Download as pdf or txt
Download as pdf or txt
You are on page 1of 15

Energy 113 (2016) 521e535

Contents lists available at ScienceDirect

Energy
journal homepage: www.elsevier.com/locate/energy

Parametric study of solar heating and cooling systems in different


climates of Algeria e A comparison between conventional and
high-energy-performance buildings
S. Bahria a, b, *, M. Amirat a, A. Hamidat b, M. El Ganaoui c, M. Slimani a
a
Laboratoire de Mecanique des Fluides Th
eorique et Appliqu
ee, Facult
e de Physique, Universit
e des Sciences et de la Technologie Houari Boumediene, BP 32
El Alia, Bab-Ezzouar, Algiers, Algeria
b
Centre de Developpement des Energies Renouvelables, CDER, 16340 Algiers, Algeria
c
University of Lorraine, LERMAB, EA 4370, IUT de Longwy, 54400 Cosnes et Romain, France

a r t i c l e i n f o a b s t r a c t

Article history: Parametric optimization using dynamic simulation of a solar thermal system for producing hot water,
Received 29 December 2015 space heating and cooling was developed. The system layouts include a single-effect absorption chiller
Received in revised form activated by heat generated by flat plate solar collectors and stored in a solar storage tank. Two con-
7 June 2016
struction types were compared; the first is the typical construction in Algeria (low thermal mass with U-
Accepted 5 July 2016
values of 1.25 W/m2K, single glazing), which represents the majority in the country, while the second is a
High-Energy-Performance building (with U-values of 0.35 W/m2K, double glazing), representing the
pilot project called ECO-BAT. Three of Algeria's regions were considered to evaluate the climatic effect of
Keywords:
Solar heating and cooling systems
solar systems integration. Algiers represents the coastal region; Djelfa, the highlands region; Tam-
High-energy-performance building anrasset, the Sahara region. In parametric study, two solar collectors' field parameters were analysed,
Dynamic simulation including the surface area and the tilt angle. The results indicated that building loads are significantly
Solar fraction reduced (12%, 44% and 22% for Algiers, Djelfa and Tamanrasset, respectively). The solar energy contri-
Parametric study bution is more than 60% for all cases, a significant contribution for an efficient building. In all cases, we
observed that the solar fraction reaches more than 45% when the optimum parameters of the solar
system are selected.
© 2016 Elsevier Ltd. All rights reserved.

1. Introduction residential buildings, a new program (called ECO-BAT) has been


adopted, aiming to yield 600 apartments that comply with the high
A solar heating and cooling (SHC) system simultaneously pro- energy performance standard. The buildings of this pilot program
duces thermal energy for heating during the winter season, cooling are distributed over different climatic zones in the country of
during the summer season and domestic hot water all year long. In Algeria. Another pilot project attempts to realize and develop solar
the recent few years, many institutions and research have focused cooling systems based on adsorption and absorption process and
on the SHC system [1e5] to promote their diffusion and reduce examines what fits are the best, in the Algerian context, with
their capital cost for residential and small commercial building respect to allowing for the reduction of fossil fuel consumption
applications. (electric and gas) and harmful emissions to the environment (CO2).
In Algeria, the building sector is the biggest energy consumer, A part of the present study provides some first evaluations of these
accounting for more than 41% of the overall energy consumption; two pilot projects.
this value has steadily increased in recent years (10.8% between In the literature, several researchers have focused on the design
2012 and 2013) [6,7]. To optimize energy consumption related to and development of solar thermal systems [8e13], while an SHC
system is rarely considered. Because the high cooling loads and
solar gains occur in the same months, the application of solar en-
* Corresponding author. Laboratoire de Me canique des Fluides The orique et ergy for air conditioning is a logical option [14]. In particular,
e, Faculte
Applique  de Physique, Universite
 des Sciences et de la Technologie Houari Gianpiero et [15] presented a thermal analysis of a new photo-
Boumediene, BP 32 El Alia 16111, Bab-Ezzouar, Algiers, Algeria. voltaicethermal (PVeT) solar panel design; also, combinations of
E-mail address: sof.bahria@gmail.com (S. Bahria).

http://dx.doi.org/10.1016/j.energy.2016.07.022
0360-5442/© 2016 Elsevier Ltd. All rights reserved.
522 S. Bahria et al. / Energy 113 (2016) 521e535

different water flow rates and different panel configurations were


analysed to determine which one has the best performance in
terms of optimal PV efficiency and available thermal energy. In
another study [16], they tested experimentally a new type of
nanofluid thermal solar collector; the experimental results showed
an increase of thermal efficiency up to 11.7% [17,18] reviewed
several solar collectors and thermal energy storage systems,
including both non-concentrating collectors and concentrating
collectors. The integrated collector storage solar water heaters were
designed, constructed and experimentally studied by Souliotis et al.
[19]. Colangelo et al. [20] conducted an overview of the innovations
introduced with respect to the flat solar thermal collectors, taking
into account new materials, geometries and heat transfer fluids.
Colangelo et al. [21] experimentally analysed a new solution for a
reduced sedimentation flat panel solar thermal collector using
nanofluids as innovative heat transfer fluids for solar energy ap-
plications. In Ref. [22], recent advances in the design aspects of
solar water heating systems in terms of both energy efficiency and
cost effectiveness were presented.
The few studies of SHC systems in the literature differ with re- Fig. 1. Daily consumption profile of DHW.
gard to the type of procedure. Some studies included a parametric
study and cost analysis to determine the least cost systems [23,24], morning profile that represents high DHW consumption in the
while others were based on the development of mathematical morning is selected as the input of our model. In Fig. 1, the hourly
models [25]. More recent works used transient modelling [4,26,27]; coefficients of the DHW consumption rate, which are summed over
most of these studies analysed only the case of European building 24 h, must be equal to 24 [32].
types in their climates. In particular, some significant works were The software has an integrated building model, which allows for
presented by Calise et al., who conducted dynamic simulation the heating and cooling load calculation by introducing the build-
studies for different plant layouts of SHC systems, driven by ing type parameters. The calculation is achieved by taking into
different types of solar collectors (evacuated, PVeT and concen- account the weather data established for each region, studied by
trating PVeT solar collectors) [4,14,28]. Buonomano et al. investi- using the METEONORM software (TM2 file type).
gated a novel transient simulation model [29]; in another study, The main model properties used in TRANSOL are [32]:
they presented different control strategies for thermal storage
management in an SHC system [30].  One zone building model (the building is simulated as one
In this study, a parametric optimization of the SHC system by thermal zone),
using dynamic simulation is developed and two construction types  Restricted walls' and windows' database (the roof and the floor
are compared to evaluate the solar fraction of heating and cooling are chosen automatically according to the wall types),
loads. The first construction (U ¼ 1.25 W/m2K, single glazing) does  Fixed shading devices inclusion: This step allows for defining
not comply with energy regulations and reflects the majority of fixed shading elements (overhangs and wing walls) for each of
buildings in Algeria due to lower prices and faster delivery time. the four main orientations of the building [35],
The second, a High-Energy-Performance (HEP) building  Internal gains computation,
(U ¼ 0.35 W/m2K, double glazing), represents the building adopted  Automatic control of the gains due to artificial lighting systems:
by the ECO-BAT pilot-project [31], which has the same size and A simple lighting control strategy based on the total horizontal
orientation. solar radiation is automatically defined (the lighting turns on
Furthermore, this paper also includes a sensitivity analysis, when the total horizontal solar radiation is under 120 W/m2 and
performed to evaluate the climatic effect on the potential integra- turns off when it is above 200 W/m2),
tion of SHC systems. Three of Algeria's regions are considered.  Occupation rate and control profiles (heating, illumination, etc.),
Algiers represents the coastal region; Djelfa, the highlands region; fixed for residential use.
Tamanrasset, the Sahara region.
In the parametric study, two solar collectors' field parameters
are analysed, including the surface area and the tilt angle. In this 2.1. Systems description
study, the TRANSOL software, based on dynamic simulation, is
used. This tool allows for sizing thermal solar systems using the This system is simulated using a scheme for DHW, i.e., heating
transient simulation tool TRNSYS power [32]. and cooling (SHC601) from the TRANSOL PRO 3.2 program [33], as
shown in Fig. 2. The system comprises a solar collector field and
2. Methodology solar and auxiliary tanks.
The solar collector field exchanges energy with the solar storage
To simulate the SHC system, the dynamic simulation software through an external heat exchanger. The solar and auxiliary stor-
TRANSOL has been used. This tool is based on dynamic simulation ages are connected by an immersed heat exchanger at the bottom
(calculation with 1-h time steps is adopted) and has been devel- of the auxiliary tank. The auxiliary storage is also heated by a hy-
oped with the TRNSYS simulation tool [33], which is a well-known draulic auxiliary heater, which warms up through an immersed
software diffusely adopted for both commercial and academic exchange in the top of the auxiliary tank. In the distribution loop, a
purposes. The software includes a large library of built-in compo- recirculation flow can be defined to obtain the DHW consumption
nents, often validated by experimental data [34]. temperature.
The domestic hot water (DHW) loads are introduced, with the The thermally driven chiller is directly connected to the solar
choice of a daily consumption profile (see Fig. 1) [33]. In all cases, a storage and switches on when a cooling demand exists and the
S. Bahria et al. / Energy 113 (2016) 521e535 523

Fig. 2. A solar thermal system for DHW production, space heating and cooling [32].

temperature in the solar tank is above the set point temperature. Table 1
The flow rate through the generator is constant; thus, the outlet Main system input parameters.

fluid is mixed at the inlet to adjust the power of the device. The Parameter description Value
tower return is always kept above a user defined temperature Solar collectors
thanks to a mixing valve with the inlet flow. Optical efficiency a0 76%
The cooling distribution loop is always simulated as a variable Loss coefficient a1 4.003 W/m2K
flow loop, with constant inlet and return temperatures. The space Loss coefficient a2 0.0150 W/m2K2
Unitary area 2 m2
heating loop can be powered by solar energy from the bottom of the
Thermal chiller
tank, and if this does not have sufficient energy, directly from the Nominal cooling power 10 kW
boiler. The auxiliary system works if the tank temperature is lower Nominal COP 0.6
than the set point temperature or if there is a space heating demand Electric power of auxiliaries 216 W
and the temperature in the solar tank is not high enough [29]. Electric chiller
Nominal cooling power 7.5 kW
Nominal COP 3
2.1.1. Solar collectors Set point temperature 7 C
In the present work, flat plate solar collectors (FPCs) are used. Cooling tower
These are widely used all over the world due to their low-cost, easy Air flow rate 12530 m3/h
Mass transfer constant 2.3
installation and cheap maintenance [20]; the different character-
Mass transfer exponent 0.72
istics of FPC are shown in Table 1. Fan electric consumption 0.63 kW
The collector area is calculated according to the following for- Fan minimum capacity 30%
mula [36]:

Pcooling 1
Ac ¼ (1) performance can be obtained [30,37]. The recommended ratio be-
COPcooling:nom hcol;nom tween storage tank volume (V) and collector field area (Ac) is given
in Ref. [37], as follows:
where Pcooling is the nominal cooling capacity (kW) of the cooling
system, COPcooling, nom is the nominal COP (performance coefficient) 0:05m  V=Ac  0:18m (2)
of the cooling system, and hcol, nom is the nominal efficiency of the
2
solar collector at the demanded temperature for driving the cooling According to [36,38], the store volume is at least 50 L per m of
system. collector surface for the central European climate. In this study, a
Considering a 10 kW nominal cooling capacity and using volume of 75 L per m2 of the collector surface is considered.
equation (1), the required collector area is approximately 20 m2 of Therefore, as mentioned above, if the total collector area is 20 m2,
the glazed flat-plate collector. then a solar storage tank of 1500 L is selected for all simulated cases.

2.1.2. Solar storage tank 2.1.3. Auxiliary storage systems


Several parametric studies of SHC systems have shown that by The total amount of water stored at 60  C in the auxiliary storage
varying the tank volume, a minor improvement of the system should be at least equal to the maximum demand at this
524 S. Bahria et al. / Energy 113 (2016) 521e535

temperature on the day with the most demand and assuming the construction types are considered.
inexistence of the solar system [32,38]. In the present work, a
storage of 200 L is selected, considering that water at 60  C is mixed 2.3. Description of the compared regions
with water at 25  C for a DHW demand of 215 L/day at 45  C.
The characteristic regions considered in the present work are
2.1.4. Thermal chiller and cooling tower Algiers (ALG), Djelfa (DJE) and Tamanrasset (TAM); the weather
The maximum cooling loads of the HEP and ordinary building data are described below:
are not constant during the entire year, only during the summer
season. To cover all the cooling loads in all case studies, an ab- - Algiers (36.8 N, 3.1 E, 25 m) is in the coastal region, in the
sorption cooling machine of 10 kW is selected, with an electric temperate zone. It enjoys a mild, Mediterranean climate (Csa
backup system of 7.5 kW. The cooling tower allows for evacuating Ko€ ppen climate classification) [42], with warm, dry summers
the heat extracted by the thermal chiller and is connected to the and mild, rainy winters. The monthly average temperatures in
condenser and the absorber by circulating cooling water. The pa- summer vary between 21  C and 25  C, and in winter, drop to
rameters are presented in the following table (Table 1). approximately 11  Ce15  C; see Fig. 7. The winter is not cold,
with rare snow, but the humidity is high, with an annual hu-
2.1.5. Cold water temperature midity average of 66.5% [43]. Algiers receives approximately
The cold water (network) temperature depends on the location 2756 h of sunshine and 546 mm of precipitation per year [44].
where the simulation is performed. A sinusoidal profile is gener- - Djelfa (34.7 N, 3.3 E, 1180 m) represents a highland region. The
ated from the minimum and maximum temperatures. Hence, the climate is transitional between the Mediterranean climate and
temperature was calculated using equation (3) [39]; the results are desert climate (between BSk, BWk and BWh Ko €ppen climate
presented in Fig. 3. classifications) [42]. The temperatures are higher during sum-
  mer, with lower air humidity (48.1%) [43]. Djelfa is significantly
Tmax  Tmin n2 colder than the other parts of the country due to its 1180-m
Ts ¼ ðTmax þ Tmin Þ=2  h cos 2p (3)
2 12 altitude above sea level. The region's weather is characterized
by daily and annual extreme temperatures, hot summers and
where cold winters, and insufficient precipitation. Annual precipitation
varies from 100 to 400 mm. On average, Djelfa enjoys 3029 h of
Tmin is the minimum temperature, sunshine per year [42,43].
Tmax is the maximum temperature - Tamanrasset (22.8 N, 5.4 E, 1362 m) represents the southern
n is the number of month desert region (Sahara). It is characterized by an arid climate
h is equal to 1 in the Northern Hemisphere and (1) in the (BWh Ko €ppen climate classification) [42], with extremely low
Southern Hemisphere. annual rainfall of less than 70 mm per year. The winter is very
mild and the summer is hot. The monthly average temperature
2.2. The building description increases from May to September, ranging from 25  C to 30  C;
see Fig. 7. Midday desert temperatures can be very hot. After
The selected reference is a one floor building, defined in the sunset, however, the clear, dry air permits rapid loss of heat and
ECO-BAT pilot program (HEP building); see Fig. 4. The floor area, the nights are cool to chilly. Enormous daily ranges in temper-
including walls and access facilities, is 75 m2. ature are recorded (a daily range of 56  C has been recorded; this
This building is oriented along the north axis. Because the sun is value is generally accepted as the greatest daily range of tem-
lower in the sky in winter than in summer, the building captures perature to have been recorded on Earth) [45].
free heat in winter and rejects the heat in summer. Its dimensions
are shown in Fig. 5 [40]. Fig. 6 shows the geographical location of Algiers, Djelfa and
The construction properties shown in Table 2 were selected Tamanrasset. The climatic data generated by Meteonorm Software
according to [33,41]. Note that the roof and the floor are chosen 7.0 are presented in Fig. 7; the climatic conditions in the three re-
automatically, according to the wall types, from the available gions studied are shown in Table 3. The climate zones are given
TRANSOL program options. For each region, two different according to the Algerian technical regulations for building con-
struction [45].

3. Results and discussion

3.1. Validation

To confirm the simulation model in this study, we compare two


SHC systems with the same initial conditions for reference and a
simulation case. For this, we use the monitoring results of the SHC
system installed in Graz (Austria) presented in IEA Task 38 [2]. The
system employs a closed absorption cycle for generating cooling
energy. The cold water generated by the absorption machine is
used to cover internal and external heat gains. In winter, the solar
collectors are assisted by the conventional space heating. In sum-
mer and in winter, the solar generated heat is stored in one buffer
storage and all energy demand is taken out of it [2]. Table 4 sum-
marizes the description of the installation.
The values of output are given for both the reference and
Fig. 3. Average monthly cold water temperature. simulation system in Fig. 8. The results show that the cooling needs
S. Bahria et al. / Energy 113 (2016) 521e535 525

Fig. 4. Building face considered and adopted in the ECO-BAT pilot-project [40].

Fig. 5. The plan of a typical house considered [40].

can be covered by the solar energy resources between April to deviation of total heating production (7%) is most notable. It is also
September, while the heating needs are not totally covered due to noted that the deviation of the solar field production is approxi-
the inverse relationship between the solar gain and heating loads in mately 6.6% (333 kWh/m2 in the experiment and 311 kWh/m2 in
winter seasons. The comparison shows that the mean deviation simulation). Therefore, it can be assumed that the SHC system
between the cooling production values is approximately 3%, but the model is simulated with an acceptable degree of accuracy and the
526 S. Bahria et al. / Energy 113 (2016) 521e535

Table 2
Parameters used for the reference building.

Case A (ordinary building) Case B (HEP building)

Walls Cement mortar 2 cm, Hollow brick 10 cm, Cement mortar 2 cm, Hollow brick 10 cm, Exp. Polystyrene 9 cm,
air cavity 10 cm, Hollow brick 10 cm, plaster 2 cm. Hollow brick 10 cm, plaster 2 cm.
U (W/m2K) 1.25 0.35
The type of window Clear, single Clear, double, with 8 mm air gap
U (W/m2K) 1.25 0.35

Common characteristics

Floors number 1
Windows (%) South 19, north 20, west 0 and east 0
Infiltration) 1/h ( 0.8
Specific gains (W/m2) 15
Occupation rate (m2) 0.06
Specific lighting (W/m2) 10

simulation results are in good agreement with those of the the heating and cooling demands for the three regions studied
experiment. showed that the Djelfa region is the coldest because it is located in
the highlands (1180 m of altitude), with a maximum demand in
3.2. Analysis of the cooling and heating loads January of 28.82 kWh/m2 for case A and 9.9 kWh/m2 for case B
(Fig. 10).
Figs. 9e11 display the monthly cooling and heating loads of HEP As shown in Figs. 9 and 10, in the Algiers and Djelfa regions, the
and ordinary building types for the selected regions. The analysis of heating season lasts 8 months and the cooling period, 4 months.

Fig. 6. Geographical location of Algiers, Djelfa and Tamanrasset with global horizontal irradiation, Average annual sum, period 1994e2010 [46].
S. Bahria et al. / Energy 113 (2016) 521e535 527

Fig. 7. Global Horizontal irradiation and average ambient temperature in Algiers, Djelfa and Tamanrasset.

Table 3 Note that the heating loads of the HEP building (case B) have
Climatic conditions in the three studied regions [48,47,49]. decreased by approximately 58% in Algeria, 72% in Djelfa and 12% in
City Algiers Djelfa Tamanrasset Tamanrasset, with a maximum of 133 kWh/m2/year in the Djelfa
Coordinates  
36.8 N, 3.1 E  
34.7 N, 3.3 E 22.8 N, 5.4 E
region (case A), while the region of Tamanrasset presents a
Region Littoral Highlands Sahara maximum cooling load of 84 kWh/m2/year. We also note that for
Climate zone A D1 and C D1and D2 the same type of building, the DHW loads are constant and inde-
Tmax  C 26 29 30 pendent of the building type. This finding is observed because the
Tmin  C 10 5 13
calculation is only based on the network's cold water temperature
Altitude m 25 1180 1362
Humidity % 72 48 20 (Equation (2)). The comparison of two cases indicates the
Sunshine h 2920 3088 3402 decreasing of total loads by 12%, 44% and 22% for Algiers, Djelfa and
Tamanrasset, respectively. Increase of the cooling loads in case B
can be explained by the climatic conditions of the Sahara region;
Table 4 consequently, the high internal gains are produced by solar radia-
Main parameters of the SHC system. tion, metabolism, and heat dissipation of electrical appliances. In
Solar thermal description
this case, the thermal insulation itself becomes insignificant [50].
Collector type High temperature flat-plate
Brand of collector €
OkoTech Gluatmugl HT 3.3. Solar fraction analysis
Collector area 60 m2 gross area

Tilt angle, orientation 11 , south
Collector fluid Water-glycol Table 6 shows the solar fraction for cooling, heating and DHW
Typical operation temperature 88  C driving temperature for different cases. Generally, we note that the solar fraction is best
Heat storage 2 m3 waters in case B in the three regions. The maximum is achieved in the case
Cold storage 0.2 m3 waters of the Tamanrasset region when the heating requirement is low
Air-conditioning unit
Brand of chiller unit Yazaki WFC SC5
(Fig. 11); in this case, the DWH and heating loads are completely
Type of closed system Absorption covered by solar energy. We also note that for all regions studied,
Cooling capacity 17.5 kW the solar fraction of DHW loads is higher than 80% due to the
Nominal COP 0.7 average solar energy received (see Fig. 7). The solar fraction of DHW
Chilled water application Chilled ceilings
varies in the same region, while the loads remain constant, which is
Heat rejection system Hybrid cooling tower
due to the fact that the solar tank is placed inside the building.
The solar and auxiliary contribution to cooling, heating and
DHW for all case studies are given in Fig. 12. Note that the solar
The reverse is observed in Tamanrasset; see Fig. 11 (i.e., 8 months contribution of the DHW is approximately 4000 kWh for Algiers
for the cooling period and 4 months for the heating season). In this and Djelfa and 5000 kWh for Tamanrasset. Additionally, the
region, the maximum cooling loads reached 18.42 kWh/m2 for the auxiliary contribution of the DHW is between 700 and 1500 kWh
ordinary building and 15.38 kWh/m2 for the HEP building. for Algiers and Djelfa and almost zero for Tamanrasset. This is due
Table 5 summarize the annual loads for all cases; it shows that to the solar potential in this region.
heating loads in case A are significantly higher than those in case B; Fig. 12 also shows that the solar and auxiliary heating contri-
however, the cooling loads are not greatly changed due to the bution is proportional to the total heat loss coefficient U; the largest
ventilation rate being fixed all year at 0.8 per hour. Additionally, values are shown in the Djelfa region where the heating loads are
given that the loads depend on the internal gains (15 W/m2), the greater. However, the auxiliary contribution is very low in the
increase of level insulation makes it harder to reject heat in the Tamanrasset region; consequently, the heating loads are
summer. completely covered by solar energy. We note that the solar
528 S. Bahria et al. / Energy 113 (2016) 521e535

Fig. 8. Comparison of the system energy management over a one year measuring period.

Fig. 11. Monthly cooling and heating demands in Tamanrasset region.


Fig. 9. Monthly cooling and heating demands in Algiers.

Table 5
System total required demand analysis.

ALG DJE TAM

Cases Case A Case B Case A Case B Case A Case B


DHW (kWh/m2/year) 33 33 35 35 29 29
Heating (kWh/m2/year) 37 16 133 38 37 4
Cooling (kWh/m2/year) 28 38 44 46 84 83
Total (kWh/m2/year) 99 87 212 118 150 117

Table 6
Solar fraction for cooling, heating and DHW in different cases.

ALG DJE TAM

Cases Case A Case B Case A Case B Case A Case B


DHW (%) 82.0 91.2 80.9 91.3 98.4 100.0
Heating (%) 52.7 87.1 47.5 74.1 90.9 98.7
Cooling (%) 28.0 24.1 31.4 33.9 30.5 35.7

Fig. 10. Monthly cooling and heating demand in Djelfa region.

Table 7 shows the solar and auxiliary total contribution for


contribution for the cooling loads is very close to the same region, different building loads. It is generally noted that the solar contri-
with a maximum of 3157 kWh at Tamanrasset, while the auxiliary bution is more important than the auxiliary contribution. An or-
contribution is almost identical to that of Algiers, but for Djelfa and dinary building (case A) in the region of Algiers consumes 2 times
Tamanrasset, is proportional to the thermal loss. more auxiliary energy compared to the HEP building type (case B).
S. Bahria et al. / Energy 113 (2016) 521e535 529

can be made for all three regions. For the cooling period, the
building temperatures are identical to the cooling set point tem-
perature (26  C). This is due to the high loads of cooling in the
selected period; see Figs. 9e11.

3.4.2. The effect of collector area


In this part, the analysis was restricted to the HEP building types
only (U ¼ 0.35 W/m2K); the surface of the solar collector (Ac) and
the tilt angle (a) were varied within the limits defined by the study
objectives (8 m2 < Ac < 40 m2 and 0 < a < 90 ) to find the optimal
that maximizes the performances of the solar system. However, it is
very important to note that the optimization goals of a solar ther-
mal system aren't always necessary to collect the maximum energy
throughout the year [51]. However, the goal is to ensure the
maximum solar contribution while avoiding overheating to pre-
Fig. 12. Solar and auxiliary contribution for cooling, heating and DHW for all case
serve the solar system lifetimes as long as possible.
studies. The effect of the solar collector area on the monthly solar frac-
tion for DHW, heating and cooling loads is shown in Figs. 14e16,
respectively. The figures show proportionality between the
The comparison shows that the solar contribution in the Djelfa monthly solar fraction and the collector area (Ac). From April to
region is greater than 20% compared with Algiers (for both cases); October, a maximum of 100% of the DHW solar fraction is reached
it's the same for the Tamanrasset region, whereas the auxiliary when the surface is superior to 36 m2 at Algiers and Djelfa, but for
energy takes the highest value of 8357 kWh for case A at Djelfa (as a Tamanrasset, 100% of the DHW loads are covered for Ac more than
result of the large heating loads of 212 kW/m2/year), representing a 24 m2 all year. The figure also indicates that 50% of the DHW loads
37% and 47% increase compared to Algiers and Tamanrasset, are assured from 28 m2 in Algiers; from this last surface, the annual
respectively. solar fraction is approximately 84% (Fig. 14d).
We note that for a collector area of 36 m2, the monthly solar
3.4. Parametric study fraction of heating (SF-H) increases at a lower rate, i.e., approxi-
mately 68% and 85% for Algiers and Djelfa, respectively. An excep-
3.4.1. The effect of the building shell on the internal temperatures tion is noted in the region of Tamanrasset, when 100% of the space
The effect of the building shell on the internal temperatures for heating demand is covered for Ac more than 20 m2 all year. This is
two cases (with and without SHC systems) is presented in Fig. 13. due to the limitation of the system to store heat in the solar storage
The three studied regions are considered. The simulation is per- tank; the same was reported by Ref. [23]. We also note that the
formed during the whole year, but only the periods of high demand maximum solar fraction is reached in the months of low loads for
are presented (5 days of January and August). The figure shows that heating (April, May and October) (Fig. 14b) and for cooling (June
all cases without the SHC system present outside thermal comfort and September) (Fig. 14c).
temperatures lower than 19  C, which is the recommended tem- The annual solar fraction of cooling (SF-C) (Fig. 14d) indicates
perature for the winter season, and higher than 26  C, i.e., the that it is null for a surface of 8 m2 (the same observations for the
recommended temperature for summer. For the cases without the Djelfa and Tamanrasset regions are shown in Figs. 15d and 16d,
SHC system and for the winter season, the inside temperature of the respectively). The reason for this behaviour is the insufficient solar
HEP building (case B) increased by 4  Ce5  C compared with the energy received by the collector area (Ac  8 m2) to heat the vol-
ordinary building (case A) for all studied regions. This effect is ume of 1500 L of the solar tank, which ensures the thermal chiller
explained by increasing the insulation level, therefore decreasing operation (the set point temperature of the generator is fixed at
heat losses of the building shell (the lower the U-value, the greater 85  C). Looking at the plot of annual SF-C versus Ac (Figs. 14d, 15d
the building resistance to heat losses). On the other hand, for the and 16d), we see that a straight line can be drawn through the
cooling season, the inside building temperature in case B remains data points (Ac < 30 m2 for Algiers, Ac < 26 m2 for Djelfa and
higher than that in case A within the gap of 2e3  C; this is due to Ac < 32 m2 for Tamanrasset). We find the equation of this straight
the effect of thermal inertia, ventilation rate constant during the line and then predict the annual SF-C at any collector area. By
year, and large internal gains, which make it difficult to remove comparing the values of successive slopes (0.2 for Algiers, 0.18 for
heat from the inside to outside of the building. Djelfa and 0.25 for Tamanrasset), we see that they are almost equal.
For the cases with the SHC system, in the heating period, the Furthermore, the annual SF-C reached its maximum for
temperature is maintained between 15  C at night and 22  C during Ac  30 m2 at Algiers, Ac  26 m2 at Djelfa and Ac  32 m2 at
the day. We see that the temperature drops considerably in case A Tamanrasset, as shown in the following figures.
(low insulation, U ¼ 1.25 W/m2K), which can be explained by the To reduce the effect of overheating and according to many
effect of thermal inertia when the wall acts to retard heat transfer studies [36,51e53], the solar fraction of cooling should not exceed
from the exterior to the interior during the day. The same remark 80%. Given this value, the optimal surface area of collectors is 24 m2

Table 7
Solar and auxiliary total contribution.

ALG DJE TAM


2
U (W/m K) Case A Case B Case A Case B Case A Case B
Total solar contribution (kWh) 8583 7105 10,789 9041 10,852 9336
Total auxiliary contribution (kWh) 5276 2601 8357 3306 4428 3727
530 S. Bahria et al. / Energy 113 (2016) 521e535

Fig. 13. Effect of the building shell on the air temperature with and without SHC system.

Fig. 14. Effect of the collectors areas on the monthly solar fraction for DHW, heating and cooling loads in Algiers region.
S. Bahria et al. / Energy 113 (2016) 521e535 531

Fig. 15. Effect of the collector areas on the monthly solar fraction for DHW, heating and cooling loads in Djelfa region.

Fig. 16. Effect of the collector areas on the monthly solar fraction for DHW, heating and cooling loads in Tamanrasset region.

in Algiers and Djelfa (representing 32% of the living space area) and DHW follows the trend of the incident solar radiation (see Fig. 7),
approximately 28 m2 in Tamanrasset (representing 38% of the living while for 60 <a < 90 , the solar fraction decreases from March to
space area). April and is null for July and August when the sun is high in the sky.
This means that using a tilt close to vertical is not a suitable choice
3.4.3. The effect of the solar collector tilt angle for collecting solar energy. We also note that the SF-DHW is greater
Figs. 17e19 show the effect of the tilt angle (a) on the monthly than 40% for all months when the tilt is between 40 and 70 for
and annual Solar Fraction for DHW (SF-DHW), Heating (SF-H) and Algiers and between 30 and 70 for Djelfa. It reaches the maximum
Cooling (SF-C) loads in the studied regions. For Algiers and Djelfa, in summer due to the region latitude and the high cold network
we note the same trend of the tilt angle effect; this is due to the water temperature (approximately 25  C) in summer (see Fig. 3).
resemblance in all loads. Additionally, given that both regions share As can be observed in Figs. 17d and 18d, the annual SF-DWH is
the Mediterranean climate, when the tilt is less than 60 , the SF- higher than 60% for a large tilt variation (0 <a < 70 ), with a
532 S. Bahria et al. / Energy 113 (2016) 521e535

Fig. 17. Effect of the tilt angle on the monthly and annual solar fraction for DHW, heating and cooling loads in Algiers region.

Fig. 18. Effect of the tilt angle on the monthly solar fraction for DHW, heating and cooling loads in Djelfa region.

stability of approximately 75% between 20 and 60 . In the case of result, the heating loads are low (less than 3 kWh/m2). The annual
the Tamanrasset region (Fig. 14a), the annual SF-DWH reaches the SF-H reported in Fig. 17d remains constant (approximately 50%) for
maximum value when the collectors are tilted at less than 60 . This 30  a  60 . It is also noted that it is still more than 25%
value decreases considerably, reaching 50% in the vertical position throughout the rest of the year.
(90 ). Fig. 17c shows that the SF-C is greater than 70% for the month of
In the Algiers region, we note that more than 30% of the heating June when 0  a  20 and for September when 20  a  50 ,
loads are covered by solar energy when 40 a  80 , as shown in while the month of August presents the lowest fraction (when
Fig. 17b. The maximum of SF-H is reached in May and October. As a loads are high: 5.6 kWh/m2). Moreover, the annual SF-C takes a
S. Bahria et al. / Energy 113 (2016) 521e535 533

Fig. 19. Effect of the tilt angle on the monthly solar fraction for DHW, heating and cooling loads in Tamanrasset region.

maximum of 60% for 15  a  25 and decreases considerably with 4. Conclusions
increasing tilt angle, whereas for tilt greater than 80 , it's almost
null all year. This change can be explained by the decreasing of solar In the present work, a parametric study of solar heating and
radiation received in the vertical position while south-facing, cooling systems in different climates of Algeria is carried out. A
especially at solar noon, which includes the most solar radiation comparison is made between two construction types located in
during the day and corresponds to the maximum time-of-use of three of Algeria's regions. The results are obtained through annual
cooling systems. simulation using the TRANSOL program. This analysis aims, on the
In the case of the Djelfa region (Fig. 18), we note that for autumn one hand, to help engineers and designers to assess the impact of
and winter (except October, when the loads are low), 40% of the HEP buildings on the heating and cooling loads compared to or-
heating loads are covered by solar energy for 40  a  70 . It dinary buildings (ECO-BAT pilot-project). We find that the total
doubles in spring (over 75%) for 20  a  70 . The monthly SF-C is loads are reduced by 12%, 44% and 22% for Algiers, Djelfa and
more than 50% for a  35 , with a maximum of 60% at 20 . The Tamanrasset, respectively. On the other hand, to show the adap-
reason for this result is the high altitude of the sun in summer tation of the SHC system to the Algerian Climate (adopted for the
months. Consequently, solar radiation is perpendicular for some national plan program of the renewable energy and energy effi-
hours of the day, which causes the optimum tilt angles in summer ciency 2011e2030), we conclude that in all cases, the solar fraction
months to have minimum values. On the other hand, in the winter is more than 45% when the optimal parameters of the SHC system
season, the optimum tilt angles present the highest values due to are selected.
the low altitude of the sun during these months. The results show that increasing the insulation level has a direct
The Tamanrasset region is characterized by a period of long- impact on the inside building temperature. For all studied regions,
term cooling (April to October). Given the high cooling loads the results show an improvement of 4  Ce5  C for winter without
(Fig. 11), the SF-C is always lower than the SF-H and SF-DHW. Note the SHC system. Note that the heating loads of the HEP building
that SF-H is more than 80%, regardless of the tilt variation. This is (case B) decreased by approximately 58% in Algeria, 72% in Djelfa
due to the low heating loads in this region. Comparing the three and 12% in Tamanrasset compared with the ordinary building (case
annual fractions (DHW, Heating and cooling), we find that the SF-C A). The analysis of the heating and cooling demands shows that the
is the most sensitive to the tilt variation; the maximum SF-C Djelfa region is the coldest (heating loads reached 133 kWh/m2 for
(approximately 63%) is reached when a is less than 20 (see Fig. 19). case A and 38 kWh/m2 for case B), while Tamanrasset is the hottest
As a result, the annual solar fraction of DHW is higher than 60% region (cooling loads reached 83 kWh/m2 for the ordinary building
for a large tilt variation. The criteria for selecting the optimal angle and 8 kWh/m2 for the HEP building). It is reasonable to conclude
is based on the most significant loads (heating or cooling). For that increasing the thermal inertia is important in winter but is
Algiers and Djelfa, the heating loads are dominant. The results insufficient in summer, when it is necessary to take into account the
show that the annual solar fraction is at maximum between 35 effect of other parameters (ventilation rate, internal gain, fixed and
and 55 . Consequently, we choose the optimal tilt angle when the movable sun protection). Moreover, it would be interesting to
solar fraction of cooling is the largest possible, which yields 35 for evaluate the effect of these parameters on the building loads in
Djelfa and Algiers (corresponding to 50% of SF-H and SF-C). For future work.
Tamanrasset, the cooling load is dominant and the optimum tilt The result shows proportionality between the monthly solar
angle varies between 0 and 20 . To reduce the overheating effect fraction and the collector area. We find that the optimal surface
during summer, a tilt angle of 5 is suggested (0 is not recom- area of collectors is 24 m2 in Algiers and Djelfa (representing 32% of
mended because of the risk of rain accumulation). the living space area) and approximately 28 m2 in Tamanrasset
534 S. Bahria et al. / Energy 113 (2016) 521e535

(representing 38% of the living space area). Additionally, note that In: Renewable and sustainable energy conference (IRSEC), 2014 international;
2014. p. 778e81.
an optimal tilt angle of 35 for Djelfa and Algiers (corresponding to
[11] Allen SR, Hammond GP, Harajli HA, McManus MC, Winnett AB. Integrated
50% of SF-H and SF-C) and 5 for Tamanrasset is suggested to appraisal of a solar hot water system. Energy Mar. 2010;35(3):1351e62.
promote cooling production during summer periods (0 is not [12] Lund PD. Sizing and applicability considerations of solar combisystems. Sol
recommended due to the risk of rain accumulation). Energy Jan. 2005;78(1):59e71.
[13] Slimani MEA, Amirat M, Bahria S, Kurucz I, Aouli M, Sellami R. Study and
We can conclude that the application of the SHC system in modeling of energy performance of a hybrid photovoltaic/thermal solar col-
Algeria's regions is promising due to its high solar potential. In fact, lector: configuration suitable for an indirect solar dryer. Energy Convers
the system works all year long. This is very important because it Manag Mar. 2016. http://dx.doi.org/10.1016/j.enconman.2016.03.059.
[14] Eicker U, Colmenar-Santos A, Teran L, Cotrado M, Borge-Diez D. Economic
helps to reduce the payback period of this type of investment. evaluation of solar thermal and photovoltaic cooling systems through simu-
lation in different climatic conditions: an analysis in three different cities in
Europe. Energy Build Feb. 2014;70:207e23.
Acknowledgment
[15] Colangelo G, Romano D, Marco Tina G. Performance evaluation of a new type
of combined photovoltaicethermal solar collector. J Sol Energy Eng Aug.
This work has been partially funded by the CDER (Centre de 2015;137(4):41012.
Developpement des Energies Renouvelables) and the GIZ GmbH [16] Colangelo G, Favale E, Miglietta P, de Risi A, Milanese M, Laforgia D. Experi-
mental test of an innovative high concentration nanofluid solar collector. Appl
(Deutsche Gesellschaft für Internationale Zusammenarbeit). Their Energy Sep. 2015;154:874e81.
contribution is greatly appreciated. We would like also to express a [17] Hossain MS, Saidur R, Fayaz H, Rahim NA, Islam MR, Ahamed JU, et al. Review
special acknowledgement to the LERMAB research laboratory of the on solar water heater collector and thermal energy performance of circulating
pipe. Renew Sustain Energy Rev Oct. 2011;15(8):3801e12.
University of Lorraine (EA 4370). [18] Tian Y, Zhao CY. A review of solar collectors and thermal energy storage in
solar thermal applications. Appl Energy Apr. 2013;104:538e53.
[19] Souliotis M, Chemisana D, Caouris YG, Tripanagnostopoulos Y. Experimental
Nomenclature
study of integrated collector storage solar water heaters. Renew Energy Feb.
2013;50:1083e94.
Ac collector field absorber area [m2] [20] Colangelo G, Favale E, Miglietta P, de Risi A. Innovation in flat solar thermal
collectors: a review of the last ten years experimental results. Renew Sustain
BSk cold semi-arid climate []
Energy Rev May 2016;57:1141e59.
BWh hot desert climate [] [21] Colangelo G, Favale E, de Risi A, Laforgia D. A new solution for reduced
BWk cold desert climate [] sedimentation flat panel solar thermal collector using nanofluids. Appl Energy
COPcooling,nom nominal performance coefficient of the cooling Nov. 2013;111:80e93.
[22] Shukla R, Sumathy K, Erickson P, Gong J. Recent advances in the solar water
system [] heating systems: a review. Renew Sustain Energy Rev Mar. 2013;19:173e90.
Csa hot summer mediterranean climate [] [23] Arsalis A, Alexandrou AN. Parametric study and cost analysis of a solar-
ktoe kilotonne of oil equivalent [] heating-and-cooling system for detached single-family households in hot
climates. Sol Energy Jul. 2015;117:59e73.
Pcooling nominal cooling capacity of the cooling system [kW] [24] Eicker U, Pietruschka D, Haag M, Schmitt A. Systematic design and analysis of
TM2 typical Meteorological Year data [] solar thermal cooling systems in different climates. Renew Energy août
VU storage tank volume [l] total heat loss coefficient [W/m2K] 2015;80:827e36.
[25] Butz LW, Beckman WA, Duffie JA. Simulation of a solar heating and cooling
system. Sol Energy de cembre 1974;16(no. 3e4):129e36.
Greeks [26] Calise F, Dentice d'Accadia M, Palombo A. Transient analysis and energy
a collector tilt angle [ ] optimization of solar heating and cooling systems in various configurations.
Sol Energy Mar. 2010;84(3):432e49.
hcol,nom nominal efficiency of the solar collector [] [27] Mateus T, Oliveira AC. Energy and economic analysis of an integrated solar
absorption cooling and heating system in different building types and cli-
mates. Appl Energy Jun. 2009;86(6):949e57.
Abbreviations
[28] Calise F, Palombo A, Vanoli L. Maximization of primary energy savings of solar
SHC solar heating and cooling systems heating and cooling systems by transient simulations and computer design of
SF-C solar fraction of Cooling loads experiments. Appl Energy Feb. 2010;87(2):524e40.
[29] Buonomano A, Calise F, Palombo A. Solar heating and cooling systems by CPVT
SF-DHW solar fraction of DHW loads
and ET solar collectors: a novel transient simulation model. Appl Energy Mar.
SF-H solar fraction of Heating loads 2013;103:588e606.
DHW domestic hot water; HEP high-Energy-Performance [30] Buonomano A, Calise F, Ferruzzi G. Thermoeconomic analysis of storage sys-
tems for solar heating and cooling systems: a comparison between variable-
volume and fixed-volume tanks. Energy Sep. 2013;59:600e16.
References [31] Salah Mohamed. In: Bouzerib, “Le Programme National de Maitrise de
l'Energie 2011-2013,” presented at the Premier Forum Alge ro - Britannique;
[1] Bongs C, Dalibard A, Kohlenbach P, Marc O, Gurruchaga I, Zetzsche M, et al. 04-Mar-2013.
Task 38 solar air-conditioning and refrigeration. 2009. [32] Aiguasol. Transol version 3.23 user manual. 2013-2012.
[2] Jaehnig Dagmar, Thuer Alexander. D-A3b: monitoring results. 2011. A tech- [33] TRANSOL Solar thermal energy software. Aiguasol. 2013.
nical report of subtask A (Pre-engineered systems for residential and small [34] Calise F. High temperature solar heating and cooling systems for different
commercial applications). Mediterranean climates: dynamic simulation and economic assessment. Appl
[3] Assunta N, Wolfram S, Alexander T, Pietro F, Bettina N. Monitoring procedure Therm Eng Jan. 2012;32:108e24.
for solar cooling systems. Italy: EURAC Research/AEE INTEC/DREAM Uni- [35] “Manual Transol 3.0,” 2011.
 di Palermo; 2011. D-A3a/D-B3b.
versita [36] Planning and installing solar thermal systems a guide for installers, architects
[4] Calise F, Dentice d'Accadia M, Palombo A, Vanoli L. Dynamic simulation of a and engineers. London; Washington, DC: Earthscan, 2010.
novel high-temperature solar trigeneration system based on concentrating [37] Rodríguez-Hidalgo MC, Rodríguez-Aumente PA, Lecuona A, Legrand M,
photovoltaic/thermal collectors. Energy Nov. 2013;61:72e86. Ventas R. Domestic hot water consumption vs. solar thermal energy storage:
[5] Arsalis A, Alexandrou AN. Parametric study and cost analysis of a solar- the optimum size of the storage tank. Appl Energy Sep. 2012;97:897e906.
heating-and-cooling system for detached single-family households in hot [38] Eicker U, Colmenar-Santos A, Teran L, Cotrado M, Borge-Diez D. Economic
climates. Sol Energy juillet 2015;117:59e73. evaluation of solar thermal and photovoltaic cooling systems through simu-

[6] “Bilan Energ tique National de l'anne
e e 2012,” Ministe re de l'Energie et des lation in different climatic conditions: an analysis in three different cities in
Mines, Algerie, 2013. Europe. Energy Build fe vrier 2014;70:207e23.

[7] “Bilan Energ tique National 2013,” Ministe
e re de l'Energie, Algerie, 2014. [39] Minister of Natural Resources Canada. Solar water heating project analysis.
[8] Bornatico R, Pfeiffer M, Witzig A, Guzzella L. Optimal sizing of a solar thermal 2001.
building installation using particle swarm optimization. Energy mai [40] Office de Promotion et de Gestion Immobilie re de Blida. Logement  a Haute
2012;41(1):31e7. performance Energe tique a Ain Romana Wilaya de Blida. Cabinet d'architec-
[9] Taşdemiroǧlu E, Awad M. Technical and economic aspects of solar space ture; 2011.
heating in Turkey. Energy Nov. 1990;15(11):1035e50. [41] Imessad K, Derradji L, Messaoudene NA, Mokhtari F, Chenak A, Kharchi R.
[10] Bahria S, Amirat M, Hamidat A, El Ganaoui M, Khoudja A. Study of the solar “Impact of passive cooling techniques on energy demand for residential
combisystems for different types of building construction in Algiers climate. buildings in a Mediterranean climate. Renew Energy Nov. 2014;71:589e97.
S. Bahria et al. / Energy 113 (2016) 521e535 535

[42] Peel MC, Finlayson BL, McMahon TA. Updated world map of the Ko € ppen- Fabrikstrasse 14 CH - 3012 Bern Switzerland.
Geiger climate classification. Hydrol Earth Syst Sci Oct. 2007;11(5):1633e44. [49] Yaiche MR, Bouhanik A. Atlas solaire Algerien. Centre de De veloppement des
[43] “Base de donne es climatiques RETScreen.” 2013. Energies Renouvelables; 2013.
[44] “Meteonorm Software 7.0,” 2014. [Online]. Available: http://meteonorm.com/ [50] Park H, Ruellan M, Martaj N, Bennacer R, Monmasson E. “Generic thermal
en/. (accessed 07.05.15.). model of electrical appliances in thermal building: application to the case of a
[45] Oliver JE. Encyclopedia of world climatology. Dordrecht, Netherlands; New refrigerator. Energy Build juillet 2013;62:335e42.
York: Springer; 2005. [51] Duffie JA, Beckman WA. Solar engineering of thermal processes. Hoboken:
[46] “SolarGIS-Solar-map-Algeria-en.png (Image PNG, 836  900 pixels).” [Online]. Wiley; 2013.
Available: http://solargis.info/doc/_pics/freemaps/1000px/ghi/SolarGIS-Solar- [52] Eicker U, Pietruschka D, Haag M, Schmitt A. Systematic design and analysis of
map-Algeria-en.png. (accessed 09.03.16.). solar thermal cooling systems in different climates. Renew Energy août
[47] B. Rebzani, K. Silhadi, and S. M. K. EL HASSAR, “Document Technique 2015;80:827e36.
glementaire DTR C 3e2 ;: Re
Re gles de calcul des de
perditions calorifiques,” [53] Eicker U, Pietruschka D, Schmitt A, Haag M. Comparison of photovoltaic and
Ministre De L'habitat. solar thermal cooling systems for office buildings in different climates. Sol
[48] Remund Jan, Müller Stefan, Kunz Stefan. Meteonorm 7.X. 2015. METEOTEST Energy Aug. 2015;118:243e55.

You might also like