Ballasts 15
Ballasts 15
Ballasts for explosion-proof and increased safety, vapour-tight, weather-proof lighting fittings (high frequency start)
Ballasts for explosion-protected and increased safety lighting fittings (quick start)
7
Characteristics of Ballasts for Fluorescent Lighting Fittings
8
Characteristics of Ballasts for Mercury Lamp Lighting Fittings
Supply voltage Frequency Primary current (A) Primary wattage Power factor
Lamp (W) Type
(V) (Hz) Starting Operating (W) (%)
100 50/60 7.6 4.8 435 90
High P. F.
200 〃 3.6 2.2 425 95
400
Constant 100 〃 4.6 4.6 445 95
wattage 200 〃 2.3 2.3 445 95
100 〃 5.8 3.6 330 90
High P. F.
200 〃 2.7 1.65 320 95
300
Constant 100 〃 3.4 3.4 335 95
wattage 200 〃 1.7 1.7 335 95
100 〃 4.8 3.0 275 90
High P. F.
200 〃 2.3 1.35 265 95
250
Constant 100 〃 2.9 2.9 280 95
wattage 200 〃 1.45 1.45 280 95
100 〃 3.8 2.5 225 90
200 High P. F.
200 〃 1.75 1.1 215 95
100 〃 2.1 1.3 120 90
100 High P. F.
200 〃 0.9 0.58 114 95
Ballasts for increased safety and ignition-proof mercury lamp lighting fittings
Supply voltage Frequency Primary current (A) Primary wattage Power factor
Lamp (W) Type
(V) (Hz) Starting Operating (W) (%)
100 50/60 7.6 4.8 438 90
High P. F.
200 〃 4.0 2.3 425 90
400
Constant 100 〃 2.2 4.6 445 95
wattage 200 〃 1.1 2.3 445 95
100 〃 5.8 3.6 330 90
High P. F.
200 〃 3.0 1.8 323 90
300
Constant 100 〃 1.6 3.4 335 95
wattage 200 〃 0.8 1.7 335 95
100 〃 4.8 3.0 275 90
High P. F.
200 〃 2.6 1.5 270 90
250
Constant 100 〃 1.2 2.9 280 95
wattage 200 〃 0.6 1.45 280 95
100 〃 3.8 2.5 229 90
200 High P. F.
200 〃 1.9 1.2 223 90
100 〃 2.1 1.3 121 90
100 High P. F.
200 〃 1.0 0.6 114 90
Supply voltage Frequency Primary current (A) Primary wattage Power factor
Lamp (W) Type
(V) (Hz) Starting Operating (W) (%)
100 50/60 7.6 4.8 438 90
High P. F.
200 〃 4.0 2.3 425 90
400
Constant 100 〃 2.2 4.6 445 95
wattage 200 〃 1.1 2.3 445 95
100 〃 5.8 3.6 330 90
High P. F.
200 〃 3.0 1.8 323 90
300
Constant 100 〃 1.6 3.4 335 95
wattage 200 〃 0.8 1.7 335 95
100 〃 4.8 3.0 275 90
High P. F.
200 〃 2.6 1.5 270 90
250
Constant 100 〃 1.2 2.9 280 95
wattage 200 〃 0.6 1.45 280 95
100 〃 3.8 2.5 229 90
200 High P. F.
200 〃 1.9 1.2 221 90
100 〃 2.1 1.3 121 90
100 High P. F.
200 〃 1.0 0.6 114 90
9
Characteristics of Ballasts for Mercury Lamp Lighting Fittings
SEIWA supplies a variety of ballasts including the general type and constant-wattage type. Ballasts for special voltages
can be supplied to order in addition to those for 100 V and 200 V.
11
11
11
Outline drawing
25
30
B
D
D
A C A C
F F
G G
Form ① ① ① ① ③ ①
A 220 200 220 200 320 260
B 66 66 66 66 82 80
Dimensions C 83 83 83 83 82 84
(mm) D 76 76 76 76 92 90
F 255 235 255 235 355 295
G 285 265 285 265 380 325
10
Characteristics of Ballasts for Mercury Lamp Lighting Fittings
11
11
11
Outline drawing
30
32
B
B
D
D
A C A
F C
F
G
G
Form ① ① ② ① ① ① ② ①
A 260 200 290 260 260 200 290 260
B 80 66 102 80 80 66 102 80
Dimensions C 84 83 112 84 84 83 112 84
(mm) D 90 76 112 90 90 76 112 90
F 295 235 330 295 295 235 330 295
G 325 265 360 325 325 265 360 325
11
11
11
Outline drawing
30
32
B
B
D
A C A
F C
F
G
G
Form ① ① ② ① ① ① ② ①
A 260 200 290 260 260 200 320 260
B 94 66 102 94 94 66 102 96
Dimensions C 105 83 112 105 105 83 112 113
(mm) D 104 76 112 104 104 76 112 106
F 295 235 330 295 295 235 360 295
G 325 265 360 325 325 265 390 325
11
Characteristics of Ballasts for Mercury Lamp Lighting Fittings
11
11
11
30
32
Outline drawing
B
D
D
A C A
F C
F
G
G
Form ② ① ② ② ② ① ② ②
A 410 260 410 410 500 280 500 500
B 112 96 112 112 140 96 140 140
Dimensions C 122 113 122 122 125 113 125 125
(mm) D 122 106 122 122 150 106 150 150
F 450 295 450 450 540 315 540 540
G 480 325 480 480 570 345 570 570
12
Characteristics of Ballasts for High Pressure Sodium Lighting Fittings
Ballasts for increased safety and ignition-proof high pressure sodium lamp lighting fittings
13
Characteristics of Ballasts for High Pressure Sodium Lighting Fittings
① 20.5 20.5 ④ 16 25
11
9
11
Outline drawing
25
30
B
B
D
D
A C A
F F C
G G
Form ④ ① ④ ① ① ①
A 260 200 280 200 260 200
B 67 66 67 66 80 66
Dimensions C 83 83 83 83 84 83
(mm) D 77 76 77 76 90 76
F 285 235 305 235 295 235
G 300 265 320 265 325 265
① 20.5 20.5
11
11
Outline drawing
30
B
D
A C
F
G
Form ① ① ① ① ① ①
A 260 200 260 200 260 200
B 80 66 94 66 94 66
Dimensions C 84 83 105 83 105 83
(mm) D 90 76 104 76 104 76
F 295 235 295 235 295 235
G 325 265 325 265 325 265
14
Characteristics of Ballasts Metal Halide Lighting Fittings
Type For 100W For 200W For 250W For 300W For 400W
① 20.5 20.5
11
11
Outline drawing
30
B
D
A C
F
G
Form ① ① ① ① ① ① ① ① ① ①
A 220 200 260 200 260 200 260 200 260 200
B 66 66 80 66 80 66 94 66 94 66
Dimensions C 83 83 84 83 84 83 105 83 105 83
(mm) D 76 76 90 76 90 76 104 76 104 76
F 255 235 295 235 295 235 295 235 295 235
G 285 265 325 265 325 265 325 265 325 265
15
Characteristics of Ballasts Metal Halide Lighting Fittings