HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA

Manufacturer Acson
BKIAP
Project Name
Location Block-1 level-1
ACD No ACD 1-1
MODEL ACA 510
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 2100
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Block-1 level-1
ACD No ACD 1-2
MODEL ACA 510
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 2100
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Domestic Check In Hall
ACD No ACD 1-3
MODEL ACA 510
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 2100
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Domestic Check In Hall
ACD No ACD 1-4
MODEL ACA 510
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 2100
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location International Arrival Lounge
ACD No ACD 1-5
MODEL ACA 510
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 2100
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location International Arrival Lounge
ACD No ACD 1-6
MODEL ACA 510
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 2100
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Immigiration Hall
ACD No ACD 1-7
MODEL ACA 510
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 2100
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Block 1 Level 1 Arrival Make up Area
ACD No ACD 1-8
MODEL ACA 510
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 2100
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Block 1 Level 1 Remote Arrival
ACD No ACD 1-9
MODEL ACA 510
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 2100
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location International Arrival Custom Area
ACD No ACD 2-1
MODEL ACA 410
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 1860
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location International Arrival Custom Area
ACD No ACD 2-2
MODEL ACA 410
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 1860
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location International Arrival Custom Area
ACD No ACD 2-3
MODEL ACA 410
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 1860
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location International Arrival Custom Area
ACD No ACD 2-4
MODEL ACA 410
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 1860
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Block 4 Security
ACD No ACD 2-5
MODEL ACA 410
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 1860
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Block 4 Security
ACD No ACD 2-6
MODEL ACA 410
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 1860
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Immigiration Hall
ACD No ACD 2-7
MODEL ACA 410
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 1860
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Immigiration Hall
ACD No ACD 2-8
MODEL ACA 410
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 1860
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Block 3 Level 1 Lift Lobby Departure
ACD No ACD 2-9
MODEL ACA 410
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 1860
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Block 3 Level 1 Lift Lobby Departure
ACD No ACD 2-10
MODEL ACA 410
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 1860
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Block 3 Level 1 Stair Lobby Remote Departure
ACD No ACD 2-11
MODEL ACA 410
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 1860
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA


HVAC SYSTEM AIR CURTAIN DEVICES TESTING PERFORMA
Manufacturer Acson
BKIAP
Project Name
Location Block 3 Level 1 Stair Lobby Remote Departure
ACD No ACD 2-11
MODEL ACA 410
Sr No Parameters Design Data Test results Remarks

High Speed
1 Air Flow (CMH) 1860
2 Noise level (DB) £ 50
3 Current (Amp)
4 Wind Speed (m/s) 18
Low Speed
1 Air Flow (CFM)
2 Noise level
3 Current (Amp)
4 Wind Speed (m/s)

QEL NESPAK CAA