Obf : Over Braking Fault Automatic Restart : YES

The fault appears when ramp adaptation is not assigned (BRA=NO), the drive is running and the DC bus voltage pass the
Principe
OBF level.

230V range 480V range 690V range


DC Volts DC Volts DC Volts
Bus voltage fault threshold
OBF 412 825 1174
Over-voltage fault threshold when no current in drive
OBR Braking transistor external control. 403 805 1127
BRA Ramp self-adapt threshold. 393 786 1105

Probable
* Too much braking energy or overhauling load.
causes

* Increase the deceleration time.


* Add or adapt a braking resistor.
* Activate the BRA function (ramp adaptation during braking) if the application permits it.
Remedies
* Made diagnostic of braking transistor.
* Change the braking transistor or IGBT or power board.
* For P > HC20N4 check the connection with the braking unit.

Experience
Nothing.