SUMMATION CURRENT TRANSFORMER

♦ When the current in a number of feeders need not be individually


metered but summated to a single meter or instrument, a summation
current transformer can be used. In consumer installation where
there are more than one feeder it is more economical to use
summation metering and for this purpose, summation CT is required.
The summation CT consists of two or more primary windings which
are connected to the feeders to be summated, and a single
secondary winding which feeds a current proportional to the
summated primary current. A typical ratio would be 5 + 5 + 5 / 5A,
which means that three primary feeders of 5 Amps are to be
summated to a single 5 Amps meter.
♦ The correct meter ratio must be used for summation metering to take
the sum of the feeders.
♦ As an example, if in a 2-way summation, each of the CTs are rated at
600/5A, then the meter should have a ratio of 1200/5A in order to
give the true reading of both feeders.

TECHNICAL SPECIFICATIONS:
Frequency…………………………… 50 / 60 Hz
Secondary Current…………............ 5A or 1A
Secondary Terminals………………. Heat resistance polycarbonate
Dielectric Strength………………….. 3kV rms for 1 minute

WIRING DIAGRAM: DIMENSIONS:


IP1 IP2 IP3

RATIO 176
IS1 IS2 IS3 152

LINE KN1 KN2 KN3


CURRENT - TRANSFORMERS

64

SUMMATION N1 N2 N3
CURRENT - TRANSFORMER

NS
IS

62
INSTRUMENT

138
08B17 - 00

151
Note: Normal rated secondary current are 1A or 5A.
Specifications are subject to change without prior notice. ®