequency match are given is Section 5.3.3.2.
The AS800 monitors the state of the breaker after initiating closure to verify that the breaker actually closed. If the breaker
closes, the AS800 suspends the synchronization process. If the breaker fails to close, the AS800 will make additional
attempts to close the breaker, until the number of attempts exceeds the value of the Attempts Breaker Close (D1)
parameter.
The dead bus automatic synchronization function is not a separate application mode, but is enabled from within either a
generator to line bus or a peer to peer automatic synchronization function by setting the Dead Bus Enable (D24.8)
parameter to a value of 1.
Even when the dead bus automatic synchronization function is not enabled, the AS800 will monitor for a dead bus
condition. When the generator to line bus automatic synchronization function is active, the AS800 will only monitor Bus A.
When the peer to peer automatic synchronization function is active, the AS800 will monitor both buses. When a dead bus
is detected, the Actual Dead Bus Input (R10.2) output parameter is set to a value of 1. The conditions that constitute a
dead bus are given in Section 5.3.7.
When the generator to line bus automatic synchronization function is active while attempting to close the breaker to a
dead bus, the breaker closure, voltage match, and frequency match control functions are available to facilitate the
matching and closure processes, however these functions are adjusted to meet the conditions for the dead bus
synchronization function. The operation of the voltage match and frequency match control functions remains the same,
except that the target windows are changed to those given in Section 5.3.3.3. The changes in the operation of the breaker
closure control function are described in the following section.
When the peer to peer automatic synchronization function is active while attempting to close the breaker to a dead bus,
the breaker closure control function is available to facilitate the closure process, however this function is adjusted to meet
the conditions for the dead bus synchronization function, as described in the following section.
The AS800 monitors the state of the breaker after initiating closure to verify that the breaker actually closed. If the breaker
closes, the AS800 suspends the synchronization process. If the breaker fails to close, the AS800 will make additional
attempts to close the breaker, until the number of attempts exceeds the value of the Attempts Breaker Close (D1)
parameter.
Section 4.2.4 provides information about how to wire the relay state feedback signals. Sections 0 and 4.2.3 provide
information about how to wire the other DI’s.
The relay state feedback DI’s are required to be wired in order for the AS800 to initiate breaker closure. Without these
signals, the AS800 will constantly report that an error condition exists.
The AS800 lights the LV1 LED of the CPM810 module whenever the Primary Relay Feedback DI is active.
This input is duplicated in the Profibus interface through the Main Breaker Status (D24.7) parameter. The AS800
considers the breaker to be closed if either of the sources for this input indicates that the breaker is closed.
The Breaker Feedback Configuration (D24.2) parameter specifies whether the Breaker Status DI will indicate that the
breaker is closed when the input signal is high or when the input signal is low. The Main Breaker Status (D24.7)
parameter always indicates that the breaker is closed when it is set to a value of 1.
The AS800 sets the value of the Module Breaker Status (R10.4) output parameter to 1 and lights the DI2 LED of the
CPM810 module whenever either the Breaker Status DI or the Main Breaker Status (D24.7) parameter indicates that the
breaker is closed.
This input is duplicated in the Profibus interface through the Auto-Sync Enable (D24.3) parameter. When Profibus
communication is active, the value of this parameter overrides the value of the DI.
56 Auto Synchronizer AS800 2VAA000334
3BOPERATION 36BDigital Outputs
Regardless of the source of the permissive, the AS800 lights the LV3 LED of the CPM810 module whenever Auto-Sync is
enabled.
This input is duplicated in the Profibus interface through the Match Frequency Enable (D24.5) parameter. When Profibus
communication is active, the value of this parameter overrides the value of the DI.
Regardless of the source of the permissive, the AS800 lights the LV5 LED of the CPM810 module whenever Frequency
Match is enabled.
This input is duplicated in the Profibus interface through the Breaker Close Enable (D24.6) parameter. When Profibus
communication is active, the value of this parameter overrides the value of the DI.
Regardless of the source of the permissive, the AS800 lights the LV6 LED of the CPM810 module whenever Breaker
Closure is enabled.
This input is duplicated in the Profibus interface through the Match Voltage Enable (D24.4) parameter. When Profibus
communication is active, the value of this parameter overrides the value of the DI.
Regardless of the source of the permissive, the AS800 lights the LV4 LED of the CPM810 module whenever Voltage
Match is enabled.
This input is duplicated in the Profibus interface through the Dead Bus Enable (D24.8) parameter. When Profibus
communication is active, the value of this parameter overrides the value of the DI.
Regardless of the source of the permissive, the AS800 lights the DI1 LED of the CPM810 module whenever Dead Bus
Closure is enabled.
Section 4.5 describes how to configure the ROM810 module. The DO function assigned to each dipswitch selection of the
ROM810 is listed in Table 4-5.
The AS800 lights the DO1 LED of the CPM810 module whenever this DO is active.
The AS800 lights the DO2 LED of the CPM810 module whenever this DO is active.
The AS800 lights the DO3 LED of the CPM810 module whenever this DO is active.
The AS800 lights the DO4 LED of the CPM810 module whenever this DO is active.
The AS800 lights the DO5 LED of the CPM810 module whenever this DO is active.
The AS800 lights the DO6 LED of the CPM810 module whenever this DO is active.
When the Profibus communication is not active, the AS800 reverts to Stand-Alone operation. In stand-alone operation,
the configuration settings are established by the values sent to the AS800 via the serial input. Likewise, the status values
and bus signal readings are reported via the serial output. The digital inputs are used to set the state of the function
permissives. A Modbus protocol interface is provided to facilitate these communication functions. The values of the
configuration parameters may also be set using terminal commands, when the Modbus interface is not used.
When the AS800 is operating in Stand-Alone mode, the five permissive values are controlled by Digital Input signals
connected to the TBU810. Refer to Sections 0 and 4.2.3 for examples of how to wire the digital inputs to the AS800.
In the absence of Profibus communication, the parameter settings of the AS800 must be entered via the serial interface
available through the SIM810 module. The values of the parameters may be set using commands entered through the
terminal interface or by using the Modbus communication protocol. The following sections describe how to use each of
these two methods.
The Holding Register values correspond directly to the Profibus parameters sent from the master to the AS800 and their
corresponding bounds as listed in Section 4.7.1, with one exception. The Stand Alone DI Source parameter is only
available via the Modbus interface. This parameter allows the Modbus master to set the values of the five permissive
parameters in place of the Digital Input signals. The Input Register values correspond directly to the Profibus output
parameters sent to the master from the AS800 as listed in Section 4.7.2.
The registers identified as Real type span two registers, with the most significant half of the 32-bit value residing in the
register with the lower number and the least significant half of the 32-bit value residing in the register with the higher
number. The registers identified as Compressed Boolean type contain 16 Boolean values, not all of which are used. The
value assigned to each individual Boolean value is listed in the table for each register of this type.
Use the DIP switch located on the bottom of the CPM810 module to select the slave address for
Modbus communication. If the AS800 will not utilize Profibus communication, then addresses 0
– 63 are valid; otherwise the normal Profibus restrictions apply, as stated in Section 4.3. The
AS800 automatically adds 128 to the value selected by the switch to use for its Modbus slave
address. This means that the corresponding valid range of addresses that may be selected in
the Modbus master is 128 – 191.
The AS800 has exceeded the maximum number of attempts to close the breaker.
The main processor of the CPM810 has lost communication with the processor of the ASM810, indicating a failure of that
processor.
The first condition is cleared by removing the Auto-Synchronize permissive. If this indicator persists after disabling the
Auto-Synchronize permissive, then the second condition exists.
When a generator to line bus automatic synchronization function is active, the status is reset to zero:
• When the current value enters the stability window
• Whenever Auto-Sync Enable is deactivated.
When a peer to peer automatic synchronization function is active, the status is reset to zero whenever Auto-Sync Enable
is deactivated.
# Name Description
The breaker is closed. This value is reported when the breaker closes as
1 Breaker Closed
a result of an initiation for closure by the AS800.
0 No Error No Error.
-3 Error Quality Either Bus A or Bus B is outside of the acceptable good quality window.
The number of attempts set by the user for breaker closure has been
-6 Error Attempts
exceeded.
The angle to initiate breaker closure exceeds the maximum closure angle
-7 Error Close Max
set by the user.
-8 Error Parameter The user entered a parameter that exceeds the valid range.
6. MAINTENANCE
R/F Health LED. If power is ok the LED is green. On power failure, the LED is either red or off.
RxTxA Profibus Bus A communication. The LED is on if the module is communicating over Bus A
RxTxB Profibus Bus B communication. The LED is on if the module is communicating over Bus B
Primary/backup. The LED is on if the module is the primary module. The LED is off if it is the
PRI
backup. For simplex modules the LED is on if running.
LV1 Primary Relay Feedback. The LED is ON if the Primary Relay is closed.
LV2 Independent Relay Feedback. The LED is ON if the independent Relay is closed.
LV3 Auto-synchronization Enabled. The LED is ON if Auto-synchronization is enabled.
LV4 Voltage Match Enabled. The LED is ON if Voltage Match is enabled.
LV5 Frequency Match Enabled. The LED is ON if Frequency Match is enabled.
LV6 Breaker Close Enable. The LED is ON if Breaker Close is enabled.
HV1 Input B. The LED is ON if Bus A is within 50-110% of the expected range.
HV2 Input A. The LED is ON if Bus B is within 50-110% of the expected range.
DI1 Dead Bus Enable. The LED is ON if Dead Bus enable is active.
DI2 Breaker Closed. The LED is ON if the Breaker is closed.
DO1 Raise Volts. The LED is ON when the Raise Volts Relay is active.
DO2 Lower Volts. The LED is ON when the Lower Volts Relay is active.
DO3 Raise Frequency. The LED is ON when the Raise Frequency Relay is active.
DO4 Lower Frequency. The LED is ON when the Lower Frequency Relay is active.
DO5 Primary Relay. The LED is ON when the Primary Close Breaker Relay is active.
DO6 Independent Relay. The LED is ON when the Independent Relay is active.
LED Description
Health LED. If power is ok, the LED is green. On power failure, the LED is either red or
R/F
off.
6.3 Troubleshooting
Symptom Possible Causes Corrective Action
6.4.1 General
All modules are designed for long, trouble-free service. If it is determined that the module is faulty, replace it with a new
one. DO NOT try to repair the module as replacing components may adversely affect the module's performance and void
the warranty. If it becomes necessary to replace any parts, contact the ABB Customer Service Department.
All modules can be exchanged on-line with the process power supply connected. However, it is important to understand
the consequences of a module exchange on-line and how it affects the process. Replacement of a module affects all
channels on the module. It also sometimes indirectly affects the outputs, via some application function, on another
module.
6.4.2 Replacement
Replace faulty or suspect modules in the following way:
• Provide access to the module by loosening the module locking device.
• Grip the module firmly and extract the module.
• Store extracted modules in anti-static envelopes.
• Insert the new module carefully and completely.
• Ensure that the module contacts mate properly with the contacts in the TBU810 and activate the locking device in
place.
Modules initialize automatically and will begin to execute in a few seconds.
Include the part description, the part number, the serial number, and the symptoms of the problem. Please provide as
much information as possible.
Parameter Setting
Bits per second 115200
Data bits 8
Parity None
Stop bits 1
Flow control None
1. Type “UPGRADE” at the “>” prompt, press the ENTER key and verify that the “ABB>” prompt is displayed on
the screen.
2. If a new boot loader is to be downloaded, continue to the next step, otherwise skip to step 10.
3. At the prompt type “dl boot” and then press the ENTER key.
4. Verify that “Ready to receive file. Use XMODEM Protocol for transmission” appears on the screen. After
that, “C” and “$” characters will begin to appear on the screen. If you do not transfer a file within
approximately 30 seconds, the connection will timeout and step 3 will need to be repeated.
5. Select the Boot Loader file to transfer in the communication program and set the transfer protocol to 1K
Xmodem.
6. Begin the file transfer. File transfer can be rejected at any time by either side (the communication program or
the AS800). Causes for the rejection can be a CRC 16 check error, transmission timeout, loss of physical
connection, etc. The communication program will display an error message if the transfer is terminated. In
this case, check the physical connection and re-send the file.
7. The transfer will take approximately 10 seconds to complete. The AS800 will then program the flash memory
of the CPM810 module. This will take approximately 5 seconds to complete.
8. When programming is complete the AS800 will automatically restart.
9. Type “UPGRADE” at the “>” prompt, press the ENTER key and verify that the “ABB>” prompt is displayed on
the screen.
10. At the prompt type “dl” and then press the ENTER key.
11. Verify that “Ready to receive file. Use XMODEM Protocol for transmission” appears on the screen. After
that, “C” and “$” characters will begin to appear on the screen. If you do not transfer a file within approximately
30 seconds, the connection will timeout and step 10 will need to be repeated.
12. Select the file to transfer in the communication program and set the transfer protocol to 1K Xmodem.
14. Begin the file transfer. File transfer can be rejected at any time by either side (the communication
program or the AS800). Causes for the rejection can be a CRC 16 check error, transmission timeout,
loss of physical connection, etc. The communication program will display an error message if the
transfer is terminated. In this case, check the physical connection and re-send the file. The transfer will
take approximately 2 minutes to complete. The AS800 will then program the flash memory of the
CPM810 module. This will take approximately 30 seconds to complete.
If the AS800 does not complete programming the flash memory, the AS800 will not operate.
The CPM810 module must be replaced and returned to ABB Inc. to be programmed.
16. If the flash memory of the ASM810 module needs to be reprogrammed, it will be done at this time.
Parameter Setting
Bits per second 57600
Data bits 8
Parity None
Stop bits 1
Flow control None
Upgrading an AS800 to Version 5.0.2 or later from an earlier version requires that a new version of the Boot Loader
be installed. Perform the following procedure to load the new Boot Loader and firmware to the AS800.
1. Type “UPGRADE” at the “>” prompt, press the ENTER key and verify that the “ABB>” prompt is displayed on
the screen.
2. At the prompt type “dl boot” and then press the ENTER key. For older versions of the firmware you may see
“ddll bboooott” on the screen.
3. Verify that “Ready to receive file. Use XMODEM Protocol for transmission” appears on the screen. After
that, “C” and “$” characters will begin to appear on the screen. If you do not transfer a file within approximately
30 seconds, the connection will timeout and step 2 will need to be repeated.
4. Select the Boot Loader file to transfer in the communication program and set the transfer protocol to 1K
Xmodem.
5. Begin the file transfer. File transfer can be rejected at any time by either side (the communication program or
the AS800). Causes for the rejection can be a CRC 16 check error, transmission timeout, loss of physical
connection, etc. The communication program will display an error message if the transfer is terminated. In this
case, check the physical connection and re-send the file.
6. The transfer will take approximately 10 seconds to complete. The AS800 will then program the flash memory of
the CPM810 module. This will take approximately 5 seconds to complete.
7. When programming is complete the AS800 will automatically restart. At this point garbage characters will begin
to be displayed on the terminal screen.
8. Disconnect the terminal program from the AS800. Change the BAUD rate of the terminal to 115200.
Reconnect the terminal program to the AS800.
9. Press the ENTER key and verify that the “ABB>” prompt is displayed on the screen. If the “>” prompt is
displayed on the screen, type “UPGRADE” and press the ENTER key, and then verify that the “ABB>” prompt
is displayed on the screen.
10. At the prompt type “dl” and then press the ENTER key.
11. Verify that “Ready to receive file. Use XMODEM Protocol for transmission” appears on the screen. After
that, “C” and “$” characters will begin to appear on the screen. If you do not transfer a file within approximately
30 seconds, the connection will timeout and step 10 will need to be repeated.
12. Select the firmware file to transfer in the communication program and set the transfer protocol to 1K Xmodem.
13. Begin the file transfer. File transfer can be rejected at any time by either side (the communication program or
the AS800). Causes for the rejection can be a CRC 16 check error, transmission timeout, loss of physical
connection, etc. The communication program will display an error message if the transfer is terminated. In this
case, check the physical connection and re-send the file.
14. The transfer will take approximately 2 minutes to complete. The AS800 will then program the flash memory of
the CPM810 module. This will take approximately 30 seconds to complete.
If the AS800 does not complete programming the flash memory, the AS800 will not operate.
The CPM810 module must be replaced and returned to ABB Inc. to be programmed.
15. Type “UPGRADE” at the “>” prompt, press the ENTER key and verify that the “ABB>” prompt is displayed on
the screen.
16. At the prompt type “pld” and then press the ENTER key. This will force the AS800 to program the PLD the next
time it restarts.
17. At the prompt type “reset” and then press the ENTER key. This will force the AS800 to restart.
18. The AS800 will program the PLD, which will take 30-45 seconds to complete. Do not interrupt the AS800 while
it is programming the PLD. When the AS800 completes programming the PLD, it will display the “ABB>” prompt
on the screen.
19. At the prompt type “reset” and then press the ENTER key. This will force the AS800 to restart.
20. If the flash memory of the ASM810 module needs to be reprogrammed, it will be done automatically at this time.
7. SPECIFICATIONS
8. REVISION HISTORY
Rev. Date / Initial
04/2004 0 Preliminary release. 04/2004 / AMD
08/2004 A Original release. 08/2004 / AMD
09/2004 A.1 General update and layout revision. 09/2004 / KD
10/2004 A.2 Replaced the title page graphics. 10/2004 / KD
04/2006 B Replaced the title page graphics; changed term MTU to TBU810; added graphics for 04/2006 / KD
module installation, terminal layout, and switches; added a graphics to show input wiring
connections; expanded the troubleshooting table; added a section to describe the
firmware upgrade procedure.
07/2008 3.0 General layout adjustments, especially to tables; added detailed descriptions of the 07/2008 / KD,
Profibus parameters and reported values; replaced the AS800 block diagram with a SLM
description of the AS800 functions; replaced flow charts in Conditions for
Synchronization with descriptions, equations, tables, and diagrams; added table for
meaning of ASM810 LED indications; added a performance section to the specifications
table; removed separate specification tables for the field input signals.
02/2009 5.0.2 Replaced the title page graphics; changed listed serial BAUD rate from 57.6 Kbs to 02/2009 / SLM
115.2 Kbs; added restriction of use of 7th Profibus address switch; modified the ROM810
contact to terminal assignment diagram; added a section to describe the ROM810 v2.0;
added a section to describe the firmware upgrade procedure from pre-5.0.2 firmware
versions.
04/2010 5.0.2.7 Added a drawing of the Rev 2 TBU810 to the TBU810 configuration section; added table 04/2010 / SLM
to configure jumpers on the TBU810; corrected the ROM810 V2 contact to terminal
assignment diagram; added Island mode to the list of application modes; added
explanation of breaker control in Island mode; improved the match window diagrams;
corrected condition for clearing reported status value to “Whenever Auto-Sync Enable is
deactivated”; added steps to upgrade the boot loader to the 5.0.2 or later firmware
upgrade procedure; removed “pending” from the CE Mark and CSA certifications in the
specifications table.
03/2011 5.0.2.8 Removed the relay feedback wiring from the Digital Inputs wiring description sections; 03/2011 / SLM
added a section to describe the connections for the relay feedback wiring; added ID
codes to all parameters and reported values; added navigational links to all section,
table, and parameter references; improved the detailed Profibus parameter descriptions;
added section to describe the synchronization process; rewrote the Conditions for
Synchronization, Line / Generator, Peer / Peer, and stand-alone operation sections;
added sections to describe Island mode, synchronizing a live bus to a dead bus, the bus
signals reported by the AS800, the digital inputs, and the digital outputs.
03/2011 5.1 Added descriptions and wiring diagrams for using an EIM810 module; added the 03/2011 / SLM
Increase Volts and Decrease Volts Profibus output values to the short and detailed
parameter description sections, added a section to describe the Modbus interface.