305026-PVE-DD-ME-DAS-006 Internal Floating Roof Rev0

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

THIẾT KẾ, CUNG CẤP THIẾT BN VÀ THI CÔNG XÂY LẮP CÔNG TRÌNH

MỞ RỘNG KHO XĂNG DẦU NGHI SƠN GIAI ĐOẠN 1


Tài liệu số.: 305026-PVE-DD-ME-DAS-003 LXB.: A Tờ: 2/ 3

KIỂM SOÁT THAY ĐỔI

LXB Ngày Mục Mô tả thay đổi


A 1/10/19
0 04/10/2019
THIẾT KẾ, CUNG CẤP THIẾT BN VÀ THI CÔNG XÂY LẮP CÔNG
TRÌNH
Tài liệu số.: MỞ RỘNG KHO XĂNG DẦU NGHI LXB.:
305026-PVE-DD-ME-DAS-006 SƠN A GIAI ĐOẠNTờ:
1 3/ 3
DATASHEET FOR INTERNAL FLOATING ROOF
1 Indicates Information completed by Purchaser Manufacturer Purchaser or Manufacturer
2 Applicable to Proposal Purchase As built
3 For PV OIL Unit
4 Site NGHI SON Service M92/M95
5 No. Required 1 Set Size Type
6 Manufacturer Model Standard
7 P & ID No. 305026-PVE-DD-PR-PID-002 Serial No.
8 TANK INFORMATION
9 Tag. No. TK-202
10 Location of tank Above Ground
11 Type of tank Steel Dome Roof Tank (w. aluminium internal floating roof)
12 Tank Inside Diameter/ Height ID 15.29m / 13.5m
o
13 Tank design pressure/Temperature -25/75mm H2O/70 C
14 Product M92/M95
3
15 Product SG 840 kg/m
3
16 Filling rate 90 m /h
17 Filling/Out nozzle size 6"/6"
18 Floating suction arm/ Inlet diffuser No
19 CA (Shell/Bottom/Roof) 2mm
20 TANK ROOF
21 Roof type/Roof construction Doom Roof/Structure Steel Profile
22 Manhole No./ Size 2 / 24" API STD
23 TANK SHELL
24 Type Butt welded
25 Clips inside/Reinforcing Ring No
26 Manhole No./ Size 2 / 24" API STD
27 Fire fighting equipment Yes (Water & Foam system)
28 TANK BOTTOM
29 Type CONE
30 Coating Bottom plate and shell up to 2m
31 INTERNAL FLOATING ROOF CONSTRUCTION
32 Design standard API STD 650 Appendix H
33 Type Float tube, non-contact (VTC)
34 Seal type Double wiper seal (VTC)
35 Anti rotation/ Anti static cable Yes
36 Manhole Yes
37 Pressure/ Vacuum vent Yes
38 Adjustable legs Yes
39 INTERNAL FLOATING ROOF MATERIAL (Note 2)
40 Deck plate/Float tube Alu./Alu. (VTC)
41 Seal VTA
42 Bolts & Nuts A193-B7/A194-2H/A307Gr.B/SS304 Alu.
43 Structure/Support Alu.(VTC)
44 WEIGHTS
45 Empty weight/Operation weight VTA
46 NOTES
47 1. VTA = Vendor To Advise, VTC = Vendor To Confirm
48 2. Vendor to verify that specified materials are suitable for the proposed service and design condition.
49 3. Vendor scope:
50 - Design, supply material, fabrication, packing, transportation, installation internal floating roof as per API 650 Annex H
51 - Perimeter primary/ secondary seal joint, seal joint for penetration willing piping
52 - Design
Design, supply of auto bleeder valve
valve, emergency hatch
hatch, vacuum relief device (If any)
53 - All nozzle, manway, ground cable,support legs
54 4. All shell nozzles will be API low type
55 5. Size & quantity of venting devices to be determined by vendor/manufacturer.