Table 3 - Design Performance Of A Two Pass Series Variable Primary Flow Plant At Different Chilled Water

Temperature Ranges.
Design SWT Range Design Perfor- CH-1 PD CH-2 PD Min Min Min Chiller Conclusion Series chillers in a variable primary flow the impact on chiller performance. This Edition No. 19 January 2004
Flow mance Flow Turndown Flow PD Price
Variable primary flow systems are system resolve the issue of transient can actually lower the cost of the

ENGINEERING
Ratio
(°F) (°F) (GPM) (kW/ton) (ft) (ft) (GPM) (%) (ft) coming of age. They cost less to build flow when a second chiller starts, chillers, in addition to all the other
Series 44 10 1920 0.547 19.1 18.7 575 30 5.4 1.00
and operate than traditional making the system even easier to capital savings that come from lowering
Series 44 12 1600 0.549 18.4 18.1 550 34 5.4 0.97
primary/secondary systems. In design. Switching to series chillers sets the design flow rate.
addition, they are less susceptible to the stage for larger chilled water
Series 42 14 1371 0.588 18.8 18.4 475 35 5.4 0.96
low delta T syndrome. temperature ranges while minimizing
Series 42 16 1200 0.581 19.7 19.2 400 33 5.4 0.91
Series 42 18 1067 0.576 15.9 15.5 400 37 5.4 0.88 S Y S T E M S O L U T I O N S
Series 40 20 920 0.641 22 21.3 300 33 5.2 0.84

Series Variable Primary


W
hen it comes to
Table 3 shows the design performance range and 42°F supply water the only goal, then the valves can be optimizing chiller plants,
from a 10°F to 20°F range for a two
pass series variable primary flow plant.
temperature allows the supply piping
to be 8 inch (versus 10 inch), which
manual. If the valves are automated
and only one chiller is operating,
the best option is to
consider variable flow. ASHRAE
Flow Design
For each design, the water pressure results in significant savings with less then the other chiller can be
The data and suggestions in this document are believed current and accurate at the time of publication, but they are not a substitute for trained, experienced Standard 90.1 requires variable flow
drop was held approximately than a 2% increase in operating cost. automatically bypassed for additional professional service. Individual applications and site variations can significantly affect the results and effectiveness of any information, the reader must satisfy While they have traditionally been the loop pressure differential which
constant. As the chilled water In addition, the chillers are 12% less pressure reduction and pump him/herself regarding the applicability of any article and seek professional evaluation of all materials. McQuay disclaims any responsibility for actions based in systems over 10 hp, and most of used for special projects and difficult adjusts the secondary pump variable
temperature was lowered, the chiller expensive while still offering excellent savings. It needs to be determined on this document. these plants are designed using retrofit applications, variable primary frequency drives (VFD). Any extra
performance decreased. However, the performance. Series chillers are one whether the pump savings will pay primary/secondary systems. However, flow systems are increasingly entering primary flow not required by the
For comments or suggestions, please call or write:
decrease in flow requires smaller of the best ways to optimize chiller for the automatic valves. Chris Sackrison, Editor this proven design is not without its the mainstream as a system for building passes through the decoupler
chilled water pumps and piping. selections. Add a VFD chiller McQuay International
schools, office buildings and process and is returned to the chiller. This
13600 Industrial Park Boulevard challenges – particularly with low
Reviewing the chiller pricing ratio, we Other Considerations Adding a VFD chiller to a series Minneapolis, MN 55441 applications. The system offers flow through the decoupler represents
Phone: (763) 553-5419 delta T issues.
see a large pricing improvement for Series Counterflow arrangement offers additional E-mail: chris.sackrison@mcquay.com designers several benefits and a few “wasted” flow because it delivers no
the same performance and water Switching to series counterflow may savings. First, it can be the lead For more information on McQuay products and services, or to speak with your local representative, call (800) 432-1342, or visit our web page at www.mcquay.com.
©2004 McQuay International Variable primary flow is quickly challenges. value to the building occupants.
pressure drop. This occurs because add even more savings. Series chiller when only one chiller is becoming an alternative to Background What the decoupler flow does provide
the lower flow for the same pressure counterflow improves annual chiller required. During these lighter loads, Figure 1 shows a conventional is constant flow through the chiller
primary/secondary systems. This
drop results in less copper tubing – performance by about 5%. However, there is likely to be condenser water primary/secondary chiller design. The evaporators. Until recently, this
the most expensive component in a the condenser water must be pumped relief that the VFD chiller can article discusses a specific application
flow through each chiller is constant constant flow was considered essential
chiller. This can be added to the other at design flow even if only one chiller benefit from. When both chillers are of variable primary flow with series for reliable chiller operation. However,
and set by the constant flow of a
capital savings (listed previously) that is operating. The increased condenser required, the VFD chiller can be the chillers. Series chillers can help primary pump. The flow in the research has shown that varying flow
result from increasing the chilled pump work may offset the chiller upstream chiller. Assuming the resolve some of the design and building, or the secondary loop, is through the chiller is possible as long
water temperature range. savings. For short condenser loops, chillers are identical and selected to operational issues associated with variable and is typically controlled by as the minimum flow is maintained.1
Table 4 shows the annual operating series counterflow may make sense. do the more difficult lead chiller variable primary flow. Series chillers
cost as the range is increased from Chiller bypass line duty, the VFD can slow the Figure 1 – Conventional Primary/Secondary System
upstream chiller down to the are also a great idea when large
10°F to 20°F. In this example, the In most cases, a chiller bypass line is
appropriate tip speed for the lower chilled water temperature ranges
best operating performance occurs at a good idea because it will allow
a 12°F range and 44°F supply water chiller servicing without shutting lift duty. This will optimize the make sense. Decoupler

temperature. However, the 18°F down the entire plant. If service is chiller for the upstream duty.
J.C. Kuttruff, our Global Account
(continued on back page)
Manager, provided technical expertise
Table 4 – Annual Operating Performance For Two Pass Series Variable Primary Flow Chiller Plants At Different in variable primary flow design for
Primary Pump
Chilled Water Temperature Ranges. this newsletter. For more information
Run SWT Range Min Flow Chiller PD Chiller Pumps Tower Fan S.A. Fan Total on variable primary flow systems,
(°F) (°F) (GPM) (ft) ($/yr) ($/yr) ($/yr) ($/yr) ($/yr) contact your local McQuay
Series 44 10 575 37.8 $ 82,584 $ 24,198 $ 6,907 $ 73,051 $ 186,740 Representative or visit
2 pass
Series 44 12 550 36.5 $ 82,104 $ 23,007 $ 6,904 $ 73,025 $ 185,040
www.mcquay.com.
2 pass Hugh Crowther
Series 42 14 475 37.2 $ 88,322 $ 22,296 $ 6,909 $ 73,078 $ 190,605
Director of Applications Secondary Pump with VFD
2 pass
Series 42 16 400 38.9 $ 87,247 $ 21,790 $ 6,907 $ 73,058 $ 189,002 McQuay International
1Redden, George. Effect of Variable Flow on Chiller Performance. ASHRAE Transaction SA- 96-12-3. 1996,
2 pass
Series 42 18 400 31.4 $ 86,470 $ 21,016 $ 6,905 $ 73,036 $ 187,427 ASHRAE, Atlanta, Ga.
2 pass
Series 40 20 300 43.3 $ 96,360 $ 20,799 $ 6,915 $ 73,136 $ 197,210
2 pass
Figure 2 – Variable Primary Flow System With Parallel Chillers Variable Primary Flow Challenges through. In many cases, the chilled A second consideration would be efficiency over base loading the first Table 1 – Design Performance For Parallel and Series One Pass and Two Pass Variable Primary Flow Chiller Plants.
Every new application creates new water supply is completely diverted opening the isolation valve slowly over chiller.
Bypass Line
challenges, and variable primary flow and the chiller sees a return water a 2 to 3 minute period. By mini- One flowmeter can be used to control Design SWT Range Design Perfor- CH-1 PD CH-2 PD Min Min Min Chiller
FLOW mance Flow Turndown Flow PD Price
is not without challenges. New design temperature equal to the supply. mizing the effect of an instantaneous the bypass valve when the flow drops Ratio
Primary Pump with VFD elements need to be addressed for a When this happens, the chiller 50% reduction of flow and load on below the minimum. Overall, series (°F) (°F) (GPM) (kW/ton) (ft) (ft) (GPM) (%) (ft)
reliable, problem-free installation. Two believes the load is satisfied and it the operating unit, you minimize the chillers are easier to design and Parallel 44 10 1920 0.560 17 17 375 20 3.1 1.00
issues are of critical importance. The shuts down. possibility of tripping a chiller. operate. 2 pass
first is transient flows encountered Transient Flows When reducing the number of chillers, Series 44 10 1920 0.547 8.6 8.4 725 38 2.8 0.95
What About The Pressure Drop? 1 pass
Flowmeter when additional chillers are enabled or As the cooling load increases, a second transient flows are usually not a When series chillers are suggested, a Series 44 10 1920 0.547 19.1 18.7 575 30 5.4 0.95
turned off. The second is maintaining chiller will be required. When the problem. When a chiller is taken off primary consideration must be the 2 pass
minimum required chiller flows at isolating valve to the second chiller line and its isolation valve closes, its pressure drop incurred when the two
very low loads. Simple solutions are opens, the flow is split, resulting in an flow is diverted through the remaining chiller pressure drops are added Los Angeles. It is a VAV system with chillers offer the best overall variable primary flow system resolves
available. immediate 50% reduction in load for operating chillers. As the flow together. The common solution is to two 400-ton chillers. We will start minimum flow at 375 gpm (or 20% the issues surrounding starting the
Minimum Flows the first chiller. If the first chiller increases, the remaining chiller(s) see change the chiller shell from a two
Chillers have maximum and cannot respond quickly enough, then an elevated supply water temperature with conventional ARI conditions, of design flow). second chiller, making the system
pass to a single pass arrangement. 44°F/54°F chilled water and even easier to design and operate.
minimum flow limits. The maximum it will trip a safety (such as low and compensate by increasing capacity. While this greatly reduces the pressure The chiller price ratio shows the
limit avoids tube erosion. The refrigerant pressure or a freezestat) and 85°F/95°F condenser water. relative price change for the series However, the real opportunity
Why Not Consider Series Chillers? drop, it also increases the minimum
Isolating Valve minimum limit provides stable heat be taken off line. Figure 3 shows a variable primary flow rate (or reduces the turndown). Table 1 shows the design chillers when compared to the comes when we consider larger
transfer in the evaporator, which The most reliable remedy for this flow system with the chillers in series. A two pass chiller at typical conditions performance of the three systems. All parallel chillers. Notice the two chilled water temperature ranges
Figure 2 shows a typical variable primary/secondary system. Unless results in stable chiller operation. reduction in flow is to reduce the In this arrangement, the flow passes can have the flow reduced to about were selected to provide about 0.55 series offerings cost about 5% less than the conventional 10°F. While
primary flow system with the chillers the flow drops below the minimum Since flow is proportional to load in a output (demand limit) of the first through both chillers so there is no 50%. A single pass chiller can only kW/ton full load performance. The because the series arrangement is a the larger range provides only
in parallel. In this system, the primary required by the chiller, any flow that variable primary flow system, chiller prior to opening the isolating problem with starting the second have the flow reduced to about 70%. performance of the series chillers is very efficient use of chillers. The nominal operating savings (See
pumps are variable flow and there are is pumped in a variable primary maintaining minimum flow across the valve for the second chiller. For chiller. Staging the chillers is very easy based on the total of the two chillers designer has the option to use this Engineering Solutions #14, Why
It is important to remember that flow (total kW/ total tons). The same cost difference to get better Change The Chilled Water
no secondary pumps. The decoupler is flow system is sent to the building evaporator becomes an issue when the example, if the operating chiller is for McQuay because our centrifugal varies through a chiller proportionally chiller model was used in both the performance from the series chillers Temperature Range, December 2002
replaced by a bypass line with a and used. cooling requirement in the facility falls demand limited to 50% capacity prior chillers come with a lead/lag load with the load in a variable flow system. lead and lag position. This allows or it can be taken as a cost savings. on www.mcquay.com), it can offer
modulating flow valve. As long as the • In many applications there are fewer below the minimum flow of one to opening the isolating valve for the balance feature that will use the As a result, the chiller sees a reduction either chiller to be the lead chiller significant capital savings on the
flow is above the minimum required pipe fittings associated with pumps chiller. second chiller, the operating chiller chiller with the least operating hours Table 2 shows the annual operating
in flow and pressure drop most of the when only one chiller is required. It entire HVAC system as it affects the
by the chiller, the bypass line remains (e.g. for check valves, isolating Normally, a bypass valve is installed to will not see the dramatic drop in load. when only one chiller is required. time. At 70% flow, the pressure drop cost for the three systems. Overall,
closed and the flow through the valves, elbows, etc.) because there is maintain minimum flow to the chiller. Demand limiting can be accomplished When a second chiller is required, the is possible to further enhance the there is very little difference between chillers, pumps, piping, cooling
across the chillers is reduced to 49%. chiller performance by selecting coils, supply air fans, etc. Generally,
chiller(s) varies with the building only one set of pumps. As a result, When the cooling load and coincident with an analog signal to most chiller two chiller control panels This results in a small annual energy the three. The higher design pressure
requirement. When the minimum the overall design pressure drop for a chilled water flow is less than a controllers. McQuay MicroTech II™ communicate via a twisted, shielded chillers specifically for the operating drop of the two pass series arrange- as the range is increased, the chilled
penalty when using a higher design conditions (See Engineering water supply temperature will have
chiller flow is reached, the bypass valve variable primary flow system will be chiller’s minimum flow limit, the controls allow the signal to be pair of wires and the second chiller is water pressure drop. ment results in only a minor cost
is modulated so that minimum flow is about 10% less than a primary/ bypass valve modulates to divert flow provided digitally and communicated started. The load is evenly distributed Solutions #10, Series Chillers - What’s penalty. The same is true for the to be lowered to strike a balance
maintained. If we accept the higher pressure drop Old Is New Again, January 2002 on higher minimum turndown for the between the fan penalty (due to
secondary system in the same back to the chiller. This is done via a via open, standard protocols using our between the two chillers which results
at design conditions and use two pass www.mcquay.com). However, it is one pass series arrangement. coils with more rows) and chiller
Variable Primary Flow Benefits application. flow sensor or by monitoring for a Protocol Selectability™ feature. in about a 2% improvement in
chillers in the same system, we gain unlikely that the upstream chiller penalty (due to increased lift).
Variable primary flow systems are • Variable primary flow creates the minimum ∆P across the evaporator What this analysis demonstrates is
better turndown at part load will operate at the higher lift Series chillers are a very good
gaining popularity for the following opportunity to operate chillers in barrel. Figure 3 – Variable Primary Flow System With The Chillers In Series that there is little or no operating
conditions. Raising this minimum conditions required by the arrangement for providing larger
reasons: their “efficiency sweet spot” without Sizing the bypass and bypass valve for turndown point reduces the flow penalty when using series chillers in
downstream chiller. ranges and lower chilled water
• They require smaller mechanical paying for extra, unused pump the chiller’s minimum flow is an through the bypass line and improves variable primary flow systems. We
energy. In other words, variable important design consideration with a Bypass Line Notice that the pressure drop for the have already established that variable temperatures. As the supply water
rooms because only one set of pump savings to offset part of the
primary flow allows two chillers to variable primary flow system. Smaller parallel chillers and the one pass primary flow systems are easier to temperature is lowered, the chillers
pumps is used. penalty incurred at design conditions.
be used when it is still possible to valves are less expensive and control chillers is the same (17 ft.). The two design and operate (as long as issues in series will require less power than
• They generally cost less to install. Performing an annual energy analysis pass series chiller pressure drop is a single chiller trying to provide the
meet the load with only one chiller. minimum flows much more using McQuay’s Energy Analyzer™ with starting the second chiller are
Once the construction team is nearly twice as high. The parallel same chilled water temperature.
Plants with dual compressor chillers accurately. software can be an invaluable design resolved). Using series chillers in a
familiar with the requirements, they
or chillers with VFDs can benefit. A common error is to size the bypass Primary Pump with VFD tool in helping to determine which (continued on next page)
are easier to design and build
because there are fewer pumps and Lower pressure drops created by valve the same as the chilled water pass arrangement will be most
splitting the flows across multiple Table 2 – Annual Operating Performance For Parallel and Series One Pass and Two Pass Variable Primary Flow
pipe fittings. More time should be line. This almost universally oversizes beneficial for a specific application. Chiller Plants.
chillers and the benefit of operating Flowmeter
allowed for commissioning because the bypass and creates problems. Performance Comparison – Parallel
in an efficiency “sweet spot” can Using an oversized valve to modulate a Run Design Min Chiller Chiller Pumps Tower S.A. Fan Total
the controls can be more and Series One Pass and Two Pass Flow Flow PD Fan
complicated, but the overall cost of provide enough savings to offset the fraction of the flow is equivalent to Variable Primary Flow Systems (GPM) (GPM) (ft) ($/yr) ($/yr) ($/yr) ($/yr) ($/yr)
a variable primary flow system can liability of additional condenser opening a barn door to let a mouse Let’s compare chillers in parallel to Parallel 1920 375 17 $ 82,482 $ 21,850 $ 7,890 $ 72,959 $ 185,181
be less than a primary/secondary pump and tower fan work. This out. The mouse gets out, but so do series chillers with one pass and series 2 pass
system. strategy will save energy (operating the rest of the farm animals. In much chillers with two pass arrangements. Series 10 725 17 $ 82,552 $ 23,629 $ 6,904 $ 73,023 $ 186,108
costs) over the life of the facility. 1 pass
• There is no wasted pump work as is the same way, instead of modulating a We will use a model office building in Series 10 575 37.8 $ 82,584 $ 24,198 $ 6,907 $ 73,051 $ 186,740
the case with the decoupler in a trickle of water, a torrent rushes pass
Figure 2 – Variable Primary Flow System With Parallel Chillers Variable Primary Flow Challenges through. In many cases, the chilled A second consideration would be efficiency over base loading the first Table 1 – Design Performance For Parallel and Series One Pass and Two Pass Variable Primary Flow Chiller Plants.
Every new application creates new water supply is completely diverted opening the isolation valve slowly over chiller.
Bypass Line
challenges, and variable primary flow and the chiller sees a return water a 2 to 3 minute period. By mini- One flowmeter can be used to control Design SWT Range Design Perfor- CH-1 PD CH-2 PD Min Min Min Chiller
FLOW mance Flow Turndown Flow PD Price
is not without challenges. New design temperature equal to the supply. mizing the effect of an instantaneous the bypass valve when the flow drops Ratio
Primary Pump with VFD elements need to be addressed for a When this happens, the chiller 50% reduction of flow and load on below the minimum. Overall, series (°F) (°F) (GPM) (kW/ton) (ft) (ft) (GPM) (%) (ft)
reliable, problem-free installation. Two believes the load is satisfied and it the operating unit, you minimize the chillers are easier to design and Parallel 44 10 1920 0.560 17 17 375 20 3.1 1.00
issues are of critical importance. The shuts down. possibility of tripping a chiller. operate. 2 pass
first is transient flows encountered Transient Flows When reducing the number of chillers, Series 44 10 1920 0.547 8.6 8.4 725 38 2.8 0.95
What About The Pressure Drop? 1 pass
Flowmeter when additional chillers are enabled or As the cooling load increases, a second transient flows are usually not a When series chillers are suggested, a Series 44 10 1920 0.547 19.1 18.7 575 30 5.4 0.95
turned off. The second is maintaining chiller will be required. When the problem. When a chiller is taken off primary consideration must be the 2 pass
minimum required chiller flows at isolating valve to the second chiller line and its isolation valve closes, its pressure drop incurred when the two
very low loads. Simple solutions are opens, the flow is split, resulting in an flow is diverted through the remaining chiller pressure drops are added Los Angeles. It is a VAV system with chillers offer the best overall variable primary flow system resolves
available. immediate 50% reduction in load for operating chillers. As the flow together. The common solution is to two 400-ton chillers. We will start minimum flow at 375 gpm (or 20% the issues surrounding starting the
Minimum Flows the first chiller. If the first chiller increases, the remaining chiller(s) see change the chiller shell from a two
Chillers have maximum and cannot respond quickly enough, then an elevated supply water temperature with conventional ARI conditions, of design flow). second chiller, making the system
pass to a single pass arrangement. 44°F/54°F chilled water and even easier to design and operate.
minimum flow limits. The maximum it will trip a safety (such as low and compensate by increasing capacity. While this greatly reduces the pressure The chiller price ratio shows the
limit avoids tube erosion. The refrigerant pressure or a freezestat) and 85°F/95°F condenser water. relative price change for the series However, the real opportunity
Why Not Consider Series Chillers? drop, it also increases the minimum
Isolating Valve minimum limit provides stable heat be taken off line. Figure 3 shows a variable primary flow rate (or reduces the turndown). Table 1 shows the design chillers when compared to the comes when we consider larger
transfer in the evaporator, which The most reliable remedy for this flow system with the chillers in series. A two pass chiller at typical conditions performance of the three systems. All parallel chillers. Notice the two chilled water temperature ranges
Figure 2 shows a typical variable primary/secondary system. Unless results in stable chiller operation. reduction in flow is to reduce the In this arrangement, the flow passes can have the flow reduced to about were selected to provide about 0.55 series offerings cost about 5% less than the conventional 10°F. While
primary flow system with the chillers the flow drops below the minimum Since flow is proportional to load in a output (demand limit) of the first through both chillers so there is no 50%. A single pass chiller can only kW/ton full load performance. The because the series arrangement is a the larger range provides only
in parallel. In this system, the primary required by the chiller, any flow that variable primary flow system, chiller prior to opening the isolating problem with starting the second have the flow reduced to about 70%. performance of the series chillers is very efficient use of chillers. The nominal operating savings (See
pumps are variable flow and there are is pumped in a variable primary maintaining minimum flow across the valve for the second chiller. For chiller. Staging the chillers is very easy based on the total of the two chillers designer has the option to use this Engineering Solutions #14, Why
It is important to remember that flow (total kW/ total tons). The same cost difference to get better Change The Chilled Water
no secondary pumps. The decoupler is flow system is sent to the building evaporator becomes an issue when the example, if the operating chiller is for McQuay because our centrifugal varies through a chiller proportionally chiller model was used in both the performance from the series chillers Temperature Range, December 2002
replaced by a bypass line with a and used. cooling requirement in the facility falls demand limited to 50% capacity prior chillers come with a lead/lag load with the load in a variable flow system. lead and lag position. This allows or it can be taken as a cost savings. on www.mcquay.com), it can offer
modulating flow valve. As long as the • In many applications there are fewer below the minimum flow of one to opening the isolating valve for the balance feature that will use the As a result, the chiller sees a reduction either chiller to be the lead chiller significant capital savings on the
flow is above the minimum required pipe fittings associated with pumps chiller. second chiller, the operating chiller chiller with the least operating hours Table 2 shows the annual operating
in flow and pressure drop most of the when only one chiller is required. It entire HVAC system as it affects the
by the chiller, the bypass line remains (e.g. for check valves, isolating Normally, a bypass valve is installed to will not see the dramatic drop in load. when only one chiller is required. time. At 70% flow, the pressure drop cost for the three systems. Overall,
closed and the flow through the valves, elbows, etc.) because there is maintain minimum flow to the chiller. Demand limiting can be accomplished When a second chiller is required, the is possible to further enhance the there is very little difference between chillers, pumps, piping, cooling
across the chillers is reduced to 49%. chiller performance by selecting coils, supply air fans, etc. Generally,
chiller(s) varies with the building only one set of pumps. As a result, When the cooling load and coincident with an analog signal to most chiller two chiller control panels This results in a small annual energy the three. The higher design pressure
requirement. When the minimum the overall design pressure drop for a chilled water flow is less than a controllers. McQuay MicroTech II™ communicate via a twisted, shielded chillers specifically for the operating drop of the two pass series arrange- as the range is increased, the chilled
penalty when using a higher design conditions (See Engineering water supply temperature will have
chiller flow is reached, the bypass valve variable primary flow system will be chiller’s minimum flow limit, the controls allow the signal to be pair of wires and the second chiller is water pressure drop. ment results in only a minor cost
is modulated so that minimum flow is about 10% less than a primary/ bypass valve modulates to divert flow provided digitally and communicated started. The load is evenly distributed Solutions #10, Series Chillers - What’s penalty. The same is true for the to be lowered to strike a balance
maintained. If we accept the higher pressure drop Old Is New Again, January 2002 on higher minimum turndown for the between the fan penalty (due to
secondary system in the same back to the chiller. This is done via a via open, standard protocols using our between the two chillers which results
at design conditions and use two pass www.mcquay.com). However, it is one pass series arrangement. coils with more rows) and chiller
Variable Primary Flow Benefits application. flow sensor or by monitoring for a Protocol Selectability™ feature. in about a 2% improvement in
chillers in the same system, we gain unlikely that the upstream chiller penalty (due to increased lift).
Variable primary flow systems are • Variable primary flow creates the minimum ∆P across the evaporator What this analysis demonstrates is
better turndown at part load will operate at the higher lift Series chillers are a very good
gaining popularity for the following opportunity to operate chillers in barrel. Figure 3 – Variable Primary Flow System With The Chillers In Series that there is little or no operating
conditions. Raising this minimum conditions required by the arrangement for providing larger
reasons: their “efficiency sweet spot” without Sizing the bypass and bypass valve for turndown point reduces the flow penalty when using series chillers in
downstream chiller. ranges and lower chilled water
• They require smaller mechanical paying for extra, unused pump the chiller’s minimum flow is an through the bypass line and improves variable primary flow systems. We
energy. In other words, variable important design consideration with a Bypass Line Notice that the pressure drop for the have already established that variable temperatures. As the supply water
rooms because only one set of pump savings to offset part of the
primary flow allows two chillers to variable primary flow system. Smaller parallel chillers and the one pass primary flow systems are easier to temperature is lowered, the chillers
pumps is used. penalty incurred at design conditions.
be used when it is still possible to valves are less expensive and control chillers is the same (17 ft.). The two design and operate (as long as issues in series will require less power than
• They generally cost less to install. Performing an annual energy analysis pass series chiller pressure drop is a single chiller trying to provide the
meet the load with only one chiller. minimum flows much more using McQuay’s Energy Analyzer™ with starting the second chiller are
Once the construction team is nearly twice as high. The parallel same chilled water temperature.
Plants with dual compressor chillers accurately. software can be an invaluable design resolved). Using series chillers in a
familiar with the requirements, they
or chillers with VFDs can benefit. A common error is to size the bypass Primary Pump with VFD tool in helping to determine which (continued on next page)
are easier to design and build
because there are fewer pumps and Lower pressure drops created by valve the same as the chilled water pass arrangement will be most
splitting the flows across multiple Table 2 – Annual Operating Performance For Parallel and Series One Pass and Two Pass Variable Primary Flow
pipe fittings. More time should be line. This almost universally oversizes beneficial for a specific application. Chiller Plants.
chillers and the benefit of operating Flowmeter
allowed for commissioning because the bypass and creates problems. Performance Comparison – Parallel
in an efficiency “sweet spot” can Using an oversized valve to modulate a Run Design Min Chiller Chiller Pumps Tower S.A. Fan Total
the controls can be more and Series One Pass and Two Pass Flow Flow PD Fan
complicated, but the overall cost of provide enough savings to offset the fraction of the flow is equivalent to Variable Primary Flow Systems (GPM) (GPM) (ft) ($/yr) ($/yr) ($/yr) ($/yr) ($/yr)
a variable primary flow system can liability of additional condenser opening a barn door to let a mouse Let’s compare chillers in parallel to Parallel 1920 375 17 $ 82,482 $ 21,850 $ 7,890 $ 72,959 $ 185,181
be less than a primary/secondary pump and tower fan work. This out. The mouse gets out, but so do series chillers with one pass and series 2 pass
system. strategy will save energy (operating the rest of the farm animals. In much chillers with two pass arrangements. Series 10 725 17 $ 82,552 $ 23,629 $ 6,904 $ 73,023 $ 186,108
costs) over the life of the facility. 1 pass
• There is no wasted pump work as is the same way, instead of modulating a We will use a model office building in Series 10 575 37.8 $ 82,584 $ 24,198 $ 6,907 $ 73,051 $ 186,740
the case with the decoupler in a trickle of water, a torrent rushes pass
Figure 2 – Variable Primary Flow System With Parallel Chillers Variable Primary Flow Challenges through. In many cases, the chilled A second consideration would be efficiency over base loading the first Table 1 – Design Performance For Parallel and Series One Pass and Two Pass Variable Primary Flow Chiller Plants.
Every new application creates new water supply is completely diverted opening the isolation valve slowly over chiller.
Bypass Line
challenges, and variable primary flow and the chiller sees a return water a 2 to 3 minute period. By mini- One flowmeter can be used to control Design SWT Range Design Perfor- CH-1 PD CH-2 PD Min Min Min Chiller
FLOW mance Flow Turndown Flow PD Price
is not without challenges. New design temperature equal to the supply. mizing the effect of an instantaneous the bypass valve when the flow drops Ratio
Primary Pump with VFD elements need to be addressed for a When this happens, the chiller 50% reduction of flow and load on below the minimum. Overall, series (°F) (°F) (GPM) (kW/ton) (ft) (ft) (GPM) (%) (ft)
reliable, problem-free installation. Two believes the load is satisfied and it the operating unit, you minimize the chillers are easier to design and Parallel 44 10 1920 0.560 17 17 375 20 3.1 1.00
issues are of critical importance. The shuts down. possibility of tripping a chiller. operate. 2 pass
first is transient flows encountered Transient Flows When reducing the number of chillers, Series 44 10 1920 0.547 8.6 8.4 725 38 2.8 0.95
What About The Pressure Drop? 1 pass
Flowmeter when additional chillers are enabled or As the cooling load increases, a second transient flows are usually not a When series chillers are suggested, a Series 44 10 1920 0.547 19.1 18.7 575 30 5.4 0.95
turned off. The second is maintaining chiller will be required. When the problem. When a chiller is taken off primary consideration must be the 2 pass
minimum required chiller flows at isolating valve to the second chiller line and its isolation valve closes, its pressure drop incurred when the two
very low loads. Simple solutions are opens, the flow is split, resulting in an flow is diverted through the remaining chiller pressure drops are added Los Angeles. It is a VAV system with chillers offer the best overall variable primary flow system resolves
available. immediate 50% reduction in load for operating chillers. As the flow together. The common solution is to two 400-ton chillers. We will start minimum flow at 375 gpm (or 20% the issues surrounding starting the
Minimum Flows the first chiller. If the first chiller increases, the remaining chiller(s) see change the chiller shell from a two
Chillers have maximum and cannot respond quickly enough, then an elevated supply water temperature with conventional ARI conditions, of design flow). second chiller, making the system
pass to a single pass arrangement. 44°F/54°F chilled water and even easier to design and operate.
minimum flow limits. The maximum it will trip a safety (such as low and compensate by increasing capacity. While this greatly reduces the pressure The chiller price ratio shows the
limit avoids tube erosion. The refrigerant pressure or a freezestat) and 85°F/95°F condenser water. relative price change for the series However, the real opportunity
Why Not Consider Series Chillers? drop, it also increases the minimum
Isolating Valve minimum limit provides stable heat be taken off line. Figure 3 shows a variable primary flow rate (or reduces the turndown). Table 1 shows the design chillers when compared to the comes when we consider larger
transfer in the evaporator, which The most reliable remedy for this flow system with the chillers in series. A two pass chiller at typical conditions performance of the three systems. All parallel chillers. Notice the two chilled water temperature ranges
Figure 2 shows a typical variable primary/secondary system. Unless results in stable chiller operation. reduction in flow is to reduce the In this arrangement, the flow passes can have the flow reduced to about were selected to provide about 0.55 series offerings cost about 5% less than the conventional 10°F. While
primary flow system with the chillers the flow drops below the minimum Since flow is proportional to load in a output (demand limit) of the first through both chillers so there is no 50%. A single pass chiller can only kW/ton full load performance. The because the series arrangement is a the larger range provides only
in parallel. In this system, the primary required by the chiller, any flow that variable primary flow system, chiller prior to opening the isolating problem with starting the second have the flow reduced to about 70%. performance of the series chillers is very efficient use of chillers. The nominal operating savings (See
pumps are variable flow and there are is pumped in a variable primary maintaining minimum flow across the valve for the second chiller. For chiller. Staging the chillers is very easy based on the total of the two chillers designer has the option to use this Engineering Solutions #14, Why
It is important to remember that flow (total kW/ total tons). The same cost difference to get better Change The Chilled Water
no secondary pumps. The decoupler is flow system is sent to the building evaporator becomes an issue when the example, if the operating chiller is for McQuay because our centrifugal varies through a chiller proportionally chiller model was used in both the performance from the series chillers Temperature Range, December 2002
replaced by a bypass line with a and used. cooling requirement in the facility falls demand limited to 50% capacity prior chillers come with a lead/lag load with the load in a variable flow system. lead and lag position. This allows or it can be taken as a cost savings. on www.mcquay.com), it can offer
modulating flow valve. As long as the • In many applications there are fewer below the minimum flow of one to opening the isolating valve for the balance feature that will use the As a result, the chiller sees a reduction either chiller to be the lead chiller significant capital savings on the
flow is above the minimum required pipe fittings associated with pumps chiller. second chiller, the operating chiller chiller with the least operating hours Table 2 shows the annual operating
in flow and pressure drop most of the when only one chiller is required. It entire HVAC system as it affects the
by the chiller, the bypass line remains (e.g. for check valves, isolating Normally, a bypass valve is installed to will not see the dramatic drop in load. when only one chiller is required. time. At 70% flow, the pressure drop cost for the three systems. Overall,
closed and the flow through the valves, elbows, etc.) because there is maintain minimum flow to the chiller. Demand limiting can be accomplished When a second chiller is required, the is possible to further enhance the there is very little difference between chillers, pumps, piping, cooling
across the chillers is reduced to 49%. chiller performance by selecting coils, supply air fans, etc. Generally,
chiller(s) varies with the building only one set of pumps. As a result, When the cooling load and coincident with an analog signal to most chiller two chiller control panels This results in a small annual energy the three. The higher design pressure
requirement. When the minimum the overall design pressure drop for a chilled water flow is less than a controllers. McQuay MicroTech II™ communicate via a twisted, shielded chillers specifically for the operating drop of the two pass series arrange- as the range is increased, the chilled
penalty when using a higher design conditions (See Engineering water supply temperature will have
chiller flow is reached, the bypass valve variable primary flow system will be chiller’s minimum flow limit, the controls allow the signal to be pair of wires and the second chiller is water pressure drop. ment results in only a minor cost
is modulated so that minimum flow is about 10% less than a primary/ bypass valve modulates to divert flow provided digitally and communicated started. The load is evenly distributed Solutions #10, Series Chillers - What’s penalty. The same is true for the to be lowered to strike a balance
maintained. If we accept the higher pressure drop Old Is New Again, January 2002 on higher minimum turndown for the between the fan penalty (due to
secondary system in the same back to the chiller. This is done via a via open, standard protocols using our between the two chillers which results
at design conditions and use two pass www.mcquay.com). However, it is one pass series arrangement. coils with more rows) and chiller
Variable Primary Flow Benefits application. flow sensor or by monitoring for a Protocol Selectability™ feature. in about a 2% improvement in
chillers in the same system, we gain unlikely that the upstream chiller penalty (due to increased lift).
Variable primary flow systems are • Variable primary flow creates the minimum ∆P across the evaporator What this analysis demonstrates is
better turndown at part load will operate at the higher lift Series chillers are a very good
gaining popularity for the following opportunity to operate chillers in barrel. Figure 3 – Variable Primary Flow System With The Chillers In Series that there is little or no operating
conditions. Raising this minimum conditions required by the arrangement for providing larger
reasons: their “efficiency sweet spot” without Sizing the bypass and bypass valve for turndown point reduces the flow penalty when using series chillers in
downstream chiller. ranges and lower chilled water
• They require smaller mechanical paying for extra, unused pump the chiller’s minimum flow is an through the bypass line and improves variable primary flow systems. We
energy. In other words, variable important design consideration with a Bypass Line Notice that the pressure drop for the have already established that variable temperatures. As the supply water
rooms because only one set of pump savings to offset part of the
primary flow allows two chillers to variable primary flow system. Smaller parallel chillers and the one pass primary flow systems are easier to temperature is lowered, the chillers
pumps is used. penalty incurred at design conditions.
be used when it is still possible to valves are less expensive and control chillers is the same (17 ft.). The two design and operate (as long as issues in series will require less power than
• They generally cost less to install. Performing an annual energy analysis pass series chiller pressure drop is a single chiller trying to provide the
meet the load with only one chiller. minimum flows much more using McQuay’s Energy Analyzer™ with starting the second chiller are
Once the construction team is nearly twice as high. The parallel same chilled water temperature.
Plants with dual compressor chillers accurately. software can be an invaluable design resolved). Using series chillers in a
familiar with the requirements, they
or chillers with VFDs can benefit. A common error is to size the bypass Primary Pump with VFD tool in helping to determine which (continued on next page)
are easier to design and build
because there are fewer pumps and Lower pressure drops created by valve the same as the chilled water pass arrangement will be most
splitting the flows across multiple Table 2 – Annual Operating Performance For Parallel and Series One Pass and Two Pass Variable Primary Flow
pipe fittings. More time should be line. This almost universally oversizes beneficial for a specific application. Chiller Plants.
chillers and the benefit of operating Flowmeter
allowed for commissioning because the bypass and creates problems. Performance Comparison – Parallel
in an efficiency “sweet spot” can Using an oversized valve to modulate a Run Design Min Chiller Chiller Pumps Tower S.A. Fan Total
the controls can be more and Series One Pass and Two Pass Flow Flow PD Fan
complicated, but the overall cost of provide enough savings to offset the fraction of the flow is equivalent to Variable Primary Flow Systems (GPM) (GPM) (ft) ($/yr) ($/yr) ($/yr) ($/yr) ($/yr)
a variable primary flow system can liability of additional condenser opening a barn door to let a mouse Let’s compare chillers in parallel to Parallel 1920 375 17 $ 82,482 $ 21,850 $ 7,890 $ 72,959 $ 185,181
be less than a primary/secondary pump and tower fan work. This out. The mouse gets out, but so do series chillers with one pass and series 2 pass
system. strategy will save energy (operating the rest of the farm animals. In much chillers with two pass arrangements. Series 10 725 17 $ 82,552 $ 23,629 $ 6,904 $ 73,023 $ 186,108
costs) over the life of the facility. 1 pass
• There is no wasted pump work as is the same way, instead of modulating a We will use a model office building in Series 10 575 37.8 $ 82,584 $ 24,198 $ 6,907 $ 73,051 $ 186,740
the case with the decoupler in a trickle of water, a torrent rushes pass
Table 3 - Design Performance Of A Two Pass Series Variable Primary Flow Plant At Different Chilled Water
Temperature Ranges.
Design SWT Range Design Perfor- CH-1 PD CH-2 PD Min Min Min Chiller Conclusion Series chillers in a variable primary flow the impact on chiller performance. This Edition No. 19 January 2004
Flow mance Flow Turndown Flow PD Price
Variable primary flow systems are system resolve the issue of transient can actually lower the cost of the

ENGINEERING
Ratio
(°F) (°F) (GPM) (kW/ton) (ft) (ft) (GPM) (%) (ft) coming of age. They cost less to build flow when a second chiller starts, chillers, in addition to all the other
Series 44 10 1920 0.547 19.1 18.7 575 30 5.4 1.00
and operate than traditional making the system even easier to capital savings that come from lowering
Series 44 12 1600 0.549 18.4 18.1 550 34 5.4 0.97
primary/secondary systems. In design. Switching to series chillers sets the design flow rate.
addition, they are less susceptible to the stage for larger chilled water
Series 42 14 1371 0.588 18.8 18.4 475 35 5.4 0.96
low delta T syndrome. temperature ranges while minimizing
Series 42 16 1200 0.581 19.7 19.2 400 33 5.4 0.91
Series 42 18 1067 0.576 15.9 15.5 400 37 5.4 0.88 S Y S T E M S O L U T I O N S
Series 40 20 920 0.641 22 21.3 300 33 5.2 0.84

Series Variable Primary


W
hen it comes to
Table 3 shows the design performance range and 42°F supply water the only goal, then the valves can be optimizing chiller plants,
from a 10°F to 20°F range for a two
pass series variable primary flow plant.
temperature allows the supply piping
to be 8 inch (versus 10 inch), which
manual. If the valves are automated
and only one chiller is operating,
the best option is to
consider variable flow. ASHRAE
Flow Design
For each design, the water pressure results in significant savings with less then the other chiller can be
The data and suggestions in this document are believed current and accurate at the time of publication, but they are not a substitute for trained, experienced Standard 90.1 requires variable flow
drop was held approximately than a 2% increase in operating cost. automatically bypassed for additional professional service. Individual applications and site variations can significantly affect the results and effectiveness of any information, the reader must satisfy While they have traditionally been the loop pressure differential which
constant. As the chilled water In addition, the chillers are 12% less pressure reduction and pump him/herself regarding the applicability of any article and seek professional evaluation of all materials. McQuay disclaims any responsibility for actions based in systems over 10 hp, and most of used for special projects and difficult adjusts the secondary pump variable
temperature was lowered, the chiller expensive while still offering excellent savings. It needs to be determined on this document. these plants are designed using retrofit applications, variable primary frequency drives (VFD). Any extra
performance decreased. However, the performance. Series chillers are one whether the pump savings will pay primary/secondary systems. However, flow systems are increasingly entering primary flow not required by the
For comments or suggestions, please call or write:
decrease in flow requires smaller of the best ways to optimize chiller for the automatic valves. Chris Sackrison, Editor this proven design is not without its the mainstream as a system for building passes through the decoupler
chilled water pumps and piping. selections. Add a VFD chiller McQuay International
schools, office buildings and process and is returned to the chiller. This
13600 Industrial Park Boulevard challenges – particularly with low
Reviewing the chiller pricing ratio, we Other Considerations Adding a VFD chiller to a series Minneapolis, MN 55441 applications. The system offers flow through the decoupler represents
Phone: (763) 553-5419 delta T issues.
see a large pricing improvement for Series Counterflow arrangement offers additional E-mail: chris.sackrison@mcquay.com designers several benefits and a few “wasted” flow because it delivers no
the same performance and water Switching to series counterflow may savings. First, it can be the lead For more information on McQuay products and services, or to speak with your local representative, call (800) 432-1342, or visit our web page at www.mcquay.com.
©2004 McQuay International Variable primary flow is quickly challenges. value to the building occupants.
pressure drop. This occurs because add even more savings. Series chiller when only one chiller is becoming an alternative to Background What the decoupler flow does provide
the lower flow for the same pressure counterflow improves annual chiller required. During these lighter loads, Figure 1 shows a conventional is constant flow through the chiller
primary/secondary systems. This
drop results in less copper tubing – performance by about 5%. However, there is likely to be condenser water primary/secondary chiller design. The evaporators. Until recently, this
the most expensive component in a the condenser water must be pumped relief that the VFD chiller can article discusses a specific application
flow through each chiller is constant constant flow was considered essential
chiller. This can be added to the other at design flow even if only one chiller benefit from. When both chillers are of variable primary flow with series for reliable chiller operation. However,
and set by the constant flow of a
capital savings (listed previously) that is operating. The increased condenser required, the VFD chiller can be the chillers. Series chillers can help primary pump. The flow in the research has shown that varying flow
result from increasing the chilled pump work may offset the chiller upstream chiller. Assuming the resolve some of the design and building, or the secondary loop, is through the chiller is possible as long
water temperature range. savings. For short condenser loops, chillers are identical and selected to operational issues associated with variable and is typically controlled by as the minimum flow is maintained.1
Table 4 shows the annual operating series counterflow may make sense. do the more difficult lead chiller variable primary flow. Series chillers
cost as the range is increased from Chiller bypass line duty, the VFD can slow the Figure 1 – Conventional Primary/Secondary System
upstream chiller down to the are also a great idea when large
10°F to 20°F. In this example, the In most cases, a chiller bypass line is
appropriate tip speed for the lower chilled water temperature ranges
best operating performance occurs at a good idea because it will allow
a 12°F range and 44°F supply water chiller servicing without shutting lift duty. This will optimize the make sense. Decoupler

temperature. However, the 18°F down the entire plant. If service is chiller for the upstream duty.
J.C. Kuttruff, our Global Account
(continued on back page)
Manager, provided technical expertise
Table 4 – Annual Operating Performance For Two Pass Series Variable Primary Flow Chiller Plants At Different in variable primary flow design for
Primary Pump
Chilled Water Temperature Ranges. this newsletter. For more information
Run SWT Range Min Flow Chiller PD Chiller Pumps Tower Fan S.A. Fan Total on variable primary flow systems,
(°F) (°F) (GPM) (ft) ($/yr) ($/yr) ($/yr) ($/yr) ($/yr) contact your local McQuay
Series 44 10 575 37.8 $ 82,584 $ 24,198 $ 6,907 $ 73,051 $ 186,740 Representative or visit
2 pass
Series 44 12 550 36.5 $ 82,104 $ 23,007 $ 6,904 $ 73,025 $ 185,040
www.mcquay.com.
2 pass Hugh Crowther
Series 42 14 475 37.2 $ 88,322 $ 22,296 $ 6,909 $ 73,078 $ 190,605
Director of Applications Secondary Pump with VFD
2 pass
Series 42 16 400 38.9 $ 87,247 $ 21,790 $ 6,907 $ 73,058 $ 189,002 McQuay International
1Redden, George. Effect of Variable Flow on Chiller Performance. ASHRAE Transaction SA- 96-12-3. 1996,
2 pass
Series 42 18 400 31.4 $ 86,470 $ 21,016 $ 6,905 $ 73,036 $ 187,427 ASHRAE, Atlanta, Ga.
2 pass
Series 40 20 300 43.3 $ 96,360 $ 20,799 $ 6,915 $ 73,136 $ 197,210
2 pass
Table 3 - Design Performance Of A Two Pass Series Variable Primary Flow Plant At Different Chilled Water
Temperature Ranges.
Design SWT Range Design Perfor- CH-1 PD CH-2 PD Min Min Min Chiller Conclusion Series chillers in a variable primary flow the impact on chiller performance. This Edition No. 19 January 2004
Flow mance Flow Turndown Flow PD Price
Variable primary flow systems are system resolve the issue of transient can actually lower the cost of the

ENGINEERING
Ratio
(°F) (°F) (GPM) (kW/ton) (ft) (ft) (GPM) (%) (ft) coming of age. They cost less to build flow when a second chiller starts, chillers, in addition to all the other
Series 44 10 1920 0.547 19.1 18.7 575 30 5.4 1.00
and operate than traditional making the system even easier to capital savings that come from lowering
Series 44 12 1600 0.549 18.4 18.1 550 34 5.4 0.97
primary/secondary systems. In design. Switching to series chillers sets the design flow rate.
addition, they are less susceptible to the stage for larger chilled water
Series 42 14 1371 0.588 18.8 18.4 475 35 5.4 0.96
low delta T syndrome. temperature ranges while minimizing
Series 42 16 1200 0.581 19.7 19.2 400 33 5.4 0.91
Series 42 18 1067 0.576 15.9 15.5 400 37 5.4 0.88 S Y S T E M S O L U T I O N S
Series 40 20 920 0.641 22 21.3 300 33 5.2 0.84

Series Variable Primary


W
hen it comes to
Table 3 shows the design performance range and 42°F supply water the only goal, then the valves can be optimizing chiller plants,
from a 10°F to 20°F range for a two
pass series variable primary flow plant.
temperature allows the supply piping
to be 8 inch (versus 10 inch), which
manual. If the valves are automated
and only one chiller is operating,
the best option is to
consider variable flow. ASHRAE
Flow Design
For each design, the water pressure results in significant savings with less then the other chiller can be
The data and suggestions in this document are believed current and accurate at the time of publication, but they are not a substitute for trained, experienced Standard 90.1 requires variable flow
drop was held approximately than a 2% increase in operating cost. automatically bypassed for additional professional service. Individual applications and site variations can significantly affect the results and effectiveness of any information, the reader must satisfy While they have traditionally been the loop pressure differential which
constant. As the chilled water In addition, the chillers are 12% less pressure reduction and pump him/herself regarding the applicability of any article and seek professional evaluation of all materials. McQuay disclaims any responsibility for actions based in systems over 10 hp, and most of used for special projects and difficult adjusts the secondary pump variable
temperature was lowered, the chiller expensive while still offering excellent savings. It needs to be determined on this document. these plants are designed using retrofit applications, variable primary frequency drives (VFD). Any extra
performance decreased. However, the performance. Series chillers are one whether the pump savings will pay primary/secondary systems. However, flow systems are increasingly entering primary flow not required by the
For comments or suggestions, please call or write:
decrease in flow requires smaller of the best ways to optimize chiller for the automatic valves. Chris Sackrison, Editor this proven design is not without its the mainstream as a system for building passes through the decoupler
chilled water pumps and piping. selections. Add a VFD chiller McQuay International
schools, office buildings and process and is returned to the chiller. This
13600 Industrial Park Boulevard challenges – particularly with low
Reviewing the chiller pricing ratio, we Other Considerations Adding a VFD chiller to a series Minneapolis, MN 55441 applications. The system offers flow through the decoupler represents
Phone: (763) 553-5419 delta T issues.
see a large pricing improvement for Series Counterflow arrangement offers additional E-mail: chris.sackrison@mcquay.com designers several benefits and a few “wasted” flow because it delivers no
the same performance and water Switching to series counterflow may savings. First, it can be the lead For more information on McQuay products and services, or to speak with your local representative, call (800) 432-1342, or visit our web page at www.mcquay.com.
©2004 McQuay International Variable primary flow is quickly challenges. value to the building occupants.
pressure drop. This occurs because add even more savings. Series chiller when only one chiller is becoming an alternative to Background What the decoupler flow does provide
the lower flow for the same pressure counterflow improves annual chiller required. During these lighter loads, Figure 1 shows a conventional is constant flow through the chiller
primary/secondary systems. This
drop results in less copper tubing – performance by about 5%. However, there is likely to be condenser water primary/secondary chiller design. The evaporators. Until recently, this
the most expensive component in a the condenser water must be pumped relief that the VFD chiller can article discusses a specific application
flow through each chiller is constant constant flow was considered essential
chiller. This can be added to the other at design flow even if only one chiller benefit from. When both chillers are of variable primary flow with series for reliable chiller operation. However,
and set by the constant flow of a
capital savings (listed previously) that is operating. The increased condenser required, the VFD chiller can be the chillers. Series chillers can help primary pump. The flow in the research has shown that varying flow
result from increasing the chilled pump work may offset the chiller upstream chiller. Assuming the resolve some of the design and building, or the secondary loop, is through the chiller is possible as long
water temperature range. savings. For short condenser loops, chillers are identical and selected to operational issues associated with variable and is typically controlled by as the minimum flow is maintained.1
Table 4 shows the annual operating series counterflow may make sense. do the more difficult lead chiller variable primary flow. Series chillers
cost as the range is increased from Chiller bypass line duty, the VFD can slow the Figure 1 – Conventional Primary/Secondary System
upstream chiller down to the are also a great idea when large
10°F to 20°F. In this example, the In most cases, a chiller bypass line is
appropriate tip speed for the lower chilled water temperature ranges
best operating performance occurs at a good idea because it will allow
a 12°F range and 44°F supply water chiller servicing without shutting lift duty. This will optimize the make sense. Decoupler

temperature. However, the 18°F down the entire plant. If service is chiller for the upstream duty.
J.C. Kuttruff, our Global Account
(continued on back page)
Manager, provided technical expertise
Table 4 – Annual Operating Performance For Two Pass Series Variable Primary Flow Chiller Plants At Different in variable primary flow design for
Primary Pump
Chilled Water Temperature Ranges. this newsletter. For more information
Run SWT Range Min Flow Chiller PD Chiller Pumps Tower Fan S.A. Fan Total on variable primary flow systems,
(°F) (°F) (GPM) (ft) ($/yr) ($/yr) ($/yr) ($/yr) ($/yr) contact your local McQuay
Series 44 10 575 37.8 $ 82,584 $ 24,198 $ 6,907 $ 73,051 $ 186,740 Representative or visit
2 pass
Series 44 12 550 36.5 $ 82,104 $ 23,007 $ 6,904 $ 73,025 $ 185,040
www.mcquay.com.
2 pass Hugh Crowther
Series 42 14 475 37.2 $ 88,322 $ 22,296 $ 6,909 $ 73,078 $ 190,605
Director of Applications Secondary Pump with VFD
2 pass
Series 42 16 400 38.9 $ 87,247 $ 21,790 $ 6,907 $ 73,058 $ 189,002 McQuay International
1Redden, George. Effect of Variable Flow on Chiller Performance. ASHRAE Transaction SA- 96-12-3. 1996,
2 pass
Series 42 18 400 31.4 $ 86,470 $ 21,016 $ 6,905 $ 73,036 $ 187,427 ASHRAE, Atlanta, Ga.