TEST REPORT FOR

SIEMENS DIFFERENTIAL PROTECTION


TS TRANSCO
RELAY

PROJECT : 132/33 KV SS AREA : CONTROL ROOM


CLIENT : M/S TS TRANSCO
PANEL NO. : TRAFO RELAY PANEL - 2TRP DATE : 19/05/2016

Location : CONTROL ROOM


Feeder Name : 132/33 KV TRAFO PANEL

Make SIEMENS

Type / Model no 7SR242

Sr. No. GF1509500296

Aux Supply 220 V DC


System Parameters:

HV Primary Current 200 A

HV Secondary Current 1A

LV Primary Current 800 A

LV Secondary Current 1A

General Inspection : OK

Measurements:

PHASE INJECTED MEASURED VALUES


VALUES
PRIMARY VALUES SECONDARY VALUES

HV R Ph 1A 199 A 0.996 A

HV Y Ph 1A 199 A 0.996 A

HV B Ph 1A 199 A 0.997A

LV R Ph 1A 797A 0.997 A

Tested by Witnessed by : TS TRANSCO

Name : Mr. B.SANTHOSH Name : Mr. B.RADHAKISHAN


Designation :Relay engineer Designation: AE
Signature & Signature &
Date Date
TEST REPORT FOR
SIEMENS DIFFERENTIAL PROTECTION
TS TRANSCO
RELAY

PROJECT : 132/33 KV SS AREA : CONTROL ROOM


CLIENT : M/S TS TRANSCO
PANEL NO. : TRAFO RELAY PANEL - 2TRP DATE : 19/05/2016

LV Y Ph 1A 798 A 0.998 A

LV B Ph 1A 797 A 0.998 A

Differential Protection:
Description Setting
Diff : Enable Yes
DIFF: Vec.gr. Ydy0
DIFF: Initial set I diff> 0.25xIn
DIFF: slope 1 0.2 x
DIFF: slope1Limit 5
DIFF: slope2 1.0 x

HV Side Differential Current Pick Up:


Injected Current
Phase Pickup Current (Amps) Relay Operation Trip time (m Sec)
(Amps)
R 0.2840° 0.2860° Trip 62.5
Y 0.284-120° 0.286-120° Trip 64.5
B 0.284120° 0.287120° Trip 76.0
R-Y-B 0.1890° 0.194 0° Trip 71.50

LV Side Differential Current Pick Up:


Injected Current
Phase Pickup Current (Amps) Relay Operation Trip time (m Sec)
(Amps)
R 0.258180° 0.260180° Trip 175.0
Y 0.25860° 0.26260° Trip 88.30
B 0.258300° 0.261300° Trip 142.1
R-Y-B 0.1720° 0.176180° Trip 73.10

Tested by Witnessed by : TS TRANSCO

Name : Mr. B.SANTHOSH Name : Mr. B.RADHAKISHAN


Designation :Relay engineer Designation: AE
Signature & Signature &
Date Date
TEST REPORT FOR
SIEMENS DIFFERENTIAL PROTECTION
TS TRANSCO
RELAY

PROJECT : 132/33 KV SS AREA : CONTROL ROOM


CLIENT : M/S TS TRANSCO
PANEL NO. : TRAFO RELAY PANEL - 2TRP DATE : 19/05/2016

High set HV Side Differential Current Pick Up


Injected Current
Phase Pickup Current (Amps) Relay Operation Trip time (m Sec)
(Amps)
R-Y-B 8.57 8.7 Trip 33.90
@LV side 1A injected

High set LV Side Differential Current Pick Up


Injected Current
Phase Pickup Current (Amps) Relay Operation Trip time (m Sec)
(Amps)
R-Y-B 7.89 8.1 Trip 39.3
@LV side 1A injected

Stability Test

Phase Injected Current(A)-HV Side Injected Current(A)-LV Side Relay Condition

R 10° 1180°

Y 1-120° 160° No Trip

B 1120° 1300°

Unstability Test

Phase Injected Current(A)-HV Side Injected Current(A)-LV Side Relay Condition

R 10° 10°

Y 1-120° 1-120° Trip

B 1120° 1120°

Slope Test:
Tested by Witnessed by : TS TRANSCO

Name : Mr. B.SANTHOSH Name : Mr. B.RADHAKISHAN


Designation :Relay engineer Designation: AE
Signature & Signature &
Date Date
TEST REPORT FOR
SIEMENS DIFFERENTIAL PROTECTION
TS TRANSCO
RELAY

PROJECT : 132/33 KV SS AREA : CONTROL ROOM


CLIENT : M/S TS TRANSCO
PANEL NO. : TRAFO RELAY PANEL - 2TRP DATE : 19/05/2016

Slope-1 Percentage Check:


Injected Injected Restraint
Fault Differential % of Slope =
Phase Current(A)-HV Current (A)- Current,
Points Current, Id(A) (Id1)/(Ir1))*100
Side LV Side Ir(A)

R 10° 0.738180° 0.249 1.190


(0.249/1.190)*100
Y Point-1 1-120° 0.73860° 0.249 1.190
=20%
B 1120° 0.738300° 0.249 1.190

Slope Test:
Slope-2 Percentage Check:

Injected Injected Restraint % of Slope =


Fault Differential
Phase Current(A)-HV Current (A)- Current, ((Id2-Id1)/(Ir2-
Points Current, Id(A)
Side LV Side Ir(A) Ir1))*100

R 50° 8.15180° 5.195 9.183

Y Point-1 5-120° 8.1560° 5.195 9.183

B 5.195 9.183 ((1.743-5.195)/


5120° 8.15300°
((5.712-
R 50° 3.35180° 1.743 5.712 9.183))*100
=100%
Y Point-2 5-120° 3.3560° 1.743 5.712

B 5120° 3.35300° 1.743 5.712

Tested by Witnessed by : TS TRANSCO

Name : Mr. B.SANTHOSH Name : Mr. B.RADHAKISHAN


Designation :Relay engineer Designation: AE
Signature & Signature &
Date Date
TEST REPORT FOR
SIEMENS DIFFERENTIAL PROTECTION
TS TRANSCO
RELAY

PROJECT : 132/33 KV SS AREA : CONTROL ROOM


CLIENT : M/S TS TRANSCO
PANEL NO. : TRAFO RELAY PANEL - 2TRP DATE : 19/05/2016

Inrush 2nd Harmonics Block Check:


Injected Current Injected Current
Phase Test Result
( HV Side @ 50Hz) (HV Side @ 100 Hz)
R 10° 0.150°
Differential Trip Blocked till 15% of
Y 1-120° 0.15-120°
2nd harmonic Id
B 1120° 0.15120°

Tested by Witnessed by : TS TRANSCO

Name : Mr. B.SANTHOSH Name : Mr. B.RADHAKISHAN


Designation :Relay engineer Designation: AE
Signature & Signature &
Date Date