BT300

Fault list
en

Original Operating Instructions .. 4200 1048 5600


Remote software........................... 4200 1017 5300
Parameter list ................................ 4200 1018 1500

09/2012 - Art. Nr. 4200 1017 8500A


09/2012 - Art. Nr. 4200 1017 8500A 1
Contents

1 LIST OF FAULT CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.1 Validity of this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2 LIST OF FAULT CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3 ASSIGNMENT OF CONFIGURATION FAULT 107 . . . . . . . . . . . . . 10

4 ASSIGNMENT OF INTERNAL FAULT 999 . . . . . . . . . . . . . . . . . . . 11

09/2012 - Art. Nr. 4200 1017 8500A 2


1 General information

1 General information
1.1 Validity of this manual

This document is a supplement to the instruction manual for the burner. It also supplements
the separate manual for the BT 3xx. It is valid only in conjunction with these documents for the
respective device. It applies to BurnerTronic BT3xx burner controllers of any configuration but
is intended specifically for the following versions:
BurnerTronic: v.3.0.0.0
Thermowattdisplay: v.01.09.04

If you have a different software version, it may be the case that some of the functions
described here are not available in your software version, or that not all functions available in
your software version are described here.

This document applies to the following devices:

BT 320
BT 330
BT 340

3 09/2012 - Art. Nr. 4200 1017 8500A


2 List of fault codes

2 List of fault codes


Fault code Description D1 D2
0 Unknown fault (internal fault)

1 Pre-ventilation signal present

2 Extraneous light

3 Flame failure during ignition

4 Flame failure during operation

5 Flame signal does not appear during 1st safety time

6 Flame signal goes out during stabilisation time

7 Flame signal goes out during 1st safety time

8 Flame signal goes out during 2nd safety time

9 Flame signal does not appear during safety time

10 Flame signal goes out during safety time

11 5 s extraneous light monitoring not observed

13 Main flame appears during ignition

103 Various data buggy

105 Curve data buggy or not present. Fuel no. Curve set

106 Parameters differ between main processor and watchdog P no.


processor
Possible fault cause:
You loaded a normal data record (not protected) and a
malfunction occurred during data transfer.
The data record was not stored correctly.
107 Impermissible configuration
See Chapter ExternalLink: Verweis auf Kapitel 107
120 Different operating mode between watchdog and main processor

121 Correction outside range Channel

09/2012 - Art. Nr. 4200 1017 8500A 4


2 List of fault codes

Fault code Description D1 D2


141 Potentiometer defect Channel

151 Recirculation flap deactivated Channel

170 Short circuit of LDR flame detector

191 1st maximum monitoring band threshold violated for too long: Channel
channel

201 1st minimum monitoring band threshold violated for too long: Channel
channel

211 2nd maximum monitoring band threshold violated for too long: Channel
channel

221 2nd minimum monitoring band threshold violated for too long: Channel
channel

231 Ratio controller hangs: channel Channel

241 Actuator not moving, i.e. giving no position feedback Channel Direction:
0-reverse,
1-forwards

251 Actuator cannot find reference position Channel


Direction:
0-reverse
1-forwards
261 Actuator returning invalid position, i.e. deviation from target Channel
position too great

271 Actuator position changing too fast, e.g. slip Channel

281 Actuator return not correct Channel

320 Load input open circuit

321 Feedback open circuit: channel Channel

351 Impermissible fuel change while burner in operation

352 Impermissible fuel signal combination (no signals present)

353 Impermissible fuel signal combination (multiple signals present)

5 09/2012 - Art. Nr. 4200 1017 8500A


2 List of fault codes

Fault code Description D1 D2


362 Lockout because burner maintenance not carried out

363 Minimum permissible O2 value violated

371 Internal load output defective

372 Load value deviation between main processor & watchdog too
great

381 Deviation between main processor & watchdog too great Correction
channel (x)

391 Curve set swapped during programming

393 EMERGENCY OFF triggered

394 BURNER ON/OFF signal from the operating unit has dropped
out illegally

451 Not all channels in ignition position in ignite mode. Channel

600 Program monitoring time expired

601 Leaktightness check fault: gas pressure still present

602 Leaktightness check fault: gas pressure not present

603 Bleed gas train manually

607 Ignition position acknowledgement dropping out illegally

608 Boiler safety chain dropping out illegally

609 Gas safety chain dropping out illegally

610 Fuel-oil safety chain dropping out illegally

611 Gas pressure too low

613 Air pressure signal absent

617 Permanent ignition flame goes out during operation

09/2012 - Art. Nr. 4200 1017 8500A 6


2 List of fault codes

Fault code Description D1 D2


624 Fuel-oil pressure too low

711 Impermissible change of operating mode

713 Incorrect terminal combination in operating mode OFF

714 Incorrect terminal combination in operating mode READY

715 Incorrect terminal combination in operating mode PRE-


VENTILATION

716 Incorrect terminal combination in operating mode IGNITION


POSITION

717 Incorrect terminal combination in operating mode IGNITION

719 Fuel valves opened for too long without flame

720 Ignition transformer switched on for too long

721 Ignition valve opened for too long

722 Fuel valves opened in maintenance mode

723 Ignition process taking too long

724 Fuel-oil pressure too low

725 Fuel-oil valves opened with gas as fuel

727 Main gas 1 opened illegally

728 All three gas valves opened for too long

729 Ignition process taking too long (without ignition burner)

730 Maintenance mode without ignition burner

731 Ignition valve opened without ignition burner

732 Incorrect signal combination during operation

7 09/2012 - Art. Nr. 4200 1017 8500A


2 List of fault codes

Fault code Description D1 D2


734 Pre-ventilation period not completed

739 Leaktightness check: gas - 2 open for too long

740 Leaktightness check: main gas 1 leaking

741 Leaktightness check: gas - 1 open for too long

742 Leaktightness check: main gas 2 leaking

743 Flame monitoring: flame burns on for too long

745 Program monitoring time exceeded

746 Solenoid valve switch-off defect

747 Leaktightness check: ventilation into burner not permitted

751 Bus card timed out.

759 BT300 in ##"EINSTELLEN"## quit automatically after 24 hours

760 Fuel change not permitted during settings configuration

763 Different curve set selection between processors

764 CO controller - internal fault Curve set

800 Bad parameter P no.

801 Channel control type of main processor not plausible to Channel


watchdog processor (serious fault, no restart)

802 Inclusion of a channel into the ratio controller taking too long Channel
(1x restart)

803 Channel hanging for too long (serious fault, no restart possible) Channel

804 Channel mode of ratio controller does not match control type Channel
(serious fault, no restart)

09/2012 - Art. Nr. 4200 1017 8500A 8


2 List of fault codes

Fault code Description D1 D2


805 Directly controlled channel (= channel that does not switch off Channel + data
and is not in the ratio controller) adopts incorrect position

888 Fault block activated! Code number

889 Remote fault release occurred too soon

990 Power failure

921 Fuel-oil valve output defective

922 Ignition transformer output defective

923 Gas valve 1 output defective

924 Gas valve 2 output defective

925 Ignition transformer output defective

928 Fuel-oil pump output defective

929 Fan output defective

986 Dynamic test detected incorrect feedback Channel

987 Changeover in multistage operation taking too long

985 VSM diagnostics fault


Possible fault cause:
BurnerTronic expects a VSM module but the exchange of
diagnostics information with the module fails.
988 Relay defective, burner selection on DFM or inconsistent
feedback from DFM

989 Plausibility test of feedback in the curve fails

990 Power failure

996 Safe writing of parameter not completed, device blocked

999 Internal fault!


See Chapter ExternalLink: Verweis auf Kapitel 999

9 09/2012 - Art. Nr. 4200 1017 8500A


3 Assignment of configuration fault 107

3 Assignment of configuration fault 107


D1 Description
1 Too many channels activated.
2 No actuator configured.
3 Permanent ignition burner configured (P 302, P 303) but no ignition flame detector present (P 800).
6 Pre-ventilation suppression by external signal not implemented.
7 Fuel change via OFF and an infinite post-ventilation time configured.
8 Pre-ventilation time less than minimum pre-ventilation time.
9 In multistage fuel-oil operation, at least one of the actuators must stop on air channel.
13 Australian flame monitoring (2 main flame detectors) configured but no ignition flame detector.
18 Standby operation in case of BT300 not permitted.
19 Impermissible fuel change selected.
20 BT300 only with separate ignition point.
21 "Ignition process with ventilator ON", only plausible with devices run purely on fuel oil.
22 Leaktightness check configuration inconsistent (gas operation possible, global leaktightness check activated globally,
but neither leaktightness check before ignition nor after switch-off active).
23 Configuration of 3 fuel oil stages possible only without ignition burner.
24 Continuous operation not permitted.
25 Fuel change not permitted.
26 Too many channels.
27 Multistage fuel-oil operation needs an air channel.
28 Bad configuration of channel function.
30 Conflicting use of terminal (more than one output signal at same output terminal).
31 No output terminal for ventilator or transformer.
32 Outputs necessary for fuel-oil operation missing (fuel-oil pump or fuel-oil valve).
33 Outputs necessary for gas operation missing (gas valve).
34 Ignition valve needed but not present in selected IO configuration.
40 No input for air pressure switch.
41 No input for fuel-oil safety chain (min fuel-oil pressure not monitored because this may be included in the safety chain).
42 No input for gas safety chain or minimum gas pressure.
43 The readback line for fuel selection has not been mapped but is needed.

09/2012 - Art. Nr. 4200 1017 8500A 10


4 Assignment of internal fault 999

4 Assignment of internal fault 999


D1 D2 Comment
0-1999 Internal faults of API system
10 return value of m_PwrOn_uiInitAPI() m_PwrOn_uiInitAPI() fails
20 0 CRC32 check of ROM fails
21 0 Cyclic CRC32 check of ROM fails during run time
22 Erroneous State State machine for CRC32 check runs in erroneous state during run time
40 0 m_PwrOn_bLoadEEPROM() fails
92 user input ATTENTION, incorrect number in incorrect module, reported from hchactab
when control tables are not correct

200 0 The last target is not a member of sER.sP


201 0 The last target is not a member of sER.sM
202 0 The last target is not a member of sER.sC
203 0 The last target is not a member of sER.sH
204 0 Target is not a member of sER.sX
210 sEECtrl.sChk.uiReadStartAddr Refresh cycle timeout expired
211 sEECtrl.sChk.uiReadStartAddr Uncorrectable error in EEPROM block
212 sEECtrl.eSeq_State Invalid status
215 uiEEFaultAddr Uncorrectable error in Parameter Set
216 uiEEFaultAddr Uncorrectable error in Miscell-Data
217 uiEEFaultAddr Uncorrectable error in curve set
220 0 pucDst == NULL
222 uiEEStartAddr Invalid EEPROM address
240 uiEEStartAddr Writing behind end of secure range!
241 uiEEStartAddr Start address in secure range not a multiple of 3
242 uiEEStartAddr Writing behind end of unsecure range!
243 uiEEStartAddr Start address in backward range!
244 ulReqFIFOSpace Not enough FIFO space
250 (ulong32)pucDst Readback error during refresh - possibly RAM cell defective

300 0 Timout sICom.uiRxLiveTimer elapsed


301 0 Timout sICom.uiRxLiveTimer elapsed
350 0 Timeout sICom.uixLiveTimer elapsed
360 0 Timeout when waiting for acknowledgement of
DUAL_BEF_CHECK_PARAM
361 0 FIFO full!
380 uiBPP_HPPunktNr Error when calling uiPutPunkt()
381 0 Leaktightness check command occurred during BM_FAT_KALTCHECK !
382 0 Timeout during cyclic parameter verification
383 uiBCP_AnzParam[0] DUAL_BEF_CHANGE_PARAM1: invalid value in receive buffer
384 uiBCP_AnzParam[1] DUAL_BEF_CHANGE_PARAM2: invalid value in receive buffer
385 sRx.Buffer.ui[ucRxOK- Cyclic parameter verification: different parameters between HP and UP!
1][uiSTARTBEF+47]
386 uiParaIdx PowerOn parameter verification: different parameters between HP and UP!

11 09/2012 - Art. Nr. 4200 1017 8500A


4 Assignment of internal fault 999

D1 D2 Comment
410 sIO.sIn.ulInputsN Detected positive half-wave on terminal input!
411 input status received from UP Different input status between controllers
412 0 The readback input of the fuel selection relay contacts in the dual fuel is
invalid. DFM probably defective.
420 uil Input status of digital input on HP and UP is inconsistent (>20 ms)
430 ucPin2Test Pin short circuit test detected an error! Currently tested pin not configured
as output or is stuck at 1
431 ucPin2Test Pin short circuit test detected an error! Short circuit between pins, pull-up of
input stage defective or pin is externally stuck at 0
440 0 sIO.sIn.uiTestSignalTimeout expired
450 0 Main power relay (K2) does not switch correctly to off when out of power.
451 ucRelay Relay does not switch correctly, when relay power is enabled (for details
see enum teRelais)
460 uiFaultParam Failure of relay power switching or readback of relay coils of K1 or
K2Param2: Bit 0 is set if readback line of K1 is erroneous, Bit 1 is set if
readback line of K2 is erroneous
461 uiFaultParam Readback status of relay K1 or K2 differs from desired switching status, relay
probably defective. Param2:Bit 0: nominal state of K1Bit 1: nominal state of
K2Bit 8: state of readback line of K1Bit 9: state of readback line of K2

500 0 Timeout while waiting for end of write cycle


501 0 SLA+W has been transmitted; NO ACK has been received
502 0 SLA+R has been transmitted; NO ACK has been received
503 0 Data byte has been transmitted; NO ACK has been received
504 0 BUS error due to an illegal START or STOP condition
505 0 Arbitration lost in SLA+R/W or Data bytes
510 ulI2CStat Unknown/invalid state!

600 sSRCtrl.uiOffset Correction of defective triple in Safety RAM structure failed


610 (ulong32)pucDst Invalid destination address
620 (ulong32)puiDst Invalid destination address
630 (ulong32)pulDst Invalid destination address

700 0 CPU selftest failed


701 sSelftest.sMngr.eState state-event-machine failed with AC_ERR
710 sSelftest.sWD.eErrorState Watchdog selftest failed
711 sSelftest.sWD.eState Invalid default case
720 Selftest.sVM.ucTest2Perform Invalid default case
721 Selftest.sVM.eErrorState Supply voltage monitor selftest failed
722 Selftest.sVM.eState Invalid default case
730 sSelftest.sRR.eErrorState Relay release circuit selftest failed
731 sSelftest.sRR.eState Invalid default case
740 sSelftest.sRPW.eErrorState Relay PWR release circuit selftest failed
741 sSelftest.sRPW.eState Invalid default case
750 0: USR-Stack, 1: IRQ-Stack Stack overflow detected
751 0 Stack address is NULL-Pointer
752 0 Stack address is NULL-Pointer

09/2012 - Art. Nr. 4200 1017 8500A 12


4 Assignment of internal fault 999

D1 D2 Comment

800 sWDog.ulReleasePtrn1 Trigger release patterns are invalid!


810 eFeedIndex Invalid Feed Index
820 eTriggerCtrl Invalid Trigger Mode
830 0 No valid watchdog trigger received (frequency or duty cycle invalid)

900 uiErrorCode Fault from LPC_API error handler


920 0 Invalid entry in iStoerResRam
930 uiMaskedFaultCode uiMaskedFaultCode out of range!

1200 0 Flame signal doesn't disappear during self-test


1210 sIFD.eTestState Invalid default case
1220 sIFD.uiClock UP is missing test impulses
1221 sIFD.uiClock Test signal duration too short
1222 sIFD.uiClock Test signal duration too short

1240 0 Detected short circuit of LDR


1250 uiADValue Circuit selftest failed, A/D value out of expected range
1260 sLDR.eTestState Invalid default case
1270 sLDR.uiClock Test interval too long
1271 sLDR.uiClock HP released test pin too late
1272 sLDR.uiClock HP released test pin too early

1290 uiMyFlames XOR uiPartnerFlames Flame signals on both controllers are inconsistent
(bit 0: main flame, bit 1: ignition flame)

1300 0 Pointer to transmit buffer is NULL

1400 psActuator->ucSANumber H_SA_INTERFACE_INVALID_ACTUATOR_TYPE


1401 psActuator->ucSANumber H_SA_INTERFACE_INVALID_DIRECTION
1405 0 H_SA_INTERFACE_WRONG_RAMP_CALCULATION
1406 0 ulGradientMax <= ulGradientDesired
1410 0 H_SA_INTERFACE_WRONG_RAMP_CALCULATION
1411 0 H_SA_INTERFACE_ERROR_TIMING
1415 psActuator->ucSANumber psActuator->ucSANumber Invalid!
1416 psActuator->ucSANumber psActuator->ucSANumber Invalid!
1420 psActuator->ucSANumber H_SA_INTERFACE_WRONG_RAMP_CALCULATION
1430 psActuator->ucSANumber H_SA_FEEDBACK_WRONG_FEEDBACK
1435 psActuator->ucSANumber H_SA_PLAUSIB_ACTUATOR_OUT_OF_RANGE
1436 psActuator->ucSANumber H_SA_PLAUSIB_SECTION_COUNT_OUT_OF_RANGE
1440 psActuator->ucSANumber H_SA_REFERENCE_SEARCH_NO_REFERENCE_FOUND
1450 psActuator->ucSANumber H_SA_STEPCALC_CALL_COUNT_OVERFLOW
1451 psActuator->ucSANumber H_SA_STEPCALC_SECTIONCOUNT_OUT_OF_RANGE
1452 psActuator->ucSANumber H_SA_STEPCALC_INVALID_DIRECTION
1453 psActuator->ucSANumber H_SA_STEPCALC_SECTIONCOUNT_OUT_OF_RANGE

13 09/2012 - Art. Nr. 4200 1017 8500A


4 Assignment of internal fault 999

D1 D2 Comment
1454 psActuator->ucSANumber H_SA_STEPCALC_INVALID_DIRECTION
1455 psActuator->ucSANumber H_SA_STEPCALC_WRONG_STATUS
1460 0 U_SA_INTERFACE_INVALID_ACTUATOR_TYPE
1461 0 U_SA_INTERFACE_INVALID_DIRECTION
1470 psActuator->ucSANumber U_SA_FEEDBACK_INVALID_DIRECTION
1471 psActuator->ucSANumber U_SA_FEEDBACK_INVALID_DIRECTION
1472 psActuator->ucSANumber U_SA_FEEDBACK_WRONG_FEEDBACK
1480 psActuator->ucSANumber U_SA_REFERENCE_SEARCH_INVALID_ACTUATOR_TYPE
1490 psActuator->ucSANumber psActuator->ucSANumber Invalid!

1500 0 Timeout while sending ICOM command


1501 0 Timeout while waiting for ACK of ICOM command
1502 0 Timeout while waiting for end of actuator initialization
1503 0 Timeout while waiting for end of actuator initialization
1504 0 Timeout while waiting for end of actuator initialization
1505 Actuator Number HP: Invalid configuration. Parameter for Actuator Type should never be
different from 1 or 2
1505 Actuator Number ÜP: Invalid configuration. Parameter for Actuator Type should never be
different from 1 or 2
2000-3999 Internal faults generated from within application (FAT and system)
2000 Unknown event, for the event handling mechanism
2001 Too many events for even queue

2100 Invalid buffer entry


2101 EEProm probably defective

2200 Invalid index for SQBLData00


2201 Invalid index for SQBLData01
2202 Invalid index for SQBLData02
2203 Invalid index for SQBLData03
2204 Invalid index for SQBLData04
2205 Invalid index for SQBLData05
2206 Invalid index for SQBLDataKurven
2207 Invalid index for SQBLDataPara
2208 Invalid index for SQBLData15
2209 Data request for data block even though no transmission currently taking place

2300 Invalid state


2301 Invalid state
2302 Delete curve, setting mode end
2303 Invalid state
2304 Invalid state
2305 Illegal parameter number (no longer exists)
2306 Illegal state, cold check
2307 Cold check

09/2012 - Art. Nr. 4200 1017 8500A 14


4 Assignment of internal fault 999

D1 D2 Comment
2308 Cold check
2309 Cold check
2310 Invalid state
2350 - Cold check
2354

2400 Attempt to write a modbus register


2401 Write to modbus register

2500 Parameter with authorisation level > 4

2600 Operating mode cannot be found


2601 Transition not permitted

2700 Delete curve, quit setting mode

2800 Air pressure signal had not dropped yet burner started anyway
2801 During the cold check, more than one valve was opened
2802 Maintenance mode active on main processor even though no maintenance
mode parameterised
2803 Maintenance mode active and yet ignition completed
2804 Burner starts even though watchdog processor blocked
2805 Burner starts even though no reference run carried out
2806 Stage sent from main processor for multistage operation appears implausible

2900 Program load by timer too high

3000 All errors for which no error number has been entered

3100 Error messages from password module


3101 Error message from password module

3200 Internal overrun, interim result pass, possibly not in Variable


3201 Overrun of end result

3230 UP version differs from HP version

3250 Parameter for multistage load controller invalid

3300 Automatic burner changeover default case entered


3301 Automatic leaktightness check default case entered
3302 Automatic FAT default case
3303 Automatic post-ventilation default case
3304 Automatic pre-ventilation default case entered
3305 Automatic ignition default case entered

15 09/2012 - Art. Nr. 4200 1017 8500A


4 Assignment of internal fault 999

D1 D2 Comment
4000-4999 Internal faults generated from within application (air/fuel ratio control [Verbundregler])
4000 0 For load of ignition point, no curve point exists
4001 0 ucPIdx_R >= ucPunktAnzahl

4100 sRampe.ucState Invalid value of sRampe.ucState

4200 ucVBMode Invalid value of ucVBMode

4302 0 If no active air channel defined (parameterisation error)

4400 ucSteuerArtEx Invalid value of ucSteuerArtEx


4401 0 Timeout while waiting for ???
4402 ucSteuerArtEx Invalid value of ucSteuerArtEx
4403 ucKanStat (ucKanStat & Def_VKM2_MSK) != Def_VKM2_DVAL
4404 0 Timeout while waiting for ???
4405 ucKanStat Disabled channel is moving!
4406 ucRzStState[ucKnr] Invalid value of ucRzStState[ucKnr]
4407 ucVBStat Invalid value of ucVBStatn

4500 0 sRampe.uiLaufzeit == 0!
4501 ucKnr IfKM_VB() returned 0

4600 ucVorgabe Invalid value of ucVorgabe


4601 (sRampe.uc2VBKMsk | With VSM_NOVB, no VB channels permitted to be active
sRampe.ucVBKMsk)
4602 sRampT.ucNState Unknown input value state
4603 sRampe.ucState Invalid value of sRampe.ucState

4700 0 Ramp run time expired!


4701 Transferred channel number outside legal range
4702 Transferred channel number outside legal range
4703 Transferred channel number outside legal range
4704 Transferred channel number outside legal range
4705 ucKnr Transferred channel number outside legal range
4706 ucKnr Transferred channel number outside legal range
4707 ucKnr Transferred channel number outside legal range
4708 ucKnr Transferred channel number outside legal range
4709 ucKnr Transferred channel number outside legal range
4710 ucKnr Transferred channel number outside legal range
4711 ucKnr Transferred channel number outside legal range
4712 ucKnr Transferred channel number outside legal range
4713 ucKnr Transferred channel number outside legal range
4714 ucKnr Transferred channel number outside legal range
4715 ucKnr Transferred channel number outside legal range
4716 ucKnr Transferred channel number outside legal range

09/2012 - Art. Nr. 4200 1017 8500A 16


4 Assignment of internal fault 999

D1 D2 Comment
4717 ucKnr Transferred channel number outside legal range

4800 uiActTmr ucErg > 0!


4801 ucSgIdx Parameter change Knf_uiActuatorDirX with ratio controller active or outside
operating modes BM_AU, BM_ST
4802 0 Permissible channel travel range too short for conducting Max Speed
measurement

4900 ucKnr Division by 0


5000-5999 Internal faults generated from within application (Load control [Laststeuerung])
5000 enInterneLastSeq invalid value of enInterneLastSeq
5001 0 Flatter signal DPS+ / DPS for load stage selection
5002 0 Curve error, curve for n-stage fuel oil or channel speed of motors not
determined
5003 0 Invalid transfer parameters
5004 0 Timers for stage changeover time check inconsistent: internal load
changeover time < changeover time of load value specified
5005 0 Invalid stage curve with internal load specified by stage controller
5007 0 Illegal load value with setting of multistage oil curve
5008 0 Invalid stage control mode
6000-6999 Internal faults generated from within UP application control (air/fuel ratio control [Verbundregler])
6000 ucSteuerArtEx Unknown mode of channel control
6001 ucBetrMoNr Overaddressing of array was detected

6100 ucKnr Unknown mode of channel control

6200 0 Avoid an endless loop


6201 0 Avoid an endless loop
6202 0 Avoid an endless loop
6203 0 SSR.sS0.ucAktKurvensatz or SSR.sS0.uiKanalenb changed without
AufrufKurve2Workram
6204 0 No entirely valid point found, but curve not blank
6205 Determined points quantity Number of points does not match Ram curve (serious fault with task)
6206 Actual curve point index Load value writing failed (ram defect)
6207 Original curve point index Load point of original curve invalid
6208 Original curve point index Invalid point index
6209 0 Point approximation impossible, no previous point present
6210 0 Point approximation impossible, no subsequent point present
6211 0 Point approximation failed, one of the points used was invalid
6212 Actual curve point index Target value writing failed (ram defect)
6213 Original curve point index Invalid point index
6214 0 Point approximation impossible, no previous point present
6215 0 Point approximation impossible, no subsequent point present
6216 0 Point approximation failed, one of the points used was invalid

17 09/2012 - Art. Nr. 4200 1017 8500A


4 Assignment of internal fault 999

D1 D2 Comment
6217 Actual curve point index Return target value writing failed (ram defect)
6218 Original curve point index Invalid point index
6219 0 Point approximation failed, one of the points used was invalid
6220 Actual curve point index Evaluated correction target value writing failed (ram defect)
6221 Original curve point index Invalid point index
6222 0 Write failed: ram defect
6223 0 Write failed: ram defect
6224 Fault quantity Too many differences between curves
(sliding counter, subtract 1 per cycle)
6225 State number Undefined state of state machine

6300 ucSMState Detect undefined state of state machine

6400 ucKnr Division by 0

09/2012 - Art. Nr. 4200 1017 8500A 18


www.elco.net

Hotline
ELCO Austria GmbH
Aredstr.16-18 0810-400010
2544 Leobersdorf
ELCO Belgium nv/sa
Z.1 Researchpark 60 02-4631902
1731 Zellik
ELCOTHERM AG
Sarganserstrasse 100
0848 808 808
7324 Vilters
Switzerland
ELCO GmbH
Dreieichstr.10
0180-3526180
64546 Mörfelden-Walldorf
Germany
Elco Industry Italy
Corte degli Speziali 10/14 +39 0321 338600
28100 Novara
ELCO Burners B.V.
Amsterdamsestraatweg 27
035-6957350
1411 AW Naarden
Netherlands
OOO «Ariston Thermo RUS LLC»
Bolshaya Novodmitrovskaya
+7 495 783 0440
St.bld.14/1 office 626
127015 Moscow -Russia

Made in the EU. Non contractual document.

You might also like