Caution
The location of the transmitters and sensors should be made in accordance with
any relevant local and national legislation, standards or codes of practice. Always
replace detectors with a detector of the same type. The detector should be mounted
where the gas is most likely to be present. The following points should be noted
when locating gas detectors.
• Consider the possible damage caused by natural events e.g. rain or flooding
when locating detectors.
• Consider ease of access for functional testing and servicing.
• Consider how escaping gas may behave due to natural or forced air
currents.
Note
The placement of detectors should be determined following the advice
of experts having specialist knowledge of gas dispersion, experts having
knowledge of the process plant system and equipment involved, safety and
engineering personnel. The agreement reached on the location of detectors
should be recorded.
1.1 Mounting the XNX Universal Transmitter
The XNX Universal Transmitter can be mounted in a number of different methods
using the integral mounting tabs.
Using the mounting tabs, the XNX can be attached to:
• flat wall surface
• Unistrut®
With the optional Pipe Mount kit, the XNX can be mounted to pipe of diameter 2 to
6 in (50 to 150mm).
A ceiling mount bracket kit (1226A0358) is also available.
Integral Mounting Lugs
Figure 1. Integral Mounting Lugs and Optional Pipe and Ceiling Mounts
w/sun shield
152 mm
6"
XNX with
Searchpoint Optima Plus
4"
101.6mm
Allow
12"
305mm
For XNX with MPD or Local EC Sensor
Maintenance
Service
Warning
When the XNX is equipped with the optional Remote Mount Kit, the remote sensor
MUST be securely mounted to a fixed position. The Remote Sensor Kit is not intended
to be used as a hand-held detector.
*
D
Option Position
C Local HART Option
®
B
MPD, 705 Series, Sensepoint Series C
Catalytic Bead Sensor C
Searchpoint Optima Plus A or E
Searchline Excel Typically C
Remote Sensor Connection (except EC ) Any remaining
Searchpoint Optima Plus - Remote Any remaining
Modbus® Any remaining
Relays Any remaining
Power Any remaining
Figure 3. XNX Universal Transmitter Cable/Conduit Entry Assignments
Integral Mounting Lugs
Figure 4. Integral Mounting Lugs and Optional Pipe and Ceiling Mounts
XNX Universal Transmitter Quick Start Guide 9
2 Wiring the XNX
Personality circuit boards determine the XNX behavior based on the sensor type
attached to the XNX interface.
The table below defines the three XNX transmitter configurations and the sensors
each support.
XNX IR Personality XNX EC Personality
XNX mV Personality
705 Local / Remote MPD Local (cat bead and IR) Sensepoint Local / Remote
705HT Local / Remote MPD Remote Sensepoint PPM Local/Remote
Sensepoint HT Remote
Caution
Before wiring the XNX, confirm the correct personality boards and options are
installed.
2.1 General Wiring Considerations
For proper operation of the XNX Universal Transmitter and Sensor Technologies,
consideration of wiring induced voltage drops, transient electrical noise and dissimilar
Earth ground potentials is imperative in the design and installation of the system.
Note:
To maintain EMC integrity, wiring must be shielded by either an integral shield
or run through conduit or pipe. Shield should provide 90% coverage.
Loading
Wiring for DC Power, 4-20mA Signal, remote wiring to sensors must be sized
sufficiently to provide sufficient voltages for the line length and the loads that will
be used.
Isolation
Isolating power and signal carrying conductors is recommended.
Circuit Protection
Supply circuits must provide over current protection. Class 2 power supplies are
required for 24 volt DC supply. Consider Inrush current in specifying any DC supply.
Power supply range is 16 to 32 VDC for EC and mV versions, 18 to 32 VDC for
10 XNX Universal Transmitter Quick Start Guide
Searchpoint Optima Plus and Searchline Excel and 16 to 32 VDC dependent on
the limitations of device for the generic 4-20mA input.
Loads
The use of High Inrush or Inductive loads may affect the performance of the XNX.
For best reliability use resistive loads only.
2.2 Distance Considerations for Installation
Types of Installations
There are three basic types of installation: a single transmitter; multiple transmitters
connected to a single power source; and multiple transmitters connected in a “daisy-
chain” configuration.
Power Source Selection
The power requirements for different transmitter configurations are:
• XNX EC (Toxic): 6.2 watts
• XNX mV (Catalytic): 6.5 watts
• XNX IR with Searchpoint Optima Plus: 9.7 watts
• XNX IR with Searchline Excel: 13.2 watts
Wire Selection
The type of wire used for connections has an effect on the distance of the
installation. This is because some of the voltage is lost in the wire on the way to
the transmitter.
Single Transmitter Distances
For installations that have dedicated wiring between the transmitter and the power
supply, use the following chart. These distances assume stranded wire is used.
OR
Class 2 Class 2
Power Supply Power Supply
Class 2
Power Supply
1. Several transmitters equally spaced from themselves and the power source.
2 Transmitters - Distance “d”
18 AWG 16 AWG 14 AWG 12 AWG
[1.0 mm2] [1.5 mm2] [2.0 mm2] [3.5 mm2]
XNX mV or EC 380 feet 600 feet 960 feet 1540 feet
With Sensor [115 meters] [183 meters] [292 meters] [469 meters]
XNX IR with 220 feet 350 feet 560 feet 900 feet
Searchpoint Optima Plus [67 meters] [106 meters] [170 meters] [274 meters]
XNX IR with 185 feet 295 feet 470 feet 750 feet
Searchline Excel [56 meters] [90 meters] [143 meters] [229 meters]
3 Transmitters - Distance “d”
18 AWG 16 AWG 14 AWG 12 AWG
[1.0 mm2] [1.5 mm2] [2.0 mm2] [3.5 mm2]
XNX mV or EC 190 feet 300 feet 480 feet 770 feet
With Sensor [58 meters] [91 meters] [146 meters] [234 meters]
XNX IR with 110 feet 175 feet 280 feet 450 feet
Searchpoint Optima Plus [33 meters] [53 meters] [85 meters] [137 meters]
XNX IR with 90 feet 145 feet 235 feet 375 feet
Searchline Excel [27 meters] [44 meters] [71 meters] [114 meters]
4 Transmitters - Distance “d”
18 AWG 16 AWG 14 AWG 12 AWG
[1.0 mm2] [1.5 mm2] [2.0 mm2] [3.5 mm2]
XNX mV or EC 110 feet 180 feet 290 feet 460 feet
With Sensor [33 meters] [55 meters] [88 meters] [140 meters]
XNX IR with 65 feet 105 feet 165 feet 270 feet
Searchpoint Optima Plus [20 meters] [32 meters] [50 meters] [82 meters]
XNX IR with 55 feet 85 feet 140 feet 225 feet
Searchline Excel [17 meters] [26 meters] [43 meters] [68 meters]
5 Transmitters - Distance “d”
18 AWG 16 AWG 14 AWG 12 AWG
[1.0 mm2] [1.5 mm2] [2.0 mm2] [3.5 mm2]
XNX mV or EC 75 feet 120 feet 190 feet 300 feet
With Sensor [23 meters] [36 meters] [58 meters] [91 meters]
XNX IR with 45 feet 70 feet 110 feet 180 feet
Searchpoint Optima Plus [13 meters] [21 meters] [33 meters] [55 meters]
XNX IR with 35 feet 55 feet 90 feet 150 feet
Searchline Excel [11 meters] [17 meters] [27 meters] [46 meters]
Class 2
Power Supply
Personality
B
Boards
Boards
Option
C
Figure 5. XNX Personality Board
Terminal Block Legend
D
Table A Table B
Board Type Function S1 S2 Board Type Connection Function
EC Personality Source EC Personality Power, 4-20mA
4-20mA
mV Personality Sink Power, 4-20mA,
Output mV Personality
IR Personality Isolated TB1 Sensor
Power, 4-20mA,
IR Personality IR Power and
Signal
Table C Table D
Board Type Function S3 S4 Board Type Connection Function
IR 4-20mA Source 6 6 EC Personality J2 EC IS Barrier
IR Personality Input Sink 5 5 IR Personality TB2 Com A and B
Table E Table F
Board Type Connection Function Board Type Connection Function
Remote Reset
Relay TB4 Relay TB3 Relay Output
Connector
Bus Loop Data
Modbus® SW5 Terminators Modbus® TB3 Connection
2.4 4-20mA Output, Common Connections and Power
Setting 4-20mA operation; S1 & S2
The XNX Universal Transmitter allows the user to configure the 4-20mA output to Sink,
Source or Isolated mode operation via two programming switches on the POD. The
table below shows the S1 and S2 setting and corresponding output configuration.
S1 S2
Source Down Up
Sink Up Down
Isolated Down Down
+VE 1 1-1
+V
RL
Signal +mA
2 1-5
Current
Flow
-VE -V
3 1-3
+VE +V
1 1-1
Signal -mA
2 1-6
RL Current
Flow
-VE -V
3 1-3
+V1 +V
1-1
+V2 1-5
+mA
-V2 -mA
1-6
-V1 -V
1-3
OUT
IN
TB-1 Terminal Block
Warning
When the XNX is equipped with the optional Remote Mount Kit, the remote sensor
MUST be securely mounted to a fixed position. The Remote Sensor Kit is not
intended to be used as a hand-held detector.
Sink ▲ ▼
-mA 1-6 Isolated ▼ ▼
EC TB-1
Position EC
J2 - EC Barrier Connector
TB1
EC Barrier J2 1 +24
XNX EC TB-1
2
3 0v
4
Figure 10. XNX EC Personality Board Terminal Blocks and Jumper Switches and
Terminal Block Assignments
Caution
Be certain to dress the wires properly to ensure cabling does not contact switches
1-2 on the back of the POD.
Do not force the POD into the enclosure as it may indicate an interference condition
resulting in damage to the wiring, POD or switch settings.
Terminal Block 1
3
+ 5
- 6
J2 EC Barrier
EC IS Barrier must
be connected to J2
HART
Adaptor
EC
Adaptor
Sensor Cartridge
Sensor Retainer
Weatherproof Cap
Sensor Mounted to
Remote Sensor Kit
Caution
For biased sensors (e.g. Nitrogen Dioxide) remove the sensor stabilizer from the
bottom of the sensor prior to installation.
Using Figure 12 as a guide, follow the procedure below:
1. Check that the label on the new sensor is the correct gas type.
2. Unscrew the weatherproof cover, loosen the retainer locking screw with the
supplied hex key and unscrew the sensor retainer.
3. Plug in the new sensor taking care to align the sensor pins with the
connector.
4. Refit the sensor retainer, tighten the locking screw with the supplied hex
key and refit the weatherproof cover.
5. Countdown time of up to 180 seconds (dependent on sensor type) is
displayed.
6. Acknowledgement of the gas type will be required before proceeding. For
more information on setting gas type, see the XNX Technical Manual Section
2.51 Gas Selection.
7. After the sensor is installed and the gas type is confirmed, the Range, alarm
levels and other important settings must be set; see appropriate section in
Section 4 - Powering the XNX for the First Time.
8. Once the XNX has been configured, calibrate the detector following the
procedures in Section 6.1 - Calibration.
Transmitter
New Sensor
3
Sensor Retainer &
Locking Screw
2 4
1 5
Weatherproof Cap
Caution
Take care not to cut the cable too short. Once cut, additional lengths of cable
cannot be added as this will invalidate the intrinsically safe certification. It is
also recommend that a loop of cable is made at the junction box to allow slack
for any future re-termination.
The enclosure of the remotely mounted sensor contains aluminum. Care must
be taken to avoid ignition hazards due to impact or friction when installed in the
Zone 1 location.
All cable entry devices and blanking elements shall be certified in type of explosion
protection flameproof enclosure “Ex e”, suitable for the conditions of use and
correctly installed.
6. Mount the remote sensor junction box ensuring enough room below to fit
the sensor and weatherproof cover.
7. Attach the cable to the remote terminal box via the gland provided.
8. Make the wiring connections as shown in Figure 13.
9. Fit the terminal box lid.
10. Plug the sensor into the socket at the bottom of the terminal box.
11. Fit the sensor retainer, tighten the locking screw and fit the weatherproof cover.
12. Calibrate the detector following the procedures in Section 6.1 - Calibration.
CAUTION
Take care not to cut the cable too short. Once cut, additional lengths of cable
cannot be added as this will invalidate the intrinsically safe certification. HA
also recommends that a loop of cable is made at the junction box to allow
Sensor Cartridge slack for any future re-termination.
The enclosure of the remotely mounted sensor contains aluminum. Care must
be taken to avoid ignition hazards due to impact or friction when installed in the
Zone 1 location.
Sensor Retainer
All cable entry devices and blanking elements shall be certified in type of
explosion protection flameproof enclosure “Ex e”, suitable for the conditions of
use and correctly installed.
Weatherproof Cap
Sensor Mounted to
Remote Sensor Kit
Caution
• Check to ensure the XNX and mV Sensor has the appropriate approvals for your
installation prior to commissioning.
• Check the mV Sensor you are installing has compatible threads - 3/4 NPT or M25.
Connections from the mV Sensor to the XNX are made via a single pluggable terminal
block allowing ease of installation and service. HA recommends an 8” (203mm)
service length for wiring be maintained. The Wire Colors for the connections for
each sensor type are shown in Figure 14.
Be sure wires for 4-20mA outputs are routed away from sources of noise such as
relay wires.
XNX Universal Transmitter Quick Start Guide 21
Note
The black and red wires from the MPD are not used with the XNX mV Personality
Board. Ensure they are properly isolated from live connections. DO NOT CUT.
Caution
Be certain to dress the wires properly to ensure cabling does not contact switches
1-2 on the back of the POD.
Do not force the POD into the enclosure as it may indicate an interference condition
resulting in damage to the wiring, POD or switch settings.
Source
HART Sensepoint
XNX mV TB-1
mV Sensor Type
Catalytic Bead MPD w/IR
Terminal Block 1
+ 5
- 6
Sense 7
Com 8
Ref 9
Local HART
IS Barrier
(optional)
HART
Adaptor
MPD
705
Sensepoint
UL/CSA Aluminum Junction Box UL/CSA Stainless Steel Junction Box ATEX/IEC Junction Box
2441-0022 2110B2103 00780-A-0100
Caution
Be certain to dress the wires properly to ensure cabling does not contact switches
1-4 on the back of the POD.
Do not force the POD into the enclosure as it may indicate an interference condition
resulting in damage to the wiring, POD or switch settings.
Warning
Setting of S3 and S4 while power is applied or improperly set prior to applying power
WILL PERMANENTLY DAMAGE the XNX. Both switches must be set in either Source
or Sink prior to applying power.
Do not adjust switch settings while power is applied to the XNX; permanent damage
WILL occur.
The 3/4” NPT entries do not require the seal and locknut, the form of the threads
provide positive locking and sealing.
Note:
When attaching the Searchpoint Optima Plus, be sure to coat the threads
with an anti-seize compound to prevent corrosion.
Searchline Excel and Searchpoint Optima Plus Remote Installation
Junction Boxes are available for the Searchline Excel and Searchpoint Optima
Plus to facilitate remote mounting from the XNX Universal Transmitter. Junction
boxes are available for installations requiring UL/CSA or ATEX approvals. Consult
the Searchline Excel Technical Handbook (2104M0506) or Searchpoint Optima
Plus Operating Instructions (2104M0508) for specifics on remote installations or
contact your Honeywell Analytics representative for more information.
Searchpoint Optima Plus or Searchline Excel Wiring Recommendations
When wiring the XNX and the Searchpoint Optima Plus or Searchline Excel for
remote applications, the General Recommendations of the ANSI/TIA/EIA-485-A
standard must be adhered to with the following additions:
26 XNX Universal Transmitter Quick Start Guide
1. When mounting the Searchline Excel or Searchpoint Optima Plus, run wiring
connections between each Excel or Optima and the XNX in a dedicated
separate conduit. Cable length should not exceed 4000 feet.
2. Use 16AWG twisted shielded cable for the RS485 connection between Excel
or Optima and the XNX. Make sure that the shield of the cable is grounded
to earth and XNX ground on one end ONLY.
3. Avoid running wiring near mains cables or other high voltage equipment.
4. DO NOT APPLY 120 Ohm terminating resistors. These resistors are not
required due to low data rates.
5. HA recommends that Excel or Optima and the XNX be wired to building
ground. The system should be grounded at one point only.
Installation Tip:
Always issue a soft reset after connecting the Optima and XNX for the first time. The soft
reset is performed by accessing the XNX calibration menu.
28
Pair 3: IR +ve and IR -ve
Pair 2: RS485+ and RS485-
(Cable Shield Grounded ONE END ONLY)
(Cable Shield Grounded ONE END ONLY)
13.2W max.
1-4
+mA 1-5 IR -ve IR -ve
-mA 1-6 Junction Box
+ Ir 1-7
- Ir 1-8
Searchline Excel
4-20mA Searchline
18-32 VDC HART Searchpoint
Sig 1-9
Ir TB-1
RS485+ RS485+
TB-2 Ir Data
RS485- RS485-
S3 S4
Source
Sink
Unit Gnd
RS485 Cable Shield
+ve Ground ONE END ONLY Searchpoint Optima Plus
Power Supply
-ve
RL
Signal +mA
1-9
Current
Flow
-IR -V
1-8
+IR +V
1-7
Signal -mA
1-9
RL Current
Flow
-IR -V
1-8
Sink ▲ ▼
1-2 ▼ ▼ 1
Isolated 2
-V 1-3 3
4
1-4 5
6
7
+mA 1-5 8
4-20mA Searchline
9
-mA 1-6 S3 and S4 - IR 20mA Input
+ Ir 1-7 Jumper Switch
- Ir 1-8 S3 S4
Sig 1-9 Source ▼ ▼
TB1
Ir TB-1 Sink ▲ ▲
TB-2 Ir Data
XNX IR TB-1 2
S3 S4 1
Source
Sink
TB2
TB1 TB2
From Searchpoint Optima Plus From Searchpoint Optima Plus
Desc. Desc.
Searchline Excel Searchline Excel
1 24v 1 Com B Orange
2 2 Com A Blue
3 Gnd See Common Connections
4 Section 2.4 XNX
5 20mA + From Searchpoint Optima Plus
Desc.
Searchline Excel
6 20mA -
Earth Green/Yellow
7 24v Red
8 0v Black
9 Sig White
Figure 19. XNX IR Personality Board Terminal Blocks, Jumper Switches and
Wiring Guide
connected to J1
1
Terminal Block 1
5
+ 6
+24 7
Gnd 8
Sig 9
S3 S4
A 1
B 2
Terminal Block 2
IR Data
Searchpoint
Optima Plus
To Building
Ground
Local HART
IS Barrier
(optional)
HART
Adaptor
To Building
Ground
IS Barrier must be
1 connected to J1
2
4
Terminal Block 1
+ 6
+24 7
Gnd 8
Sig 9
S3 S4
A 1
B 2
Terminal Block 2
IR Data
To Building
Ground
Local HART
IS Barrier
(optional)
HART
Adaptor
Searchline Excel
Relay
9
TB4
8
7
6
TB3
5
Remote
Reset SW
4
3 1 NC
2
1
Relay Ratings
250VAC 5A
2 C
24VDC 5A
3-1 NC
3 NO
Level 2 Level 1
3-2 C TB3 4 NC
3-3 NO
3-4 NC
5 C
3-5 C 6 NO
3-6 NO
3-7 NC
2
1
7 NC
Fault
3-8 C 8 C
3-9 NO
TB-3 RELAY TB4 9 NO
Warning: Power
externally supplied.
TB4
TB3 Relay Connections
Disconnect at source
prior to servicing. Warning: Power externally
supplied, disconnect at source
1 1
2
prior to servicing
Relay Contact Ratings:
250 VAC 5 amps
2
24 VDC 5 amps
Out
In
Modbus®
TB-3 Modbus
TB3
3-1 + SW5 - Loop Termination
3-2 + 1 +
3-3 -
10 2 +
3-4 - 9
8
3-5 A 7
6
3 -
5
3-6 A 4
3
2
4 -
3-7 B 1
3-8 B 5 A
3-9 S 6 A
3-10 S
Use shorting jumper 7 B
supplied to maintain
connection during TB3 Modbus Connections
8 B
service
Use Jumper 9 S
to maintain
connection
during service 10 S
Figure 25. XNX Modbus® Option Board Terminal Block and Jumper Switch
WARNING
Prior to carrying out any work, ensure local and site procedures are followed.
Ensure that the associated control panel is inhibited so as to prevent false alarms.
Minimum and maximum controller alarm levels should not be set at less than 10%
or greater than 90% of the full scale range of the detector. CSA and FM agency
limits are 60% LEL or 0.6mg/m3.
Caution
The following procedure should be followed carefully and only performed by
suitably trained personnel.
1. Check that the transmitter is wired correctly according to this manual and
the associated control equipment manual.
2. If equipped, unscrew the weatherproof cover, loosen the sensor retainer
locking screw and unscrew the retainer.
3. Plug in the sensor cartridge taking care to align the sensor pins with the
connector holes in the PCB.
Caution
For toxic sensors, remove the shorting clip from the bottom of the sensor prior to
installation. For O2 sensors, there is no shorting clip provided.
4. Refit the sensor retainer, tighten the locking screw and refit the weatherproof
cover.
Note:
Before replacing the cover on the transmitter housing, coat the threads with
anti-seize compound to prevent corrosion buildup.
Also inspect the cover o-ring for cracking or any other defect that might
compromise the integrity of the seal. If it is damaged, replace with the o-ring
supplied in the accessory kit.
5. Apply power to the XNX which will in turn provide power to the detector.
6. The detector output will be forced to 3mA (default fault/inhibit).
7. The XNX display will enter a start up routine displaying the initialization
screen, then the transmitter loads its operating system, data from the
sensor and checks if it is the same type transmitter and sensor software
version numbers, gas type, the detection range and span calibration gas
level, estimated time to next calibration due, and self test result. The boot-up
procedure takes approximately 45 seconds.
Caution
The following procedure should be followed carefully and only performed by
suitably trained personnel
1. Check that the transmitter is wired correctly according to this manual and
the associated control equipment manual.
2. Apply power to the XNX which will in turn provide power to the detector.
3. The detector output will be forced to 3mA (default fault/inhibit).
4. The XNX display will enter a start up routine as described in Section
4.1.7
Target Gas
Concentration
Figure 33. General Status Alarm Detail
In an overrange condition, the alarm icon will display but the target gas concentration bar graph
and alarm setpoints will flash, see illustration below.
Alarm Level Triggered
Full Scale
Concentration
Using the switch resets all alarms and faults and returns to the General Status
Screen. Choosing ‘X’ will return to the General Status Screen without resetting the
alarms and faults.
Warning
The factory-set passcodes must be reset to prevent unauthorized access to the
XNX menus (see the XNX Universal Transmitter Technical Manual).
Once the Passcode Screen is displayed, the first passcode digit is highlighted. Use
the switches to increment or decrement through the values. Once the correct
value is displayed for the first digit, accepts the value and moves to the next digit
or will move to the previous digit of the passcode.
Figure 39. Gas Calibration Menu
Align Excel
Caution
The calibration procedure should only be performed by qualified personnel.
Note:
HA recommends that the maximum calibration interval be 30 days or in
accordance with customer site procedures to assure the highest level of
safety. Correct operation of each sensor/detector should be confirmed with
test gas of known concentration before each use.
See Section 7 - XNX Electrochemical Sensor Data for Calibration Gas
specifications.
6.1.1 Calibration Procedure
Note:
Follow the specific procedure outlined in the Operating Manual for each
sensing device.
1. If using compressed gas cylinder, attach the calibration gas flow housing
onto the bottom of the sensor and apply the gas.
2. Access the calibration mode.
Sensor Reading
at Current Settings
Caution
Before initial calibration, allow the detector to stabilize for 30 minutes after
applying power. When in zero and span calibration mode, the current output from
the detector is inhibited (default 3mA) to avoid false alarms.
It is recommended for most sticky gases (i.e.: HCl, Cl2) the tubing should be PTFE
with short pieces of rubber tube to make the final connection due to the inflexibility
of PTFE. This minimizes adhesion of the gas to the tube surface and allows for
more accurate measurement.
Recalibration is recommended if the temperature of local environment has varied
by more than +/-15 degrees C from the temperature of calibration.
To calibrate the detector, use an appropriate span gas cylinder, flow regulator set
to 300-375mL/min, tubing, magnet and calibration gas flow housing. A compressed
gas cylinder (20.9%Vol oxygen) should be used to perform the zero calibration if the
area where the detector is located contains any residual amount of the target gas. If
no residual gas is present then the background air can be used to perform the zero
calibration. Contact your HA representative for details of suitable calibration kits.
To calibrate the detector follow the procedure in Section 6.1.1.
Note:
The Oxygen sensor does not require a zeroing procedure. Background air
(20.9%Vol oxygen) can be used to span the oxygen sensor in place of a
compressed air cylinder (20.9%Vol oxygen).
6.1.3 Zero and Span Calibration of XNX EC Hydrogen Sulfide (H2S) Sensors
Caution
Before initial calibration, allow the detector to stabilize for 30 minutes after
applying power. When in zero and span calibration mode, the current output from
the detector is inhibited (default 3mA) to avoid false alarms.
Recalibration is recommended if the temperature of local environment has varied
by more than +/-15 degrees C from the temperature of calibration.
Hydrogen Sulfide sensors can be affected by extreme humidity changes.
A sudden increase in ambient humidity can result in a short-term positive
drift in the instrument’s reading. A sudden decrease in ambient humidity can
XNX Universal Transmitter Quick Start Guide 45
result in a short-term negative drift in the instrument’s reading. These are
most likely to be noticed during calibration with dry or cylinder gas.
When calibrating Hydrogen Sulfide cartridges the following should be taken into
account while following the procedure in Section 6.1.1:
1. To zero the sensor, use a compressed gas cylinder of 20.9%Vol oxygen
(not Nitrogen). Do not use background air.
2. If a span calibration is to be performed, the span calibration gas should be applied
to the sensor immediately after the zeroing procedure. Do not allow the sensor to
return to ambient air conditions.
6.1.4 XNX EC Sensor Operational Life
Typical life of a toxic gas sensor is dependent on the application, frequency and amount
of gas exposure. Under normal conditions, with a 3 month visual inspection and 6 month
test/re-calibration, the toxic sensor has an expected life equal to or greater than the
lifetime as listed below:
• 18 months for Chlorine and Chlorine Dioxide sensors.
• 12 months for Ammonia and Hydrogen Fluoride sensors. (See Ammonia note
below.)
• 24 months for Oxygen and other toxic sensors.
Caution
Oxygen deficient atmospheres (less than 6%V/V) may result in inaccuracy of
reading and performance.
Note:
Ammonia electrochemical cells are reliable and suitable for applications where no
background concentration of ammonia exists. Under these conditions the cells
are expected to operate for 12 to 24 months.
These ammonia cells are of the consumptive type. Their operating life can be
adversely affected by continuous or excessive exposure to ammonia, or by
prolonged exposure to high temperatures and moisture.
To ensure continued detection availability, it is recommended that the detectors are
regularly bump tested and a relevant cell replacement program be implemented.
6.1.5 Zero and Span Calibration for MPD Sensors
Caution
Before initial calibration allow, the detector to stabilize for 30 minutes after
applying power. When in zero and span calibration mode, the current output from
the detector is inhibited (default 3mA) to avoid false alarms.
This section describes how to calibrate MPD flammable sensors fitted to the XNX.
The calibration adjustments are made on the XNX’s display and gassing is performed
at the sensor. This may be locally or remotely located.
WARNING
As some test gases may be hazardous, the Flow Housing outlet should exhaust
to a safe area.
4. Follow the procedure in Section 6.1 for both Zero and Span calibrations.
5. Apply the target gas to the sensor. Pass the gas through the flow housing
at a rate of between 0.7l/m and 1.0l/m.
Caution
Where the user calibrates any sensor using a different gas, responsibility for
identifying and recording calibration rests with the user. Refer to the local
regulations where appropriate.
6. Ensure that the sensor and the vicinity around it is clear all traces of the
calibration gas before continuing. This is to avoid triggering spurious
alarms. If calibration fails at any point, discard the cartridge and replace with a
new one.
7. Remove the test equipment, refit the weatherproof cap to the sensor (if
previously removed for the test) and return the system to normal operation.
6.1.6 Cross Calibration procedure for MPD-CB1
CAUTION
Where the user calibrates any sensor using a different gas, responsibility for
identifying and recording calibration rests with the user. Refer to the local
regulations where appropriate.
When the MPD-CB1 Combustible LEL sensor is to be calibrated with a gas which is
different to the gas or vapor to be detected, the following cross calibration procedure
should be followed:
NOTE
• Table 1 lists the gases according to the reaction they produce at a given
detector.
• An eight star (8*) gas produces the highest output, while a one star (1*)
gas produces the lowest output. (These are not applicable at ppm levels.)
WARNING
It is recommended to bump test the sensors frequently to ensure proper operation.
It is recommended that the detector is tested frequently to ensure the system is
operating properly. Keep in mind different sensor types may require more frequent
maintenance depending on the environmental conditions and gases present. The
weatherproof cover has a spigot for attaching tubing from a gas cylinder. This may
be used for a simple functional (or bump) test of the sensor. However, this method
may not be suitable for all gas types and/or applications due to environmental
conditions. It is the responsibility of the user to ensure suitability of this method for
each application.
1. When bump gas is applied to the sensor, the bump test screen displays
the current reading of the sensor and the peak reading that has occurred
during the bump test.
Peak Reading
Alarm Levels
Figure 49. Bump Test Screen
2. If the difference between reading and applied gas concentration is outside
the acceptable limits for the application follow the procedures for zeroing and
calibrating the detector (see Section 6.1).
3. If reading is still inaccurate replace the sensor.
50 XNX Universal Transmitter Quick Start Guide
7 XNX Electrochemical Sensor Data
Cartridge Maximum Selectable Default Cal Gas
Target Gas Increment Cal Gas Range Cal Gas P/N
Part No Range Range Range Description
O2 Oxygen XNX-XS01SS 25.0 %Vol N/A N/A 25.0 %Vol 20.9 %Vol N/A N/A
O2 Oxygen XNX-XS01FM 21.0 %Vol N/A N/A 21.0 %Vol 20.9 %Vol N/A N/A
H2S Hydrogen Sulfide (Low Low Range) XNX-XSH3SS 15.0 ppm N/A N/A 15.0 ppm 5.0 to 10.0 ppm GFV263 10 ppm H2S
H2S Hydrogen Sulfide (Low Range) XNX-XSH1SS 50.0 ppm 10.0 to 50.0 ppm 0.1 ppm 50.0 ppm 3 to 35 ppm GFV258 25 ppm H2S
H2S Hydrogen Sulfide (Low Range) XNX-XSH1FM 50.0 ppm 10.0 to 50.0 ppm 0.1 ppm 50.0 ppm 3 to 35 ppm GFV258 25 ppm H2S
H2S Hydrogen Sulfide (High Range) XNX-XSH2SS 500 ppm 50 to 500 ppm 10 ppm 100 ppm 15 to 350 ppm GFV421 50 ppm H2S
CO Carbon Monoxide XNX-XSC1SS 1,000 ppm 100 to 1,000 ppm 100 ppm 300 ppm 30 to 200 ppm GFV295 100 ppm CO
CO Carbon Monoxide XNX-XSC1FM 1,000 ppm 100 to 1,000 ppm 100 ppm 300 ppm 30 to 200 ppm GFV295 100 ppm CO
SO2 Sulfur Dioxide (Low Range) XNX-XSS1SS 20.0 ppm 5.0 to 20.0 ppm 5.0 ppm 15.0 ppm 2 to 14 ppm Contact HA 7.5 ppm SO2
SO2 Sulfur Dioxide (High Range) XNX-XSS2SS 50.0 ppm 20.0 to 50.0 ppm 10 ppm 50.0 ppm 6 to 35 ppm GFV441 25 ppm SO2
51
52
8 XNX Catalytic Bead and IR Replacement Sensor Cartridges
Cartridge Part Maximum Default Cal Gas
Sensor Type Target Gas Selectable Range* Increment Cal Gas Range Cal Gas Description
No Range Range P/N
MPD-IC1 Carbon Dioxide 1226-0301 5.00 %Vol 1.00 to 5.00 %Vol 1.00 %Vol 5.00 %Vol 1.50 to 3.5 %Vol Contact HA 2.5 %VOL CO2 in Air
MPD-IV1 Methane 1226-0299 5.00 %Vol 1.00 to 5.00 %Vol 1.00 %Vol 5.00 %Vol 1.50 to 3.5 %Vol GFV352 2.5 %VOL CH4 in Air
MPD-IF1 Flammables 1226-0300 100 %LEL 20 to 100 %LEL* 10 %LEL 100 %LEL 30 to 70 %LEL GFV406 1 %VOL C3H8 in Air
MPD-CB1 Flammables 1226A0359 100 %LEL 20 to 100 %LEL* 10 %LEL 100 %LEL 30 to 70 %LEL GFV352 50 %LEL CH4 in Air
* On XNX %LEL Units carrying UL/CSA certifications, the range is not adjustable, it is fixed at 100%LEL
9 Warning Messages
Warning
Number Description Condition Recovery
XNX 24 VDC Supply Bad
EC DC power supply at/below 16VDC or at/above Check PSU start voltage, check cable loop
mV 33VDC for XNX impedance, check terminal connections.
W001
IR
XNX Temperature Warning
EC Check unit location for external heat source, fit
XNX internal temperature exceeding stated limits sunshade or other protection, possibly re-site unit
mV All personalities
W002
and/or consider sampling system.
IR
Simulated Warning
See Alarm/Fault Simulation. After simulation, reset
EC all faults and alarms before exiting ‘Alarm/Fault
Simulated warning from Alarm/Fault Simulation
mV All personalities Simulation’ - the front panel LED and relays will
W003
remain in fault/warning/alarm mode until reset.
IR
W005
or consider sampling system.
IR Excel/Optima Temperature
Sensor Negative Drift
EC Check sensor location for external interference,
Sensor connected to unit has an internal 'zero' shift
check sensor for operation and re-zero where
mV exceeding its stated limits
W006
appropriate.
IR
Calibration Needed Soon Recalibrate or disable the Calibration Interval - See
Calibration Interval.
EC
W007
XNX front panel, the fault relay WILL NOT
IR BE ACTIVATED.
W009
IR IR Sensor Voltage - Excel/Optima
Obscured Beam or Optics
Check sensor location for external interference
EC (obstruction in IR path), check sensor for 'dirty'
N/A Optical sensor connected is losing/has lost IR signals
mV windows. Check Excel alignment; transmitter
W010
operation.
IR Excel/Optima
53
54
Warning
Number Description Condition Recovery
Lamp Output
EC
N/A Optima+ sensor has an internal lamp issue Remove sensor and return to HA for repair.
mV
W011
IR Optima
Excessive Float
EC Check sensor location for external interference,
Sensor connected to unit has an internal baseline
N/A check sensor for operation and re-zero where
mV shift exceeding its stated limits
W012
appropriate.
IR Excel/Optima
Sensor Loop Warning
EC Check supply voltage is stable, check cable loop
Optical sensor connected is losing/has lost mA
N/A impedance, check terminal connections. Perform soft
mV output signals
W013
reset on Excel (see Soft Reset).
IR Excel/Optima
Real Time Clock Error
EC
N/A Excel sensor has an internal real time clock error If repeated, contact HA Service.
mV
W014
IR Excel
Excel Software Diagnostic
EC Re-cycle Excel power and confirm 'fault cleared', if
N/A Excel sensor has an internal software error
mV not remove and return to Honeywell for repair.
W015
IR Excel
Installation Not Completed
EC Excel sensor has not completed a 'full' installation Check Excel alignment and confirm operating
N/A
mV procedure distance, rerun 'installation procedure'.
W016
W018
IR
Internal Power Supply Defect
EC 5V power supply failure in Excel receiver Remove and return to HA for repair.
N/A
mV
W019
IR Excel
Forced mA Timeout
EC
W020
IR
Force Relay Timeout
EC
XNX in force relay mode too long Exit Force Relay mode. See Force Relays.
mV All Personalities
W021
IR
mV Sensor Calibration Needed
EC N/A The mV sensor is different than current configuration;
a change in target gas; change in sensor type. After adjusting configuration, reset alarms and faults.
mV mV Personality Board
W022
Calibrate before use.
IR N/A
55
56
10 Fault Messages
Fault
Number Description Condition Recovery
Sensor Abnormal Reboot
EC Cartridge If repeated, check supply voltage, check cable loop
Sensor connected has restarted
impedance, check terminal connections.
F101
mV PCB Personality
IR Sensor
XNX Temperature Error
EC The temperature of the XNX is out of range -30°c Check XNX location for external heat source, shade,
to +83°c possibly re-site XNX. See Transmitter Status.
F103
mV All Personalities
IR
XNX 24 VDC Supply Bad
EC Correct PSU voltage, verify cable loop impedance,
XNX DC supply at/below 15VDC or at/above 34VDC
verify terminal connections.
F104
mV All Personalities
IR
XNX Internal Power Supply Diagnostic
EC
POD power supply failure Check Transmitter Status. Contact HA Service.
F105
mV All Personalities
IR
XNX Real Time Clock Failure
EC
Reset clock, see Set Date & Time.
F106
mV All Personalities
IR
F107
mV All Personalities
IR
XNX mA Output Loop failure
EC Check control circuit, check supply voltage is
Digital diagnostic has detected an analog output
stable, check cable loop impedance, check terminal
problem
F108
mV All Personalities connections.
IR
Simulated Fault
EC
F109
mV All Personalities
IR
Sensor SW Mismatch
EC N/A The XNX will not support Optima operating software
Contact HA Service.
below release 3.0
F110
mV N/A
IR Searchpoint Optima Plus
Negative Drift
EC Check sensor location for external interference,
Sensor connected to XNX has a negative drift
check sensor for operation and re-zero where
exceeding its stated limits
F111
mV All Personalities appropriate, replace sensor if required.
IR
Sensor 24 VDC Supply Bad
EC Correct PSU voltage, verify cable loop impedance,
N/A IR sensor connected has DC at or below lower limit
verify terminal connections.
F112
mV
57
IR IR Sensor Voltage - Excel/Optima
58
Fault
Number Description Condition Recovery
Internal 5V Power Supply Defect
EC
N/A Excel sensor has an internal 5 volt power supply fault Remove and return to Honeywell for repair.
F113
mV
IR IR Power Supply - Excel
Optima Lamp Output
EC
N/A Optima+ sensor has an internal lamp issue Remove sensor and return to Honeywell for repair.
F114
mV
IR
Sensor Internal Failure
EC Optical sensor connected has an internal software
N/A Remove sensor and return to Honeywell for repair.
fault
F116
mV
IR Excel/Optima
Sensor Loop Failure
EC Optical sensor connected is losing/has lost mA Check supply voltage is stable, check cable loop
N/A
output signals impedance, check terminal connections.
F117
mV
IR Excel/Optima
Sensor Real Time Clock invalid
EC Reset 'date and time' in Excel, re-cycle Excel power
N/A Excel sensor has an internal 'real time clock' issue and confirm 'date and time', if not retained remove
F118
mV and return to Honeywell for repair.
IR Excel
Cartridge Failed
EC EC Cartridge Check cartridge connections, check sensor
Internal electrical failure operation, fit replacement cartridge, replace
F119
mV mV Personality Board
F120
mV No mV Board Communication
IR No RS485 Communication
Wrong Cartridge
EC EC Sensor Cartridge
Gas parameters invalid Contact HA Service.
F121
mV mV Personality Board
IR N/A
DSP Problem
EC Check sensor location for external interference
Optical sensor connected is losing/has lost
F122
mV Honeywell for repair.
IR Excel/Optima
Sensor Temperature Error
EC EC Cartridge Check sensor location for external heat source, fit
Sensor connected to unit has an internal temperature
sunshade or other protection, possibly re-site sensor
exceeding its stated limits
F123
mV N/A and/or consider sampling system.
IR Excel/Optima
Calibration Required
EC EC Cartridge Sensor connected has exceeded maximum
Re-calibrate the sensor.
calibration interval
F125
mV mV Personality Board
IR N/A
59
60
Fault
Number Description Condition Recovery
Sample Path Obscured
EC Check sensor location for external interference,
N/A Optima is losing/has lost IR signals
check sensor for 'dirty' windows.
F126
mV
IR Optima
Beam Block
EC Check sensor location for external interference
N/A Excel is losing/has lost IR signals (obstruction in IR path), check sensor for 'dirty'
F127
mV windows. Check unit alignment.
IR Excel
Sensor Installation Checklist ot Complete
EC Excel sensor has not completed a 'full' installation Check Excel alignment and confirm operating
N/A
procedure distance, rerun 'installation procedure' and calibrate.
F128
mV
IR Excel
Option communication Failure
EC
Internal option board not communicating with XNX. Contact HA Service.
F130
mV All Personalities
IR
Low Optical Sample Signal
EC Check sensor location for external interference
N/A Excel is losing/has lost IR signals (obstruction in IR path), check sensor for 'dirty'
F133
mV windows. Check unit alignment.
IR Excel
F141
mV mV Personality Board
IR N/A
Stabilization Timeout
EC
Unstable Sensor Output
mV Sensor exceeds normal warm-up time Cycle power, contact HA Service if problem persists.
F143
Sensor Exceeded Expected Stabilization
IR
Time
Reflex Failure
F145
mV
N/A
IR
General Optical Fault
EC
N/A Contact HA Service.
F146
mV
IR Excel/Optima
Option Board Failure
EC
Internal option board hardware failure. Contact HA Service.
F148
mV All Personalities
IR
61
62
Fault
Number Description Condition Recovery
Internal Communication Failure (mA)
EC Internal 4-20 mA monitoring circuit communication
Contact HA Service.
failure.
F149
mV All Personalities
IR
mA Output Monitoring Fail
EC
mA not producing expected levels. Contact HA Service.
F150
mV All Personalities
IR
Sensor Module Type Changed
For EC: Perform Accept New Sensor function, if
EC EC Cartridge w/Different Gas Type Sensor with different gas type installed or different problem persists contact HA Service.
sensor installed.
F151
mV N/A
mV/IR: Contact HA Service.
IR Switching Between Excel and Optima
Option Module Configuration Error
EC Confirm option properly installed, reconfigure unit
Invalid substitution of option boards.
contact HA Service.
F152
mV All Personalities
IR
Digital Communication Fail
EC
N/A Analog output of sensor is out of tolerance. Contact HA Service.
F153
mV
IR Excel/Optima
F154
mV
IR Excel/Optima
Generic mA Sensor Type Error
EC Check mA input wiring and device, check positions of
N/A Generic mA input below 3 mA.
S3 and S4. Contact HA Service.
F155
mV
IR Generic mA Sensor Type Error
mV Current Control Fail
EC N/A Set correct mV type (see Set mV Sensor Type),
F156
mV Control Range Error personality. Contact HA Service.
IR N/A
Sensor Drift Fault
EC EC Sensor Background gas concentration present, sensor Perform zero calibration using zero air, replace
defective. sensor.
F157
mV mV Personality Board
IR N/A
Sensor/Personality Part Number Mismatch
EC
Installed sensor hardware mismatches configuration. Contact HA Service.
F158
mV All Personalities
IR
63
64
Fault
Number Description Condition Recovery
Option Part Number Mismatch
EC
Installed option hardware mismatches configuration. Contact HA Service.
F159
mV All Personalities
IR
Hardware Diagnostic Failure
EC EC Cartridge
Defective EC cartridge or mV personality board. Replace EC cartridge. Contact HA Service.
F160
mV mV Personality Board
IR N/A
Fault Level mA Input Failure
EC
N/A IR mA input indicates sensor failure, less than 1 mA. Check mA input wiring. Contact HA Service.
F161
mV
IR Excel/Optima
CAUTION: • FOR SAFETY REASONS THIS EQUIPMENT MUST BE OPERATED AND SERVICED BY QUALIFIED PERSONNEL ONLY. READ AND UNDERSTAND MANUAL PRIOR TO SI
LAS FIE
TRANSMITTER
XNX Universal Transmitter for use in Class I, Div. 1 Groups B,C & D
UNIVERSAL
UNIVERSAL
SERVICING. • HIGH OFF SCALE READING MAY INDICATE EXPLOSIVE CONCENTRATIONS.
Class 1, Zone 1, Groups IIB+H2 Haz Loc. Tamb °C to °C Temp Code T4
XNX
• THIS AREA MUST BE FREE OF FLAMMABLE GASES DURING CALIBRATION.
C
XNX
D
AVERTISSEMENT: • POUR REDUIRE LE RISQUE D' ALLUMAGE DANS L'ATMOSPHÈRE. LES CONDUITS DOIVENT AVOIR UN JOINT D'ÉTANCHÉITÉ INSTALLÉS À MOINS DE Only as to Explosion, Fire, Electrical and Shock Hazard
ATTENTION: 18 " [457 mm] DU BOITIER. When Installed Per XNX Manual R
• POUR DES RAISONS DE SECURITÉ, CET EQUIPMENT DOIT ETRE UTILISÉ, ENTRETENU ET REPARÉ UNIQUEMENT PAR UN PERSONNEL QUALIFIÉ SEULEMENT.
Relay Option XNX - UT -R or XNX-RLY
LIRE ET COMPRENDRE LE MANUEL D'INSTRUCTIONS AVANT UTILISATION.
• DES LECTURES HORS ECHELLE PEUVENT INDIQUER DES CONCENTRATIONS EXPLOSIVES Contact Ratings: 250 VAC 5A, 24VDC 5A Resistive Loads Only35YL
• CETTE ZONE DOIT ETRE EXEMPTE DE GAZ INFLAMMABLES PENDANT L'ETALONNAGE Mfg'd by: Honeywell Analytics, Inc., 405 Barclay Blvd. Lincolnshire, IL 60069 USA
TRANSMITTER
XNX Universal Transmitter for use in Class I, Div. 1 Groups B,C & D [Exia]
LAS IE
UNIVERSAL
UNIVERSAL
• FOR SAFETY REASONS THIS EQUIPMENT MUST BE OPERATED AND SERVICED BY QUALIFIED PERSONNEL ONLY. READ AND UNDERSTAND MANUAL PRIOR TO SERVICING
Class 1, Zone 1, Groups IIB+H2 Haz Loc. Tamb °C to °C Temp Code T4
XNX
• HIGH OFF SCALE READING MAY INDICATE EXPLOSIVE CONCENTRATIONS.
C
XNX
D
• THIS AREA MUST BE FREE OF FLAMMABLE GASES DURING CALIBRATION. Only as to Explosion, Fire, Electrical Shock Hazard and Intrinsic Safety
Associated Apparatus Providing Intrinsically Safe Circuits When Installed Per
AVERTISSEMENT: • POUR REDUIRE LE RISQUE D' ALLUMAGE DANS L'ATMOSPHÈRE. LES CONDUITS DOIVENT AVOIR UN JOINT D'ÉTANCHÉITÉ INSTALLÉS À MOINS DE 18 " [457 mm] DU BOITIER XNX Manual and Control Drawing 1226E0402 Um=250V R
ATTENTION: • LA SUBSTITUTION DES COMPOSANTES PEUT COMPROMETTRE LA SÉCURITÉ INTRINSÉQUÉ. Relay Option XNX - UT -R or XNX-RLY
• POUR DES RAISONS DE SECURITÉ, CET EQUIPMENT DOIT ETRE UTILISÉ, ENTRETENU ET REPARÉ UNIQUEMENT PAR UN PERSONNEL
QUALIFIÉ SEULEMENT LIRE ET COMPRENDRE LE MANUEL D'INSTRUCTIONS AVANT UTILISATION • DES LECTURES HORS ECHELLE PEUVENT INDIQUER DES 35YL
Contact Ratings: 250 VAC 5A, 24VDC 5A Resistive Loads Only
CONCENTRATIONS EXPLOSIVES • CETTE ZONE DOIT ETRE EXEMPTE DE GAZ INFLAMMABLES PENDANT L'ETALONNAGE Mfg'd by: Honeywell Analytics, Inc., 405 Barclay Blvd. Lincolnshire, IL 60069 USA
User Warnings/Cautions
Temperature Class
Protection Concept Gas Group
Equipment Protection Level
ATEX Coding Ambient Range
(-20°C to 40°C unless stated on label)
Ingress Protection
EN 50271 Electrical apparatus for the detection and XNX-****-**NNN Dekra Exam
Pending measurement of combustible gases, toxic gases or XNX-****-**CB1
Q4 2009 Completion oxygen - Requirements and tests for apparatus using
software and / or digital technologies
EN 61508 Functional safety of electrical / electronic / XNX-****-**NNN TUV
Pending programmable electronic safety-related systems XNX-****-**CB1 Rhineland
Q4 2009 Completion
EN 60079-29-1 Electrical apparatus for the detection and XNX-AM*I-**NNN Dekra Exam
Pending measurement of flammable gases - Part 4: with Searchpoint
Q4 2009 Completion Performance requirements for group II apparatus Optima Plus,
indicating a volume fraction up to 100% lower Searchline Excel
explosive limit XNX-AM*V- **CB1
XNX-AM*V-**NNN
With MPD-AMCB1
Or Sensepoint
EN50104:2002 Electrical Apparatus for the detection and XNX-AM*E-**** Dekra Exam
Pending measurement of Oxygen. Performance requirements with XNXXSO1SS
Q4 2009 Completion and test methods O2 Cartridge
EN 45544:2000 Workplace atmospheres - Electrical apparatus used XNX-AM*E-**** Dekra Exam
Pending for the direct detection and direct concentration with XNXXSH*SS,
Q4 2009 Completion measurement of toxic gases and vapors. Parts 1-4 H2S cartridge,
XNXXSC1SS CO
Cartridge
UL International DEMKO A/S Baseefa (2001) LDA
Lyskaer 8, P.O. Box 514 Address: Rockhead Business Park
DK-2730 Herlev, Denmark Staden Lane, Buxton,
ID# 0539 SK17 9RZ United Kingdom
Identification Number: 1180
Notified Body Document Identification Number
DEMKO A/S EC Type Examination Certificate 09ATEX0809943X
Baseefa (2001) LDA Quality Assurance Notification Baseefa ATEX 5989
Americas
Honeywell Analytics Inc.
405 Barclay Blvd.
Lincolnshire, IL 60069
USA
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
Fax: +1 847 955 8210
detectgas@honeywell.com
Asia Pacific
Honeywell Analytics Asia Pacific
#508, Kolon Science Valley (I)
187-10 Guro-Dong, Guro-Gu
Seoul, 152-050
Korea
Tel: +82 (0)2 2025 0300
Fax: +82 (0)2 2025 0329
analytics.ap@honeywell.com Please Note:
While every effort has been made to ensure accuracy in this publication, no
responsibility can be accepted for errors or omissions. Data may change, as well
Technical Services as legislation, and you are strongly advised to obtain copies of the most recently
issued regulations, standards and guidelines. This publication is not intended to
EMEAI: HAexpert@honeywell.com form the basis of a contract.
US: ha.us.service@honeywell.com
AP: ha.ap.service@honeywell.com 1998-0744 Release 4
October 2009
MAN0881_EMEAI
www.honeywell.com © 2009 Honeywell Analytics